Fan Coil Unit Application Guide

VTR8300/VT8300 Series Room Controllers


2 Application Guide Fan Coil Unit Controller Series

VTR8300 and SC3000 | Line-voltage Fan coil terminal equipment controllers and relay packs
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components; the VTR8300 Terminal
Equipment Controller and the SC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and temperature
controller to be re-used, thereby reducing overall costs and installation time.
The SC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional
horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is not
required for the VT8300 Series models.

Commercial interface (local override)


Power Part Number Description Humidity Onboard Communication
PIR

VTR8300A50xxB BACnet fan coil terminal equipment controller No No BACnet

VTR8300A55xxB BACnet fan coil terminal equipment controller No Yes BACnet

VTR8350A50xxB BACnet fan coil terminal equipment controller Yes No BACnet

VTR8350A55xxB BACnet fan coil terminal equipment controller Yes Yes BACnet

Transformer Relay Packs for VTR8300 Series


Power Part Number Description
SC3500E5000 Transformer relay pack five relay fan outputs
SC3504E5000 Transformer relay pack five relay fan outputs, and four inputs
SC3514E5000 Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
SC3400E5000 Transformer relay pack four relay outputs and smart VDC output
SC3404E5000 Transformer relay pack four relay outputs, smart VDC output, and four inputs

SC3300E5000 Transformer relay pack three relay fan outputs

ZigBee Pro Module for VT(R)8300 Series


Part Number Description

Power
VCM8000V5045P Optional ZigBee Pro module for VT8300 Series room controllers.

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 3

VT8300 Low-voltage 24 vac fan coil terminal equipment controllers


This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the VT8300 Terminal Equipment Controller.
The VT8300 Terminal Equipment Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions,
when control of both line-voltage and low-voltage end devices is required.

Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power Part Number Description Humidity PIR Communication
Sensor

VT8300U50XXB BACnet fan coil terminal equipment controller No No BACnet

VT8300U55xxB BACnet fan coil terminal equipment controller No Yes BACnet

VT8350U50xxB BACnet fan coil terminal equipment controller Yes No BACnet

VT8350U55xxB BACnet fan coil terminal equipment controller Yes Yes BACnet

Mixed-voltage Relay Packs for VT8300 Series


Part Number Description

SC1300E5045 3 on/off outputs, 110/130V 3 speed

SC2300E5045 3 on/off outputs, 220/240V 3 speed

Wireless Accessories for VT(R)8300 Series


Power Part Number Description

SED-DOR-P-5000 Wireless door switch

SED-WIN-P-5000 Wireless window switch

SED-CMS-P-5045 Wireless ceiling mounted motion sensor

SED-WDS-P-5045 Wireless window and door switch

SED-WMS-P-5045 Wireless wall mounted motion sensor 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
4 Application Guide Fan Coil Unit Controller Series

VTR83x0A5xxxB with SC3500E5000 Relay and VCM8000V5045P Zigbee pro module: Heating/
cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with wireless door switch

Fan Airflow Direction Cooling Coil Heating Coil

2 POSITION 2 POSITION
COOLING VALVE HEATING VALVE

VTR8300

SC3500E5000

Door Switch
SED-DOR-P-5000

Onboard
PIR Sensor

AND / OR
OR*

Wired Remote Wireless Remote


PIR Sensor PIR Sensor

Configuration
Configuration Settings
Parameter Name

Fan Menu L-M-H-A


Fan cont. heat. On
BI1 Motion NO or Motion NC (remote PIR sensor only)
BI2 Door Dry
Pulsed heating Off
Pipe no. 4
Seq. operation Ht - Cl 2015 Viconcis Technologies. All rights reserved.

* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 5

SC3500E5000

1 Tx/Rx
VTR8300
2 7 Vdc
3 Com
Tx / Rx
7 VDC
Com
BACnet REF
UI 16 - BI1

UI 17 - BI2
BACnet+
BACnet-

SCom

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
Stand-by Mode (only available when PIR motion detector Can be configured for 2-pipe systems (without changeover).
sensor is used) Binary inputs can be configured to control occupancy via door
Setpoints revert to those defined by stand-by cooling and heating. or window contact, remote motion sensor, or remote night
Unoccupied Mode setback.
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
6 Application Guide Fan Coil Unit Controller Series

VTR8350A5XxXB with SC3404E5000 Relay: Cooling and electric heat 2-pipe fan coil unit with
3-speed fan, dehumidification and 2-position valves

Fan Airflow Direction Cooling Coil Electric Heating

2 POSITION
COOLING VALVE

VTR8300 SSR
SOLID STATE RELAY
(GENERIC)

SC3404E5000

Configuration
Configuration settings
parameter name

Fan menu L-M-H-A


Fan cont. heat On
Pulsed heating On
Pipe no. 2
Seq. operation Ht-Cl

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 7

SC3404E5000

1 Tx/Rx
VTR8300
2 7 Vdc
3 Com
Tx / Rx
7 VDC
Com

4 RUI 1
5 SCom
6 RBI 2
7 SS
8 RS
9 Heat -
10 Heat +

SOLIDSTATE (-)
RELAY
(4-32Vdc) (+)
BACnet REF
UI 16 - BI1

UI 17 - BI2
BACnet+

BACnet-

SCom

Sequence of Operation and Wiring On a Demand for Dehumidification


Occupied Mode Dehumidification achieved via cooling coil using reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating. Dehumidification only allowed in COOL mode or if cooling is enabled
Stand-by Mode (only available when PIR motion detector in AUTO mode.
sensor is used) Dehumidification disabled if room temperature falls below low
Setpoints revert to those defined by stand-by cooling and heating. ambient lockout temperature, which is cooling setpoint minus
Unoccupied Mode configuration defined deadband value.
Setpoints revert to those defined by unoccupied heating and
cooling.
Options
Wireless adapter modules for BACnet models are available.
Occupied Override Mode
(see Appendix B for network wiring).
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. Remote wall mount or return duct sensor ready.


On Call for Cool Can be configured for 2-pipe systems with changeover.
Cooling valve opens to maintain room temperature. Binary inputs can be configured to control occupancy via
On Call for Heat door or window contact, remote motion sensor, remote night
Electric heat operates to maintain room temperature. Cooling valve setback, or provide alarms for service or filter monitoring.
closes and dehumidification is disabled. Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
8 Application Guide Fan Coil Unit Controller Series

VTR83x0A5xxxB with SC3504E5000 relay and VCM8000V5045P Zigbee pro module: Heating/
cooling with changeover sensor 2-pipe fan coil unit with 3-speed fan and wirelesss window
switch

Window Switch
SED-WIN-P-5000
Fan Airflow Direction Cooling / Heating Coil Supply Sensor

2 POSITION SENSOR
COOLING VALVE / HEATING VALVE

VTR8300
Onboard
PIR Sensor
C/O
SENSOR

SC3504E5000

Changeover Sensor: 10K Ohm type 2

Supply Sensor: 10K Ohm type 2

Configuration
Configuration Settings
Parameter Name

Fan Menu L-M-H-A


Fan cont On
BI1 Window
2015 Viconcis Technologies. All rights reserved.

RUI1 COS
Pipe No 2
Seq. operation Cool

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 9

SC3504E5000

1 Tx/Rx
VTR8300
2 7 Vdc
3 Com
Tx / Rx
7 VDC
Com

4 RUI 1
5 SCom
6 RBI 2
7 SS
8 RS
BACnet REF
UI 16 - BI1

UI 17 - BI2
BACnet+

BACnet-

SCom

Sequence of Operation and Wiring Wireless Window Switch


Wireless window switch automatically locks out heating/cooling
Occupied Mode
when window is opened.
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector Options
sensor is used)
Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by stand-by cooling and heating.
(see Appendix B for network wiring).
Unoccupied Mode
Remote wall mount or return duct sensor ready.
Setpoints revert to those defined by unoccupied heating and
cooling. Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
2015 Viconcis Technologies. All rights reserved.

