Ruchira Papers Limited (WPP)

Motor Sr No NA01452367 Equipment Name Spare Motor At work Shop


Motor Type Motor Normal Running Hours 0 Hrs
Motor Name Plate RPM 2950 RPM. Optional Unit Cost 4.3 RS
Motor Name Plate KW 45 KW Data Cost of Motor 45000 Rs
Motor Name Plate PF 0.87 PF New Motor Efficency 95 %
Motor Name Plate Current 62 Amp
Motor Name Plate Effeciency 93.6 % Running Energy Cost in 1 Year Total Cost of Motor
Note All Fields
are Required Motor Name Plate Amb.Temp 24 Deg C
Motor Name Plate Duty S1 45000; 3.56%
Motor Name Plate Freq. 50 HZ
Motor No Load Power (KW) 3 KW
Motor No Load Power (KVA) 4 KVA
Motor No Load Amp 4 Amp
Motor Stator Resistance/Phase. 0.34 Ohm
Motor Temp at Res. Measuremen 50 Deg C

Motor Effeciency 88.73 % 1219050; 96.44%

This motor is low effeciency motor if we replace This motor to EFF1 the annual savings will be as per below data
Total Savings by EFF 2 motor is 76459 rupees per annum at 90 % load
Pay back for New motor will be in 0.59 Years

Remarks

Electrical Department (WPP) rev 1_25_2_2015 01/07/2018


Electrical Department (WPP) rev 1_25_2_2015 01/07/2018
Required Motor RPM Name Plate 2950 RPM. No Of pole of motor
Required Motor KW 45 KW
Required Motor PF 0.87 PF
Required Motor Rated Current 62 Amp
Required Motor Effeciency 93.6 %
Required Motor Type 0
Required Motor Ambient Temp 24 Deg C 55
Required Motor Duty s1
Required Motor Freq. 50 HZ 12.070395
Required Motor No Load Power (KW) 3 KW
Required Motor No Load Power (KVA) 4 KVA
Required Motor No Load Amp 4 Amp R2 235 + t2 = , where, t1 =
Required Motor Stator Resistance . 0.34 Ohm R1 235 +t1
Motor No Load PF 0.75 PF
Motor RPM with Tacho Meter 1470 RPM

R2 235 + t2 = , where, t1 = ambient temperature, °C & t2 = operating temperature, °C.


R1 235 +t1
Motor Temp 50 Deg. C.
Resistance at Test Temp R2 0.3341379 Mill Ohm. R2= R1x ((235+T2)/(235+T
Stator Copper Loss 5.3462069 watts
No Load Motor Iron Loss + Fw Friction Windage 2994.6538
Full Load Full Load Copper Loss 1284.4262
Full Load Slip 0.0166667
Rotor input 45762.712 Watts

As per IEEE the stray losses are 1.5 % of the Input.


Extra Stray Loss 675
Total Motor Input Power 50716.792 Watts

Effeciency of motor 88.73 %

This Sheet is developed by Mr. Sandeep Kalsi . In case of Any sugesstion or Query Please ask at 08053800846 or san
2

R2 235 + t2 = , where, t1 = ambient temperature, °C & t2 = operating temperature, °C.

Stray Load Losses: These losses are difficult to measure with any accuracy. IEEE Standard
112 gives a complicated method, which is rarely used on shop floor. IS and IEC standards take
R2= R1x ((235+T2)/(235+T1)) a fixed value as 0.5 % of input. The actual value of stray losses is likely to be more. IEEE –
112 specifies values from 0.9 % to 1.8 % (see Table 2.1.)
TABLE 2.1 MOTOR RATING VS. STRAY
LOSSES - IEEE
Motor Rating Stray Losses
1 – 125 HP 1.8 %
125 – 500 HP 1.5 %
501 – 2499 HP 1.2 %
2500 and above 0.9 %

ask at 08053800846 or sandeepkalsi008@gmail.com


curacy. IEEE Standard
. IS and IEC standards take
ely to be more. IEEE –
New Motor Efficency 95 % IE2 Motor Effeciency
Effeciency of Motor 88.73 % Effeciency Savings

Normal Running Hours of 7000 Hrs


Motor Power 45 KW
Unit Consumption 315000 KWH
Running Energy Cost in 1 1219050 Rupees
Total Cost of Motor 45000 Rupees
Savings 76459
Pay back time for New EFF1 motor 0.5885531
IE2 Motor Effeciency 95.00
Effeciency Savings 6.27 95

7000 7000
4.3 6
45000 1500