Sei sulla pagina 1di 43

REVISED LIST

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER


CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

Quantity (1ST LOT)

Sl. UMC
Item Description Unit SMS FEB'13 MAR'13 APR'13 MAY'13 JUN'13 JUL'13 AUG'13 SEP'13 OCT'13 NOV'13 DEC'13
No. NO.

(1) (2) (3)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 6000 3000 1500 1500

ii. 240 sq. mm. M 11000 4000 3000 4000

iii. 185 sq. mm. M 3500 2000 1500

iv. 150 sq. mm. M

v. 120 sq mm M

vi. 70 sq mm M

4 6.6 KV (E)/3.8 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M 4000 2000 2000

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE

Sheet 1 of 43
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

50 sq. mm. M 750 750

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M 1000 1000

ii. 4 sq. mm. M 3500 3500

iii. 2.5 sq. mm. M 8500 8500

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes
(For LCSS transformer neutral)

630 sq mm M 2000 1000 1000

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

i. 630 sq mm M 74000 20000 20000 34000

ii. 500 sq.mm M

iii. 400 sq.mm M

iv. 300 sq.mm M 3000 3000

v. 240 sq.mm M 1000 1000

vi. 185 sq.mm M

vii. 150 sq.mm M 1000 1000

viii. 120 sq.mm M 1000 1000

ix. 95 sq.mm M 2000 2000

x. 70 sq.mm M 500 500

xi. 50 sq.mm M 2000 2000

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

i. 35 sq.mm M

ii. 25 sq.mm M 650 650

iii. 16 sq.mm M 2600 2600

iv. 10 sq.mm M 2600 2600

v. 6 sq.mm M 4000 4000

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M 30000 10000 10000 10000

ii. 240 sq mm M 20000 10000 5000 5000

iii. 185 sq mm M 3000 1000 1000 1000

iv. 150 sq mm M 18000 6000 6000 6000

v. 120 sq mm M 5000 2000 1500 1500

vi. 95 sq mm M 20000 7000 7000 6000

vii. 70 sq mm M 17000 6000 5000 6000

viii. 50 sq mm M 18000 6000 6000 6000

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

Sheet 2 of 43
i. 35 sq mm M

ii. 25 sq mm M 30000 10000 10000 10000

iii. 16 sq mm M 48000 10000 20000 18000

iv. 10 sq mm M 40000 10000 15000 15000

v. 6 sq mm M 60000 20000 30000 10000

12 1.1 kV grade as per IS:7098 (Part-I)-1988,


2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M

ii. 185 sq mm M

iii. 150 sq mm M

iv. 120 sq mm M

v. 95 sq mm M 4000 2000 2000

vi. 70 sq mm M

vii. 50 sq mm M 500 500

13 1.1 kV grade as per IS:1554-1988, 2-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M 500 500

iii. 16 sq mm M 1000 1000

iv. 10 sq mm M 1000 1000

v. 6 sq mm M 1000 1000

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M 12000 4000 4000 4000

ii. 2.5 sq mm M 25000 5000 10000 10000

Sheet 3 of 43
15 1.1 kV grade as per IS: 7098 (PartI)-1988,
XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M 3500 3500

ii. 70 sq mm M 2500 2500

iii. 50 sq mm M 3500 3500

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M 1000 1000

ii. 25 sq mm M 1000 1000

iii. 16 sq mm M 1500 1500

iv. 10 sq mm M 1000 1000

v. 6 sq mm M 500 500

vi. 4 sq mm M

vii. 2.5 sq mm M 500 500

viii. 1.5 sq mm M

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M 500 500

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M 500 500

ii. 4 sq. mm. M 500 500

iii. 2.5 sq. mm. M 1500 1500

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

i. 2.5 sq-mm M 4000 2000 2000

ii. 1.5 sq-mm M 2000 1000 1000

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M 1500 1500

ii. 4 core, 6 sq mm M 2500 2500

iii. 4 core, 4 sq mm M

iv. 4 core, 2.5 sq mm M 1500 1500

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes

i. 3 Core, 240 sq.mm M 500 500

ii. 4 Core, 10 sq.mm M 500 500

iii. 4 Core, 4 sq.mm M 500 500

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M 15000 7500 7500

v. 19 core M 40000 20000 20000

Sheet 4 of 43
vi. 16 core M 5000 2500 2500

vii 12 core M 40000 20000 20000

viii. 10 core M 5000 2500 2500

ix. 7 core M 35000 17500 17500

x. 5 core M 42000 21000 21000

xi. 4 core M

xii. 3 core M 70000 35000 35000

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984, Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M 8000 2000 4000 2000

v. 19 core M 7000 2000 3000 2000

vi. 16 core M 12000 3000 6000 3000

vii 12 core M 10000 2500 5000 2500

viii. 10 core M 12000 3000 6000 3000

ix. 7 core M 15000 4000 7000 4000

x. 5 core M 18000 5000 8000 5000

xi. 4 core M

xii. 3 core M 20000 7000 6000 7000

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

i. 18 core, 1.5 sq mm M 500 500

ii. 7 core, 1.5 sq mm M 500 500

iii. 5 core, 1.5 sq mm M 500 500

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC

Sheet 5 of 43
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

iii. 2 Pair X 1.0 sq.mm M

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M

ii. 10T X 1.0 sqmm M

30 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm

ii. 5 P X 1.0 sq.mm

TOTAL 875100

Sheet 6 of 43
REVISED LIST

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER


CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

Sl. UMC
Item Description Unit HSM FEB'13 MAR'13 APR'13 MAY'13 JUN'13 JUL'13 AUG'13 SEP'13 OCT'13 NOV'13 DEC'13
No. NO.

