Sei sulla pagina 1di 9

A BARBOUR GUIDE

Fire Detection and Alarm Systems

The Official BIFM Information Service Partner


01 Current Position
Fire detection and alarm systems serve to enhance safety and reduce loss by the detection of fire,
and enable an alarm signal to be generated so that emergency actions may be taken.

A fire detection and alarm system can be divided into the following key elements:

• system categories - the main types of fire detection and alarm systems
• zones/system layouts
• detectors - fire, smoke, heat and other detectors
• sounders and call points.


Fire legislation, which is written for the purpose of life to the services of an alarm-receiving centre who will then
Automatic
safety, requires duty holders in non-domestic premises to respond to alarms by notifying Fire Authorities and key
detection is not
assess fire risks and put in place arrangements for a) the holders of the company. Such systems are also useful
required in all prevention of fire and b) to protect people from fire when where persons present on the site may not have the time,
premises it occurs. Protection includes having in place a means or cannot be relied upon, to call the emergency services.
of detection and of raising an alarm. In all but extremely
small premises an electrically operated alarm is essential It should be noted however, that many fire authorities
for the purposes of effectively raising the alarm to alert have implemented policies where the fire brigade do
other occupants. Automatic detection is not required in not respond to a call initiated as a result of automatic
all premises and depends on the findings of the fire risk fire detection during set daytime hours and, in some
assessment. cases, at other times unless there is a confirmed fire. The
exact policy varies between Fire Authorities and can vary
Legislation also requires that new buildings and between types of premises. Withdrawal of fire brigade
alterations to structures, whether domestic or non- response to automatic alarms can also occur where there
domestic, comply with Building Regulations standards is a high unwanted (false) fire alarm rate. It is therefore


on fire safety. Building Regulations are country-specific important to establish the current position in relation to
although there are significant similarities from country to a specific premises. Some Fire Authorities also impose
country. charges where there is an excessive number of unwanted
call outs from automatic detection. In the case of the
Many organisations choose to have automatic fire London Fire Brigade, charges are made to call-outs from
detection systems throughout their premises for unwanted alarms to non-domestic premises where
should include the allocation of responsibilities and
the purpose of business protection or insurance these exceed 10 in any 12-month period. The charge
arrangements for putting the policy into effect. All of the this type is commonly referred to as ‘Planned Preventive
requirements. For maximum effectiveness, where there is is currently £295 per call-out. It should be noted that
no 24-hour presence on site, businesses often subscribe during fire brigade strikes the normal arrangement for

PAGE 1 > BARBOUR – SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01
contingent fire-fighting cover provided by Fire Authorities building or a manually operated alarm (such as a rotary
is that they will only respond at any time to a call indicating gong) would be similarly audible.
a confirmed fire, as opposed to one initiated by automatic
fire detection. The other important sources of information when
determining the need for fire alarm and detection systems
are the Building Regulations 2010 (as amended) and BS
Legal Requirements 5839 Part 1 2013. The most relevant documents in these
categories are listed within the ‘Related Documents’ and
The Regulatory Reform (Fire Safety) Order 2005 applies ’Further Information and References’ sections of this
in England and Wales and requires Responsible Persons, guide. Similar requirements are contained in the Building
in relation to non-domestic premises, to conduct a risk (Scotland) Act 2003 and The Building Regulations (Northern
assessment and to implement fire precautions. Responsible Ireland) 2012. It should be noted that the requirements of
Persons are normally employers but in the absence the above Building Regulations and similar legislation are
of a relevant employer (which is normally a corporate not retrospectively applied to existing buildings (except
organisation), the duties fall to others who have control of where there are changes, extensions or alterations).
non-domestic premises. Similar legislation applies within However the requirements of the Regulatory Reform (Fire
Scotland and Northern Ireland. Safety) Order 2005 do apply retrospectively having regard
to the precautions necessary to ensure adequate standards
Article 13 of the Order requires that fire detectors and of fire safety.
alarms are installed where it is necessary for life protection.
The systems must be maintained in an efficient state, Whilst Guidance and British Standards are not legal
efficient working order and in good repair (Article 17) and requirements, these are established industry standards
in the case of a shared building, arrangements can be which are relied upon in court as evidence of the expected
made with another occupier to undertake the maintenance standards to be adopted. It is therefore important for a fire
required. safety risk assessor to take this information into account
when determining the fire precautions which should be
Employees and other persons using the premises must be installed or applied.
informed of the emergency procedures and given details of
the preventive and protective measures which have been
implemented. Information
To determine whether fire detection and alarm systems The information within this section is set out under the
are required for life protection, the risk assessor needs following sub-headings:
to refer to established standards and industry guidance.
The initial source of guidance in England and Wales are a. System Categories
the Communities and Local Government Guides to Fire
Risk Assessment. It should be noted that there are many b. Addressable Systems
different guides, each addressing different types of business
(see ‘Related Documents’). c. Zone/System Layout

