Application Note 1321

Industrial Field Bus Networks Optical Isolation for Field Bus


Before field bus, an industrial Networks
control system was built up CENTRAL Numerous and large transient
around a central controller with CONTROLLER bursts are common in an
input and output cards to input industrial environment. These
signals from sensors and output I/O transient bursts can disrupt the
CARDS
signals to actuators. Usually, the data transmission and even
controller, I/O cards and motor potentially damage the
drivers were installed in the interconnected equipment. In
MOTOR
central cabinet, which was DRIVER
order to ensure error-free data
connected with the remote transmission in high-speed field
devices (Figure 1a). bus communication, an industry
DEVICE A
system designer has to take
Field bus networks, however, MOTOR efforts to eliminate disturbances.
DEVICE B
communicate between the Typically galvanic isolated
controller and field devices in a optocouplers (Figure 2) are used
DEVICE C
sequential information manner to retain data integrity and protect
(Figure 1b). Controllers and interconnected equipment.
Figure 1a. Conventional controller and
devices are connected to the field remote devices connected by parallel
bus cable in bus, star, tree or ring International standard IEC 61000-
topologies. 4-4 specifies electrical fast
transient/burst immunity test
From the mid 1980’s, field bus CENTRAL related to the immunity
technology was ready to move CONTROLLER requirement of EMC. All of
onto the factory floor. Industrial MOTOR
Agilent’s high-speed CMOS
field buses are classified accord- DRIVER optocouplers have transient
ing to their performance immunity performance CMR
DEVICE A
capabilities. What field bus stan- 10 kV/µs at common mode voltage
dard one ultimately chooses up to 1000 Volts. Optocouplers
MOTOR DEVICE B
chiefly depends upon the amount isolate transient/burst
of data that a bus is able to handle interference and transmit data
DEVICE C
and its associated speed or propa- between bus transceiver and
gation delay requirements. There controller. Since network
are perhaps dozens of popular communication is bi-directional
Figure 1b. Controller and remote devices
network standards and hundreds connected by fieldbus network (involving receiving data from and
of proprietary or home brewed transmitting data onto the
standards. The development and network) two optocouplers are
usage of field buses has grown needed per node.
rapidly. During the end of 1999 networks in total. Appendix 1 lists
and 2000, there was approval for a performance comparison of
IEC61158, which is an interna- some popular field bus standards
tional standard covering several discussed in this application note.
CONTROLLER

BUS INTERFACE

OPTICAL ISOLATION

TRANSCEIVER
FIELD BUS

TRANSCEIVER TRANSCEIVER TRANSCEIVER TRANSCEIVER

OPTICAL OPTICAL OPTICAL OPTICAL


ISOLATION ISOLATION ISOLATION ISOLATION

BUS BUS BUS BUS


INTERFACE INTERFACE INTERFACE INTERFACE

000
XXXXX SENSOR

YYY
000
DEVICE MOTOR
CONFIGURATION MOTOR STARTER CONTROLLER

Figure 2. Field Bus Communication Physical Model

Recommended Optocouplers
The following optocouplers use system requirements, with data
the latest CMOS IC technology to rate and regulatory requirements
achieve outstanding system playing an important role.
performance. The optocoupler
choice will depend on the overall

HCPL- 7710 0710 7720 0720 7721 0721 0708 0738 7723 0723
Speed 12.5 MBd 25 MBd 15 MBd 50 MBd
Max. 40 ns 60 ns 22 ns
Propagation
Delay
Min. 80 ns 40 ns 100 ns 20 ns
Pulse Width
Max. PWD 8 ns 6 ns 30 ns 2 ns
Max. 20 ns 40 ns 15 ns
Propagation
Delay Skew
Min. CMR 10 kV / µs @ Vcm = 1000 V
Package 300 mil SO8 300 mil SO8 300 mil SO8 SO8 SO8 300 mil SO8
Type DIP8 DIP8 DIP8 Dual DIP8
VDE 0884 *630 *560 *630 *560 *630 *560 *560 *630 *560
[Viorm] Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak
UL [Viso] 3750 2500 3750 2500 3750 2500 2500 Vrms 3750 2500
Vrms Vrms Vrms Vrms Vrms Vrms Vrms Vrms
* Option 060 required.
2
Isolation Node Power Supply
Design Considerations
There are an AC line in device
power supplies and DC power in
field bus cables. It is very flexible
for the isolation node to tap
power from the above two
sources. The basic consideration
is that two power supplies must

