Sei sulla pagina 1di 31

Pöyry Energy

TWO(2) X 500MW
MONG DUONG 1 THERMAL POWER PLANT

APPROVED A
Approved without exception

APPROVED WITH COMMENTS AC


Approved Subject to Incorporation of comments
RETURNED FOR CORRECTION RT
Insufficient Information/ Detail
Resubmit for Approval
REJECTED RJ
Complete redesign required
RECEIVED FOR INFORMATION I
Returned without comments
RECEIVED FOR INFORMATION IC
Returned with comments
Note: Approval or comments does not relieve the Contractor of
any obligations covered under contract

Engineer: David Langhorne


Discipline: Mec Engineer
7-Nov-13
Date:

FOR INFORMATION

B 26-09-13 Revised as per comment S.M.LEE H.D.KIM Y.D.KIM


A 14-01-13 Issued for Information S.M.LEE H.D.KIM G.T.JUNG
REV. DATE DESCRIPTION DSGN CHKD APPD

SUB-CONTRACTOR’S DOCUMENT NUMBER: MD1-0-V-111-02-00001

A 14-01-13 Issued for Information J.A.SEO M.K.LEE J.Y.KIM


REV. DATE DESCRIPTION DSGN CHKD APPD

PROJECT :

TWO(2) x 500 MW MONG DUONG 1 THERMAL POWER PLANT


EMPLOYER :

CONSULTANT :

CONTRACTOR : SUB-CONTRACTOR :

DESIGNED BY DATE TITLE :

S.M.LEE 14-01-13
CHECKED BY DATE
PIPING MATERIAL SPECIFICATION
FOR STEAM TURBINE PACKAGE
H.D.KIM 14-01-13
APPROVED BY DATE PROJECT NUMBER DOCUMENT NUMBER REV.

G.T.JUNG 14-01-13 ADB/MD1-TPIP/EPC150911 MD1-0-V-111-02-00001 A


TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

CONTENTS

1. SCOPE 3

2. CODES & STANDARDS 3

3. GENERAL REQUIREMENT 4

4. ABBREVIATIONS 9

5. MATERIAL CLASS 12

6. INDEX OF PIPING MATERIAL CLASSIFICATION 13

7. BRANCH CONNECTION 17

8. VENT & DRAIN 18

9. PRESSURE & TEMPERATURE INSTRUMENT CONNECTION 19

10. THERMOWELL INSTALLATION 20

11. PIPING MATERIAL CLASSIFICATION SHEETS 22

Sheet 2 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

1.0. Scope

1.1. This specification covers the basic requirements for the materials of the piping system in Two(2) x 500MW
Mong Duong I Thermal Power Plant, Vietnam.

1.2. This specification shall be applied to piping materials indicated on P&I diagrams. Piping systems, however,
which are furnished, as a regular part of proprietary or standard equipment (or package facility) shall be in
accordance with the equipment supplier's standard provided that the equipment supplier’s standard meets the
requirements of the Contract.

1.3. When the piping is connected to equipment, this specification shall be applied to the extent indicated below;
1) Companion flanges, gaskets, bolts and nuts at the equipment nozzle.
2) Companion flanges, gaskets, bolts and nuts at the matching point between the piping furnished as a part
of equipment by its supplier and that provided by purchaser.
3) First shutoff valve with companion flange, gaskets, bolts and nuts in the instrument connecting line.

Note. "First or Second shutoff valve" in instrument connecting line as used herein shall mean the nearest valve to
a line to which the instrument is connected.

1.4. This piping material classification shall not be applied to specially designed companion flanges, gaskets, bolts
and nuts at the equipment nozzles.

2.0. Codes and Standards

2.1. Design, fabrication, testing and inspection of piping materials shall be accomplished in accordance with the
following listed Codes and Standards including revision and addenda in effect at the time of execution of the contract.
If conflict between the requirements of contract and Code & standards, the contract’s requirements shall govern.

ANSI - American National Standards Institute


API - American Petroleum Institute
ASME - American Society of Mechanical Engineers
ASME Sec. I - Rules for Construction of Power Boilers
ASME Sec. II Part A - Ferrous Material Specifications
ASME Sec. II Part D - Properties
ASME Sec. V - Boiler and Pressure Vessel Code, Section V: Nondestructive Examination
ASME Sec. IX - Boiler and Pressure Vessel Code, Section IX: Welding and Brazing Qualifications
ASME B31.1 - Power Piping
ASTM - American Society of Testing & Materials
AWS - American Welding Society
AWWA - American Water Works Association
DIN - Deutsches Institut fur Normung

Sheet 3 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

ISO - International Organization for Standardization


JIS - Japan Industry Standard
MSS - Manufacturers Standardisation Society of the Valve & Fittings Industry Inc.
NFPA - National Fire Protection Association
PFI - Pipe Fabrication Institute
SSPC - Steel Structures Painting Council

2.2. Piping design, materials, fabrication, inspection, testing etc. shall be in accordance with ASME B31.1 latest edition
unless otherwise specified.

2.3. All valves and pipe fittings material shall be as indicated in ASME and ASTM code or approved equivalent.

3.0. General Requirement

3.1. Unit

Unless otherwise specified, SI units shall be applied as the measurement system for the drawings and documents
to be submitted.

3.2. Standard Material

Material for individual piping components shall conform to the requirements of the applicable Codes and Standards
in para. 2.0.

3.3. Pipes

1) Dimensions of pipes shall be in accordance with the following standard.

ASME B36.10M : Welded and Seamless Steel Pipe


ASME B36.19M : Stainless Steel Pipe

2) Minimum wall thickness of straight pipe under internal pressure shall be designed in accordance with
paragraph 104.1.2 and 104.1.4 of ASME B31.1.