The guides advise that fire detection is normally required d. Detectors


for life protection purposes to cover areas of a premises
where a fire may grow undetected, where people work e. Sounders
alone, where people are sleeping or where a building is
so large that it would not be possible for the occupants to i) Audible Signals
quickly identify fire in the building. Other areas requiring fire
ii) The Management of Alarms
detection will include, where such detection is necessary,
actuate devices such as fire door releases, fire curtains or
f. Manual Call Points
shutters, or to shut down ventilation plant or close fire and
smoke dampers. Smoke detection is normally also required
g. Servicing
where there is an inner room with escape only possible
through an outer room, unless there are vision panels
h. Routine Testing and Inspection
between the inner and outer room.
a. System Categories
Electric fire alarm sounders are normally required, even
where automatic detection is not necessary. The only Fire detection and alarm systems can be divided into
exception would be for small premises where a person three broad categories, as detailed in BS 5839-1 2013
shouting ‘fire’ is able to be clearly heard throughout the ‘Fire Detection and Alarm Systems for Buildings - Code of

PAGE 2 > BARBOUR – SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01

“ Alarm signals
must be clearly
audible to those
Practice for System Design, Installation, Commissioning and
Maintenance’. These categories are:

yy Category L: Automatically Activated Systems that are


more than two output states to be given representing
normal, fire and at least one other abnormal condition.

This differs from two state fire detection systems stems,


intended to hear Designed to Protect Life which incorporate two-stage detectors that provide a
them normal or alarm condition signal. The main benefit offered
ºº L1: Systems Installed Throughout the Protected by analogue detectors is that the output signal they provide
Building can give an early indication of fire.

” ºº

ºº
L2: Systems Installed Only in Defined Parts of the
Protected Building

L3: Systems Installed Only for the Protection of


c. Zones/System Layout

There are a number of design requirements under BS 5839-


1 that determine the way in which the protected areas
Escape Routes within a building are divided into zones. These include:

ºº L4: Systems Installed in Circulation Areas Used as yy the total floor area for a zone should not exceed
Escape Routes 2,000m2, other than in the case of a zone with only
manual call points comprising mainly a large open plan
ºº L5: Systems Installed to Satisfy Specific Fire Safety area such as the floor of a warehouse where the zone
Objectives can be 10,000m2

yy Category M: Manually Operated Systems (no sub- yy a zone should not cover more than a single floor. (This
categories) does not apply to buildings with a floor area of under
300m2 which, due to their size, can have a single zone
yy Category P: Automatically Activated Systems Designed covering all floors)
to Protect Property
yy zones should not be divided between tenants in a
ºº P1: Systems Installed Throughout the Protected multiple-occupancy building
Building
yy generally, an individual conducting a search within a
ºº P2: Systems Installed Only in Defined Parts of the zone should not need to travel more than 60m from
Protected Building their point of entry into the zone before becoming
aware of the fire location
ºº BS 5839-6 2013 ‘Fire Detection and Alarm Systems
for Buildings - Code of Practice for the Design, yy the 2013 edition of the standard emphasises the
Installation and Maintenance of Fire Detection and importance of a zone plan being displayed next to the
Fire Alarms Systems in Domestic Premises’ deals fire alarm control panel.
specifically with domestic dwellings and includes a
similar categorisation system to that outlined above d. Detectors
but with three life safety categorisations LD1, LD2
and LD3. There are two basic types of heat and smoke detector used
in fire alarm systems:
b. Addressable Systems
yy line detectors, which respond to changes in
The British Standard definition of an addressable system is ‘a temperature or other phenomena sensed in the vicinity
system in which signals from detectors, manual call points of a continuous line; typically these can be cable
or any other devices are individually identified at the control detectors or optical beam smoke detectors which cover
and indicating equipment’. In more basic, non-addressable an area by shining a beam over a distance
systems it is only the detector circuit serving each zone
that is monitored and, in the event of a fire, the specific yy point detectors, which respond to smoke, flame, or
detector(s) that triggered the alarm condition cannot be changes in temperature within the vicinity of the
identified beyond the zone in which they are installed. detector. There are a number of different types of point
detector, including:
An addressable analogue system uses detectors that
d. Control
provide of Contractors
an analogue signal. In practical terms, the output fixed-temperature heat detectors
ºº Notifiable
duties. projects are those which involve more
signal from each detector varies in proportion to the level
than 30 days, or more than 500 person days of con -
of the smoke, heat or flame that is being sensed enabling ºº rate of rise heat detectors
struction work. Further details are available within Barbour
Guide ‘CDM and Construction Site Safety’.

