Sei sulla pagina 1di 1

SPECIFICATION IDENTIFICATION

FLOW SWITCHES DATA DOCUMENT 2016052-DI041-509


SHEET PAGES 1 OF 1
REV. BY CHK APPR. DATE
A CCdR PAR PAR Mar-2017
0 CCdR PAR PAR Mar-2017
1 CCdR PAR PAR Jun-2017
INGENIERA DE DETALLE DE EQUIPOS Y PROCESO CL PROJECT
PROJECT
PARA EL PROYECTO MAQUI - ECOLAB EQ PROJECT 2016052-EC

1 TAG NO. FSL-509


2 SERVICE Stop pump P-509 A/B
3 GENERAL P&ID 2016052-PID-509
4 INFORMATION
5
6
7 FLUID Sodium Hypochlorite 16% wt
8 LINE 3"-NaClO-4J-0-5907
9 TEMPERATURE MIN / NORM / MAX, C 25 60
10 PROCESS PRESSURE MIN / NORM / MAX, kg/cm2g atm 6
DATA 3
11 FLOW MIN / NORM / MAX, m /h 25
12 OPER. SPECIFIC GRAVITY 1,26
13 OPER. VISCOSITY, cP 1,4
14
15 FLOW SWITCH TYPE Paddle
16 BOX
17 SERVICE Sodium Hypochlorite
18 FLOW DIRECTION Perpendicular to sensor
19 WETTED PARTS MATERIAL PVC o Teflon
20 ELECTRIC CONNECTION 1/2" FNPT
21 PROCESS CONNECTION 1" flanged FF
22 MAX. PRESSURE, kg/cm2g 6
3
23 SET FLOW, m /h 1,0
DESIGN DATA
24 SETTING
25 ELECTRICAL CLASSIFICATION General Purpose
26 SWITCHES VOLTAGE/RATING 24 Vdc /5A
27 TYPE SPDT
28 INSERTION LENGTH By vendor
29 TIME RESPONSE, seconds 10
30 PROTECTION IP 65 / NEMA 4X
31 INSTALLATION Outdoor
32 FUNCTION LED (STATUS) By vendor
33
34 MANUFACTURER
PURCHASE
35 MODEL & MFR NUMBER
INFORMATION
36
37

NOTES:

Basado en formato ISA S20.41a

Potrebbero piacerti anche