B 3) The corrosioin allowance for piping shall be applied as below ;


Where necessary, under corrosive or erosive operating conditions, an additional allowance of 1.5mm shall be
made to ensure that the piping systems concerned shall function satisfactorily over the life of the plant.

B 5) The allowance for thinning of pipe extraos for hot and cold bending piping shall be applied as below ;

Sheet 4 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

Minimum Thickness Recommended


Radius of Bends
Prior to Bending

6 Pipe diameters or greater 1.06 tm


5 Pipe diameters 1.08 tm
4 Pipe diameters 1.14 tm
3 Pipe diameters 1.25 tm

6) Whenever stainless steel pipe are used, the associated fitting and valve shall also be stainless steel material.

3.4. Fittings

1) Dimension shall be as follows :

ASME B16.1 : Gray Iron Pipe Flanges and Flanged Fittings


ASME B16.3 : Malleable Iron Threaded Fittings
ASME B16.4 : Gray Iron Threaded Fittings
ASME B16.9 : Factory-Made Wrought Buttwelding Fittings
ASME B16.11 : Forged Fittings, Socket-Welding and Threaded
ASME B16.28 : Wrought Steel Buttwelding Short Radius Elbows and Returns

2) Fitting construction shall be as follows;

- DN50 and smaller : socket weld or screwed according to the individual specification class.
- DN65 and larger : butt weld

3) All screwed connections shall have taper threads in accordance with ASME B1.20.1 Pipe Threads,
General Purpose.
4) Long radius elbows shall be generally used for all piping, unless otherwise noted.

3.5. Flanges

1) Dimension shall be as follows :

ASME B16.1 : Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250
B
ASME B16.5 : Pipe Flanges and Flanged Fittings: NPS 1/2 (DN15) through NPS 24 (DN600)
Metric/Inch Standard
B
ASME B16.47 : Large Diameter Steel Flanges: NPS 26 (DN650) Through NPS 60 (DN1500)
Metric/Inch Standard
AWWA C207 : Steel Pipe Flanges for Waterworks Service - Sizes 4 in. Through 144 in.
(100 mm Through 3,600 mm)
ISO 7005-1 : Metallic flanges - Part 1: Steel flanges

Sheet 5 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

ISO 7005-2 : Metallic flanges - Part 2: Cast iron flanges

2) All bolt holes shall be spot-faced for nuts.


3) The bore of welding neck flanges shall correspond to the inside diameter of the connecting pipe or fitting.

3.6. Gaskets

1) Dimensions shall be as follows :

ASME B16.20 : Metallic Gaskets for Pipe Flanges - Ring-Joint, Spiral-Wound, and Jacketed
ASME B16.21 : Nonmetallic Flat Gaskets for Pipe Flanges

2) The limiting dimensions of gaskets other than ring joint gaskets for ASME flanges shall be in accordance
with ASME B16.5, Appendix B.

3) Gasket dimensions for flanges larger than DN600 shall be in accordance with the flange standard specified
in the individual specification class.

3.7. Bolts and Nuts for Flange

1) Dimensional requirements of bolts and nuts for flange connection shall be in accordance with ASME B16.5
Table 1C as follows ;

ASME B18.2.1 : Square and Hex Bolts and Screws - Inch Series
ASME B18.2.2 : Square and Hex Nuts (Inch Series)

2) The hot dip galvanized shall be applied according to ASTM A153, BS EN ISO 1461 and applicable standards for
design temperature 210i and below based on ASTM A193 Appendixes X2. Coatings and Application Limits.

B 3) All nuts, bolts and studs for pressure parts shall be stamped to identify the material grade and manufacturer.

3.8. Valves

1) Valve shall conform to the stipulated standards , but not limited to, as below ; ASME

ASME B16.10 : Face to Face and End-to-End Dimensions of Valves


B ASME B16.25 : Buttwelding Ends
ASME B16.34 : Valves Flanged, Threaded and Welding End

B The valve assemblies shall be designed for the pressure and temperature ratings of the piping class specified
in the Piping Material Classification.

Sheet 6 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

2) The material used for valve casings shall be compatible with the material of the related pipes, and comply
with the requirements of specified standards.

3) The actuating force to be exerted to the hand-wheels of valves under hot or cold condition must not exceed
18 kg force. Valves larger than DN 250 shall be geared to minimize effort and shall be, additionally,
provided with stub shafts, to permit manual application of a portable motor.

4) The manually operated valves in the sizes and pressure classes shown below shall be provided with a gear
operator as minimum. Handwheels shall be provided with provisions for pneumatic wrench operation.

ASME Gate Globe Plug / Ball Butterfly


Rating Valve Valve Valve Valve

150 DN 250 and Larger DN 250 and Larger DN 150 and Larger B DN 200 and Larger
300 DN 250 and Larger DN 250 and Larger DN 150 and Larger B DN 200 and Larger
600 DN 250 and Larger DN 200 and Larger DN 150 and Larger -
900 DN 200 and Larger DN 150 and Larger - -
1500 DN 150 and Larger DN 100 and Larger - -
2500 DN 150 and Larger DN 100 and Larger - -

Gear Operating Type


- Gate, Globe Valves : Bevel-gear type
- Ball, Plug, Butterfly Valves : Worm-gear type

5) All valves shall be fitted with outside screw rising spindles unless otherwise specified or approved.
Spindles of valves for outdoor use shall have weatherproof protection covers. In general all valves exposed
to the elements shall be corrosion resistant.

6) Hydrostatic testing for valves shall be in accordance with B16.34.

7) Nameplates shall be of stainless steel with engraved letters filled with black wax or enamel.

8) Any valve which is designed uni-directional flow shall have an arrow embossed or cast on the valve
body clearly indicating the required flow direction.

3.9. Pipeline Velocities

The following maximum fluid velocities or lower velocities, if necessary shall be used in the selection of piep sizes.
For pipe sizes between tabulated values, the velocities associated with the smaller pipe size shall be used.

