Generator data:
CT / PT Details
Generator 15.75kV side, CT ratio: 8000/1 A
GROUND CT RATIO: 50/1 A
Generator PT ratio: 15.75kV/ 3/ 110/ 3 V
The differential current pickup setting can be set as low as 5% of rated generator current, to
provide protection for as much of the winding as possible. Thus, to obtain maximum
sensitivity, the differential pickup current is chosen as 0.05 P.U.
Slope 2, set at 80 %.
The STATOR DIFF BREAK 2 setting is set at 3 PU.
6.0
5.0
4.0
IOperate (Multiples of CT)
Operating
Region
Slope 2
3.0 80 %
2.
0 Restraint
Slope 1 Region
1.0 15 %
Example: Fig-1
System Details:
Xd = 2.105 pu
X’d = 0.227 pu
MVA = 187.5
CTR/PTR = (8000 / 5 ) x (110/15750) = 11.1746
Zbase (sec) = (base kV2 / base MVA) x (CTR/VTR)
= (15.75 kV2 / 187.5 MVA) x 11.1746 = 14.78
Xd (sec) = Xd x Zb
= 2.105 ×14.78 =31.112
The time settings should also be depended on the withstand levels of the machine
Rated frequency is 50 Hz
UNDERFREQUENCY 1
Sl Protection Function Setting Available in the Recommended Remarks
No Relay Setting
1 Min Volt/Amp 0.10 to 1.25 p.u in steps 0.5 To Trip
of 0.01 86C
Pickup 20.00 to 65.00 Hz in 47.8
steps of 0.01
UNDERFREQUENCY 2
Sl Protection Function Setting Available in the Recommended Remarks
No Relay Setting
1 Min Volt/Amp 0.10 to 1.25 p.u in steps 0.5 To Trip
of 0.01 86B
Pickup 20.00 to 65.00 Hz in 47.5
steps of 0.01
OVERFREQUENCY 1
Sl Protection Function Setting Available in the Recommended Remarks
No Relay Setting
1 Min Volt/Amp 0.10 to 1.25 p.u in steps 0.5 To Trip
of 0.01 86C
Pickup 20.00 to 65.00 Hz in 52.0
steps of 0.01
Protection Setting
VOLTS PER HERTZ 1 (Stage-1)
Sl Protection Function Setting Available in the Recommende Remarks
No Relay d Setting
1 Pickup 0.80 to 4.00 p.u in steps of 1.4 To TRIP
0.01 86B
The pickup of this element is set at a safe margin above the maximum load expected on the
machine.
= 1.1 x 6873
8000
= 0.945 P.U
T = TDM x K
I E
I Pick up -1
Where, K = 0.14 and E = 0.020, I=Input current and I pickup = Nominal current
0.50
TDM = 0.14
0.945 0.02
0.859 -1
TDM = 0.0068
Protection setting
The Neutral IOC pickup setting is set as 50% of rated generator current.
Directional Power
= ½ X 3.0MW
= 0.0068 P.U
To prevent mal-operation for power swings the element is typically time delayed for Trip
by 2 seconds
Assuming 10% as the minimum power below which the generator should trip on turbine
faults, we get: 10% of 135MW = 0.1 X 150 = 15.0 MW
= 15.0MW
= 0.0687 P.U
Smin = 0.0687 P.U (For Low forward power SMIN < 0. Refer ‘b’ diagram below)
Delay = 1 seconds
RCA = 180˚
This element has two stages, stage 1 to Trip the machine & stage 2 for Alarm. Set the
pickup to 0.15 for both stages to provide adequate overlap with the Auxiliary voltage
element. Set stage 1 to 0.375V secondary (this value may be increased for security in
particularly noisy environments). Stage 2 is typically set at 0.3 V secondary. The
supervision settings are expressed in per unit of the Nominal phase VT secondary setting.
The time delay settings are 5 seconds for stage 1 and 1 second for stage 2 elements
respectively
This protection will be set after measurement of third harmonic voltage generated by the
machine at various loads.
Protection Setting
= 0.179 Ohm
= 0.1438 x 1600
143.18
= 1.607 Ohm
= 0.00004 Ohm
= 0.158 x 1600
143.18
= 1.768 Ohm
= j2.105 x 15.752
187.5
= j2.785Ohm
= j37.346Ohm
The out of step protection is used to detect a loss of synchronism of the generator. The
impedance locus is measured as compared with blinders and MHO circle.
