Limit: DC burden 50 watts typically. (Refer to the reference technical manual page 24).
SRR-3012-REL670 DIST&DEF
SITE INSPECTION AND TEST RECORD ΑΤΣ
Description: Contract no.: Record no. :
FPFM1-REL670- DISTANCE&DEF RELAY 30631089/00 STR-3011
Customer: Contractor: Sheet:
SEC-COA AL FANAR 2 of 15
Site: Drawing ref.: Project no.:
S/S 9021 S
SRR-3012-REL670 DIST&DEF
SITE INSPECTION AND TEST RECORD ΑΤΣ
Description: Contract no.: Record no. :
FPFM1-REL670- DISTANCE&DEF RELAY 30631089/00 STR-3011
Customer: Contractor: Sheet:
SEC-COA AL FANAR 4 of 15
Site: Drawing ref.: Project no.:
S/S 9021 S
3 phase 40
-Freja general mode, sequence, 3 stages.
-1ST STAGE: 3phase V&I to get the impedance outside the outer zone area (I=Ir & V/I>Zouter and T =1 SEC).
-2ND STAGE: 3phase V&I to get the impedance between the outer and the inner zone area (I=Ir, V/I<Zouter,
V/I >Zinner and adjust the time; start with 30 msec; till you get PSD start).
-3RD STAGE: 3phase V&I to get the impedance inside zone1 (I=Ir & V/I<Zzone1 and T =0.1 SEC).
SRR-3012-REL670 DIST&DEF
SITE INSPECTION AND TEST RECORD ΑΤΣ
Description: Contract no.: Record no. :
FPFM1-REL670- DISTANCE&DEF RELAY 30631089/00 STR-3011
Customer: Contractor: Sheet:
SEC-COA AL FANAR 5 of 15
Site: Drawing ref.: Project no.:
S/S 9021 S
Indication :
3.4.6.2. No carrier receive + Zone 2 fault
3.4.6.3. Trip Time :
Indication :
3.4.6.4. Zone 1 fault
Indication :
Carrier send time: ms.
T send min. : ms (100 ms setting)
* To check the T send min. time; the injection time should be less than 100ms.
Limit: ± 10 ms for operating time (see the tech. ref. manual page 122).
SRR-3012-REL670 DIST&DEF
SITE INSPECTION AND TEST RECORD ΑΤΣ
Description: Contract no.: Record no. :
FPFM1-REL670- DISTANCE&DEF RELAY 30631089/00 STR-3011
Customer: Contractor: Sheet:
SEC-COA AL FANAR 6 of 15
Site: Drawing ref.: Project no.:
S/S 9021 S
Distance Protection
SOTF - ON PHASE Trip Time indications
(msec)
*Internal SOTF with Select A
impedance mode. B LED4 SOTF TRIP
C
External SOTF with manual A
Close pulse. B LED4 SOTF TRIP
C
* Make at setting autoinit (on).
Testing guidelines: refer to the function logic and the commissioning manual page 140.
10% 10% B
(6.6) (0.1)
C
3U0= Ua + Ub + Uc
3I0= Ia + Ib + Ic
Limit: ± 1 % of Ur for 3U0> and ± 1 % of Ir (see the tech. ref. manual page 468 table 256).
Testing guidelines: refer to the function logic and the commissioning manual page 185.
GENERAL MODE
-1ST STAGE: 3PHASE V&I HEALTHY CASE.
- DECREASE ONE PHASE VOLTAGE TILL THE INDICAION LED FUSE FAIL APPERAS.
- DECREASE THE SAME PHASE CURRENT TILL THE INDICTION LED FUSE FAIL RESET.
3.4.9.1 Fuse failure operating time: m sec.
-1ST STAGE: 3PHASE V&I HEALTHY CASE.
-2ND STAGE: PUT FUSE FAIL CONDITION (TAKE CONTACT FUSE FAIL)
3.4.9.2 Check the blocking of the relay when the general block functions
(VT MCB TRIP) is activated [ ].
