Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Introduction
Power System Control and Operation In actual power system, the active power (P) and the
reactive power (Q) demand varies continuously.
Topic: Frequency Control and AGC Steam input to generators must be regulated
continuously to meet the active power (P) demand,
Dr C
C.Y.
Y Chung so that the frequency can be kept constant. ( P-f
Tel: 27666165 control)
Email: eecychun@polyu.edu.hk While
Whil the
th excitation
it ti fi
field
ld off the
th generator
t is
i
controlled to match the reactive power (Q) demand
Room CF610,, EE Department,
p , PolyU
y in order to maintain a constant voltage.
voltage (Q-
(Q V
(ftp://www.ee.polyu.edu.hk/cychung/ee505/fre control)
q
quency_control.pdf)
y p ) Nowadays, power system are kept in normal
(Reference Book: “Power System Stability and Control” operating state by means of continuous, automatic
by Prabha Kundur, McGraw Hill Inc., 1993) closed-loop control.
1 2
turbine
governor
Pm system
potential
+
transformer fspec
voltage V t
TPUT
reactive power Q
active power Pe
OUT
frequency f
Vref excitation Efd rotor speed
+ system
power
system
Epss stabilizer 3 4
Turbine Speed Governing System Load Frequency Control
Fly ball speed governor: This is the heart of the system which senses • For satisfactory operation of a power system, the frequency should
the change in speed (frequency). As the speed increases the fly remain nearly constant.
balls move outwards and the point B on linkage mechanism moves • Constancy of speed of motor drives is particularly important for
downwards. The reverse happens when the speed decreases. satisfactory performance of generating units as they are highly
dependent on the performance of all the auxiliary drives
Hydraulic amplifier: It comprises a pilot valve and main piston associated with the fuel,, the feed-water and the combustion air
arrangement. t LLow power level
l l pilot
il t valve
l movementt is i converted
t d supply systems.
into high power level piston valve movement. This is necessary in • As frequency is a common factor throughout the system, a change
order to open or close the steam valve against high pressure in active power demand at one point is reflected throughout the
system.
system system
t b
by a change
h in
i frequency.
f Because
B there
th are many
Linkage mechanism: ABC is a rigid link pivoted at B and CDE is another generators supplying power into the system, some means must be
rigid link pivoted at D. This link mechanism provides a movement provided to allocate change in demand to the generators.
to the control
cont ol valve
al e in p
proportion
opo tion to change in speed
speed. It also • A speed governor on each generating unit provides the primary
provides a feedback from the steam valve movement (link 4). speed control function, while supplementary control originating at
a central control centre allocates generation.
Speed changer: It provides a steady state power output setting for the • In an interconnected system with two or more independently
t bi
turbine. It d
downward d movementt opens th the upper pilot
il t valve
l so controlled areas, in addition to control of frequency, the
that more steam is admitted to the turbine under steady generation within each area has to be controlled so as to maintain
conditions (hence more steady power output). The reverse scheduled power interchange.
happens for upward movement of speed changer. changer • The
h controll off generation and
d frequency
f is commonly l referred
f d to
5 as Load Frequency Control (LFC). 6
1. Generator Model
II Modeling of power system
II.
The relationship between rotor speed, electrical and
Valve/gate Generator
Tm
Pm Pe
q
mechanical torques.
Steam Turbine G d ( )
or water Ta 2 H Tm Te 2 H Ms
Te dt
Speed Load PL Where H = inertia constant, M = 2H
Governor = angular
g acceleration
Therefore, Pm Pe Tm Te The frequency-dependent load change can be denoted
Pm Pe Ms by:
PL ( freq ) D
+ 1
Pm
–
Ms where D is the percent change in load divided by
percent change on frequency
Pe 9 10
Non-frequency Frequency 1
= sensitive From the block diagram:
g (Pm PL D )
iti load
l d + sensitive
iti load
l d
change change
Ms
( Ms D) (Pm PL )
IIncorporating
ti thi
this into
i t the
th previous
i block
bl k
1
diagram, we get:- (Pm PL )
M sD
+ 1
Pm Ms
Pm
+
1
– MsD
–
–
PL D
11 PL 12
Example 1 Answer
A small system consists of 4 identical 500MVA
500
H 5 .0 ( ) 4 5 .0
generating units feeding a total load of 2000
1020MW. The inertia constant H of each unit M 2 H 10 . 0
is 55.0
0 on 500 MVA base
base. The load varies by
1.5% for a 1% change in frequency. When Expressing D for the remaining load (1020-20
there is a sudden dropp in load byy 20MW. =1000MW) on 2000MVA
(a) Determine the system block diagram with D 1.5
1000
0.75
constant H and D expressed
p on 2000MVA 2000
base. The equivalent block diagram is:-
((b)) Find the frequency
q y deviation,, assuming
g + 1
that there is no speed-governing action. Pm 10 s 0.75
–
13 PL 14
Block diagram of a speed governor with droop Percent speed regulation or droop
The value of R (droop) determines the steady-state speed versus load
Y characteristic of the generating unit.