Maximum Allowable Fluid Velocities


Service or Type of Fluid

Sheet 7 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

Pipe Sizes (Inside Diameter), mm 50 200 350 500 and Larger


Superheated Steam
* Contiuous Service m/sec 30 45 70 70
* Intermittent Service m/sec 38 56 90 103
Saturated Steam m/sec 15 30 30 30
Sub-Atmosheric Steam m/sec -- 40 40 40
All Gases and Air m/sec 15 20 25 25
Condensate, Fuel Oil Heating Steam,
Condensate, Water treatment System
(Not Rubber Lined)
* Pump Suction (At Design Flow) m/sec 0.61 1.52 1.52 1.52
* Pump Discharge m/sec 1.52 3.05 3.66 4.57
Gravity Drains m/sec 0.91 1.22 1.52 2.44

In the selection of pipe sizes for the steam turbine bypass system, the velocities of continuous serviceshall be used.
The fuel oil and lubricating oil piping shall be sized based on flow rate, viscosity, and available or allowable head loss
rather than velocity criteria. As a secondary criteria, the maximum oil velocity shall not exceed 2.00 meters per second.

3.10. Design Criteria for Piping System

The following design criteria for piping have been considered as per the most stringent condition of the contract requirements
vendor data and maximum operating condition on heat balance diagrams.

1) Main Steam System


- HP Steam System
Design Temperature : 553°C
Design Pressure : 176.1barg

- Cold Reheat Steam System


Design Temperature : 365°C
Design Pressure : 51barg

Sheet 8 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

2) Other System
- According to contract requirement “para 4.11.3.4 Pipe Design Temperature & Pressure”.

4.0. ABBREVIATIONS

Abbreviations used in this specification are defined in table of "ABBREVIATION" as follows.


CODE ABBREVIATION DESCRIPTION
AG Aboveground
A
A/S Alloy Steel
B&S Bell & Spigot
BALL Ball Type
BB Bolted Bonnet
BC Bolted Cap
BE Bevelled End
B
BFP Boiler Feedwater Pump
BHN Brinell Hardness Number
BN Buna-N Lining
BPVC Boiler and Pressure Vessel Code
BW Butt Weld
CA Corrosion Allowance
CALC. Calculation
CEP Condensate Extraction Pump
C CL. Class
CPVC Chlorinate Polyvinyl Chloride
C/S Carbon Steel
CRH Cold Reheat
DI Ductil Iron
D DU-PL-SPL Dual Plate Spring Loaded Type (for Check Valve)
DN Nominal Diameter
EC External Coating
EFW Electric Fusion Welding
E
ERW Electric Resistance Welding
EXT External

Sheet 9 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

CODE ABBREVIATION DESCRIPTION


FB Full Bore Type
FF Full Face (Flat Face)
FLG Flange
FLGD Flanged
F F to F Face to Face
FP Full Port
FR Flat Ring
F.V. Full Vacuum
FWH Feedwater Heater
GALV. Galvanized
GR. Grade
G
GRP Glass-Fiber Reinforced Thermosetting-Resin Plastic Polyester
GRE Glass-Fiber Reinforced Plastic Epoxy
HD Hardened
HDPE High Density Poly Ethylene
HEX NUT Hexagonal Nut
H HF Hardfaced
H. HEX. NUT Heavy Hexagonal Nut
HRH Hot Reheat
HP High Pressure
ID Inside diameter
IP Intermediated Pressure
ISNS Inside Screw and Non-Rising Stem
I
ISRS Inside Screw and Rising Stem
ISO. Isolation
IR Inner ring
LIFT Lift Type (for Check Valve)
L LJ Lapped (Loose) Joint
LP Low Pressure
M. BOLT Machine Bolt
M&F Large Male and Female Face
M
MJ Mechanical Joint
MOV Electric Motor Operated Valve
OD Outside Diameter
OR Outer Ring
O
OSNB Outside Screw Non-Bonnet
OS & Y Outside Screw and Yoke Type

Sheet 10 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

CODE ABBREVIATION DESCRIPTION


PB Pressure Seal Bonnet
PC Pressure Seal Cap
PCV Pressure Control Valve
P
PE Plain End, Poly Ethylene
PRV Pressure Regulating Valve
PVC Polyvinyl Chloride
RF Raised Face
R/L Rubber Lined
RP Reducing Port
R
RTJ Ring Type Joint Face
RT Radiographic Testing
RTFE Reinforced Teflon
SB Screwed Bonnet
SC Screwed Cover
SCR'D Screwed
SCH Schedule
SE Screwed Socket End
S/H Superheater
S SMLS Seamless
SO Slip-On Weld
S/S Stainless Steel
SW Socket Weld
SWING Swing Type (for Check Valve)
ST Steam Turbine
STL Stellited
T or THK. Thickness (in, mm)
T
TE Threaded End
UB Union Bonnet
U UC Union Cap
UG Underground
W Welded Product
WC Welded Cover
W
WN Welding Neck
WB Welded Bonnet
Y Y Y-Type / Y-Pattern

Sheet 11 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

5.0. MATERIAL CLASS

1) 2) 3) 4)

1) Class / Rating : See Para. 5.1


2) Material : : See Para. 5.2
3) Serviced Area : See Para. 5.3
4) Sequence Number : See Para. 5.4

5.1. Class / Rating


A : 2500# Over ASME B16.34
B : 2500# ASME B16.34
C : 1500# ASME B16.34
D : 900# ASME B16.34
E : 600# ASME B16.34
F : 400# ASME B16.34
G : 300# ASME B16.34
H : 150# ASME B16.34 / AWWA C207
CL.D I : - Not Used
J : 125# ASME B16.1
K : - Manufacturer’s Rating

5.2. Materials
A : Alloy Steel (Cr-Mo)
B : Carbon Steel
C : Stainless Steel
D : High Density Poly Ethylene (HDPE)
E : Polyvinyl Chloride (PVC)
F : Glass-fiber Reinforced Plastic Polyester (GRP)
G : Dutile Iron
H : Glass-fiber Reinforced Plastic Epoxy (GRE)

5.3. Sequence Number


This is a sequential number for the piping material classification.