(1) (2) (3)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 6000 600 1200 1800 1800 600

ii. 240 sq. mm. M 41000 4100 8200 12300 12300 4100

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 4000 400 800 1200 1200 400

ii. 240 sq. mm. M 32000 3200 6400 9600 9600 3200

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 0 0 0 0 0

ii. 240 sq. mm. M 36000 3600 7200 10800 10800 3600

iii. 185 sq. mm. M 1000 100 200 300 300 100

iv. 150 sq. mm. M 5000 500 1000 1500 1500 500

v. 120 sq mm M 0 0 0 0 0

vi. 70 sq mm M 0 0 0 0 0

4 6.6 KV (E)/3.8 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M 0 0 0 0 0

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

50 sq. mm. M 0 0 0 0 0

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M 0 0 0 0 0

ii. 4 sq. mm. M 0 0 0 0 0

iii. 2.5 sq. mm. M 0 0 0 0 0

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes

Sheet 7 of 43
(For LCSS transformer neutral)

630 sq mm M 2000 200 400 600 600 200

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

i. 630 sq mm M 25000 2500 5000 7500 7500 2500

ii. 500 sq.mm M 6000 600 1200 1800 1800 600

iii. 400 sq.mm M 66000 6600 13200 19800 19800 6600

iv. 300 sq.mm M 24000 2400 4800 7200 7200 2400

v. 240 sq.mm M 7000 700 1400 2100 2100 700

vi. 185 sq.mm M 2000 200 400 600 600 200

vii. 150 sq.mm M

viii. 120 sq.mm M

ix. 95 sq.mm M

x. 70 sq.mm M

xi. 50 sq.mm M 10000 1000 2000 3000 3000 1000

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

i. 35 sq.mm M 6000 600 1200 1800 1800 600

ii. 25 sq.mm M 25000 2500 5000 7500 7500 2500

iii. 16 sq.mm M 10000 1000 2000 3000 3000 1000

iv. 10 sq.mm M 22000 2200 4400 6600 6600 2200

v. 6 sq.mm M 10000 1000 2000 3000 3000 1000

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M 249000 24900 49800 74700 74700 24900

ii. 240 sq mm M 16000 1600 3200 4800 4800 1600

iii. 185 sq mm M 40000 4000 8000 12000 12000 4000

iv. 150 sq mm M 12000 1200 2400 3600 3600 1200

v. 120 sq mm M 3000 300 600 900 900 300

vi. 95 sq mm M 22000 2200 4400 6600 6600 2200

vii. 70 sq mm M 13000 1300 2600 3900 3900 1300

viii. 50 sq mm M 40000 4000 8000 12000 12000 4000

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M 53000 5300 10600 15900 15900 5300

ii. 25 sq mm M 82000 8200 16400 24600 24600 8200

iii. 16 sq mm M 48000 4800 9600 14400 14400 4800

iv. 10 sq mm M 32000 3200 6400 9600 9600 3200

v. 6 sq mm M 50000 5000 10000 15000 15000 5000

Sheet 8 of 43
12 1.1 kV grade as per IS:7098 (Part-I)-1988,
2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M 2000 200 400 600 600 200

ii. 185 sq mm M 1000 100 200 300 300 100

iii. 150 sq mm M 1000 100 200 300 300 100

iv. 120 sq mm M 1000 100 200 300 300 100

v. 95 sq mm M 0 0 0 0 0

vi. 70 sq mm M 0 0 0 0 0

vii. 50 sq mm M 33000 3300 6600 9900 9900 3300

13 1.1 kV grade as per IS:1554-1988, 2-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M 0 0 0 0 0

ii. 25 sq mm M 3000 300 600 900 900 300

iii. 16 sq mm M 6000 600 1200 1800 1800 600

iv. 10 sq mm M 13000 1300 2600 3900 3900 1300

v. 6 sq mm M 1000 100 200 300 300 100

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M 92000 9200 18400 27600 27600 9200

ii. 2.5 sq mm M 0 0 0 0 0

Sheet 9 of 43
15 1.1 kV grade as per IS: 7098 (PartI)-1988,
XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M 3000 300 600 900 900 300

ii. 70 sq mm M 0 0 0 0 0

iii. 50 sq mm M 4000 400 800 1200 1200 400

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M 0 0 0 0 0

ii. 25 sq mm M 3000 300 600 900 900 300

iii. 16 sq mm M 0 0 0 0 0

iv. 10 sq mm M 0 0 0 0 0

v. 6 sq mm M 0 0 0 0 0

vi. 4 sq mm M 0 0 0 0 0

vii. 2.5 sq mm M 0 0 0 0 0

viii. 1.5 sq mm M 0 0 0 0 0

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M 0 0 0 0 0

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M 0 0 0 0 0

ii. 4 sq. mm. M 0 0 0 0 0

iii. 2.5 sq. mm. M 0 0 0 0 0

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

i. 2.5 sq-mm M 30000 3000 6000 9000 9000 3000

ii. 1.5 sq-mm M 10000 1000 2000 3000 3000 1000

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M 0 0 0 0 0

ii. 4 core, 6 sq mm M 0 0 0 0 0

iii. 4 core, 4 sq mm M 0 0 0 0 0

iv. 4 core, 2.5 sq mm M 0 0 0 0 0

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes 0 0 0 0 0

i. 3 Core, 240 sq.mm M 0 0 0 0 0

ii. 4 Core, 10 sq.mm M 0 0 0 0 0

iii. 4 Core, 4 sq.mm M 0 0 0 0 0

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M 17000 1700 3400 5100 5100 1700

