same current

rating, check ti time better to use a load


For each sub panel, break switch
tripping for an check the time
optimal selectivity instead of breaker
tripping as the rating for selectivity and
current of the 2CB cost purpose. Pilot
Add ELC are the same, supply light may be
protections selectivity is not useful for tenants
granted

Indicate power of
each sub panel

The 2 CB have the same


current rating, check ti time
tripping for an optimal
selectivity no need to have 2
breaker in serie, load break
swicth can replace downstream
breaker
Supplied from
SPD 2 protection type
which circuit shall be installed every Add CB to protect
breaker? 30 m height. there is the line+ breaker
no point to install it for control circuit
every floors as it will
take the surge directly
on the busway.