V+

V+
be isolated across the
optocoupler isolation boundary. NETWORK
POWER HCPL-

TRANSCEIVER
There are three types of solutions, SUPPLY x710/x72x
ASIC/
namely: MICROPROCESSOR
1. Isolation Node Powered by the HCPL-
x710/x72x
Network (Figure 3);
2. Isolation Node with Transceiver
Powered by the Network REG
(Figure 4);
3. Isolation Node Providing Power
ISOLATED
to the Network (Figure 5). DC/DC
CONVERTER
1. Isolation Node Powered by the
DRAIN/SHIELD

Network
POWER

SIGNAL
GALVANIC
If the network power can supply ISOLATION
BOUNDARY
the devices sufficiently, then it is
not necessary to power field
devices from the AC line. As seen
in Figure 3, a non-isolated voltage
Figure 3. Isolation Node Powered by the Network
regulator supplies the transceiver
and half of two optocouplers,
while an isolated DC/DC
converter supplies the controller
and the other side of two
optocouplers.
V+

V+
V-
V-

2. Isolation Node with Transceiver NETWORK


POWER HCPL-
Powered by the Network x710/x72x
SUPPLY
Figure 4 shows when an TRANS- ASIC/
CEIVER MICROPROCESSOR
application requires a significant HCPL-
amount of power. In this case, the x710/x72x
field device is powered by the AC
line source while the transceiver
REG
and isolated side of the two
optocouplers are powered by the FIELD
network. This method is also DEVICE
SUPPLY
desirable as it does not heavily
load the network.
DRAIN/SHIELD

AC LINE
POWER

SIGNAL

GALVANIC
ISOLATION
BOUNDARY

Figure 4. Isolation Node with Transceiver Powered by the Network

3
3. Isolation Node Providing Power to
the Network
The method shown in Figure 5 is
recommended when there are a
limited number of devices on the

V+

V+
V-
network that do not require much
power, thus eliminating the need HCPL-
x710/x72x
for separate network power TRANS- ASIC/
supplies. The AC line powers the CEIVER MICROPROCESSOR
HCPL-
field device supply locally and x710/x72x
also powers the isolated power
supply. This supply powers the
REG
network, from which one
regulator derives DC 5 V to power FIELD
the transceiver and the isolated ISOLATED DEVICE
POWER SUPPLY
(network) side of two SUPPLY
optocouplers.
DRAIN/SHIELD

POWER

SIGNAL GALVANIC
Recommended DeviceNet ISOLATION
Application Circuit BOUNDARY AC LINE
A CAN bus is used by DeviceNet
physical layer implementation.
The recommended DeviceNet
application circuit is shown in Figure 5. Isolation Node Providing Power to the Network
Figure 6. Since the high-speed
CMOS optocouplers HCPL-x710/
x72x are fully compatible with
CMOS logic level signals, the two
optocouplers are connected
directly to the CAN transceiver.
Two bypass capacitors (with
values between 0.01 and 0.1 µF)
are required and should be
located as close as possible to the
input and output power supply
pins of the optocoupler. For each
capacitor, the total lead length
between both ends of the
capacitor and the power supply
pins should not exceed 20 mm.
The bypass capacitors are either AC line power to the node
required because of the high- is lost or the node powered-off.
speed digital nature of the signals Specifically, when input power
inside the optocoupler. (VDD1) to the HCPL-x710/x72x
located in the transmit path is
More importantly, the unique eliminated, a RECESSIVE bus
“dual-inverting” design of the state is ensured as the HCPL-
Agilent HCPL-x710/x72x ensures x710/x72x output voltage (VO)
the network will not “lock-up” if goes HIGH.