5.4. Suffix(Service Area / Additibe Material)

None : Above Ground

U : Under Ground

G : Galvanized

B : Basalt Lined

Sheet 12 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

6.0. INDEX OF PIPING MATERIAL CLASSIFICATION

Most Stringent
Condition
Class Basic Corrosio
System Remarks
Rating Material n
Design Design
Class Allowance
Press. Temp.
('c)
(barg)

* TBN MAIN Steam


* MSV #1,2 Before/After SEAT Drain 2500# 184 550 1.5 mm
* #1,2,3,4 MS LEAD PIPE Drain A/S
B BA31 * HP INNER Casing Drain (P91, 9Cr-1Mo-V)
* BDV Inlet
* VENTILATOR Valve Discharge

* CRV-1,2 Before/After SEAT Drain 600# A/S 49 549 1.5 mm


B EA31 * Equalizer Valve Discharge (P91, 9Cr-1Mo-V)

A/S
* VENTILATOR Valve 1ST LEAK-OFF 600# (P22,2-¼Cr-1Mo) 51 490 1.5 mm
* BDV 1ST LEAK-OFF
* HP OUTER CASING Drain
B EA33
* BDV Outlet

A/S
* CV 1,2,3,4 1ST Steam LEAK-OFF 600# (P11,1-¼Cr-1/2Mo) 20 529 1.5 mm
* CV 1ST Steam LEAK-OFF COMMON
B EA34

* Aux. Steam SEAL Feed Bypas, Drain


* CEP Disch. To WSS Bypass, WSV Inlet
* Heating Steam (HSPV IN/OUTLET) 300# C/S (A106-B) 20 365 1.5 mm
* Heating Steam Drain
* SSAFV & HSBV INLET
B GB31 * GENERATOR SHAFT SEAL SYSTEM

A/S
* VENTI. VV/BDV 2ND LEAK-OFF 150# 0.3 516 1.5 mm
* MSV1&2 1ST Steam LEAK-OFF (P22, 2-¼Cr-1Mo)
* MSV1&2 2ND Steam LEAK-OFF
B HA31

* MSV2 1ST Steam LEAK-OFF A/S


B
HA32 * CV 1,2,3,4 2ND Steam LEAK-OFF 150# 0.3 516 1.5 mm
(P11, 1-¼Cr-½Mo)

Sheet 13 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

Most Stringent
Condition
Class Class Basic Corrosio
System n
Rating Material Design Design Remarks
Allowance
Press. Temp.
(barg) (i )

* Auxiliary Steam System (LP)


* PACKING STEAM SEAL
100% RT for
* LP A , B WASTE Water
DN650 and
B HB31 * PACKING STEAM SEAL EXHAUST 150# C/S (A106- 8 304 1.5 mm
Larger
* STEAM SEAL DUMP B)
* STEAM SEAL LOW POINT Drain
* GLAND STEAM CONDENSER Drain
* STEAM SEAL HEADER
* H2&CO2 CONTROL PIPING

B
* BEARING OIL Drain S/S (A312-TP316)
HC31 150# 10 50 0 mm
* OIL FEED TO BEARING
* OIL TO SIGHT DISCH. FOR
BEARING
* CONDITIONER IN/OUTLET
* HYDROGEN SEAL OIL TO TE / CE

* Instrument Air S/S (A312-TP316)


B HC32 150# 10 60 2.0 mm
* Service Air

* STATOR COOLING WATER


B
HC33 S/S (A312-TP304)
150# 10 40 0 mm

Sheet 14 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

7.0. BRANCH CONNECTION

BRANCH

MAIN LINE

TEE SWEEPOLET WELDOLET STUB-IN


SOCKOLET
THREADOLET
SYMBOL : T - TEE
W - WELDOLET
I - STUB IN
S - SOCKOLET / H.CPLG / THREADOLET
R - REDUCING TEE

65 T
80 R T 20 T
100 R R T 25 R T
150 R R R T 40 R R T
200 W W R R T 50 R R R T
MAIN PIPE SIZE [DN]

MAIN PIPE SIZE

250 W W R R R T 65 S S S S
300 W W W R R R T 80 S S S S
350 W W W R R R R T 100 S S S S
400 W W W R R R R R T 150 S S S S
450 W W W W R R R R R T 200 S S S S
500 W W W W R R R R R R T 250 S S S S
600 W W W W W R R R R R R T 300 S S S S
700 W W W W W W R R R R R R T 350 S S S S
800 W W W W W W W R R R R R R T 400 S S S S
900 W W W W W W W W R R R R R R T 450 S S S S
1000 W W W W W W W W W R R R R R R T 500 S S S S
1100 W W W W W W W W W W R R R R R R T 600 S S S S
1200 W W W W W W W W W W W R R R R R R T above S S S S
65
80

1000
1100
1200

20
25
40
50
100
150
200
250
300
350
400
450
500
600
700
800
900

BRANCH PIPE SIZE BRANCH PIPE SIZE


(DN65 and Larger) (DN50 and Smaller)

Sheet 15 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

8.0. VENT & DRAIN

Vent & Drains Vent Drain


Minimum Size & Valve Type DN20 Globe DN25 Globe

8.1. Valves shall be in accordance with the applicable piping class sheet.

8.2. Double isolation globe valves shall be provided on vents and drains of system having pressure 40 bar and higher.

8.3. Vents and drains required solely for testing shall be plugged with cap.

8.4. All drain valves shall be a minimum of DN25 and provided with a chained cap.
All vent valves shall be a minimum of DN20 and provided with a chained cap.
Valves, smaller than DN25 shall only be used where the size of main pipe is DN20 or smaller.

