Area of the Plan = 100 m2
No. of Storey = 5 (G+4)
Height of each Storey = 4 m (GF)
3.5 m (R
Plan of the Building
Dimensions of Elements
Storey Height Qi
4 18 m 180.24 kN
3 14.5 m 169.74 kN
2 11 m 97.70 kN
1 7.5 m 45.41 kN
GF 4m 12.92 kN
Wind Load Calculations
The wind load is calculated as per IS 875(Part-III)
VZ = Vb*k1* k2* k3
where ,
Vz = design wind speed at any height z in m/s;
k1 = probability factor (risk coefficient)
k2 = terrain, height and structure size factor
k3 = topography factor.
Data available:
Vb= design wind speed at any height z in m/s
=33 km/h
k1 = probability factor (risk coefficient) =1.0
k2 = terrain, height and structure size factor
=category 3; building class B
k3 = topography factor=1.0
Design Wind Pressure:
PZ =0.6VZ2
where,
PZ = design wind pressure in N/m2 at height z
VZ = design wind velocity in m/s at height z
Height K2 Vz Pz
(m/s) (kN/m2)
Up to 9 m 0.88 29.04 0.506
height
9m to 15m 0.94 31.02 0.577
15m to 18m 0.98 32.34 0.627