Occupied Override Mode


setback, or provide alarms for service or filter monitoring.
System reverts to occupied mode for duration determined by
ToccTime parameter.
On Call for Cool
If supply water temperature is less than 24C (75F), valve opens to
maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25C (77F), valve opens
to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
10 Application Guide Fan Coil Unit Controller Series

VTR8350A5xxxB with SC3400E5000 relay: Cooling and electric heat 2-pipe fan coil unit with
3-speed fan, dehumidification and 2-position valves

Fan Airflow Direction Cooling Coil Electric Heating

2 POSITION
COOLING VALVE

VTR8300 SSR
SOLID STATE RELAY
(GENERIC)

SC3400E5000

Configuration
Configuration settings
parameter name
Fan menu L-M-H-A
Fan cont. heat. On
Pulsed Heating On
Pipe No 2
Seq. operation Cool-Rht

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 11

SC3400E5000

1
VTR8300
2
3
Tx / Rx
7 VDC
Com

9
10

SOLIDSTATE (-)
RELAY
(4-32Vdc) (+)
BACnet REF

UI 16 - BI1
UI 17 - BI2
BACnet+
BACnet-

SCom

Sequence of Operation and Wiring On a Demand for Dehumidification


Dehumidification achieved via cooling coil using reheat if necessary.
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. Dehumidification only allowed in COOL mode or if cooling is enabled
in AUTO mode.
Stand-by Mode (only available when PIR motion detector
sensor is used) Dehumidification disabled if room temperature falls below low
Setpoints revert to those defined by stand-by cooling and heating. ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
Options
cooling.
Wireless adapter modules for BACnet models are available.
Occupied Override Mode
(see Appendix B for network wiring).
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. Binary inputs can be configured to control occupancy via


door or window contact, remote motion sensor, remote night
On Call for Cool
setback, or provide alarms for service or filter monitoring.
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve
closed and dehumidification is disabled.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
12 Application Guide Fan Coil Unit Controller Series

VTR83x0A5xxxB with SC3514E5000 Relay: Heating/cooling 2-pipe fan coil unit with 3-speed fan,
fresh air damper and 2-position valves

Fresh Air Fan Airflow Direction Cooling / Heating Coil Supply Sensor

DAMPER 2 POSITION SENSOR


COOLING VALVE / HEATING VALVE

Return Air

VTR8300
Supply Sensor: 10K Ohm type 2.
C/O
SENSOR

Changeover Sensor: 10K Ohm type 2.


SC3514E5000

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Fan cont. heat On
RUI1 COS
Pulsed Heating Occ Out
Pipe no. 2
Seq. operation Cool
2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 13

SC3514E5000

1 Tx/Rx
VTR8300
2 7 Vdc
3 Com
Tx / Rx
7 VDC
Com
4 RUI 1
5 SCom
6 RBI 2
7 SS
8 RS
9 OCC -

7Vdc
RELAY
COIL
BACnet REF

UI 16 - BI1

UI 17 - BI2
BACnet+

BACnet-

SCom

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
The occupancy output opens fresh air damper to minimum position.
Remote wall mount or return duct sensor ready.
Stand-by Mode (only available when PIR motion detector
Binary inputs can be configured to control occupancy via
sensor is used)
door or window contact, remote motion sensor, remote night
Setpoints revert to those defined by stand-by cooling and heating.
setback, or provide alarms for service or filter monitoring.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling. The fresh air damper closes.
Occupied Override Mode
2015 Viconcis Technologies. All rights reserved.

