ISSN 1546-9239
© 2006 Science Publications
Abstract: An important consideration when evaluating the impact of harmonics is their effect on
power system component and loads. Transformers are major components in power systems. The
increased losses due to harmonic distortion can cause excessive losses and hence abnormal
temperature rise. The measurement of iron losses and copper losses of single-phase transformers is
important in particular for transformers feeding nonlinear loads. In computing of transformer losses, it
is assumed that source voltage is sinusoidal and load impedance is linear. This study presents the
effects of harmonic distortion of load current and voltage on single-phase transformer losses utilizing
the on-line measurements (monitoring) method of the primary side. The transformer is loaded with an
SCR speed controller that consists of a single-phase full-bridge rectifier, SCR and a resistant load to
generate various total harmonic current and voltage distortions (THDi and THDv) conditions.
Key words: Harmonic, sinusoidal source, nonlinear load, total harmonic distortion (THD)
Corresponding Author: Syafruddin Hasan, School of Electrical System Engineering, Kolej Universiti Kejuruteraan
Utara, Malaysia, 02600 Jejawi, Perlis, Malaysia, Tel: +604-9798146, Fax: +604-9798304
2131
Am. J. Applied Sci., 3 (12): 2131-2133, 2006
H a rm o n ic A ve ra g e
1 + THD 2
0.004
where DPF is the displacement power factor, assuming
0.003
that for non-inductive or non-capacitive loads, the value
can be considered as 1. 0.002
0.001
Experimental set-up: The arrangement of equipment
set-up is as shown in Fig. 1. The experiment was 0.000
conducted by varying the input voltage but constantly 2 6 10 14 18 22 26 30 34 38
maintained the SCR trigger angle and load resistance Harmonic order
value.
a. Harmonic distribution of input current for Vin=75V
Vin = 75 V
0.16
0.14
H a r m o n ic V - rm s
0.12
0.10
0.08
0.06
0.04
Fig. 1: Arrangement of experimental set-up 0.02
0.00
RESULT AND DISCUSSION 2 6 10 14 18 22 26 30 34 38
Harmonic order
The experimental results are as shown in Table 1.
The related current and voltage waveforms and the b. Harmonic distribution of input voltage for Vin=75V
respective harmonic distribution for the two input or
primary voltages (75 V and 200 V) are depicted as b. For Vin = 200 V
shown in Fig. 2 and 3.
Fig. 2: Current and Voltage waveforms for input Fig. 3: Current and Voltage waveform for input
voltage of 75 V voltage of 200 V
2132
Am. J. Applied Sci., 3 (12): 2131-2133, 2006
0.006
0.005 CONCLUSION
0.004
0.003 In this study, the operation of a single phase
0.002 transformer is considered for sinusoidal power source
0.001 and nonlinear load only.
0 From experimental results, it is observed that input
2 5 8 11 14 17 20 23 26 29 32 35 38 power factor is significantly dependent on the harmonic
Harmonic order content of the system. The power factor decreases with
the increasing of total harmonic distortion. The total
a. Harmonic distribution of input current for Vin=200V harmonic distortion and crest factor are higher at low
Vin = 200 V input voltage compared to higher input voltage. These
conditions are represented clearly by current and
0.60 voltage waveforms in Fig. 2 and 3. As a conclusion, the
0.50 transformer is not recommended to operate at lower
Harmonic V-rms
0.40
than its rated voltage.
0.30
REFERENCES
0.20
0.10
1. Jayasinghe, R.N. et al., 2003. Power system
0.00 harmonic effects on distribution transformers and
2 5 8 11 14 17 20 23 26 29 32 35 38 new design considerations for K factor
Harmonic order transformers. IEE Sri Lanka Annual Sessions.
2. Maswood, I.A. et al., 2002. Harmonics, sources,
b. Harmonic distribution of input voltage for Vin=200 V
effects and mitigation techniques. Second Intl.
Conf. on Electrical and Computer Engineering,
ICECE 2002, Dhaka, Bangladeh, pp: 26-28.
3. Salih, T.M. et al., 2000. The Effect of the harmonic
components upon transformer active losses in case
of (non) sinusoidal sources and (non) linear loads.
Department of Electrical Engineering Yildiz
Technical University, Istambul, Turkey.
4. Gregory, M.W., 1994. Estimation methods for
power system harmonic effects on power
distribution transformers. IEEE Trans. Industry
Appl., 30: 2.
5. Skvarenina, L.T. and D.E. William, 2004.
Fig. 4: Variations of CF and PF due to change of Electrical Power and Controls. 2nd Edn. Pearson
input voltage Prentice Hall, New Jersey.