ii. 30 core M 36000 3600 7200 10800 10800 3600

iii. 27 core M 0 0 0 0 0

iv. 24 core M 6000 600 1200 1800 1800 600

v. 19 core M 14000 1400 2800 4200 4200 1400

vi. 16 core M 41000 4100 8200 12300 12300 4100

vii 12 core M 0 0 0 0 0

viii. 10 core M 18000 1800 3600 5400 5400 1800

ix. 7 core M 6000 600 1200 1800 1800 600

x. 5 core M 54000 5400 10800 16200 16200 5400

xi. 4 core M 0 0 0 0 0

xii. 3 core M 104000 10400 20800 31200 31200 10400

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and

Sheet 10 of 43
outer sheathed as per IS:5831-1984, Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M 0 0 0 0 0

ii. 30 core M 3000 300 600 900 900 300

iii. 27 core M 0 0 0 0 0

iv. 24 core M 0 0 0 0 0

v. 19 core M 1000 100 200 300 300 100

vi. 16 core M 1000 100 200 300 300 100

vii 12 core M 0 0 0 0 0

viii. 10 core M 20000 2000 4000 6000 6000 2000

ix. 7 core M 5000 500 1000 1500 1500 500

x. 5 core M 32000 3200 6400 9600 9600 3200

xi. 4 core M 0 0 0 0 0

xii. 3 core M 38000 3800 7600 11400 11400 3800

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M 20000 2000 4000 6000 6000 2000

ii. 30 core M 20000 2000 4000 6000 6000 2000

iii. 27 core M 0 0 0 0 0

iv. 24 core M 0 0 0 0 0

v. 19 core M 6000 600 1200 1800 1800 600

vi. 16 core M 12000 1200 2400 3600 3600 1200

vii 12 core M 19000 1900 3800 5700 5700 1900

viii. 10 core M 5000 500 1000 1500 1500 500

ix. 7 core M 25000 2500 5000 7500 7500 2500

x. 5 core M 8000 800 1600 2400 2400 800

xi. 4 core M 0 0 0 0 0

xii. 3 core M 145000 14500 29000 43500 43500 14500

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

i. 18 core, 1.5 sq mm M

ii. 7 core, 1.5 sq mm M

iii. 5 core, 1.5 sq mm M

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

iii. 2 Pair X 1.0 sq.mm M

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M

ii. 10T X 1.0 sqmm M

Sheet 11 of 43
30 Twisted triad, 700V grade, stranded copper
conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm

ii. 5 P X 1.0 sq.mm

TOTAL 1859000

Sheet 12 of 43
REVISED LIST

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER


CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

Sl. UMC
Item Description Unit RMH FEB'13 MAR'13 APR'13 MAY'13 JUN'13 JUL'13 AUG'13 SEP'13 OCT'13 NOV'13 DEC'13
No. NO.

(1) (2) (3)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 28000 9000 8500 10500

ii. 240 sq. mm. M

iii. 185 sq. mm. M

iv. 150 sq. mm. M

v. 120 sq mm M 7000 4000 1750 1250

vi. 70 sq mm M 25000 7500 7500 10000

4 6.6 KV (E)/3.8 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

50 sq. mm. M

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes

Sheet 13 of 43
(For LCSS transformer neutral)

630 sq mm M 2700 1500 1200

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

i. 630 sq mm M

ii. 500 sq.mm M

iii. 400 sq.mm M

iv. 300 sq.mm M

v. 240 sq.mm M

vi. 185 sq.mm M

vii. 150 sq.mm M

viii. 120 sq.mm M

ix. 95 sq.mm M

x. 70 sq.mm M

xi. 50 sq.mm M 9000 2500 2250 4250

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

i. 35 sq.mm M

ii. 25 sq.mm M 11000 3000 3750 4250

iii. 16 sq.mm M 10000 2500 2500 5000

iv. 10 sq.mm M 1500 750 750

v. 6 sq.mm M

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M 50000 15000 15000 20000

ii. 240 sq mm M 30000 9000 10000 11000

iii. 185 sq mm M 20000 5000 5000 10000

iv. 150 sq mm M 16000 5000 5000 6000

v. 120 sq mm M 45000 10000 10000 25000

vi. 95 sq mm M 45000 10000 10000 25000

vii. 70 sq mm M 25000 8000 7000 10000

viii. 50 sq mm M 45000 10000 10000 25000

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M 80000 20000 20000 40000

ii. 25 sq mm M 53000 15000 15000 23000

iii. 16 sq mm M 50000 13000 13000 24000

iv. 10 sq mm M 65000 16000 16000 33000

v. 6 sq mm M 65000 16000 16000 33000

Sheet 14 of 43
12 1.1 kV grade as per IS:7098 (Part-I)-1988,
2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M

ii. 185 sq mm M

iii. 150 sq mm M

iv. 120 sq mm M

v. 95 sq mm M 5000 1500 3000 500

vi. 70 sq mm M

vii. 50 sq mm M 3000 1000 2000

13 1.1 kV grade as per IS:1554-1988, 2-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M 110000 28000 56000 26000

ii. 2.5 sq mm M

Sheet 15 of 43
15 1.1 kV grade as per IS: 7098 (PartI)-1988,
XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M 1000 500 500