PAGE
PAGE 33 >> BARBOUR
BARBOUR ENVIRONMENT, HEALTH & SAFETY
– SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01
ºº flame detectors two-stage systems allows managers to target staff resources
to assist persons to evacuate areas at greatest risk from a
ºº ionisation smoke detectors fire. In a healthcare environment it enables a progressive
horizontal evacuation strategy to be pursued. This involves
ºº optical smoke detectors (chambers type) moving non-ambulant patients from the area involved in
the fire to a separate fire compartment (normally with at
ºº aspirating smoke detectors least 60 minutes’ fire resistance) and then if necessary to
the next fire compartment further away from the fire. In
yy some point detectors incorporate more than one multi-storey buildings the system is often used to prioritise
of these techniques (ie dual function detectors). For use of the stairways by those at immediate risk and prevent
example, they may require the presence of heat and overcrowding of the stairways. In some cases the design of
smoke to trigger an alarm condition. The benefit of this the building may have permitted a staircase which is not of
approach is that the occurrence of unwanted (false) adequate capacity to allow a simultaneous evacuation, and
alarms can be reduced a two-stage alarm system is part of the building design.

yy sprinkler heads incorporate heat detection and Alarm signals must be clearly audible to those intended to
therefore where sprinklers are installed they provide hear them. This normally requires a sound pressure level of
additional automatic detection within a building 65dB(A) in all areas (60dB(A) in small areas and stairways).
Where a signal is intended to rouse a person who may be
yy BS 5839-1 contains further details to assist in the sleeping the sound pressure level should be at least 75dB(A)
specification of the optimal type and layout of at the bed head. Where the background noise level is
detectors for the circumstances. Detectors should be 60dB(A) or greater, then the sounder should achieve a level
selected primarily on the speed of response required, at least 5dB(A) higher.
the need to minimise false alarms and the nature of the
fire hazard. There may be a need for supplementary systems to take
account of noisy conditions or the needs of hearing-
For point smoke detectors to operate effectively a clear impaired workers, including:
space of 500mm around and below should be maintained
and the detectors should not be sited within one metre of yy mechanisms that shut down noisy machinery in the
air inlets or forced ventilation systems. Other requirements event of an alarm signal
apply where the detectors may be near obstructions or in
the apex of a roof. yy visual warning beacons

e. Sounders yy portable alarm devices

A ‘sounder’ is a general term used to describe devices yy pillow vibrating pads.


which provide an audible alarm, such as bells, sirens, and
klaxons or voice sounders. BS 5839-1 includes a detailed A system should have at least two sounders.
explanation of the requirements for sounders in property
protection and life protection fire alarm systems. Where the system utilises speech sounders, the
recommendations of BS 5839-8 should be incorporated.
i) Audible Signals
ii) The Management of Alarms
Alarm signals should be consistent throughout a premises,
so for example, a mixture of bells and sirens should not be There is a need for caution when determining procedures
used in the same building. The sound should be distinctive for silencing alarms. In general alarms should not be
when compared with any other alarm systems in the silenced automatically although BS 5839–1 allows some
building. exceptions.

