EH2 EH3
Special D Function EX SX Attribute Latched Default
SV SV2
SS SC On RUN STOP
D1000* Scanning watchdog timer (WDT) (Unit: ms) 200 - - R/W NO 200
Displaying the program version of EH2/EH3 # # #
D1001 R YES #
DVP-PLC (initial factory setting) Others - - -
Program capacity
D1002* # -> EH2:15,872; SA: 7,920; ES: 3,792; # - - R NO #
EH3/SV2: 30000
Sum of program memory
D1003 # -> EH2: -15,873; SA: -7,920; ES: -3,792; - - - R YES #
EH3/SV2: -30000
D1004* Syntax check error code 0 0 - R NO 0
Number of times the low voltage of the battery
D1007 - - - R Yes 0
is recorded (EH2 and V1.8 above)
D1008* STSC address when WDT is On 0 - - R NO 0
ES/SA: recording number of occurrences of LV
signals
D1009 - - - R YES 0
EH2/SV/EH3/SV2: register for SRAM lost data
error code
D1010* Current scan time (Unit: 0.1ms) 0 - - R NO 0
D1011* Minimum scan time (Unit: 0.1ms) 0 - - R NO 0
D1012* Maximum scan time (Unit: 0.1ms) 0 - - R NO 0
0~32,767 (unit: 0.1ms) accumulative
D1015* 0 - - R/W NO 0
high-speed timer
After a PLC is powered, it will delay detecting
the extension modules connected to it for a
D1016 V1.62 - - - R/W YES K25
certain amount of time. (Time unit: 100ms) The
setting range is K20 ~ K50.
D1018* PI (low byte) H’0FDB H’0FDB H’0FDB R/W NO H’0FDB
D1019* PI (high byte) H’4049 H’4049 H’4049 R/W NO H’4049
X0 ~ X7 input filter (Unit: ms); modulation
D1020* 10 - - R/W NO 10
range: 2~20ms
ES/EH/EH2/SV: X10 ~ X17 input filter (Unit:
ms)
D1021* 10 - - R/W NO 10
SC: X10 ~ X17 input filter (time base: scan
cycle), range: 0 ~ 1,000 (Unit: times)
Multiplied frequency of A-B phase counters for
D1022 0 - - R/W NO 0
ES/SA
Register for detected pulse width, Unit: 0.1ms
D1023* (Available in ES/EX/SS_V6.4, SA/SX_V1.6, 0 - - R/W NO 0
SC_V1.4 and versions above)
D1025* Code for communication request error 0 - - R NO 0
When M1156 is On, the (32-bit) pulse Low
D1026* number for masking Y0 is set. If the 0 0 -- R/W NO 0
word
value is less than or equal to 0, the
function will not be enabled. (Default High
D1027* 0 0 -- R/W NO 0
value: 0) word
D1028 Index register E0 0 - - R/W NO 0
D1029 Index register F0 0 - - R/W NO 0
D1030* Number of Y0 output pulses (low word) 0 - - R NO 0
D1031* Number of Y0 output pulses (high word) 0 - - R NO 0
D1032 Number of Y1 output pulses (low word) 0 - - R/W NO 0
D1033 Number of Y0 output pulses (high word) 0 - - R/W NO 0
D1034 Work mode of frequency measurement card - - - R YES 1
D1035* No. of input point X as RUN/STOP - - - R/W YES 0
D1036* COM1 communication protocol H’86 - - R/W NO H’86
D1037 Repetition time of HKY key - - - R/W NO 0
Delay time of data response when PLC MPU as
slave in RS-485 communication, range: 0 ~
10,000 (unit: 0.1ms)
D1038* SA: delay time for sending the next - - - R/W YES 0
communication data in PLC LINK (unit for
SA/SX/SC: 1 scan cycle; EH2/SV/EH3/SV2:
0.1ms)
D1039* Fixed scan time (ms) 0 - - R/W NO 0
Normally On contact
in PLC RUN Keeps being On
M1001:
M1001 (B contact) is constantly “On” during operation and detection. When PLC is in RUN status, M1001 remains
“On”.
M1002:
M1002 is “On” during the first scan when PLC starts to RUN and remains “Off” afterward. The pulse width = 1 scan
time. Use this contact for all kinds of initial settings.
M1003:
M1003 is “Off” during the first scan when PLC starts to RUN and remains “On” afterward. M1003 enables
negative-direction (“Off” immediately when RUN) pulses.
PLC RUN
M1000
M1001
M1002
M1003
scan time