4
GALVANIC
ISOLATION
ISO 5 V BOUNDARY
5V
LINEAR OR
1 VDD1 VDD2 8 SWITCHING
+ REGULATOR +
Tx0
2 VIN 7
0.01 µF
HCPL-x710 VCC
0.01 µF 3 VO 6 TxD 5 V+
CANH 4 CAN+
4 GND1 GND2 5 +
C4 82C250 3 SHIELD
0.01 µF
CANL 2 CAN–
GND
Rs REF VREF 1 V–
GND
GND RxD

5 GND2 GND1 4
D1
30 V C1 R1 1 M
Rx0
6 VO 3 0.01 µF
0.01 µF
HCPL-x710 500 V
0.01 µF 7 VIN 2

8 VDD2 VDD1 1

ISO 5 V 5V

GND

5 GND2 GND1 4
BUS V+
SENSE
6 VO 3
0.01 µF
HCPL-x710* *OPTIONAL FOR BUS V+ SENSE
0.01 µF 7 VIN 2

8 VDD2 VDD1 1

ISO 5 V 5V

Figure 6. Recommended DeviceNet Application Circuit

*Bus V+ Sensing
It is suggested that the Bus V+ attribute would be returned to the
sense block shown in Figure 6 be “hold in bus-off ” (00) value. The
implemented. A locally powered BOI attribute should not be left in
node with an unpowered isolated the “auto-reset” (01) value since
Physical Layer will accumulate this defeats the jabber protection
errors and become bus-off if it capability of the CAN error
attempts to transmit. The Bus V+ confinement.
sense signal would be used to
change the BOI attribute of the
DeviceNet Object to the “auto-
reset” (01) value. Refer to
DeviceNet Specification Volume
1, Section 5.5.3. This would cause
the node to continually reset until
bus power was detected. Once
power was detected, the BOI

5
Recommended PROFIBUS
Application Circuit
In PROFIBUS physical layer close as possible to the input and necessary to make the bus free
implementation, transmission output power-supply pins of the after each master/slave
technologies RS485 and IEC1158-2 optocoupler. For each capacitor, transmission cycle. Specifically,
are adopted by PROFIBUS. The the total lead length between both the HCPL-061N disables the
recommended PROFIBUS ends of the capacitor and the transmitter of the line driver by
application circuit is shown in power supply pins should not putting it into a high state mode.
Figure 7. Since the high-speed exceed 20 mm. The bypass In addition, the HCPL-061N
CMOS optocouplers HCPL-772x/ capacitors are required because switches the RX/TX driver IC into
072x are fully compatible with of the high-speed digital nature of the listen mode. The HCPL-061N
CMOS logic level signals, the the signals inside the optocoupler. offers HCMOS compatibility and
optocouplers are connected the high CMR performance
directly to the transceiver. Two Being very similar to multi-station (1 kV / µs at VCM = 1000 V)
bypass capacitors (with values RS485 systems, the HCPL-061N essential in industrial
between 0.01 and 0.1 µF) are optocoupler provides a transmit communication interfaces.
required and should be located as disable function which is

GALVANIC
ISOLATION
BOUNDARY ISO 5 V
5V

8 VDD2 VDD1 1 ISO 5 V

0.01 µF 7 VIN 2 8
HCPL-772x 1 VCC
Rx 6 VO HCPL-072x 3 R
0.01 µF 0.01 µF
6
A +
5 GND2 GND1 4 4
D
3 SN75176B
DE RT 3 SHIELD
2 7
RE B –
5V ISO 5 V GND
5
1 VDD1 VDD2 8
1M
0.01 µF
Tx 2 Vin 7
0.01 µF
HCPL-772x
0.01 µF 3 HCPL-072x VO 6