Within certain types of premises, particularly hospitals and Where there is a procedure for allowing some investigation,
care homes and certain high-rise buildings, it is normally eg by security personnel, on activation of a device prior
required/advisable to operate a two-stage alarm system. to a full alarm sounding, the system must automatically
This enables areas at immediate threat to be signalled sound the alarm after a short period of time. Such systems
to evacuate whilst areas that are not immediately at risk should also be designed so that it is not possible for the
receive an alert signal. Commonly the full evacuation signal investigator to silence the alarm if two or more detectors
will be a continuous alarm whilst the alert signal will be an have been activated or if a single manual call point has
intermittent signal. In the case of voice alarm systems, there been activated.
will be clear instructions broadcast for each area. The use of

PAGE 4 > BARBOUR – SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01

“ Manual
call points
should be kept
Unwanted (false) alarms cause inconvenience and expense.
Advice on the prevention of false alarms can be found
within Section 3 of BS 5839-1 and also in the document
‘Guidance for the Reduction of False Alarms and Unwanted
operation of the fire alarm system, by raising the cover, is
alerted.

Manual call points should be kept unobstructed and clearly


unobstructed and visible. Where the call point is not visible from all directions,
Fire Signals’ - (Chief Fire Officers Association).
clearly visible it may be necessary to display a sign in the vicinity where
BS 5839-2013 emphasises the importance, for residential it can be seen. Signs should meet the requirements of the
care homes, of there being no delay between alarm Health and Safety (Safety Signs and Signals) Regulations


activation and calling the fire brigade. 1996, which means that the sign should have a red
background and include a standard white pictogram.
Details of false alarms should be recorded in the system log
book. g. Servicing

f. Call Points Inspection and servicing of the system should be


undertaken by a competent engineer on at least a
A simple, manual fire alarm system is likely to use manual 6-monthly basis, and more frequently if a risk assessment
call points as the primary means of triggering an alarm determines it is required. Servicing companies should have
condition. Additionally, manual call points are usually UKAS certification. Where in-house personnel are used to
incorporated into automatic systems as a means of undertake servicing it should be ensured that they have
manually raising an alarm. Specific requirements for the sufficient competence to undertake the work correctly
installation and operation of manual call points are detailed in accordance with the British Standard. BS 5839-1:2013.
in BS 5839-1. The main points are: Section 6 specifies in detail the tests and inspections which
should be undertaken including certain more detailed
yy the method of operation of all manual call points in an checks, including functional testing of all detectors, which
installation should be identical unless there is a specific should take place on an annual basis.
reason for difference
Details of all servicing and testing should be updated on
yy the delay between the operation of a call point and the system log book.
the giving of an alarm, at least in the zone of operation,
should not exceed 3 seconds h. Routine Testing and Inspection

yy manual call points must be located on staircases, The requirements for routine testing are set out within BS
landings, exit routes and exits from zone areas and exits 5839-1:2013 Section 6 and are summarised below. This
from the buildings testing can usually be carried out in-house by a person who
has received basic instruction in operation of the alarm
yy to activate a manual call point, it should not be system.
necessary to travel more than 45m within the building,
except for high fire risk premises or if a significant The control panel should be checked daily to confirm that
proportion of the building occupants have limited there are no faults on the system.
mobility, when 25m shall be used
Every week, at approximately the same time, a manual call
yy in general, manual call points should be mounted at a point should be operated during normal working hours.
height of 1.4m above the floor, easily accessible, well The test, which should last for less than one minute, is
illuminated and free from obstruction. A variation to this used to check correct operation of the control panel and
height of 300mm is acceptable. This lower height can audibility within the building. The test should also be
be used when the first person to raise the alarm is likely used to check the correct operation of doors and shutters
to be a wheelchair user. designed to close automatically on activation of the alarm.
Call points should be tested one per week in rotation until
Manual call points within unsupervised public areas may all have been tested.
be subject to malicious operation. It may be practicable
to use an alternate system such as an emergency voice Occupants should be informed of the time of the test and
communication system. Hinged covers are also available asked to report any problems with receiving the signal. In
which reduce accidental operation of call points. The premises where some employees work a different schedule
introduction of such hinged covers is normally regarded of hours so that they would normally miss the test, a second
as d. Controltoof
a variation Contractors
compliance with BS 5839 and should be test should
duties. be carried
Notifiable outare
projects once per
those month
which at a more
involve time when
noted on the system documentation. Some types of hinged they are on duty.
than 30 days, or more than 500 person days of con -
covers also contain a local alarm, so an attempt at malicious struction work. Further details are available within Barbour
Guide ‘CDM and Construction Site Safety’.