ii. 70 sq mm M 500 250 250

iii. 50 sq mm M 1000 500 500

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M 1000 500 500

v. 6 sq mm M

vi. 4 sq mm M

vii. 2.5 sq mm M 1000 500 500

viii. 1.5 sq mm M

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M 1000 500 500

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

i. 2.5 sq-mm M 12000 3000 3000 6000

ii. 1.5 sq-mm M 6500 2000 2000 2500

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M

ii. 4 core, 6 sq mm M

iii. 4 core, 4 sq mm M

iv. 4 core, 2.5 sq mm M

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes

i. 3 Core, 240 sq.mm M

ii. 4 Core, 10 sq.mm M

iii. 4 Core, 4 sq.mm M

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M

ii. 30 core M 30000 8000 7000 15000

iii. 27 core M

iv. 24 core M 14000 5000 5000 4000

v. 19 core M 52000 14000 14000 24000

vi. 16 core M 50000 12000 12000 26000

vii 12 core M

viii. 10 core M 30000 10000 20000

ix. 7 core M 17000 5000 5000 7000

x. 5 core M 100000 20000 20000 60000

xi. 4 core M

xii. 3 core M 70000 15000 15000 40000

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and

Sheet 16 of 43
outer sheathed as per IS:5831-1984, Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M

ii. 30 core M 15000 5000 5000 5000

iii. 27 core M

iv. 24 core M 17000 5000 5000 7000

v. 19 core M 57000 15000 15000 27000

vi. 16 core M 75000 20000 20000 35000

vii 12 core M

viii. 10 core M 43000 10000 10000 23000

ix. 7 core M 15000 4000 4000 7000

x. 5 core M 55000 15000 15000 25000

xi. 4 core M

xii. 3 core M 80000 20000 20000 40000

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

i. 18 core, 1.5 sq mm M

ii. 7 core, 1.5 sq mm M

iii. 5 core, 1.5 sq mm M

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M 9000 3000 3000 3000

ii. 5 Pair X 1.0 sq.mm M 15000 5000 5000 5000

iii. 2 Pair X 1.0 sq.mm M 70000 20000 20000 30000

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M 11000 5000 5000 1000

ii. 10T X 1.0 sqmm M 35000 10000 10000 15000

Sheet 17 of 43
30 Twisted triad, 700V grade, stranded copper
conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm

ii. 5 P X 1.0 sq.mm

TOTAL 1685200

Sheet 18 of 43
REVISED LIST

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER


CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

Sl. UMC
Item Description Unit BF-AUX. FEB'13 MAR'13 APR'13 MAY'13 JUN'13 JUL'13 AUG'13 SEP'13 OCT'13 NOV'13 DEC'13
No. NO.

(1) (2) (3)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

iii. 185 sq. mm. M

iv. 150 sq. mm. M

v. 120 sq mm M

vi. 70 sq mm M

4 6.6 KV (E)/3.8 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

50 sq. mm. M

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes
(For LCSS transformer neutral)

630 sq mm M

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

Sheet 19 of 43
i. 630 sq mm M

ii. 500 sq.mm M

iii. 400 sq.mm M

iv. 300 sq.mm M

v. 240 sq.mm M

vi. 185 sq.mm M

vii. 150 sq.mm M

viii. 120 sq.mm M

ix. 95 sq.mm M

x. 70 sq.mm M

xi. 50 sq.mm M

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

i. 35 sq.mm M

ii. 25 sq.mm M

iii. 16 sq.mm M

iv. 10 sq.mm M

v. 6 sq.mm M

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M 1800 1800

ii. 240 sq mm M 1000 1000

iii. 185 sq mm M

iv. 150 sq mm M

v. 120 sq mm M 470 470

vi. 95 sq mm M 900 900

vii. 70 sq mm M

viii. 50 sq mm M

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M 650 650

ii. 25 sq mm M 2300 2300

iii. 16 sq mm M 3100 3100

iv. 10 sq mm M 100 100

v. 6 sq mm M 3500 3500

Sheet 20 of 43
12 1.1 kV grade as per IS:7098 (Part-I)-1988,
2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M

ii. 185 sq mm M

iii. 150 sq mm M

iv. 120 sq mm M 30 30

v. 95 sq mm M 420 420

vi. 70 sq mm M

vii. 50 sq mm M

13 1.1 kV grade as per IS:1554-1988, 2-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M

ii. 2.5 sq mm M

Sheet 21 of 43
15 1.1 kV grade as per IS: 7098 (PartI)-1988,
XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M 50 50

ii. 70 sq mm M

iii. 50 sq mm M

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

vi. 4 sq mm M

vii. 2.5 sq mm M

viii. 1.5 sq mm M

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M

ii. 4 sq. mm. M 400 400

iii. 2.5 sq. mm. M 1350 1350

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

i. 2.5 sq-mm M

ii. 1.5 sq-mm M

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M

ii. 4 core, 6 sq mm M

iii. 4 core, 4 sq mm M 250 250

iv. 4 core, 2.5 sq mm M

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes

i. 3 Core, 240 sq.mm M

ii. 4 Core, 10 sq.mm M

iii. 4 Core, 4 sq.mm M

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984, Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M

ii. 30 core M

Sheet 22 of 43
iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M 280 280

vii 12 core M

viii. 10 core M 70 70

ix. 7 core M 130 130

x. 5 core M

xi. 4 core M

xii. 3 core M 70 70

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

i. 18 core, 1.5 sq mm M

ii. 7 core, 1.5 sq mm M 250 250

iii. 5 core, 1.5 sq mm M

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

iii. 2 Pair X 1.0 sq.mm M

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M

ii. 10T X 1.0 sqmm M

30 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm

Sheet 23 of 43
ii. 5 P X 1.0 sq.mm

TOTAL 17120

Sheet 24 of 43
REVISED LIST

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER


CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

INSTRUMENTATION
Sl. UMC
Item Description Unit FEB'13 MAR'13 APR'13 MAY'13 JUN'13 JUL'13 AUG'13 SEP'13 OCT'13 NOV'13 DEC'13
No. NO.

