Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
In a primary-secondary-tertiary system (Figure 3), things start to get a bit more complicated, but the
principles are all the same. The common pipe (whether it is between the primary loop and the
secondary loop, or the secondary loop and the tertiary loop) acts as the decoupler, so flows act
independently of one another and there is extra degree of thermal isolation.
Primary-secondary-tertiary designs may also be hybridized, meaning you don’t have to put a tertiary
loop on every zone. Rather, you can isolate a high head loss zone with a tertiary pump while
continuing to efficiently serve nearby zones with the secondary pumps. Figure 4 shows a primary-
secondary-tertiary hybrid design.
Pros/Cons: This approach offers all the efficiency and flexibility of a standard primary-secondary-
tertiary, but does eliminate some of the extra equipment costs.
Primary-Secondary – Zone
This type of design has the potential for high energy savings, but with certain caveats, including slow
reaction time to changes in system demand. Because the pumps are in parallel, special attention
must the paid to the selection and performance curves must be compatible. Also, under certain load
conditions, the return pressure may be higher than the supply pressure, which could create
problems with the primary loop equipment.
Pros/Cons: The main advantage to this piping arrangement is significantly lower system pressures,
and reduced horsepower. Controllability, however, is a challenge because there is no decoupling
between zones. Expanding the system could also be quite costly.