Sheet 16 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

9.0. PRESSURE & TEMPERATURE INSTRUMENT CONNECTION

9.1.1. Pressure class of fitting (i.e. 3000#, 6000# or 9000#) in accordance with applicable piping material classification.

Pipe Line Pressure Instrument Temperature Instrument


Class Connection Connection
2500# Flange Rating DN 20 Socket Welding - Pipe wall thickness greater
Classes and Higher than 19.05mm (Note 1)

1500# & 900# Flange DN 20 Socket Welding - Pipe wall thickness


Rating Classes 19.05mm & Less (Note 2)

- DN 80 and Smaller (Note 3)

600# Flange Rating DN 20 Socket Welding - DN 25 Threaded half Coupling


Classes & Lower
DN 25 Flanged FF - DN 25 Socket Welding
(For GRP piping) (For Fuel Oil and Steam System)

- DN 80 and Smaller (Note 3)

Note) 1. Para. 10.1 : “Nominal pipe wall thickness greater than 19.05mm”
2. Para. 10.2 : “Nominal pipe wall thickness 19.05mm & less”
3. Para. 10.3 : “Thermowell installation in DN 80 and smaller piping”
4. Para. 10.4 : “Thermowell material selection chart”

9.1.4. Double root valves arranged in series shall be provided for all high pressure application to ASME CL.600 and above.

Sheet 17 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

10.0. THERMOWELL INSTALLATION

10.1. Nominal Pipe Wall Thickness Greater Than 19.05 mm (3/4 in.)

10.2. Nominal Pipe Wall Thickness 19.05 mm (3/4 in.) & Less

Sheet 18 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

10.3. Thermowell Installation in DN80 and Small Lines

10.3.1. Description of parts

A : Standard Thermowell, Material per sheet Para. 10.4.


B : Half coupling / Sockolet
C : Reducer (DN100 to Run size for DN65 and DN80) ; All Butt weld
Swage (DN100 to Run size for DN50 and below) ; Butt weld and Socket weld
D : Pipe ; DN 100 per piping class sheet
E : Line pipe ; Butt weld for DN65 and DN80, Socket weld for DN50 and below
F : Fillet/socket weld
G : Full penetration weld

10.3.2. Preferred Arrangement

(1) Vertical lines - concentric.


(2) Horizontal lines - Eccentric. Install well in horizontal plane.

Sheet 19 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION
Rev. B

10.4. Thermowell Material Selection Chart

Pipe Material
Thermowell
Specification
ASTM Bar Forging
Carbon Steel
SA/A 106 - B SA/A 479 TP316 SA/A 182 F316
SA/A 106 - C SA/A 479 TP316 SA/A 182 F316
SA/A 53 - B SA/A 479 TP316 SA/A 182 F316
SA/A PI 5L - B SA/A 479 TP316 SA/A 182 F316

Alloy Steel
SA/A 335 - P11 (1.1/4Cr-1Mo-Si) SA/A 182 F11
SA/A 335 - P22 (2.1/4Cr-1Mo) N/A SA/A 182 F22
SA/A 335 - P91 (9Cr-1Mo-V) SA/A 182 F91
SA/A 335 - P5 (5Cr-1/2Mo) SA/A 182 F5

Stainless Steel
SA/A 312 Gr.TP304 SA/A 479 TP316 SA/A 182 F316
SA/A 312 Gr.TP304L SA/A 479 TP316L SA/A 182 F316L
SA/A 312 Gr.TP316 SA/A 479 TP316 SA/A 182 F316
SA/A 312 Gr.TP316L SA/A 479 TP316L SA/A 182 F316L

11.0. Piping Material Classification Sheets

Each piping material classes indicates the maximum design pressures and temperatures for which the piping
material classes may be used. For each piping system, or portion thereof, a piping material class shall be
selected which provides material appropriate for the service conditions and which has a maximum allowable
design pressure and temperature which equal or exceeds the design pressure and temperature of the line
for which it is to be used.

Please refer to Attached Piping Material Classification sheets.

Sheet 20 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

SYST DESIGN DESIGN CORROSION


PRESS. (barg) TEMP. (℃) ALLOWANCE MATERIAL CLASS BA31
EM

SERVICE RATING ASME CL.2500


* TBN MAIN Steam 175.1 553
* MSV #1,2 Before / After SEAT Drain 175.1 553
553 APPLICATION CODE ASME B31.1
* #1,2,3,4 MS LEAD PIPE Drain 175.1
B * HP INNER Casing Drain B 143.2 B
522.3
1.5 MM
* BDV Inlet 94.0 499.6
* VENTILATOR Valve Discharge 175.1 553 MATERIAL ALLOY STEEL

PIPE AND FITTING VALVE


SIZE WALL THK SIZE
ITEM (DN) / RATING MATERIAL DESCRIPTION (DN) MATERIAL & DESCRIPTION

20 ~ 50 SCH.160 A335-P91 SMLS, PE GATE

65 ~ 250 SCH.160 A335-P91 SMLS, BE


20 ~ 50 A182-F91, CL.2500, SW
300 MWT 30.48 A335-P91 SMLS, BE
65 ~ 500 A217-C12A, CL.2500, BW
PIPE

GLOBE

20 ~ 50 A182-F91, CL.2500, SW

65 ~ 500 A217-C12A, CL.2500, BW


20 ~ 50 CL.6000 A182-F91 SW

FITTING 65 ~ 500 (1) A234-WP91 SMLS, BW CHECK

20 ~ 50 A182-F91, CL.2500, SW, Y-LIFT


20 ~ 50 CL.2500 A182-F91 SW, RF
65 ~ 500 A217-C12A, CL.2500, BW, TILTING
FLANGE 65 ~ 500 CL.2500 A182-F91 WN, RF

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL .2500 WITH GRAPHITE FILLER, INNER &
OUTER RINGPER ASME B16.20

N/A

- STUD BOLT : A193-B16


BOLT / NUT ALL
- HEAVY HEX NUT : A194-3

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.15) STANDARD CLASS
OTHERS TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 1000 3030 537.8 208.9