(1) (2) (3)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

iii. 185 sq. mm. M

iv. 150 sq. mm. M

v. 120 sq mm M

vi. 70 sq mm M

4 6.6 KV (E)/3.8 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

50 sq. mm. M

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M 12000 8500 3500

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes
(For LCSS transformer neutral)

630 sq mm M

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

Sheet 25 of 43
i. 630 sq mm M

ii. 500 sq.mm M

iii. 400 sq.mm M

iv. 300 sq.mm M

v. 240 sq.mm M

vi. 185 sq.mm M

vii. 150 sq.mm M

viii. 120 sq.mm M

ix. 95 sq.mm M

x. 70 sq.mm M

xi. 50 sq.mm M

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

i. 35 sq.mm M

ii. 25 sq.mm M

iii. 16 sq.mm M

iv. 10 sq.mm M

v. 6 sq.mm M

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M

ii. 240 sq mm M

iii. 185 sq mm M

iv. 150 sq mm M

v. 120 sq mm M

vi. 95 sq mm M

vii. 70 sq mm M

viii. 50 sq mm M

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

Sheet 26 of 43
12 1.1 kV grade as per IS:7098 (Part-I)-1988,
2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M

ii. 185 sq mm M

iii. 150 sq mm M

iv. 120 sq mm M

v. 95 sq mm M

vi. 70 sq mm M

vii. 50 sq mm M

13 1.1 kV grade as per IS:1554-1988, 2-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M

ii. 2.5 sq mm M

Sheet 27 of 43
15 1.1 kV grade as per IS: 7098 (PartI)-1988,
XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M

ii. 70 sq mm M

iii. 50 sq mm M

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

vi. 4 sq mm M

vii. 2.5 sq mm M

viii. 1.5 sq mm M

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

i. 2.5 sq-mm M

ii. 1.5 sq-mm M

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M

ii. 4 core, 6 sq mm M

iii. 4 core, 4 sq mm M

iv. 4 core, 2.5 sq mm M

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes

i. 3 Core, 240 sq.mm M

ii. 4 Core, 10 sq.mm M

iii. 4 Core, 4 sq.mm M

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M 3000 3000

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M 1500 1500

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984, Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M

ii. 30 core M

Sheet 28 of 43
iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

i. 18 core, 1.5 sq mm M

ii. 7 core, 1.5 sq mm M

iii. 5 core, 1.5 sq mm M

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M 2000 200 240 560 800 200

ii. 5 Pair X 1.0 sq.mm M 2000 200 240 560 800 200

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M 20000 2000 2400 5600 8000 2000

ii. 5 Pair X 1.0 sq.mm M 11500 1150 1380 3220 4600 1150

iii. 2 Pair X 1.0 sq.mm M

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M 35500 3550 4260 9940 14200 3550

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M 2500 250 300 700 1000 250

ii. 10T X 1.0 sqmm M 5000 500 600 1400 2000 500

30 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M 2500 250 300 700 1000 250

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm 500 50 60 140 200 50

Sheet 29 of 43
ii. 5 P X 1.0 sq.mm 500 50 60 140 200 50

TOTAL 98500

Sheet 30 of 43
REVISED LIST

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES,
CONTROL CABLES AND INSTRUMENTATION CABLES

Sl. UMC
Item Description Unit UTILITY FEB'13 MAR'13 APR'13 MAY'13 JUN'13 JUL'13 AUG'13 SEP'13 OCT'13 NOV'13 DEC'13
No. NO.

(1) (2) (3)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M

ii. 240 sq. mm. M 8960 8960

iii. 185 sq. mm. M

iv. 150 sq. mm. M

v. 120 sq mm M

vi. 70 sq mm M

4 6.6 KV (E)/3.8 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

50 sq. mm. M

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes
(For LCSS transformer neutral)

630 sq mm M

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

Sheet 31 of 43
i. 630 sq mm M

ii. 500 sq.mm M

iii. 400 sq.mm M

iv. 300 sq.mm M

v. 240 sq.mm M

vi. 185 sq.mm M

vii. 150 sq.mm M

viii. 120 sq.mm M

ix. 95 sq.mm M

x. 70 sq.mm M

xi. 50 sq.mm M

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

i. 35 sq.mm M

ii. 25 sq.mm M

iii. 16 sq.mm M

iv. 10 sq.mm M

v. 6 sq.mm M

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M 1500 1500

ii. 240 sq mm M

iii. 185 sq mm M

iv. 150 sq mm M

v. 120 sq mm M

vi. 95 sq mm M

vii. 70 sq mm M

viii. 50 sq mm M

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

Sheet 32 of 43
12 1.1 kV grade as per IS:7098 (Part-I)-1988,
2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M

ii. 185 sq mm M

iii. 150 sq mm M

iv. 120 sq mm M

v. 95 sq mm M

vi. 70 sq mm M

vii. 50 sq mm M

13 1.1 kV grade as per IS:1554-1988, 2-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M

ii. 2.5 sq mm M

Sheet 33 of 43
15 1.1 kV grade as per IS: 7098 (PartI)-1988,
XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M

