INSTALLATION INSTRUCTIONS FOR THE


by Honeywell DUCT SMOKE DETECTOR
These are Installation Instructions (DWG.# HA-06-094) for the Duct Housing customized as follows:
SD505-DUCT Duct Housing with the SD505-APS Analog Photoelectric Smoke Sensor*
SD505-DUCTR Duct Housing with the SD505-APS Analog Photoelectric Smoke Sensor & Relays*
SD505-DTS-K Remote Test Switch

I. LOCATION REQUIREMENTS
Duct Smoke Detector Location
Requirements: To prevent false alarms the detectors should
not be mounted in areas of extreme high or low temperatures,
in areas where high humidity exist, or in areas where duct air
may contain gases or excess dust. The duct detector should,
when possible, be located a minimum of six duct widths
downstream from a source of turbulence (bends, inlets, or
deflection plates). At these locations, air flow is less turbulent
and the air/smoke mixture should be more homogenous.
Refer to NFPA 90A, 72, and 101 for more information. See
Figure 1A and 1B.
Exception: Where it is physically impossible to locate
the duct detector accordingly, the duct detector can be
positioned closer than six duct widths, but as far as
possible from inlets, bends, or deflection plates.

II. MOUNTING THE DETECTOR


TOP OF DUCT HOUSING
A. DUCT PREPARATION
FIGURE 1B: DUCT HOUSING MOUNTING
1. Remove paper backing from mounting template AP 121 (packaged in installation kit) and
affix to duct at desired location.
2. Using template as a guide, drill 4 mounting holes (3/32" diameter) for duct mounting
screws (4 #12 x 1/2" sheet metal screws packaged in installation kit). Drill or punch holes
for sampling tubes in air ducts (1-3/8" diameter), using template as a guide. Clean all holes.

B. VERIFY AIR FLOW AND DIRECTION


The Duct Detectors are designed for use in ducts where the air velocities are
from 300 to 4000 feet per minute. Verify this by checking specifications of
installation and if necessary, use an Alnor Model 6000P velocity meter (or
equivalent) to check the air velocity. See Figure 2 for sampling tube
orientation to air flow direction.
C. SAMPLING TUBE ASSEMBLY (See Figure 2)
The sampling tubes may be ordered to a desired length or
ordered in one of 3 standard lengths and cut per requirements.
The intake sampling tube consists of a piece of steel piping with
a series of holes drilled the entire length of the tube and should
extend the entire width of the duct. The holes must be facing
into the air flow (see Figure 2). The exhaust tube consists of a
piece of steel piping approximately 7-1/2" long.
INTAKE SAMPLING TUBES STANDARD LENGTHS:
SD505-T2 For duct widths of 1.0' to 2.5'
SD505-T5 For duct widths of 2.5' to 5.0'
SD505-T10 For duct widths of 5.0' to 10.0'
1. Cut the intake sampling tube to the desired length.
2. Firmly insert the stopper (packaged in installation kit) in the end of the INTAKE sampling tube.
D. MOUNT SAMPLING TUBES (See Figure 2)
1. Sampling tube connectors are equipped with set screws, which allow the tubes to be mounted only in directions shown in
Figure 2. Establish proper orientation considering airflow direction.
2. Insert intake and exhaust tubes into connectors, align set screw to set screw hole in tubes and tighten firmly.
E. MOUNT THE DUCT HOUSING (See Figure 1B & 2)
Move duct housing/sampling tube assembly to desired location. Use 4 mounting screws (4 #12 x 1/2" sheet metal screws,
packaged in installation kit) to secure the housing to the air duct.

F. VERIFY AIR SAMPLING (See Figure 3)


To verify proper sampling of air, use a Dwyer Model 4000 differential pressure gauge (or equivalent). See Figure 3 for
gauge connections. The pressure differential between input sampling tube and exhaust tube should be greater than
0.01" of water and less than 1.2" of water.

Installation Instructions (P/N 1700-09882 HA-06-094) Page 1 of 3 Specifications subject to change without notice. * September 2014
SPECIFICATIONS
SPECIFICATIONS RATING
SD505-DUCT SD505-DUCTR
Alarm Relay Contact Rating 10A @ 24VDC
10A @ 115VAC
10A @ 240VAC
Trouble Relay Contact Rating 2.5A @ 30VDC
Operating Voltage 24VDC
Aux. Power Input Current 20mA Standby
62mA Alarm
SLC Input Current 0.5mA 0.5mA
Maximum SLC Resistance 50 Ohms 50 Ohms
Operating Temperature 32F ~ 100F 32F ~ 100F
Humidity 10% ~ 85% RH Non-Condensing 10% ~ 85% RH Non-Condensing
Air Velocity Rating 300 ~ 4000 ft./min. 300 ~ 4000 ft./min.

EXHAUST TUBE INTAKE TUBE


III. ELECTRICAL INSTALLATION HOLE &
CONNECTOR
HOLE &
CONNECTOR
A. GENERAL INFORMATION
Wiring must conform to applicable local codes, ordinances and regulations LOW PRESSURE
SIDE
HIGH PRESSURE
SIDE
covering these types of devices. Wire the detectors according to the
engineering drawings for the particular job requirements. These detectors
are not intended for open area protection, nor should they be used for
open air protection. Refer to NFPA 90A and NFPA 72 for general and
additional information on Duct Smoke Detectors concerning operation
and installation. Terminals are suitable for up to #14 gauge wire.