r – 1
K s
The ratio of speed deviation (r) or frequency (f) to change in
value/gate position (Y) or power output (P) is equal to R.
–
It can be expressed in percent as
R R
percentt speed
d or frequency
f change
h
percent power output change
100
f
R
f f Frequency (Hz ) P
NL FL
100 f f f 0
1 f0
TG fNL
KR f0 f
For example, a 5% droop or fFL
+ 1 1 regulation means that a 5%
Y P
ref R 1 s TG frequency deviation causes
– r 100% change in value position 100
or power output
output.
19 Percent power output 20
Load sharing by parallel units Time response
If two or more generators with drooping governor characteristics Because of the droop characteristic, the increase in power output is
are connected to a ppower system,
y , there will be a unique
q frequency
q y p
accompanied byy a steady-state
y speed
p or frequency
q y deviation.;;
at which they will share a load change.
f f P1 R r
R1 ; R2 2 ref Time
P1 P2 P2 R1
ss
Frequency (Hz ) Frequency (Hz )
Unit 1 Unit 2 Pm
f0
f
f’ Pm
Pm 0 Time
P1 P2
Power output Power output
Response of a generating unit with a governor having
P1 P1’ P2 P2’ 21 speed-droop characteristic 22
–
R1 Consider an interconnected system as in the
Prime
Pmech1
1 previous block diagram:
Governor
mover + M1 s D1
+ – 1
PL1
–
+ Assume a load change of PL1 in area 1,
Ptie
Load reference T hile PL2 = 0
while
Load reference s
PL2 – –
2 At stead
steady-state,
state the ffrequency
eq enc will
ill be
+ +
Prime 1 constant and same for both areas.
Governor
mover + M 2 s D2 1 = 2 =
Pmech2
–
1
R2 37 38
R1
Then substitute into (6), we get:-
Pmech2 (4) 1
R2 PL1 D 2
Ptie R2 PL1 2 (8)
1 ti
(1) (3), we have : - Ptie PL1 D1 (5) 1
1
D1 D 2 1 2
R1 R1 R 2
1 Equations (1) to (8) are for new steady-state
(2) (4), we have : - Ptie D 2 (6)
R2 conditions
co dto s a after
te load
oad cchange.
a ge
39 40
An increase in area 1 load by PL1 results in a
frequency reduction in both areas and a tieline Frequency error for
f step change
h in load
l d
flow of P12. A negative
g P12 is indicative of flow Load
from area 2 to area 1. PL1 Step load change
Ti
Time
Similarly, for a change in area 2 load by PL2, we Frequency
error
have
Response with no governor action
PL2 PL2 +
(9) PL1
1
1
D1 D 2 1 2 –
D1 D 2
R1 R 2
Frequency
1
PL2 D1 error + Response with governor action
R1 PL2 1
Ptie P12 P21 (10) – PL1
1
1
D1 D 2 1 2
1 1
D1 D 2
R1 R 2 41
R1 R 2 42
Basis for selection of bias factor Basis for selection of bias factor
• From steady-state performance considerations, • From dynamic performance considerations,
the choice of bias factor is not important
important. the choice of bias factor is more important
important.