ii. 70 sq mm M

iii. 50 sq mm M

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M

iii. 16 sq mm M

iv. 10 sq mm M

v. 6 sq mm M

vi. 4 sq mm M

vii. 2.5 sq mm M

viii. 1.5 sq mm M

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M

ii. 4 sq. mm. M

iii. 2.5 sq. mm. M

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

i. 2.5 sq-mm M

ii. 1.5 sq-mm M

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M

ii. 4 core, 6 sq mm M

iii. 4 core, 4 sq mm M

iv. 4 core, 2.5 sq mm M

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes

i. 3 Core, 240 sq.mm M

ii. 4 Core, 10 sq.mm M

iii. 4 Core, 4 sq.mm M

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984, Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M

ii. 30 core M

Sheet 34 of 43
iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M

ii. 30 core M

iii. 27 core M

iv. 24 core M

v. 19 core M

vi. 16 core M

vii 12 core M 4480 4480

viii. 10 core M

ix. 7 core M

x. 5 core M

xi. 4 core M

xii. 3 core M

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

i. 18 core, 1.5 sq mm M

ii. 7 core, 1.5 sq mm M

iii. 5 core, 1.5 sq mm M

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M

ii. 5 Pair X 1.0 sq.mm M

iii. 2 Pair X 1.0 sq.mm M

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M

ii. 10T X 1.0 sqmm M

30 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm

Sheet 35 of 43
ii. 5 P X 1.0 sq.mm

TOTAL 14940

Sheet 36 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)

HT CABLES

1 11/11kV (UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated as per IS 7098-Pt-II/1985,
insulation screening by copper tape,
extruded PVC inner and outer sheathed as per
IS:5831-1984, aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 6000 6000

ii. 240 sq. mm. M 41000 41000

2 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape, extruded PVC inner and
outer sheathed as per IS:5831-1984,
hard drawn aluminium wire armoured as per
IS:3975-1999, 1-Core, of following sizes. (copper tape
screen and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 4000 4000

ii. 240 sq. mm. M 32000 32000

3 11kV(E)/6.6kV(UE) grade as per IS 7098-Pt II/1985,


stranded Aluminium conductor as per IS:8130-1984,
conductor screening by extruded semi-conductor
compound, XLPE insulated, insulation screening by
copper tape for individual core, extruded
PVC inner and outer sheathed as per IS:5831-1984,
hard drawn galvanised steel strip armoured as per
IS:3975-1999, 3-Core (copper tape screen
and armour together shall be able to carry 2000
A for 3 Sec E/F current without exceeding 200deg.
Centegrade temperature rise)

i. 300 sq. mm. M 6000 28000 35500 34000

ii. 240 sq. mm. M 11000 8960 36000 55960

iii. 185 sq. mm. M 3500 1000 4500

iv. 150 sq. mm. M 5000 5000

v. 120 sq mm M 7000 7750 7000

vi. 70 sq mm M 25000 30000 25000

4 11 KV (E)/6.6 KV (UE) grade as per IS 7098-Pt


II/1985, stranded Copper conductor as per
IS:8130-1984, conductor screening by extruded
semi-conductor compound, XLPE insulated, insulation
screening by extruded semiconducting compound and
copper tape, extruded PVC inner and outer sheathed
as per IS:5831-1984, aluminium wire armoured
as per IS:3975-1999, 1-Core, (copper tape
screen and armour together shall be able
to carry 2000 A E/F current for 3 Sec without
exceeding 200deg. Centegrade temperature rise)

300 sq mm M 4000 4000

LT CABLES

5 1.1 kV grade as per IS 7098-Part-I (1988), stranded


Copper conductor as per IS:8130-1984, XLPE
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn
aluminium wire armoured as per
IS:3975-1988, 1-core, of following sizes:

Sheet 37 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)
50 sq. mm. M 750 750

6 1.1 kV grade as per IS:1554-1988, stranded


Copper conductor as per IS:8130-1984, PVC
insulation as per IS:5831-1984, extruded
PVC inner and outer sheath as per
IS:5831-1984 Hard drawn aluminium wire armoured
as per IS:3975-1988, 1-core, of following sizes:

i. 16 sq. mm. M 1000 1000

ii. 4 sq. mm. M 3500 3500

iii. 2.5 sq. mm. M 8500 3500 12000

7 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC sheathed as per IS:5831-1984,
Hard drawn aluminium wire armoured
1-core, of following sizes
(For LCSS transformer neutral)

630 sq mm M 2000 2000 2700 2700 6700

8 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium wire armoured
1-core, of following sizes:

i. 630 sq mm M 74000 25000 99000

ii. 500 sq.mm M 6000 6000

iii. 400 sq.mm M 66000 66000

iv. 300 sq.mm M 3000 24000 27000

v. 240 sq.mm M 1000 7000 8000

vi. 185 sq.mm M 2000 2000

vii. 150 sq.mm M 1000 1000

viii. 120 sq.mm M 1000 1000

ix. 95 sq.mm M 2000 2000

x. 70 sq.mm M 500 500

xi. 50 sq.mm M 2000 10000 9000 9750 21000

9 1.1 kV grade as per IS 1554 (1988), stranded Aluminium


conductor, PVC insulated as per IS 5831 (1988),
extruded PVC inner and outer sheath as per
IS:5831-1984, Hard drawn aluminium srip armoured for
diameter above 13 mm and aluminium wire armoured for
diameter below 13 mm, 1-core, of following sizes

