Optocoupler Applications in
Industrial Field Bus Networks
Application Note 1321
BUS INTERFACE
OPTICAL ISOLATION
TRANSCEIVER
FIELD BUS
000
XXXXX SENSOR
YYY
000
DEVICE MOTOR
CONFIGURATION MOTOR STARTER CONTROLLER
Recommended Optocouplers
The following optocouplers use system requirements, with data
the latest CMOS IC technology to rate and regulatory requirements
achieve outstanding system playing an important role.
performance. The optocoupler
choice will depend on the overall
HCPL- 7710 0710 7720 0720 7721 0721 0708 0738 7723 0723
Speed 12.5 MBd 25 MBd 15 MBd 50 MBd
Max. 40 ns 60 ns 22 ns
Propagation
Delay
Min. 80 ns 40 ns 100 ns 20 ns
Pulse Width
Max. PWD 8 ns 6 ns 30 ns 2 ns
Max. 20 ns 40 ns 15 ns
Propagation
Delay Skew
Min. CMR 10 kV / µs @ Vcm = 1000 V
Package 300 mil SO8 300 mil SO8 300 mil SO8 SO8 SO8 300 mil SO8
Type DIP8 DIP8 DIP8 Dual DIP8
VDE 0884 *630 *560 *630 *560 *630 *560 *560 *630 *560
[Viorm] Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak Vpeak
UL [Viso] 3750 2500 3750 2500 3750 2500 2500 Vrms 3750 2500
Vrms Vrms Vrms Vrms Vrms Vrms Vrms Vrms
* Option 060 required.
2
Isolation Node Power Supply
Design Considerations
There are an AC line in device
power supplies and DC power in
field bus cables. It is very flexible
for the isolation node to tap
power from the above two
sources. The basic consideration
is that two power supplies must
V+
V+
be isolated across the
optocoupler isolation boundary. NETWORK
POWER HCPL-
TRANSCEIVER
There are three types of solutions, SUPPLY x710/x72x
ASIC/
namely: MICROPROCESSOR
1. Isolation Node Powered by the HCPL-
x710/x72x
Network (Figure 3);
2. Isolation Node with Transceiver
Powered by the Network REG
(Figure 4);
3. Isolation Node Providing Power
ISOLATED
to the Network (Figure 5). DC/DC
CONVERTER
1. Isolation Node Powered by the
DRAIN/SHIELD
Network
POWER
SIGNAL
GALVANIC
If the network power can supply ISOLATION
BOUNDARY
the devices sufficiently, then it is
not necessary to power field
devices from the AC line. As seen
in Figure 3, a non-isolated voltage
Figure 3. Isolation Node Powered by the Network
regulator supplies the transceiver
and half of two optocouplers,
while an isolated DC/DC
converter supplies the controller
and the other side of two
optocouplers.
V+
V+
V-
V-
AC LINE
POWER
SIGNAL
GALVANIC
ISOLATION
BOUNDARY
3
3. Isolation Node Providing Power to
the Network
The method shown in Figure 5 is
recommended when there are a
limited number of devices on the
V+
V+
V-
network that do not require much
power, thus eliminating the need HCPL-
x710/x72x
for separate network power TRANS- ASIC/
supplies. The AC line powers the CEIVER MICROPROCESSOR
HCPL-
field device supply locally and x710/x72x
also powers the isolated power
supply. This supply powers the
REG
network, from which one
regulator derives DC 5 V to power FIELD
the transceiver and the isolated ISOLATED DEVICE
POWER SUPPLY
(network) side of two SUPPLY
optocouplers.
DRAIN/SHIELD
POWER
SIGNAL GALVANIC
Recommended DeviceNet ISOLATION
Application Circuit BOUNDARY AC LINE
A CAN bus is used by DeviceNet
physical layer implementation.
The recommended DeviceNet
application circuit is shown in Figure 5. Isolation Node Providing Power to the Network
Figure 6. Since the high-speed
CMOS optocouplers HCPL-x710/
x72x are fully compatible with
CMOS logic level signals, the two
optocouplers are connected
directly to the CAN transceiver.
Two bypass capacitors (with
values between 0.01 and 0.1 µF)
are required and should be
located as close as possible to the
input and output power supply
pins of the optocoupler. For each
capacitor, the total lead length
between both ends of the
capacitor and the power supply
pins should not exceed 20 mm.
The bypass capacitors are either AC line power to the node
required because of the high- is lost or the node powered-off.
speed digital nature of the signals Specifically, when input power
inside the optocoupler. (VDD1) to the HCPL-x710/x72x
located in the transmit path is
More importantly, the unique eliminated, a RECESSIVE bus
“dual-inverting” design of the state is ensured as the HCPL-
Agilent HCPL-x710/x72x ensures x710/x72x output voltage (VO)
the network will not “lock-up” if goes HIGH.