• Any combination of the area control errors • For example, a sudden increase in load will
containing components of tieline power result
lt in
i a decrease
d in
i system
t frequency,
f
deviation and frequency deviation will result in
steady-state
y restoration of the tie flow and followed by governor response which limits
frequency since the integral control action th maximum
the i frequency
f excursion
i andd
ensures that ACE is reduced to zero. subsequently (typically on the order of 10s)
bi
brings the
th frequency
f deviation
d i ti backb k to
t a
ACE1 P12 B1f 0 value, which determined by the regulation
ACE2 P21 B2 f 0 characteristics
h t i ti off both
b th systems:
t
PL1
P12 0 and f 0 f R
47 1 2 48
• At this p
point,, there is a deviation of tieline flow Performance of AGC under normal and
from the scheduled value. The supplementary abnormal conditions
control ((which is much slower than the primary
p y • Under normal conditions,
conditions with each area able to carry
speed control) will now commence responding. out its control obligations, steady-state corrective
action of AGC is confined to the area where the
• With B1 = 1 and B2 = 2 : deficit or excess of generation occurs
occurs. Interarea
PL1 power transfers are maintained at scheduled levels
ACE1 P12 B1f R ( 2 1 ) PL1 and system frequency is held constant.
1 2
• U d abnormal
Under b l conditions,
diti one or more areas may
PL1 be unable to correct for the generation-load
ACE2 P12 B2 f R ( 2 2 ) 0
1 2 mismatch due to insufficient g generation reserve on
• Only the supplementary control in area 1 will AGC. In such h an event, other
h areas assist by b
permitting the interarea power transfers to deviate
respond
p to the load change
g and changeg from scheduled values and byy allowing g system
y
generation so as to bring ACE1 to zero. The frequency to depart from its pre-disturbance value.
Each area participates in frequency regulation in
load change
g in area 1 is unobservable to the proportion
p p to its available regulating
g g capacity
p y relative
supplementary control in area 2. 49
to that of the overall system. 50
Change in system frequency due to loss of 1,000MW load in area 1 is (b) (i) Loss of 1,000MW load in area 1
PL ((1000)
f 0.04619Hz Area 1 has
h a generating capacity off 4,000MW on
1 / R D 20,666,67 983.33
Load changes in the two areas due to increase in frequency are supplementary control, and this will reduce generation so
PD1 D1f 316.67 0.04619 14.63MW as to
t b bring
i ACE1 tot zero. Si
Similarly,
il l area 2 generation
ti on
PD 2 D2 f 666.67 0.04619 30.79MW supplementary control will keep ACE2 at zero:
ACE1 B1f P12 0
Generation changes in the two areas due to speed regulation are
1
PG1 f 6,666.67 0.04619 307.93MW
ACE2 B2 f P12 0
R1
1
PG 2 f 14,000.00 0.04619 646.65MW
R2
Total effective load damping of the two areas is
Hence,
A
Area
Load
1
= 20,000-1,000+14.63
A
Area
Load
2
= 40,000+30.79
f 0 P12 0
= 19,014.63MW = 40,030.79MW Area 1 ggeneration and load are reduced byy 1,000MW.
,
Generation= 19,000-307.93 Generation= 41,000-646.64
= 18,692.07MW = 40,353.35MW There is no steady-state change in area 2 generation and load,
Tieline power flow from area 2 to area 1 is 322.56MW or the tieline flow.
Steady-state frequency is 60.04619 Hz
55 56
(b) (ii) Loss of 500MW generation, carrying part of the (b) (iii) Loss of 2,000MW generation, not carrying spinning reserve, in
spinning reserve,
reserve in area 1.
1 area 1
Area 1 has a spinning reserve of 1,000MW spread uniformly Half of the generation loss will be made up by the 1,000MW spinning
over a generation of 44,000MW
000MW capacity (3
(3,000MW
000MW reserve on supplementary
pp y control in area 1. When this limit is reached,,
area 1 is no longer able to control ACE. Supplementary control in area
generation + 1,000MW reserve).
