SUBSTATION VIEWS AND FOUNDATION PROPOSAL

Housing lightning protection system

Aluminium louver
Aluminium louver 2x(750x680mm)
2x(450x550mm)

"K"

NOTES:
1) The Electrical switchroom will be laid on a concrete foundation as proposed.
2) Provision shall be taken for inlet or outlet of kiosk installation cables.
3 Openings or holes for cables entry should be sealed after installation.
4) Where cable trench exists, the minimum height it is proposed to be 1,2 meters.
5) Provision for cable trench drainage should be taken. The same must apply even if the housing is elevated.
6) Some Air louvers and outside cowls will be delivered loose and assembled on site. Their openings will be closed
with temporary transportation panels to avoid ingress of water into the housing.
7) The gap between wall panels and screen around the perimeter of the housing must be thoroughly sealed
Οι τεχνικές πληροφορίες που περιέχονται σε αυτό το έντυπο είναι αποκλειστική ιδιοκτησία της ΣΝΕΝΤΕΡ ΕΛΕΚΤΡΙΚ Α.Ε. και δεν επιτρέπεται να χρησιμοποιηθούν ούτε να διανεμηθούν χωρίς προηγούμενη γραπτή συγκατάθεση

to avoid rain water entering into cable space.


8) The metallic cladding under the baseframe must be fixed leaving 50mm distance from outside perimeter
for sealing purposes.
Detail "K" HOUSING
Scale 1:5

Anchoring bolts
M12x200
All technical information contained in this document is the exclusive property of SCHNEIDER ELECTRIC AE and may neither be used nor disclosed without its prior written consent.

Concrete armoured
ANCHORING AND LIFTING ANGLE foundation
Scale 1:5
- __-__-__ - - - - - ΥΛΙΚΟ: - - Σύμφωνα με πρώτυπο ή προδιαγραφή: -
Material: - As per Standard or Specification: -
- __-__-__ - - - - -
Θερμική επεξεργασία/Heat treatment - Σύμφωνα με προδιαγραφή: -
- __-__-__ - - - - - As per specification:
Επικάλυψη επιφανείας/Surface protection - -
- __-__-__ - - - - -
∆ιαστάσεις συμπεριλαμβανομένης της επικάλυψης/Dimensions including coating: - ΝΑΙ/YES - ΟΧΙ/NO
- __-__-__ - - - - - ISO 8015 - Γενικές Ανοχές / General tolerances: -
- __-__-__ - Κλίμ. ΠΕΛΑΤΗΣ ΤΙΤΛΟΣ / TITLE
- - - -
Scale 1:28 Project kIEFER TEK
- __-__-__ - - - - -
ΦΑΚΕΛΟΣ -
MV-LV SUBSTATION - KIOSK LAYOUT
__-__-__ - File
- - - - -
Κωδικός / Code FTHIA ENERGEIAKI
NOTE: Lifting hole Φ30 - __-__-__ - - - - -

A 12-05-17 ΓΙΑ ΕΓΚΡΙΣΗ / FOR APPROVAL V. A. P. A. P. A. - EE-3517003592 BIOGAS FARSALA STATION