1022 3016.8 550.0 208.0

1050 3000 565.6 206.9

Sheet 21 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS EA31
PRESS. (barg) TEMP. (℃) ALLOWANCE

* CRV-1,2 Beforte / After SEAT Drain SERVICE RATING ASME CL.600


43.3 553 1.5 MM
B
* Equalizer Valve Discharge 43.3 553
APPLICATION CODE ASME B31.1

MATERIAL ALLOY STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20~50 XS A335-P91 SMLS, PE GATE

20 ~ 50 A182-F91, CL.600, SW

PIPE

GLOBE

20 ~ 50 A182-F91, CL.600, SW

20 ~ 50 CL.3000 A182-F91 SW

FITTING CHECK

20 ~ 50 A182-F91, CL.600, SW, Y-LIFT


20 ~ 50 CL.600 A182-F91 SW, RF

FLANGE

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL CL.600 WITH GRAPHITE FILLER,
INNER & OUTER RING PER ASME B16.20
N/A

- STUD BOLT : A193-B16


BOLT / NUT ALL
- HEAVY HEX NUT : A194-3

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.15) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 1000 725 537.8 50.0
(2) For DN 650 and larger, all piping material will be welded type with 100% RT. 1020.2 723.0 549.0 49.9
(3) The dimension of flagne, gasket and bolt shall be met the requirement 1050 720 565.6 49.6
of ASME B16.47 series-A.

Sheet 22 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS EA33
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.600


* VENTILATOR VALVE 1ST LEAK-OFF 41.2 481 1.5 MM
* BDV 1ST LEAK-OFF 41.2 438
* HP OUTER CASING Drain 48.2 364.1 APPLICATION CODE ASME B31.1
B * BDV Outlet 41.2 499.2
MATERIAL ALLOY STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~ 50 XS A335-P22 SMLS, PE GATE

20 ~ 50 A182-F22, CL.600, SW

PIPE

GLOBE

20 ~ 50 A182-F22, CL.600, SW

20 ~ 50 CL.3000 A182-F22 SW

FITTING CHECK

20 ~ 50 A182-F22, CL.600, SW, Y-LIFT


20 ~ 50 CL.600 A182-F22 SW, RF

FLANGE

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL CL.600 WITH GRAPHITE FILLER,
INNER & OUTER RING PER ASME B16.20
N/A

- STUD BOLT : A193-B16


BOLT / NUT ALL
- HEAVY HEX NUT : A194-3

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.9) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

850 975 454.4 67.2


897.8 903.3 481 62.3
900 900 482.2 62.1

Sheet 23 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION


DESIGN DESIGN CORROSION
SYSTEM MATERIAL CLASS EA34
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.600


* CV 1,2,3,4 1ST Steam LEAK-OFF 41.2 481 1.5 MM
* CV 1ST Steam LEAK-OFF COMMON 41.2 481
APPLICATION CODE ASME B31.1

MATERIAL ALLOY STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

B 15 ~ 50 XS A335-P11 SMLS, PE GATE

65 ~ 100 STD.WT A335-P11 SMLS, PE


B 15 ~ 50 A182-F11, CL.600, SW

PIPE

GLOBE

B 15 ~ 50 A182-F11, CL.600, SW

B 15 ~ 50 CL.3000 A182-F11 SW

FITTING 65 ~ 100 (1) A234-WP11 SMLS,BW CHECK

B 15 ~ 50 A182-F11, CL.600, SW, Y-LIFT


B 15 ~ 50 CL.600 A182-F11 SW, RF

FLANGE
65 ~ 100 CL.600 A182-F11 WN, RF

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL CL.600 WITH GRAPHITE FILLER,
INNER & OUTER RING PER ASME B16.20
N/A

- STUD BOLT : A193-B16


BOLT / NUT ALL
- HEAVY HEX NUT : A194-3

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.9) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 850 975 454.4 67.2
897.8 903.3 481 62.3
900 900 482.2 62.1

Sheet 24 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS GB31
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.300


* Aux. Steam SEAL Feed Bypas, Drain 20 365 1.5 MM
* CEP Disch. To WSS Bypass, WSV Inlet 33 60
APPLICATION CODE ASME B31.1
B * Heating Steam (HSPV IN/OUTLET) 9.5 215
* Heating Steam Drain 9.5 215
MATERIAL CARBON STEEL
* SSAFV & HSBV INLET 20 / 10.3 365 / 327
* GENERATOR SHAFT SEAL SYSTEM 10 85

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~50 XS A106-B SMLS, PE GATE

65 ~ 600 STD.WT A106-B SMLS, BE


20 ~ 50 A105, CL.600, SW

65 ~ 600 A216-WCB, CL.300, BW


PIPE

GLOBE

20 ~ 50 A105, CL.600, SW

65 ~ 600 A216-WCB, CL.300, BW


20 ~ 50 CL.3000 A105 SW

FITTING 65 ~ 600 (1) A234-WPB SMLS, BW CHECK

20 ~ 50 A105, CL.600, SW, Y-LIFT


20 ~ 50 CL.300 A105 SW, RF
65 ~ 600 A216-WCB, CL.300, BW, SWING
FLANGE
65 ~ 600 CL.300 A105 WN, RF

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL CL.300 WITH GRAPHITE FILLER,
INNER & OUTER RING PER ASME B16.20
N/ A