4 GND1 GND2 5

ISO 5 V

5V 1 VCC 8
680 Ω
2 ANODE VE 7
1.0 K Ω 0.01 µF
Tx ENABLE 3 CATHODE VO 6

4 GND 5

HCPL-O61N

Figure 7. Recommended PROFIBUS Application Circuit

6
Recommended CC-Link
Application Circuit
CC-Link (Control and Agilent HCPL-772x/072x are fully 20 mm. The bypass capacitors are
Communication Link) is compatible with CMOS logic level required because of the high-
developed to merge control and signals, the optocouplers are speed digital nature of the signals
information in the low-level connected directly to the inside the optocoupler. Two
network (field network) by PCs, transceiver. Two bypass HCMOS-compatible and low cost
thereby making the multivendor capacitors (with values between optocouplers HCPL-2611 transmit
environment a reality. It has data 0.01 µF and 0.1 µF) are required Enable signals to the receiver and
control and message-exchange and should be located as close as driver separately. Alternatively
function, as well as bit control possible to the input and output one dual-channel optocoupler
function, and operates at the power supply pins of the HCPL- HCPL-4661 or HCPL-0738 can
speed up to 10 Mbps. 772x/072x. For each capacitor, the be applied here to save cost
total lead length between both and PCB size.
The recommended CC-Link circuit ends of the capacitor and power
is shown in Figure 8. Since the supply pins should not exceed

VDD2 VDD1
5V 5V
HCPL-7720#500
SN75ALS181NS
VCC VDD1 VDD2 10 K
VCC
DA A R VI VO RD1
DB FIL B RE 0.1 µF 0.1 µF
DG
GND1 GND

DE
Y
D GND2 GND1
Z
SLD
GND HCPL-7720#500
GND
FG VDD2 VDD1

VO VI SD
0.1 µF 0.1 µF
GND GND

HCPL-2611#560

1K VOE NC MPU
BOARD
VDD +
OUTPUT
VO –
0.1 µF 390
HC14 HC14
10 K GND NC

HCPL-2611#560

1K VOE NC
VDD + SDGATEON
VO –
0.1 µF 390
HC14 HC14
10 K GND NC

Figure 8. Recommended CC-Link Application Circuit

7
Appendix 1
Table 1. Popular Field Bus Specifications and Comparison

CC-Link DeviceNet ProfiBus CAN


Max. Devices 64 per master 64 127 nodes 127
or Nodes (124 slaves -4 seg, 3 rptrs)
+ 3 masters
Max. Baud rate 156 Kbps to 10 Mbps 500 kBd 12 MBd 1 Mbd
depending upon (9.6 kBd to 12 MBd
distance are supported)
Max. Extension 1200 m (twisted pair), 100 m at 500 kBd, 100 m between 1 km at 10 kBd,
Master plus 10 500m at 125 kBd, segments at 40 m at 1 MBd
repeaters = 13.2 Km 6 km with repeaters 12 MBd, 24 km (Fiber)
(baud rate and media
dependent)
Network Trunk line, drop Line, Star, or Ring Trunk line,
Topology line with branching drop line
Typical Commonly found Most commonly Commonly found Commonly found
Applications in factory floor found in assembly, in Process control in Automotive
Processes welding, automotive, and large assembly, and Motion
semiconductor, and and material control systems,
material handling handling machines assembly,
machines. welding, and
material handling
machines
Technology Mitsubishi Electric Layer 1, 2: Bosch AG, Siemens Layer 1, 2:Bosch AG,
Developer Layer 7: 1994 Profibus DP Layer 7: CAN
Rockwell Automation (Decentral In Automation,
(Allen-Bradley) Periphery) 1994 Philips, 1995
Profibus PA
(Process Automation)
1995

www.agilent.com/semiconductors
For product information and a complete list of
distributors, please go to our web site.
For technical assistance call:
Americas/Canada: +1 (800) 235-0312 or
(408) 654-8675
Europe: +49 (0) 6441 92460
China: 10800 650 0017
Hong Kong: (+65) 6271 2451
India, Australia, New Zealand: (+65) 6271 2394
Japan: (+81 3) 3335-8152(Domestic/International), or
0120-61-1280(Domestic Only)
Korea: (+65) 6271 2194
Malaysia, Singapore: (+65) 6271 2054
Taiwan: (+65) 6271 2654
Data subject to change.
Copyright © 2002 Agilent Technologies, Inc.
November 7, 2002
5988-8267EN

Potrebbero piacerti anche