PAGE
PAGE 35 >> BARBOUR
BARBOUR ENVIRONMENT, HEALTH & SAFETY
– SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01
Where the system is connected to an alarm receiving yy confirm local fire authority policy in respect of response
centre, the centre should be informed of the test to calls made due to automatic fire detection, and
immediately before it takes place and confirmation should implement relevant procedures accordingly
be sought afterwards that the signal has been received.
yy arrange for daily checks of the control panel, weekly
Standby power supplies should be checked on a monthly testing of the alarm and periodic servicing of the alarm
basis in accordance with BS 5839-1:2013 Section 6. system

The result of the tests should be recorded including the yy ensure that records are made of all servicing, testing
identity of the call point that was tested. and alarm activations.

Key Actions Key Terms


Those with responsibility for non-domestic premises should: Addressable system – a system in which signals from
detectors, manual call points or any other devices are
yy arrange for a competent fire safety risk assessor to individually identified on the control panel.
undertake an assessment, part of which will be to
evaluate the current detection and alarm system within Alarm receiving centre – continuously manned premises,
the premises remote from the location of the alarmed premises, which
acts in accordance with BS EN 50518-1:2013, BS EN 50518-
yy determine the detection system category required 2:2013, BS EN 50518-3:2013, BS 8591:2014.

yy check that suitable numbers and types of detectors, False alarm – fire signal resulting from a cause other than
and manual call points, are appropriately located fire.
throughout the building taking into account the
required category of system Zone – geographical sub-division of a premises which can
be distinguished from other areas for the purpose of fire
yy check that the alarm signal is audible to the required detection and, in some cases, alarm signalling.
standard throughout the premises and is supplemented
by additional visual and other signals where necessary

yy ensure that there are safe and suitable procedures for


Related Documents
investigating alarms and for evacuating the building The following documents provide further guidance:

yy ensure that staff have been trained and that all persons yy Firecode : Fire Safety in NHS : Operational Provisions,
present in the buildings are provided with relevant Part B, Fire Detection and Alarm Systems Department
information about the alarm system, the response of Health – NHS Estates Health Technical Memoranda
required by key individuals, including arrangements for HTM 05-03
calling the fire brigade and the evacuation procedure
yy Building Regulations (England and Wales) Approved
yy ensure that there is a zone plan displayed next to the Document B Vol 1
fire alarm control panel
yy Building Regulations (England and Wales) Approved
yy conduct drills Document B Vol 2

yy check periodically that detectors and manual call points yy Regulatory Reform (Fire Safety) Order 2005
are clear and unobstructed
yy Fire (Scotland) Act 2005
yy have the automatic detection system connected to a
24-hour alarm receiving centre, if desired or if necessary yy Fire Safety (Scotland) Regulations 2006

yy ensure that for a residential care home there is no delay yy Fire Safety Regulations (Northern Ireland) 2010
for investigation between the fire alarm and detection
system operating and a call being made to the fire yy Safety at Sports Grounds Department of Environment,
brigade Heritage and Local Government 1996

yy SI 2010/2214 ‘Building Regulations, England and Wales’


(as amended in 2012 and 2013)

PAGE 6 > BARBOUR – SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01

“ Standby
power supplies
should be
yy Building (Scotland) Regulations 2004 as amended and
Associated Non-domestic Technical Handbook Section
2 Fire (2015)
yy Small Premises providing Sleeping Accommodation

yy Educational and Day Care for Children Premises

checked on a yy Building Regulations (Northern Ireland) 2012 and yy Large and Medium Premises Providing Sleeping
monthly basis associated DFP Technical Booklet E: 2012. Accommodation