- STUD BOLT : A193-B7


BOLT / NUT ALL
- HEX NUTS : A194-2H

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.1) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 650 550 343.3 37.9
656.6 547.4 347.0 37.7
700 530 371.1 36.5

Sheet 25 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS HA31
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.150


* VENTILATOR VV 2’ND LEAK-OFF 0.3 458 1.5 MM
* BDV 2ND LEAK-OFF 0.3 412
* MSV 1 1ST Steam LEAK-OFF 0.3 516 APPLICATION CODE ASME B31.1
* MSV 1 &2 2ND Steam LEAK-OFF 0.03 515
MATERIAL ALLOY STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~ 50 XS A335-P22 SMLS, PE GATE

65 ~ 100 STD.WT A335-P22 SMLS, BE


20 ~ 50 A182-F11, CL.600, SW

65 ~ 100 A217-WC9, CL.150, BW


PIPE

GLOBE

20 ~ 50 A182-F11, CL.600, SW

65 ~ 100 A217-WC9, CL.150, BW


20 ~ 50 CL.3000 A182-F22 SW

FITTING 65 ~ 100 (1) A234-WP22 SMLS, BW CHECK

20 ~ 50 A182-F11, CL.600, SW, Y-LIFT


20 ~ 50 CL.150 A182-F22 SW, RF
65 ~ 100 A217-WC9, CL.150, BW, SWING
FLANGE
65 ~ 100 CL.150 A182-F122 WN, RF

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL CL.150 WITH GRAPHITE FILLER,
INNER & OUTER RING PER ASME B16.20
N/A

- STUD BOLT : A193-B16


BOLT / NUT ALL
- HEAVY HEX NUT : A194-3

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.9) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 950 35 510 2.4
960.8 31.8 510.4 2.2
1000 20 537.8 1.4

Sheet 26 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS HA32
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.150


* MSV2 1ST Steam LEAK-OFF 0.3 516 1.5 MM
* CV 1,2,3,4 2ND Steam LEAK-OFF 0.3 458
* CV 2ND LEAK-OFF COMMON 0.3 458 APPLICATION CODE ASME B31.1

MATERIAL ALLOY STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~ 50 XS A335-P11 SMLS, PE GATE

65 ~ 100 STD.WT A335-P11 SMLS, BE


20 ~ 50 A182-F11, CL.600, SW

65 ~ 100 A217-WC6, CL.150, BW


PIPE

GLOBE

20 ~ 50 A182-F11, CL.600, SW

65 ~ 100 A217-WC6, CL.150, BW


20 ~ 50 CL.3000 A182-F11 SW

FITTING 65 ~ 100 (1) A234-WP11 SMLS, BW CHECK

20 ~ 50 A182-F11, CL.600, SW, Y-LIFT


20 ~ 50 CL.150 A182-F11 SW, RF
65 ~ 100 A217-WC6, CL.150, BW, SWING
FLANGE
65 ~ 100 CL.150 A182-F11 WN, RF

OTHER

4.5mm THK. SPIRAL WOUND 304 S/S


GASKET ALL CL.150 WITH GRAPHITE FILLER,
INNER & OUTER RING PER ASME B16.20
N/A

- STUD BOLT : A193-B16


BOLT / NUT ALL
- HEAVY HEX NUT : A194-3

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.9) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 850 65 454.4 4.5
856.4 63.1 458 4.4
900 50 482.2 3.5
B 960.8 B 31.8 B 516 B 2.2

Sheet 27 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS HB31
PRESS. (barg) TEMP. (℃) ALLOWANCE

* PACKING Steam SEAL 0.4 328.1 SERVICE RATING ASME CL.150


* LP A , B WASTE Water 0.1 55 1.5 MM

B * PACKING Steam SEAL EXHAUST 0.1 324.9


APPLICATION CODE ASME B31.1
* STEAM SEAL DUMP 0.4 335.8
* STEAM SEAL LOW POINT DRAIN 0.1 172.5
MATERIAL CARBON STEEL
* GLAND STEAM CONDENSER DRAIN 8.8 60
* STEAM SEAL HEADER 0.4 335.8
* H2 & CO2 CONTROL PIPING 9 80

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~ 50 XS A106-B SMLS, PE GATE

65 ~ 600 STD.WT A106-B SMLS, BE


20 ~ 50 A105, CL.600, SW

PIPE (2) 65 ~ 600 A216-WCB, CL.150, BW

GLOBE

20 ~ 50 A105, CL.600, SW
20 ~ 50 CL.3000 A105 SW
65 ~ 600 A216-WCB, CL.150, BW
FITTING (2) 65 ~ 600 (1) A234-WPB SMLS, BW

CHECK

20 ~ 50 CL.150 A105 SW, RF


20 ~ 50 A105, CL.600, SW, Y-LIFT
65 ~ 600 CL.150 A105 WN, RF
FLANGE 65 ~ 600 A216-WCB, CL.150, BW, SWING

BALL

4.5mm THK. SPIRAL WOUND 304SS B


15 ~ 50 A105, CL.600, SW
20 ~ 600 CL.150 WITH GRAPHITE FILLER,
OUTER RING PER ASME B16.20 65 ~ 600 A216-WCB, CL.150, BW
GASKET

- STUD BOLT : A193-B7, HOT DIP. GALVA.


BOLT / NUT ALL
- HEX NUTS : A194-2H, HOT DIP. GALVA.

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 1.1) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 500 170 260.0 11.7
(2) For DN 650 and larger, all piping material will be welded type with 100% RT. 552.2 154.3 289.0 10.6
(3) The dimension of flagne, gasket and bolt shall be met the requirement 600 140 315.6 9.7
of ASME B16.47 series-A.