3.4.9.3 Check the latching facility of fuse fail function [ ].
SRR-3012-REL670 DIST&DEF
SITE INSPECTION AND TEST RECORD ΑΤΣ
Description: Contract no.: Record no. :
FPFM1-REL670- DISTANCE&DEF RELAY 30631089/00 STR-3011
Customer: Contractor: Sheet:
SEC-COA AL FANAR 7 of 15
Site: Drawing ref.: Project no.:
S/S 9021 S
3.4.9.5 Check the relay operation if a fault occurred during the fuse fail [ ].
* General mode:
- 1ST STAGE: FUSE FAIL CONDITION (TAKE TIME 1 SEC)
-2ND STAGE: FAULT CONDITION
3.4.9.6. Check the blocking of the relay when the general block functions
(DISCPO binary input) is activated [ ].
Simulate normal operating conditions 3PHASES V&I HEALTHY CASE
Active DISCPO binary input The BLKU Signals appear without any time delay
The BLKZ and 3PH Signals not appear.
Only distance protection function operates.
-2ND STAGE: PUT 3 PHASE (V) TO ACHIVE THE DLD AND FUSE FAIL FOR MORE THAN 5 SEC.
-USE CONTACT FUSE -VTF3PH
From st2 change the voltages and currents in all three phases simultaneously The voltage change should be greater then set DU>& The voltage
change should be Lessr than set DI<
Connect nominal dc voltage to the CBCLOSED binary input.
The BLKU and BLKZ Signals appear without any time delay .BLKZ signal will be activated ,only if the DLD is not activated at the same time.
Also 3PH Should appear after 5 sec if the remaining voltage levels are lower than the set UDLD < VDLDPU OF THE DLD Function.
Apply normal conditions the BLKU, BLKZ and 3PH signals should reset.
DU> OP = ( 66.4-voltage get from stage2 when fuse fail alarm get) and also DI< =( 1.0 - CURRENT get from stage2 when fuse fail alarm get)
SRR-3012-REL670 DIST&DEF
SITE INSPECTION AND TEST RECORD ΑΤΣ
Description: Contract no.: Record no. :
FPFM1-REL670- DISTANCE&DEF RELAY 30631089/00 STR-3011
Customer: Contractor: Sheet:
SEC-COA AL FANAR 8 of 15
Site: Drawing ref.: Project no.:
S/S 9021 S
Values Sec. Values Prim. values Values Sec. Values Prim. Values
UL1 IL1
UL2 IL2
UL3 IL3
UL4 IL4
- -
UL1 – UL2 P
- -
UL2 – UL3 Q
- -
UL3 – UL1 F
Pick-up Drop-off
SET TIME
Disturbance
Angle OP TIME
Value (mA) Value (mA) recorder
SEC
0 FORWARD
0.0
FORWARD
60 1.0
1.5 FORWARD
145
- - REVERSE
155
- - REVERSE
225
- - REVERSE
270
- - REVERSE
325
1.0 FORWARD
335
Pick-up Drop-off
Setting
INNonDir Value (mA) Value (mA)
Indication
0.05 X Ibase
=0.05 A
0.20 x 67N/51N DELAY
Ibase=0.20 A TRIP LED 6
0.5 X Ibase
=0.50 A
1.0X base=1.0
A
* Voltage accuracy: ± 1 % of Ur (see tech. ref. manual page 648 table 342)
Measured Trip time = ________________ms
- - ( time accuracy ± 0.5% ± 10 msec).
-See the technical reference manual–page:648table 342.
b. Apply a reverse fault with CR and check for the above condition that
no WEI trip is given. : ___________
3.5.10 CURRENT REVERSAL LOGIC CHECK:Curr Rev = ON
a) Apply a reverse fault to check: t pick up (I > I setting and V > V setting
Freja general mode, sequence, 3 stages 1ST STAGE: 3phase V&I to get the forward fault
2ND STAGE: 3phase V&I to get the get reverse fault T≥Tdelay seting
3RD STAGE: 3phase V&I to get the forward fault T≥Tdelay seting
T pick up:
T pick up Operating time Contact Indication
(ms) ms
0 mSec U11.115.X131:13
500mSec U11.115.X131:14
1000mSec