AMD drive1 electric board

Supervision LEDs
LED Name LED illuminates/colour
H80 5V power Board is powered (5V).
H20 Watch dog Microprosessor defect. LED is blinking or illuminating / red.

During commissioning and self-learning led is off.


Blinking or illuminating, if a fault is detected (see error code
H40 State table).
Door at the panels closed position and Reference switch is
H10 Reference switch active / green.

AMD drive1 ERROR TABLE (STATE LED flash code)


Door performs following
LED flashes Fault Correction possibility, solution
Action
Check wires and connectors,
1 time Encoder or Motor fault RESET
exchange motor unit
2 times Wrong motor direction RESET Exchange red and black wire
Move door manually and check that
3 times Power stage too hot STOP for cooling down door is running smooth and easily,
wait until door restarts.
Move door manually and check that
door is running smooth and easily,
4 times Motor too hot STOP for cooling down
wait until motor is cooled down and
door restarts.
Check that reference switch is
adjusted right, switch and magnet has
5 times Reference switch error SLOW MOVE a distance of about 3mm and cover
each other when door panel fully
closed
Motor temperature sensor Check wires and connectors,
6 times SLOW MOVE
broken exchange motor unit
If an error is present then STATE Led flashes an error code. It flashes in the following manner: LED error code
(flashes)- delay (Led off) - LED error code (flashes) .....So you can read out the error code by counting the flashes
between two longer dark phases of the LED

2009 KONE Corporation appendix to IL-000026


All rights reserved. 1 (3) (A) 2009-12-03
Trouble shooting Instruction for AMD drive 1
Effect / Symptom Failure description Correction possibility, solution

Check power supply POWER LED must be lit if LINE IN is


The door does not Power supply missing
connected and the circuit breaker in the elevator control panel is
move at all LED does not light
ON , change board
Count flashes between longer delay and see error code table in
State LED flashes
AM-03.35.022, page 9
Watchdog LED light
Switch door off/on and replace electronic if it still lights
or blinks
Low voltage protection activated, check supply voltage
Motor does not move Check that door moves easily and belt is OK

Check that the motor wires are connected to plug X4

Power stage short circuited, check wiring or change motor


External 24VDC
Door cannot be
supply for control Check that lift control interface is powered by EXTERNAL 24V,
moved by lift
interface missing, LED +24V EXT (H200) must lit
commands
LED does not light
Service drive input
Door can be moved by test drive button only, deactivate SD input
ON
Open command Check that the control panel is giving an Open command (X1/16)
Door cannot open
missing LED H2
Close command
Check that close command is not active
always ON
Motor does not move
Check that door moves easily
to open
Close command Check that the control panel is giving an Close command (X1/17)
Door cannot close
missing LED H1
Open command Check reopen output and position of Dip switch S1/1, if NC contact
always on is not closed replace unit
Motor does not move
Check that door moves easily
to close
The closing force may be too low (or friction too high). Turn
CLOSE FORCE potentiometer slightly clockwise to increase the
force.

Door only partly Commands open and Check that the open and close signal times (Led H1, H2) from the
opens or closes close too short elevator controller are long enough.

Door moves in the wrong direction the drive electronic detects a


Door starts and stops fault and stops the door movement immediately - the red STATE
after few cm running LED is flashing twice and a reset is done - LED WATCHDOG
flashes. Exchange the two motor wires on connector X4.
Encoder supervision activated, change motor
The door is reopened by lift controller only. To reopen the door the
elevator controller must receive either a REOPEN REQUEST
Door does not open command
signal from the door electronics or from an independently wired
reopen missing
safety device (e.g. Photocell or COL...), remove close command
and set open command
Check DIP switch position S2/1, should be on when Reopen
Request output switches to GND.
Reopen request Check the adjustment of close force limiter, reopen output must
signal missing active if close force limiter is active.
- The lock mechanically jamming (snatching) on open
Doors running - The reference switch not close enough
slowly - Debris in the back of the door tracks
- Bad alignment of the lock rollers in the skate (coupler)

2009 KONE Corporation appendix to IL-000026


All rights reserved. 2 (3) (A) 2009-12-03
OTHER POINTS TO BE CHECKED:

- wiring of reference switch terminals


- reference switch wire must be in good
reference switch condition
- ensure reference switch correct operation by
checking LED H10 when door close

AMD railing1 / railing2

- coupling system;
- lock rollers are in middle between coupler
vanes
mechanical - engagement of coupler vane lock rollers
installation
AMD slim - test door operation on another floor; if
(min8) (min8)
12 12
problem occurs only at one floor it is not
board failure
17.5

25

- rollers must be securely fastened and should


run smoothly, aligned with guide rail
mechanical - anti-tip rollers must slightly touch the rail,
installation finger tight (pu-roller A, railing1).
- anti-tip rollers (metal roller B, railing2) should
have 0.15 mm clearance to the rail.

- ensure correct operation of curtain of light /


function of door photo cell re-open door when ray are
safety devices interrupted
(curtain of light / - ensure that those device are not confusing
photo cess) AMD board operation by disconnecting door
safety device temporarily

AMD drive1 DIP switches

2009 KONE Corporation appendix to IL-000026


All rights reserved. 3 (3) (A) 2009-12-03