Sheet 28 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS HC31
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.150


B * BEARING OIL DRAIN 2.5 80 0 MM
* OIL FEED TO BEARING 4.9 85
* OIL TO SIGHT DISCH. FOR BEARING 2.5 85 APPLICATION CODE ASME B31.1
* CONDITIONER IN/OUTLET 4.9 85
* HYDROGEN SEAL OIL TO TE/CE 7 46
MATERIAL STAINLESS STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~ 50 SCH.40S A312-TP316 SMLS, PE GATE

65 ~ 600 SCH.10S A312-TP316 WELD, BE


20 ~ 50 A182-F316, CL.600, SW

65 ~ 600 A351-CF8M, CL.150, FLGD-RF


PIPE

GLOBE

20 ~ 50 A182-F316, CL.600, SW

65 ~ 600 A351-CF8M, CL.150, FLGD-RF


20 ~ 50 CL.3000 A182-F316 SW

FITTING 65 ~ 600 (1) A403-WP316W WELD, BW CHECK

20 ~ 50 A182-F316, CL.600, SW, Y-LIFT

20 ~ 50 CL.150 A182-F316 SW, RF 65 ~ 250 A351-CF8M, CL.150, WAFER, DU-PL-SPL

FLANGE 300 ~ 600 A351-CF8M, CL.150, FLGD-RF


65 ~ 600 CL.150 A182-F316 SO, RF

BUTTERFLY

65 ~ 250 A351-CF8M, CL.150, WAFER


3.2mm THK. NON-ASBESTOS
GASKET ALL CL.150 COMPRESSED FIBER FLAT RING 300 ~ 600 A351-CF8M, CL.150, FLGD-RF
PER ASME B16.21
BALL

- STUD BOLT : A193-B8M B 15 ~ 50 A182-F316, CL.800, SW


BOLT / NUT ALL
- HEX NUTS : A194-8M 65 ~ 600 A351-CF8M, CL.150, BW

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 2.2) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 100 275 37.8 19.0
122 259 50.0 17.9
200 235 93.3 16.2

Sheet 29 of 30
TWO(2) X 500MW MONG DUONG1 THERMAL POWER PLANT
PIPING MATERIAL CLASSIFICATION Rev.B

PIPING MATERIAL CLASSIFICATION

DESIGN DESIGN CORROSION


SYSTEM MATERIAL CLASS HC33
PRESS. (barg) TEMP. (℃) ALLOWANCE

SERVICE RATING ASME CL.150


B * STATOR COOLING WATER 10 40 0 MM
10 40
APPLICATION CODE ASME B31.1
10 40

MATERIAL STAINLESS STEEL

PIPE AND FITTING VALVE

SIZE WALL THK SIZE


ITEM MATERIAL DESCRIPTION MATERIAL & DESCRIPTION
(DN) / RATING (DN)

20 ~ 50 SCH.40S A312-TP304 SMLS, PE GATE

65 ~ 600 SCH.10S A312-TP304 WELD, BE


20 ~ 50 A182-F304, CL.600, SW

65 ~ 600 A351-CF8, CL.150, FLGD-RF


PIPE

GLOBE

20 ~ 50 A182-F304, CL.600, SW

65 ~ 600 A351-CF8, CL.150, FLGD-RF


20 ~ 50 CL.3000 A182-F304 SW

FITTING 65 ~ 600 (1) A403-WP304W WELD, BW CHECK

20 ~ 50 A182-F304, CL.600, SW, SWING


20 ~ 50 CL.150 A182-F304 SW, RF
65 ~ 600 A351-CF8,CL.150, FLGD-RF, SWING
FLANGE
65 ~ 600 CL.150 A182-F304 SO, RF

BUTTERFLY

65 ~ 250 A351-CF8,CL.150, WAFER


3.2mm THK. NON-ASBESTOS
GASKET ALL CL.150 COMPRESSED FIBER FLAT RING 300 ~ 600 A351-CF8,CL.150, FLGD-RF
PER ASME B16.21
BALL

- STUD BOLT : A193-B8 B 15 ~ 50 A182-F304, CL.800, SW


BOLT / NUT ALL
- HEX NUTS : A194-8 65 ~ 600 A351-CF8, CL.150, BW

PRESSURE-TEMPERATURE RATING
ASME B16.34(GROUP 2.1) STANDARD CLASS
OTHERS
TEMP PRESSURE TEMP PRESSURE
(deg F) (psi g) (deg C) (bar g)

NOTE : (1) Thickness shall be equal to or greater than that of pipe. 100 275 37.8 19.0
104 273.2 40.0 18.9
200 230 93.3 15.9

Sheet 30 of 30
Pőyry Comment
Two(2) x 500MW Mong Duong 1 Thermal Power Plant Project

Piping Material Specification


Dwg. / Doc. Title Dwg. / Doc. No. MD1-0-V-111-02-00001
for Steam Turbine Package
HDEC DT No. MD1-HDH-EVN-X-5071 Submitted Date Rev. A
Pőyry TR No. Received Date
New HDEC DT Re-Submitted
No. Date
Status Received for Information – Returned with Comments

No. Pőyry’s Comments Contractor’s Reply / Action


1 Section 3.10 – The main steam line design
criteria differs from the data in Section 6.0.
Note that Section 6.0 is the same as specified in
MD1-0-P-400-02-00001.

2 Section 3.10 – The design criteria for piping


system should include hot reheat as there
appears to be a section pipe between the control
valves and the turbine nozzles.

3 Section 6 – Where is the IP exhaust to LP


turbine inlet pipe? It should be in HB31.

4 Section 6 material classifications need to be


added to the appropriate steam turbine P&I
Diagrams.

5 Section 6 – P&I Diagram MD1-0-V-111-21-


00003 indicates pipe stubs for all extraction
connections so they should be included in
Section 6.

6 Section 6 – Why is the generator shaft seal


system listed in GB31 which has design
conditions of 20 bar and 365 deg C?

Page 1 / 1