DWYER #4000 DIFFERENTIAL


B. DETECTOR WIRING PRESSURE GAUGE (OR
EQUIVALENT) WITH TUBING
1. With power source de-energized and the smoke detector not installed, wire AND SIZE 0 RUBBER STOPPERS
all connections per engineering drawings. Refer to the applicable figures below (HA PART# 0700-01118).
FIG. 3 AIR SAMPLING
depending on your duct housing model number. VERIFICATION
2. With all wiring in place, install the detector head.
3. Energize the duct detector.

C. WIRING DIAGRAMS ANALOG SENSOR

L1 L2 -R +R STANDBY and ALARM current should


SD505-DUCT WIRING DIAGRAM be 0.55mA

The SD505-DUCT is not a self-contained sensor.


This product is compatible only with fire alarm
NOT USED
control panels that utilize Silent Knight's Digital
1 2 3 4
Communications Protocol.
LOOP INTERFACE
CONTROL PANEL

S (+)
TO NEXT
UL LISTED

SENSOR

SC (-)

FAN SHUTDOWN EXAMPLE


SD505-DUCTR WIRING DIAGRAM
OBSERVE POLARITY
INPUT VOLTAGE
24 V.D.C.
FAN
SUPPLY VOLTAGE
20 mA Standby
62mA Alarm

+ -

ADDRESSABLE
LOOP

13 14 1 2 9 10 11 12
3 4 5 6 7 8
Test GND PILOT ALARM
SW LED LED

C C
REMOTE TEST NC NO NC NO
SWITCH
ALARM CONTACTS TROUBLE
UL LISTED SD505-DTS
10.0A @ 250VAC 10.0A @ 250VAC

CONTROL PANEL
(Test function only. Does not reset.)
S (+)
A.A. TO NEXT SENSOR
ANALOG ADDRESSABLE
CONTROL OR RETURN
PANEL SC (-) FIELD LOOP WIRING
TO CONTROL PANEL
Terminate Remote Accessories as indicated above (if required).
This is not a self-contained stand alone detector.
A U.L. Listed Analog Addressable Fire System is required.

Installation Instructions (P/N 1700-09882 HA-06-094) Page 2 of 3 Specifications subject to change without notice. * September 2014
SD505-DUCTR AND SD505-DTS-K
WIRING CONNECTIONS

REFER TO INSTALLATION INSTRUCTIONS (HA-06-094)


* SILENT KNIGHT DETECTORS ARE INTENDED FOR USE WITH AIR DUCT VELOCITIES FROM 300 TO 4000 FEET PER MINUTE.
VERIFY THIS BY CHECKING THE SPECIFICATIONS OF HVAC INSTALLATION AND IF NECESSARY, USE AN ALNOR
MODEL 6000P VELOCITY METER OR EQUIVALENT TO CHECK AIR VELOCITY.
* PRESSURE DIFFERENTIAL MEASUREMENTS SHOULD BE MADE USING A DWYER PRESSURE GAGE (CATALOG
#2003 - 3" WATER FULL SCALE) TO INSURE AIR FLOW IN THIS CHAMBER. THE PRESSURE DIFFERENTIAL
BETWEEN INPUT AND EXHAUST TUBE SHOULD BE BETWEEN 0.01 AND 1.2 INCHES OF WATER.
* DO NOT INSTALL WHERE AMBIENT TEMPERATURE EXCEEDS 100 °F (38 °C).

CAUTION: FOR TERMINALS 3,4,5,6,7,8 DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTION. TEST GND PILOT ALARM
LED LED
24 VDC NC COM NO NC COM NO TEST GND PILOT ALARM SLC- SLC+
(+) (-) ALARM TROUBLE SW LED LED
YB E YB E YB E YB E YB E
BJ

9 W7 4 4 2
5
A

2127H1

+ BASE -

9 10
4 73

A7
5

4N 1P
9

105
A E DV
4 73 152
EBY

50K
4 73

730

037
K05
702

A7 2T 9 10
5

501
152
1V H
MADE IN INDONESIA

4 73
N4
75M

1 05
730
50K
105

RG4
LM3
93
CR7
Bot t om View

730
50K
105

3 35
2 004

4 74

4 73
2 004

4 73

4 74

725
D2
17

4 71 2 004
S
V104

MM
76A

5 1 05
1 05
A7

1 53
4 73
A7

4 73
5 4 73
725
D2
17
1V H

105
4 72

50K
730
1 53
4 73
4 73

152

2 004

1V H
1P

4 72

2T
9 1 04 E6 1
01
376
2T

725S
D217
1P

BJ
5

9 V104
1 53
A7

152

1 04

1 53

1 02

5 1 05
103

207 673
G43

C2K

1 05 10
16E

Silent Knight Control Panel

SC- S+ SC- S+
SLC OUT SLC IN
TEST GND PILOT ALARM SLC- SLC+
SW LED LED
Class A (Style 6) Wiring YB E YB E
EBY

Silent Knight Control Panel

TEST GND PILOT ALARM SLC- SLC+


SC- S+ SC- S+ SW LED LED
SLC OUT SLC IN YB E YB E

TEST GND PILOT ALARM SLC- SLC+


SW LED LED
YB E YB E
EBY

Duct Detectors Smoke Detection – NFPA 90A Code


Class B (Style 4) Wiring Requirements
EBY

Air Handlers | Heating and Cooling R

by Honeywell
12 Clintonville Road
Northford, CT 06472
Installation Instructions (P/N 1700-09882 HA-06-094) Page 3 of 3 Phone: 203-484-7161 * Fax: 203-484-7118 Specifications subject to change without notice. * September 2014