4
GALVANIC
ISOLATION
ISO 5 V BOUNDARY
5V
LINEAR OR
1 VDD1 VDD2 8 SWITCHING
+ REGULATOR +
Tx0
2 VIN 7
0.01 µF
HCPL-x710 VCC
0.01 µF 3 VO 6 TxD 5 V+
CANH 4 CAN+
4 GND1 GND2 5 +
C4 82C250 3 SHIELD
0.01 µF
CANL 2 CAN–
GND
Rs REF VREF 1 V–
GND
GND RxD
5 GND2 GND1 4
D1
30 V C1 R1 1 M
Rx0
6 VO 3 0.01 µF
0.01 µF
HCPL-x710 500 V
0.01 µF 7 VIN 2
8 VDD2 VDD1 1
ISO 5 V 5V
GND
5 GND2 GND1 4
BUS V+
SENSE
6 VO 3
0.01 µF
HCPL-x710* *OPTIONAL FOR BUS V+ SENSE
0.01 µF 7 VIN 2
8 VDD2 VDD1 1
ISO 5 V 5V
*Bus V+ Sensing
It is suggested that the Bus V+ attribute would be returned to the
sense block shown in Figure 6 be “hold in bus-off ” (00) value. The
implemented. A locally powered BOI attribute should not be left in
node with an unpowered isolated the “auto-reset” (01) value since
Physical Layer will accumulate this defeats the jabber protection
errors and become bus-off if it capability of the CAN error
attempts to transmit. The Bus V+ confinement.
sense signal would be used to
change the BOI attribute of the
DeviceNet Object to the “auto-
reset” (01) value. Refer to
DeviceNet Specification Volume
1, Section 5.5.3. This would cause
the node to continually reset until
bus power was detected. Once
power was detected, the BOI
5
Recommended PROFIBUS
Application Circuit
In PROFIBUS physical layer close as possible to the input and necessary to make the bus free
implementation, transmission output power-supply pins of the after each master/slave
technologies RS485 and IEC1158-2 optocoupler. For each capacitor, transmission cycle. Specifically,
are adopted by PROFIBUS. The the total lead length between both the HCPL-061N disables the
recommended PROFIBUS ends of the capacitor and the transmitter of the line driver by
application circuit is shown in power supply pins should not putting it into a high state mode.
Figure 7. Since the high-speed exceed 20 mm. The bypass In addition, the HCPL-061N
CMOS optocouplers HCPL-772x/ capacitors are required because switches the RX/TX driver IC into
072x are fully compatible with of the high-speed digital nature of the listen mode. The HCPL-061N
CMOS logic level signals, the the signals inside the optocoupler. offers HCMOS compatibility and
optocouplers are connected the high CMR performance
directly to the transceiver. Two Being very similar to multi-station (1 kV / µs at VCM = 1000 V)
bypass capacitors (with values RS485 systems, the HCPL-061N essential in industrial
between 0.01 and 0.1 µF) are optocoupler provides a transmit communication interfaces.
required and should be located as disable function which is
GALVANIC
ISOLATION
BOUNDARY ISO 5 V
5V
0.01 µF 7 VIN 2 8
HCPL-772x 1 VCC
Rx 6 VO HCPL-072x 3 R
0.01 µF 0.01 µF
6
A +
5 GND2 GND1 4 4
D
3 SN75176B
DE RT 3 SHIELD
2 7
RE B –
5V ISO 5 V GND
5
1 VDD1 VDD2 8
1M
0.01 µF
Tx 2 Vin 7
0.01 µF
HCPL-772x
0.01 µF 3 HCPL-072x VO 6
4 GND1 GND2 5
ISO 5 V
5V 1 VCC 8
680 Ω
2 ANODE VE 7
1.0 K Ω 0.01 µF
Tx ENABLE 3 CATHODE VO 6
4 GND 5
HCPL-O61N
6
Recommended CC-Link
Application Circuit
CC-Link (Control and Agilent HCPL-772x/072x are fully 20 mm. The bypass capacitors are
Communication Link) is compatible with CMOS logic level required because of the high-
developed to merge control and signals, the optocouplers are speed digital nature of the signals
information in the low-level connected directly to the inside the optocoupler. Two
network (field network) by PCs, transceiver. Two bypass HCMOS-compatible and low cost
thereby making the multivendor capacitors (with values between optocouplers HCPL-2611 transmit
environment a reality. It has data 0.01 µF and 0.1 µF) are required Enable signals to the receiver and
control and message-exchange and should be located as close as driver separately. Alternatively
function, as well as bit control possible to the input and output one dual-channel optocoupler
function, and operates at the power supply pins of the HCPL- HCPL-4661 or HCPL-0738 can
speed up to 10 Mbps. 772x/072x. For each capacitor, the be applied here to save cost
total lead length between both and PCB size.
The recommended CC-Link circuit ends of the capacitor and power
is shown in Figure 8. Since the supply pins should not exceed
VDD2 VDD1
5V 5V
HCPL-7720#500
SN75ALS181NS
VCC VDD1 VDD2 10 K
VCC
DA A R VI VO RD1
DB FIL B RE 0.1 µF 0.1 µF
DG
GND1 GND
DE
Y
D GND2 GND1
Z
SLD
GND HCPL-7720#500
GND
FG VDD2 VDD1
VO VI SD
0.1 µF 0.1 µF
GND GND
HCPL-2611#560
1K VOE NC MPU
BOARD
VDD +
OUTPUT
VO –
0.1 µF 390
HC14 HC14
10 K GND NC
HCPL-2611#560
1K VOE NC
VDD + SDGATEON
VO –
0.1 µF 390
HC14 HC14
10 K GND NC
7
Appendix 1
Table 1. Popular Field Bus Specifications and Comparison
www.agilent.com/semiconductors
For product information and a complete list of
distributors, please go to our web site.
For technical assistance call:
Americas/Canada: +1 (800) 235-0312 or
(408) 654-8675
Europe: +49 (0) 6441 92460
China: 10800 650 0017
Hong Kong: (+65) 6271 2451
India, Australia, New Zealand: (+65) 6271 2394
Japan: (+81 3) 3335-8152(Domestic/International), or
0120-61-1280(Domestic Only)
Korea: (+65) 6271 2194
Malaysia, Singapore: (+65) 6271 2054
Taiwan: (+65) 6271 2654
Data subject to change.
Copyright © 2002 Agilent Technologies, Inc.
November 7, 2002
5988-8267EN