2, however, is able to control its ACE. Hence,
Spinning reserve lost with generation loss is
500 ACE2 B2 f P12 0 P12 B2 f 5,000f
1,000 166.67MW
3,000 There is thus a net reduction in system frequency.
frequency This causes a
Spinning reserve remaining is 1,000-166.67=833.33MW. reduction in loads due to frequency sensitivity.
which is sufficient to make up
p for 500MW generation
g loss. Area 1 load damping:
p g 20,000 100
Hence, the generation and load in two areas are restored to
D1 1 333.33MW/Hz
MW/H
100 60
their pre-disturbance values. The balance of generation loss in area 1 is made up by a reduction in
There is no change in tieline flow or system frequency load and tieline flow from area 2. Hence,
(However, spinning reserve is reduced from 1,000MW to 1,000 D1f P12 333.33f 5,000f
333.33MW) 57 f 0.1875Hz 58
Change in area 1 load is (b) (iv) Tripping of the tieline, (no change in interchange schedule)
The supplementary control in area 1 attempts to maintain interchange
PD1 D1f 333.33 (0.1875) 62.5MW
schedule at 1,000MW. Hence,
The tieline flow change is
AC 1 B1f1 P12 2,500
ACE 00f1 1,000 0 f1 0.4Hz
P12 5,000 (0.1875) 937.5MW Change
g in area 1 load is
Change in area 2 load is
PD1 D1f 333.33(0.4) 133.33MW
PD 2 D2 f 666.67 (0.1875) 125MW Similarly for area 2:
Area 1 Area 2 1,000
Load = 20,000
20 000-62
62.5
5 Load = 40,000
40 000-125
125.0
0
f 2 0.2Hz PD 2 666.67 0.2 133.33MW
5,000
= 19,937.5MW = 39,875.0MW Area 1 Area 2
Generation= 19,000-1,000 Generation= 41,000-125+937.5 Load = 20,000-133.33 Load = 40,000+133.33
= 18,000.0MW = 41,812.5MW = 19,866.67MW = 40,133.33MW
Tieline power flow from area 2 to area 1 is 1,937.5MW Generation= 19,866.67MW Generation= 40,133.33MW
St d
Steady-state
t t frequency
f is
i 60-0.1875=59.8125Hz
60 0 1875 59 8125H f1= 59.6Hz
59 6H f2 = 60.2Hz
60 2H
59 60
(b) (v) Tripping of the tieline, with interchange schedule IV. Implementation of AGC
switched to zero • The control actions are determined for each control area at a
central location called the dispatch centre.
• The tieline flows,
flows system frequency and unit MW loadings is
With interchange schedule switched to zero, area 1 telemetered to the central location.
supplementary control will pick up 1,000MW generation • Control actions are determined by digital computer and transmitted
to make up for loss of import power.
power through the same telemetry channels to the generators.
Similarly,
Si il l area 2 supplementary
l t control
t l reduces
d
generation by 1,000MW to compensate for loss of
export The generation in each area is equal to the
export.
respective loads and the area frequencies are equal to
60Hz.
61 62
• Market objective
Market operator: to minimize AGC payments to Gencos
while encourage Gencos to provide sufficient regulation
power.
p A synchronous area in AGC frameworks
Gencos: maximize their profits as allocations are made. 83 84
AGC model and bilateral contracts New information signals
g due to possible
p various contracts
For a system with N control areas (Discos) and n Gencos: between Disco i and other Discos and Gencos:
Generation p participation
p factor of the generator
g of Genco Ptie -i,i scheduled Export power Import power
k in area j following the load change i is gpfkj,i Area i
((based on a specified
p bilateral contract).
) N n n N
Generator owned by
Gencos 1…k,…n gpf ki , j PLj - gpf kj ,i PLi
Generation participation matrix (GPM):
Disco i j 1 k 1 k 1 j 1
gpf11,i gpf12,i gpf1( N 1),i gpf1N ,i
j i j i
gpf gpf 2 N ,i
21,i gpf 22,i gpf 2( N 1),i Change
g of Pm ((Genco k):
) N
GPM
gpf ( n 1)1,i gpf ( n 1) 2,i gpf ( n 1)( N 1),i
gpf ( n 1) N ,i
For load change in area i only Pmk gpf
j 1
j1
kj ,i PLi
Nine-bus
Nine bus system
Conventional generation:
567.5 MW total
PV unit: 2MW Wind velocityy and output
p power
p of RES units
Wind farm: 30MW total 91 92
Dashed line shows response with PV unit only