System reverts to occupied mode for duration determined by


ToccTime parameter.
On Call for Cool
If supply water temperature is less than 24C (75F), cooling valve
opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25C (77F), heating valve
opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
14 Application Guide Fan Coil Unit Controller Series

VTR83x0A5xxxB with SC3500E5000 and SC3300E5000 RELAYS: Heating/cooling 4-pipe fan coil unit
with 3-speed fan and 2-position valves with slave relay pack

Fan Airflow Direction Cooling Coil Heating Coil

2 POSITION 2 POSITION
COOLING VALVE HEATING VALVE

VTR8300

SC3300E5000 SC3500E5000

Configuration
Configuration Settings
Parameter Name
Fan menu L-M-H-A
Fan cont. heat On
Pipe No 4
Seq. operation Ht-Cl

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 15

SC3500E5000T

1
VTR8300
2
3
Tx / Rx
7 VDC
Com

SC3300E5000

1
2
3
BACnet REF

UI 16 - BI1
UI 17 - BI2
BACnet+
BACnet-

SCom

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
Stand-by Mode (only available when PIR motion detector Can be configured for 2-pipe systems without changeover.
sensor is used)
Binary inputs can be configured to control occupancy via
Setpoints revert to those defined by stand-by cooling and heating.
door or window contact, remote motion sensor, remote night
Unoccupied Mode setback, or provide alarms for service or filter monitoring.
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
16 Application Guide Fan Coil Unit Controller Series

VTR83x0A5xxxB with SC3504E5000 relay: Cooling and electric heat


2-pipe fan coil unit with 3-speed fan and 2-position valves with wired window switch

Window Switch
SED-WIN-P-5000 Fan Airflow Direction Cooling / Heating Coil Supply Sensor

2 POSITION SENSOR
COOLING VALVE / HEATING VALVE

VTR8300

C/O
SENSOR
Onboard
PIR Sensor

SC3504E5000

Changeover Sensor: 10K Ohm type 2

Supply Sensor: 10K Ohm type 2

Configuration Parameter Configuration Settings


Name
Fan menu L-M-H-A
Fan cont. heat On
BI1 Window
RUI1 COS
Pipe no. 2
Seq. operation Cool

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 17

SC3504E5000

1 Tx/Rx
VTR8300
2 7 Vdc
3 Com
Tx / Rx
7 VDC
Com

4 RUI 1
5 SCom
6 RBI 2
7 SS
8 RS
BACnet REF
UI 16 - BI1

UI 17 - BI2
BACnet+
BACnet-

SCom

BI1 (Window) SCom

Sequence of Operation and Wiring Wired Window Switch


The window switch automatically locks out heating/cooling when
Occupied Mode
window opens.
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector Options
sensor is used)
Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by stand-by cooling and heating.
(see Appendix B for network wiring).
Unoccupied Mode
Models available with factory installed PIR sensor.
Setpoints revert to those defined by unoccupied heating and
cooling. Remote wall mount or duct sensor ready.
Occupied Override Mode Can be configured for 2-pipe systems with changeover.
System reverts to occupied mode for duration determined by Binary inputs can be configured to control occupancy via door
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. or window contact, remote night setback, or provide alarms for
On Call for Cool service or filter monitoring.
If supply water temperature is less than 24C (75F), cooling valve Universal input can be configured for changeover sensor.
opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25C (77F), heating valve
opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
18 Application Guide Fan Coil Unit Controller Series

VTR83x0A5xxxB with SC3500E5000 RELAY: Heating/cooling 4-pipe fan coil unit with 3-speed fan
and 2-position valves with wired door switch

Fan Airflow Direction Cooling Coil Heating Coil

2 POSITION 2 POSITION
COOLING VALVE HEATING VALVE

VTR8300

SC3500E5000

Door Switch
SED-DOR-P-5000

Onboard
PIR Sensor

AND / OR
OR*

Wired Remote Wireless Remote


PIR Sensor PIR Sensor

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Fan cont. heat On
BI1 Motion NO or Motion NC (remote PIR sensor only)
BI2 Door Dry
Pipe No 4
Seq. Operat Ht-Cl
2015 Viconcis Technologies. All rights reserved.

* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 19

SC3500E5000

1 Tx/Rx
VTR8300
2 7 Vdc
3 Com
Tx / Rx
7 VDC
Com
BACnet REF

UI 17 - BI2
UI 16 - BI1
BACnet+
BACnet-

SCom

BI2 (Door) SCom

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
Stand-by Mode (only available when PIR motion detector Models available with factory installed PIR sensor.
sensor is used)
Can be configured for 2-pipe systems without changeover.
Setpoints revert to those defined by stand-by cooling and heating.
Binary inputs can be configured to control occupancy via
Unoccupied Mode
door or window contact, remote motion sensor, remote night
Setpoints revert to those defined by unoccupied heating and
setback, or provide alarms for service or filter monitoring.
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
Door Switch
Door switch automatically toggles occupancy.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
20 Application Guide Fan Coil Unit Controller Series
VT8350U5XXXB Heating/cooling 4-pipe fan coil unit with 3-speed fan, tri-state floating valves
and dehumidification sequence for low voltage with wireless door switch

Fan Airflow Direction Cooling Coil Heating Coil

TRI-STATE TRI-STATE
COOLING VALVE HEATING VALVE

VT8300
Door Switch
SED-WDS-P-5045

Onboard
PIR Sensor

AND / OR
OR*
Wired Remote Wireless Remote
PIR Sensor PIR Sensor

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Control Type Floating
UI16 Motion NO or Motion NC (remote PIR sensor only)
UI17 Door Dry
Pipe no. 4
Seq. operation Cool / Heat
2015 Viconcis Technologies. All rights reserved.

* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 21

VT8300 Floating Control

RH

BO8 - Aux Heat

UO9 - Close Cool V

UO10 - Close Heat V


UO11 - Open Cool V

UO12 - Open Heat V


BO2 - Fan L
BO3 - Fan M

BO4 - Fan H

RC (24 Vac)
C (Common)
HEATING VALVE COOLING VALVE
Close Open Com. Close Open Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

FAN HI
13 14 15 16 17 18 19 20 21 22 23 24 FAN MED

FAN LO
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
Dehumidification is only allowed in COOL mode, or if cooling is
Stand-by Mode (only available when PIR motion detector
enabled in AUTO mode.
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating. Dehumidification is disabled if room temperature falls below low
ambient lockout temperature, which is the cooling setpoint minus
Unoccupied Mode
the configuration defined deadband value.
Setpoints revert to those defined by unoccupied heating and
cooling. Reheat disabled if cooling demand reaches 100%.
Occupied Override Mode
Options
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve Remote wall mount or duct sensor ready.
closes. Can be configured for 2-pipe systems with changeover.
On Call for Heat 3 universal inputs can be used and configured for advanced
Heating valve opens to maintain room temperature. Cooling valve functionality as required by the application.
closes.
Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
22 Application Guide Fan Coil Unit Controller Series

VT8350U5XXxB Heating/cooling 4-pipe fan coil unit with 3-speed fan, 0-10 VDC Analog valves and
dehumidification sequence for low voltage with wireless Window switch

Fan Airflow Direction Cooling Coil Heating Coil

ANALOG ANALOG
COOLING VALVE HEATING VALVE
Window Switch
SED-WDS-P-5045

VT8300

Onboard
PIR Sensor

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Pipe no. 4
Seq. operation Cool / Heat

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 23

VT8300 Modulating Control

RH

BO8 - Aux Heat

V
UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L
BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)
HEATING VALVE COOLING VALVE
0-10 v 24 v Com. 0-10 v 24 v Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

FAN HI
13 14 15 16 17 18 19 20 21 22 23 24 FAN MED

FAN LO
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
The changeover sensor sends supply air temperature to controller. Dehumidification only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Stand-by Mode (only available when PIR motion detector
sensor is used) Dehumidification disabled if room temperature falls below low
Setpoints revert to those defined by stand-by cooling and heating. ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and Reheat disabled if cooling demand reaches 100%.
cooling.
Options
Occupied Override Mode
2015 Viconcis Technologies. All rights reserved.