Communities and Local Government Guides to Fire Risk yy Transport Premises


Assessment:
yy Evacuation of Disabled Persons from Buildings.
yy Regulatory Reform, Fire Safety, Order 2005 : Short Guide

Further Information
to Making your Premises Safe from Fire

yy Animal Premises and Stables

yy Healthcare Premises
and References
yy BS 5839-1: 2013 ‘Fire Detection and Fire Alarm Systems
yy Residential Care Premises for Buildings - Code of Practice for System Design,
Installation, Commissioning and Maintenance of
yy Open Air Events and Venues Systems in Non Domestic Premises’

yy Sleeping Accommodation yy BS 5839-6: 2013 ‘Fire Detection and Alarm Systems for
Buildings - Code of Practice for the Design, Installation
yy Small and Medium Places of Assembly and Maintenance of Fire Detection and Fire Alarms
Systems in Domestic Premises’
yy Theatres, Cinemas and Similar Premises
yy BS 5839-8: 2013 ‘Fire Detection and Fire Alarm Systems
yy Offices and Shops for Buildings Code of Practice for Design, Installation,
Commissioning and Maintenance of Voice Alarm
yy Large Places of Assembly Systems’

yy Factories and Warehouses yy BS EN 54 Parts 1 - 13, 1996-2011 ‘Fire Detection and


Alarm Systems’
yy Transport Premises and Facilities
yy BS 8591:2014 ‘Remote centres receiving signals from
yy Educational Premises alarm systems - code of practice.’

yy Residential Care Premises yy CIBSE Guide E ‘Fire Engineering’ 2010

yy Means of Escape for Disabled People, Supplementary yy Guidance for the Reduction of False Alarms & Unwanted
Guide. Fire Signals - (Chief Fire Officers Association) 2010

Note that there are differences between the Scottish guides yy Information on fire safety and legislation is available
and these Communities and Local Government Guides, for from the Communities and Local Government
example, the Scottish Government has produced a guide Department http://www.communities.gov.uk/fire/
for small sleeping premises. It is therefore recommended
that those involved in Scottish premises also review the yy Information from the Scottish Government on fire safety
Scottish Practical Fire Safety Guides: can be found at: http://www.infoscotland.com/firelaw/

yy Places of Entertainment and Assembly yy Information on fire safety and legislation in Northern
Ireland is available at: http://www.nifrs.org/
yy Healthcare Premises
Date of Review: November 2015
yy Care Homes

d. Control of Contractors duties. Notifiable projects are those which involve more
yy Offices, Shops and Similar Premises
than 30 days, or more than 500 person days of con -
yy Factories and Storage Premises struction work. Further details are available within Barbour
Guide ‘CDM and Construction Site Safety’.

PAGE
PAGE 37 >> BARBOUR
BARBOUR ENVIRONMENT, HEALTH & SAFETY
– SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01
Disclaimer
Barbour is a trading division and trading name of UBM
Information Limited (UBMi). It has published this Guide in
order to help the promotion of good practice amongst
knowledgeable and competent specialists in the subject
covered by this Guide. By using this Guide, the user
acknowledges, accepts and agrees to the following:

UBMi does not give any condition, warranty or other


term, or accept any duty of care or liability, in connection
with the quality or fitness for purpose of this Guide, or
any loss or damage resulting from reliance on it, and it
excludes all these.

When deciding whether or how to act, the user should


always obtain appropriate professional advice and should
not rely on any information, advice or recommendation
in this Guide, however it has been expressed. The user
is responsible for obtaining professional advice, and
acknowledges that any defects in this Guide would be
detected by a knowledgeable and competent specialist
providing that advice.

Any use of this Guide by any person is subject to UBMi’s


user terms for Barbour services, and by using it the user
is accepting those terms, and agreeing to be bound by
them, on behalf of the user and all other persons for
whom the user undertakes any work.

The user waives (and agrees to waive) all claims for loss or
damage which it might otherwise have against UBMi in
connection with this Guide other than those arising out
of a liability which UBMi has for personal injury (whether
fatal or otherwise) resulting from negligence.

PAGE 8 > BARBOUR – SAFE IN OUR KNOWLEDGE Fire Detection and Alarm
Systems
> 01

Potrebbero piacerti anche