SGnom = 187.5MVA
UGnom = 15.75KV
Xd = 2.105
Xd’ = 0.227
Primary impedance from nominal (generator) voltage and nominal apparent power
Generator Impedance
Zg = j.Xd’sec = 3.356i
Transformer Impedance
Zt = j.ZTsec = 2.00i
Zsext = 3.97 . exp (j.86 deg) (Assumed. Customer to give the exact value)
The impedance is based on 400KV and has to be adapted to the generator voltage,
System Impedance:
Z = Zg + Zt + Zs = 0.0145 + 5.427i
MHO Characteristics
Reach =150%
The forward angle is equal to the angle of the system impedance as following:
Reach=200%
Blinder Calculation
out = 60˚
The offset between the right and left blinder is calculated according the picture above as
following:
180˚ - out
tan 2
Offsetout = . |Z| = 9.575
sin (arg(Z))
With this offset the position of the right and left blinder is as following:
180˚ - out
tan 2 |Z| |Zg|
Blinderoutright = . + = 5.942
sin (arg(Z)) 2 tan(arg(Z))
in = 120˚
The offset between the right and left blinder is calculated according the picture above as
following:
180˚ - in
tan 2
Offsetin = . |Z| = 3.189
sin (arg(Z))
With this offset the position of the right and left blinder is as following:
180˚ - in
tan 2 |Z| |Zg|
Blinderintright = . + = 2.247
sin (arg(Z)) 2 tan(arg(Z))
PROTECTION SETTING
Sl Protection Function Setting Available in the Recommende Remarks
No Relay d Setting
Power Swing Shape Mho, Quad Mho To trip 86B
Power Swing Mode Two step, Three step
TWO STEP
Power Swing Supv 0.050 to 30.00 p.u in steps of 0.6
0.001
Power Swing Fwd Rch 0.1 to 500.00 Ohm in steps of 3.0
0.01
Power Swing Quad 0.1 to 500.00 Ohm in steps of -
Fwd Rch 0.01
Power Swing Quad 0.1 to 500.00 Ohm in steps of -
Fwd Rch Mid 0.01
Find below LBB logic. We have considered this protection using current operated pickup
elements with additional timing of 200ms using Flex Logic.
Dead machine protection – dedicated relay with 3rd DC supply.- To trip 86A
Generator Stator Winding Temperature Protection: 115 Deg.C for alarm and 120 Deg.C for
Trip
Generator DE/NDE Bearing Temperature Protection: 85 Deg.C for alarm and 90 Deg.C for
Trip
CT / PT Details
Generator Transformer HV side, CT ratio: 400/1 A
NEUTRAL CT RATIO: 400/1 A
PT ratio: 400KV/ 3/ 110/ 3 V
PROTECTION SETTING
Sl Protection Setting Available in the Relay Recommended Remarks
No Function Setting
Protection Setting
VOLTS PER HERTZ 1 (Stage-1)
Sl Protection Function Setting Available in the Relay Recommende Remarks
No d Setting
1 Pickup 0.80 to 4.00 p.u in steps of 0.01 1.4 To trip
The phase overcurrent element is used as definite time element. The input current is the
fundamental phasor magnitude.
PROTECTION SETTING
Sl Protection Function Setting Available in the Relay Recommend Remarks
No ed Setting
Phase TOC1 Input Phasor/RMS Phasor
Pickup 0.000 to 30.000pu in steps of 0.001 1.1 p.u
Phase TOC1 Curve Over Current Type Table
IEC CURVE A
Phase TOC1 TD 0.00 to 600.00 in steps of 0.01 0.5
Multiplier
Phase TOC1 Reset Instantaneous/Timed 'Instantaneo
us
Phase TOC1 Voltage Disabled/Enabled 'Disabled
Restraint
The phase overcurrent element is used as definite time element. The input current is the
fundamental phasor magnitude.
PROTECTION SETTING
Sl Protection Function Setting Available in the Relay Recommend Remarks
No ed Setting
Phase IOC1 Input Phasor/RMS Phasor
Pickup 0.000 to 30.000pu in steps of 0.001 3 p.u
Delay 0.00 to 600.00 in steps of 0.01 0.1
Phase IOC1 Reset Instantaneous/Timed 'Instantaneo
us
CT / PT Details
The phase over current element is used as definite time element. The input current is the
fundamental phasor magnitude.
PROTECTION SETTING
Sl Protection Function Setting Available in the Relay Recommend Remarks
No ed Setting
Phase TOC1 Input Phasor/RMS Phasor
The phase overcurrent element is used as definite time element. The input current is the
fundamental phasor magnitude.
PROTECTION SETTING
Sl Protection Function Setting Available in the Relay Recommend Remarks
No ed Setting
Phase IOC1 Input Phasor/RMS Phasor
Pickup 0.000 to 30.000pu in steps of 0.001 3 p.u
Delay 0.00 to 600.00 in steps of 0.01 0.1
Phase IOC1 Reset Instantaneous/Timed 'Instantaneo
us