Sheet 38 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)
i. 35 sq.mm M 6000 6000

ii. 25 sq.mm M 650 25000 11000 12750 36650

iii. 16 sq.mm M 2600 10000 10000 10000 22600

iv. 10 sq.mm M 2600 22000 1500 1500 26100

v. 6 sq.mm M 4000 10000 14000

10 1.1 kV grade, stranded Aluminium conductor,


XLPE insulated as per IS 7098-Part-I (1988),
extruded PVC inner and outer sheath as per IS 5831-1984,
galvanised steel strip armoured as per IS 3975-1999
3-core, of following sizes

i. 300 sq mm M 30000 1800 1500 249000 50000 62000 14200 408500

ii. 240 sq mm M 20000 1000 16000 30000 37000 8900 112900

iii. 185 sq mm M 3000 40000 20000 24500 87500

iv. 150 sq mm M 18000 12000 16000 18500 4650 69150

v. 120 sq mm M 5000 470 3000 45000 56500 5600 115570

vi. 95 sq mm M 20000 900 22000 45000 53500 14650 156050

vii. 70 sq mm M 17000 13000 25000 30500 2400 87900

viii. 50 sq mm M 18000 40000 45000 53500 10000 166500

11 1.1 kV grade as per IS:1554-1988, 3-core,


stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M 650 53000 80000 98500 232150

ii. 25 sq mm M 30000 2300 82000 53000 64000 12000 243300

iii. 16 sq mm M 48000 3100 48000 50000 56500 12150 217750

iv. 10 sq mm M 40000 100 32000 65000 78500 10100 225700

v. 6 sq mm M 60000 3500 50000 65000 78000 24350 280850

12 1.1 kV grade as per IS:7098 (Part-I)-1988,


2-core, stranded aluminium conductor as per
IS:8130-1984, XLPE insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999, of
the following sizes:

i. 240 sq mm M 2000 2000

ii. 185 sq mm M 1000 1000

iii. 150 sq mm M 1000 1000

iv. 120 sq mm M 30 1000 1030

v. 95 sq mm M 4000 420 5000 5000 9420

vi. 70 sq mm M

vii. 50 sq mm M 500 33000 3000 3000 36500

Sheet 39 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)
13 1.1 kV grade as per IS:1554-1988, 2-core,
stranded aluminium conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984, galvanised
steel strip armouring as per IS:3975-1999 for diameter
above 13 mm and steel wire armouring for diameter
below 13 mm, of the following sizes:

i. 35 sq mm M

ii. 25 sq mm M 500 3000 3500

iii. 16 sq mm M 1000 6000 7000

iv. 10 sq mm M 1000 13000 14000

v. 6 sq mm M 1000 1000 2000

14 1.1 kV grade as per IS:1554-1988, 3-core,


stranded copper conductor as per
IS:8130-1984, PVC insulation as per
IS:5831-1984, extruded PVC inner and outer
sheathed as per IS:5831-1984,
galvanised steel strip armouring for diameter above 13
mm and steel wire armoured for diameter below 13 mm
as per IS:3975-1999, of the following sizes :

i. 4 sq mm M 12000 92000 110000 136500 214000

ii. 2.5 sq mm M 25000 800 25800

15 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 95 sq mm M 3500 50 3000 1000 2000 300 9850

ii. 70 sq mm M 2500 500 1000 3000

iii. 50 sq mm M 3500 4000 1000 2000 800 11300

16 1.1 kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 1-core of the following sizes:

i. 35 sq mm M 1000 1000

ii. 25 sq mm M 1000 3000 550 4550

iii. 16 sq mm M 1500 200 1700

iv. 10 sq mm M 1000 1000 1750 2000

v. 6 sq mm M 500 500 1000

vi. 4 sq mm M 600 600

vii. 2.5 sq mm M 500 1000 1000 700 3200

viii. 1.5 sq mm M

17 1.1 kV grade as per IS: 7098 (PartI)-1988,


XLPE insulated & overall sheathed flexible
copper cable having stranded conductor as per
IS: 8130, 3-core of the following sizes:

70 sq. mm. M 500 500

18 1.1kV grade as per IS: 1554-1988,


PVC insulated & overall sheathed flexible
copper cable having stranded conductor as per
Cl. 5 of IS: 8130, 3-core of the following sizes

i. 10 sq. mm. M 500 500

ii. 4 sq. mm. M 500 400 900

iii. 2.5 sq. mm. M 1500 1350 1000 1000 3850

19 1.1kV grade generally as per IS: 694, 1-core,


PVC insulated unsheathed flexible copper
cable having stranded conductor as per Cl. 5 of
IS: 8130 of the following sizes:

Sheet 40 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)
i. 2.5 sq-mm M 4000 30000 12000 15000 46000

ii. 1.5 sq-mm M 2000 10000 6500 7500 18500

20 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes :

i. 4 core, 10 sq mm M 1500 1500

ii. 4 core, 6 sq mm M 2500 2500

iii. 4 core, 4 sq mm M 250 250

iv. 4 core, 2.5 sq mm M 1500 1500

21 1.1 kV grade flexible annealed tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed cables of the following sizes

i. 3 Core, 240 sq.mm M 500 500

ii. 4 Core, 10 sq.mm M 500 500

iii. 4 Core, 4 sq.mm M 500 500

CONTROL CABLES

22 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984,
galvanized steel strip/wire armoured
as per IS:3975-1999, of the following No. of
cores

i. 37 core M 17000 17000

ii. 30 core M 36000 30000 38500 66000

iii. 27 core M

iv. 24 core M 15000 6000 14000 17000 35000

v. 19 core M 40000 14000 52000 62500 106000

vi. 16 core M 5000 41000 50000 66000 1000 163000

vii 12 core M 40000 40000

viii. 10 core M 5000 3000 20000 30000 39000 3500 100500

ix. 7 core M 35000 6000 17000 21000 7350 86350

x. 5 core M 42000 54000 100000 149500 15050 360550

xi. 4 core M

Sheet 41 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)

