Princess Noura Bint Abdulrahman University for Women Project Joint venture

Riyadh, Kingdom of Saudi Arabia El Seif/CCC


part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 8:13 AM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

The subject of this SCR are steel brackets which supports the supply / return steel pipes
for the radiators in the Chiller builidng.

For Your kindly approval , please find attached:


> Calculations for the steel bracket using steel grade 40 as per ASTM A36.
> The sketch for adopted design, and
> Related references,
> Printed section property pages for adopted steel sections.

Please note that the site work for Chiller building is in progress, and approve proposal for
our future actions.

Aleksandar Jankovic
senior structural design engineer
Building / area: Chiller Building rev: THE PIPE SUPPORT Sheet:
issued for: APPROVAL 0 steel bracket 0 0 1

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 8:13 AM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

1. INPUT DATA
The weight of fluid……………………………………………………. 1000 kg/m3
The weight of structural steel……………………………………….. 7860 kg/m3
The yield strength of the structural steel Py=……………………. 245 N/mm2
Adopted bolts are hot deep galvanized with grade………………. 4.6 GR
Adopted diameter of the bolts. Db=……………………………….. 12 mm
The strength of fillet weld as per AISC ASD (60% of Py), Pyw= 147 N/mm2
The electrode classification number Fexx=Pyw=………………… 147 N/mm2
The outside pipe diameter 4"= 114.3 mm, with total L=.. 4.5 m,T= 8 mm
The outside pipe diameter 6"= 168.3 mm, with total L=.. 4 m,T= 8 mm
The outside pipe diameter 8"= 219.1 mm, with total L=.. 3 m,T= 9 mm
The weight of 100 mm valve…… 33 kg, with total No=.. 2 pcs
The weight of 150 mm valve…… 50 kg, with total No=.. 2 pcs
The weight of 200 mm valve…… 85 kg, with total No=.. 1 pcs
The distance between pipe CL and the steel support…………… 205 mm
Assumed pressure variation of.. 0.5 bars, due to the pump work regime.

2. THE CONCEPT
The concept is shown on the following figures.
The lateral stability of pipe is provided by its connections to the radiator.

figure 1

3. THE LOADS
3.1 The dead load
3.1.1 The supply pipes
Pipe 100 mm dia, total length= 2.4 m, total weight G1= 50.371709 kg
Pipe 150 mm dia, total length= 4.7 m, total weight G2= 148.75568 kg
Pipe 200 mm dia, total length= 4.9 m, total weight G3= 228.67402 kg
The water weight, pipe 100 mm……………………………….G4= 6.4086144 kg
The water weight, pipe 150 mm……………………………….G5= 18.925659 kg
The water weight, pipe 200 mm……………………………….G6= 29.0933874 kg
The weight from valves………………………………………….G7= 251 kg
total weight Gt= 733.22908 kg,= 7.33 kN
Building / area: Chiller Building rev: THE PIPE SUPPORT Sheet:
issued for: APPROVAL 0 steel bracket 0 0 2

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 8:13 AM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

3.1.2 The return pipes


Pipe 100 mm dia, total length= 5 m, total weight G1= 104.94106 kg
Pipe 150 mm dia, total length= 2 m, total weight G2= 63.30029 kg
Pipe 200 mm dia, total length= 2.5 m, total weight G3= 116.67042 kg
The water weight, pipe 100 mm……………………………….G4= 13.35128 kg
The water weight, pipe 150 mm……………………………….G5= 8.053472 kg
The water weight, pipe 200 mm……………………………….G6= 14.843565 kg
The weight from valves………………………………………….G7= 251 kg
total weight Gt= 572.16009 kg,= 5.72 kN

Dead load taken in to consideration……………………………G= 7.3322908 kN G= 7.33229 kN

3.2 The live load


Water surge due to pressure variation………………………….L= 1.5873175 kN L= 1.58732 kN

4.0 THE LOAD ANALYSES


The load distribution on the steel supports will be as follows (figure 2):
dead load:
vertical force……………………………………………. 1.8330727 kN
bending moment……………………………………….. 0.3757799 kNm
live load:
vertical force……………………………………………. 0.3968294 kN
bending moment……………………………………….. 0.08135 kNm

figure 2

5.0 THE CHECK OF THE STEEL FRAME


Is calculated in STAAD PRO 2006 and input / output files are shown on following pages
including AISC ASD design criteria
Building / area: Chiller Building rev: THE PIPE SUPPORT Sheet:
issued for: APPROVAL 0 steel bracket 0 0 3

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 8:13 AM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

7. THE CHECK OF STEEL STUD WELDED TO THE STEEL PIPE figure 2


Adopted section………………… UB 127x76x13
The section property are as:
Aa= 1650 mm2
Wx= 75000 mm3
Shear, Pscap= 242.55 > 3.201229 kN-total shear…………………………………….. safe
Bend, Mbcap= 18.375 > 0.656252 kNm-total moment……………………………….. safe
Stress ratio R=((Mb/Mbcap)^2+(Ps/Pscap)^2))^0.5……………… 0.0380751 < 1……….. safe
since all checks are safe adopted section is safe for using

8. THE CHECK OF THE WELD BETWEEN STUD / PIPE


The length of the weld…….Lw= 100 mm
Total shear force……………….. 3.201229 kN
Adopted size of weld ………….. 4 mm
Shear, Pscap= 82.32 > 3.201229 kN………………………………………………….. safe

9. THE CHECK OF BOLTS BETEEN STUD / STEEL BEAM


Total benidng moment..…Mb= 0.574902 kNm
Distance between two bolts L= 50 mm
Tension bolt force……..…….F= 11.49804 kN
Tension bolt strength……….Pt= 240 N/mm2
Tension capacity………..Ptcap= 21.70368 > 11.49804 kN……………………………….. safe
Building / area: Chiller Building rev: THE PIPE SUPPORT Sheet:
issued for: APPROVAL 0 steel bracket 0 1 6