xii. 3 core M 70000 1500 104000 70000 98000 11200 354700

23 1.1 kV grade as per IS:1554-1988, 1.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984,extruded PVC inner and
outer sheathed as per IS:5831-1984, overall Cu tape
Shielded, galvanized steel strip/wire
armouring as per IS:3975-1999, of the
following No. of cores:

i. 37 core M

ii. 30 core M 3000 3000

iii. 27 core M

iv. 24 core M

v. 19 core M 1000 1000

vi. 16 core M 1000 1000

vii 12 core M

viii. 10 core M 20000 20000

ix. 7 core M 5000 5000

x. 5 core M 32000 32000

xi. 4 core M

xii. 3 core M 38000 38000

24 1.1 kV gradeas per IS:1554-1988, 2.5 sq mm,


high conductivity stranded copper
conductor as per IS:8130-1984, PVC insulation
as per IS:5831-1984, extruded PVC inner and
outer sheath as per IS:5831-1984, galvanized
steel strip/wire as per IS:3975-1999, of the
following No. of cores

i. 37 core M 20000 20000

ii. 30 core M 20000 15000 18000 35000

iii. 27 core M

iv. 24 core M 8000 17000 21000 25000

v. 19 core M 7000 6000 57000 71500 70000

vi. 16 core M 12000 280 12000 75000 106500 205780

vii 12 core M 10000 4480 19000 33480

viii. 10 core M 12000 70 5000 43000 53500 113570

ix. 7 core M 15000 130 25000 15000 20000 2000 77130

x. 5 core M 18000 8000 55000 78000 81000

xi. 4 core M

xii. 3 core M 20000 70 145000 80000 113500 2000 360570

25 1.1 kV grade flexible tinned copper


conductor, heat resistant, EPR insulated,
CSP sheathed drag chain/trailing cables of
the following sizes:

Sheet 42 of 43
ANNEX - 1A

BILL OF QUANTITY AND PRICE SCHEDULE FOR SUPPLY OF HT, LT POWER CABLES, CONTROL CABLES AND INSTRUMENTATION CABLES

UNIT FIXED PRICE TOTAL FIXED PRICE

Quantity (1ST LOT)

INSTRUMENTATION
Unit Price TOTAL Minimum
Transit Transit
Ex-Works Excise Duty F.O.T. Unit Price Ex-Works Price F.O.T. TOTAL CENVAT
Insurance Insurance
UMC Revised price incl. Tariff & Sales Tax Freight Stores/Site F.O.T. price incl. Freight Store/ Price F.O.T. benefit to
Sl. No. Item Description Unit SMS BF-AUX. UTILITY HSM RMH AC-VENT Total Excise Duty Edu. Cess (for re- Excise Duty Edu. Cess Sales Tax (for re-
NO. RMH packing & Percentage on (5+7+8) Charges Net of Stores/ packing & Charges Site net of stores/site be passed
imbursmen imbursmen
forwarding (%) CENVAT Site forwarding CENVAT basis on to TATA
t) t)
Benefit benefit STEEL

(12=5+9+10 (13=5+7+8+
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (14=5 X 4) (15=7 x 4) (16=8 x 4) (17=9 x 4) (18=10 x 4) (19=11 x 4) (20=12 x 4) (21=13 x 4) (22)
+11) 9+10+11)
i. 18 core, 1.5 sq mm M 500 500

ii. 7 core, 1.5 sq mm M 500 250 750

iii. 5 core, 1.5 sq mm M 500 500

INSTRUMENTATION CABLES

26 Screened twisted pair, 700V grade, CU cables


HR-PVC insulated, AL melinex tape screened,
galvanised steel wire armoured and PVC outer
sheath of following sizes:-

i. 2 Pair X 1.0 sq.mm M 2000 2000

ii. 5 Pair X 1.0 sq.mm M 2000 2000

27 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988, aluminium
tape screened with tinned copper drain wire,
of the following sizes:

i. 10 Pair X 1.0 sq.mm M 20000 9000 12500 29000

ii. 5 Pair X 1.0 sq.mm M 11500 15000 19200 26500

iii. 2 Pair X 1.0 sq.mm M 70000 101750 70000

28 Twisted pair, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, unarmoured, aluminium tape
screened with tinned copper , drain wire, of
the following sizes:

2 Pair X 1.0 sq.mm M 35500 35500

29 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, galvanised steel strip/wire
armoured as per IS: 3975-1988,
aluminium tape screened with tinned copper
drain wire, of the following sizes:

i. 5T X 1.0 sqmm M 2500 11000 13350 13500

ii. 10T X 1.0 sqmm M 5000 35000 41750 40000

30 Twisted triad, 700V grade, stranded copper


conductor as per IS: 8130-1984, PVC
insulation as per IS: 5831-1984, extruded PVC
inner and outer sheathed as per IS:
5831-1984, aluminium tape screened with
tinned copper drain wire, of the following
sizes:

1T X 1.0 sqmm M 2500 2500

31 700 V grade , twisted pair, copper conductor,


heat resistant, EPR insulated, CSP sheathed,
individual & overall screened drag Chain/
trailing cables of following sizes:

i. 14 P X 1.0 sq.mm 500 500

ii. 5 P X 1.0 sq.mm 500 500


TOTAL (Approx.) 4709 KM