System reverts to occupied mode for duration determined by Wireless adapter modules for BACnet models are available.
ToccTime parameter. (see Appendix B for network wiring).
On Call for Cool Remote wall mount or duct sensor ready.
Cooling valve opens to maintain room temperature. Heating valve Can be configured for 2-pipe systems.
closes. Dehumidification enabled.
3 universal inputs can be used and configured for advanced
On Call for Heat functionality as required by the application.
Heating valve opens to maintain room temperature. Cooling valve
closes. Dehumidification disabled. Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
24 Application Guide Fan Coil Unit Controller Series
VT8350U5XXXB Heating/cooling 4-pipe fan coil unit with 3-speed fan, 2-position valves and
dehumidification sequence for low voltage

Fan Airflow Direction Cooling Coil Heating Coil

2 POSITION 2 POSITION
COOLING VALVE HEATING VALVE

VT8300

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Control Type On/Off
Pipe no. 4
Seq. operation Cool/Heat

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 25

VT8300 On / Off Control

RH

BO8 - Aux Heat

UO9 - NC Cool V

UO10 - NC Heat V
UO11 - NO Cool V

UO12 - NO Heat V
BO2 - Fan L
BO3 - Fan M

BO4 - Fan H

RC (24 Vac)
C (Common)
HEATING VALVE COOLING VALVE
IF NC IF NO Com. IF NC IF NO Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

FAN HI
13 14 15 16 17 18 19 20 21 22 23 24 FAN MED

FAN LO
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
Dehumidification only allowed in COOL mode, or if cooling is
Stand-by Mode (only available when PIR motion detector
enabled in AUTO mode.
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating. Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
Unoccupied Mode
configuration defined deadband value.
Setpoints revert to those defined by unoccupied heating and
cooling. Reheat disabled if cooling demand reaches 100%.
Occupied Override Mode
Options
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve Models available with factory installed PIR sensor.
closes. Dehumidification enabled. Remote wall mount or duct sensor ready.
On Call for Heat Can be configured for 2-pipe systems.
Heating valve opens to maintain room temperature. Cooling valve
closes. Dehumidification disabled. 3 universal inputs can be used and configured for advanced
functionality as required by the application.
Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
26 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB cooling only 2-pipe fan coil unit with single speed fan, 2-position cooling valve
and fresh air damper for low voltage

Fresh Air Fan Airflow Direction Cooling Coil

DAMPER 2 POSITION
COOLING VALVE

Return Air

VT8300

Configuration
Configuration Settings
Parameter Name

Fan menu On-Auto


Control Type On/Off
BO8 AuxOut Aux NO
Pipe no. 2
Seq. operation Cool only

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 27

VT8300 On / Off Control

RH

BO8 - Aux Heat

OU9 - NC Cool V

UO10 - NC Heat V
UO11 - NO Cool V

UO12 - NO Heat V
BO2 - Fan L
BO3 - Fan M

BO4 - Fan H

RC (24 Vac)
C (Common) FRESH AIR DAMPER
ON / OFF ACTUATOR COOLING VALVE
L IF NC IF NO Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24 FAN
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
The auxiliary contact closes forcing fresh air damper to its minimum Remote wall mount or duct sensor ready.
position.
Can be configured for 4-pipe systems.
Stand-by Mode (only available when PIR motion detector
sensor is used) 3 universal inputs can be used and configured for advanced
Setpoints revert to those defined by stand-by cooling and heating. functionality as required by the application.
Unoccupied Mode Can be configured for two speed or three speed fan control.
Setpoints revert to those defined by unoccupied heating and
cooling. The auxiliary contact opens causing fresh air damper to
2015 Viconcis Technologies. All rights reserved.

close completely.
Occupied Override Mode
System reverts to occupied mode for duration determined by
ToccTime parameter. The auxiliary contact closes forcing fresh air
damper to its minimum position.
On Call for Cool
Cooling valve opens.
On Call for Heat
Cooling valve closes.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
28 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB cooling with reheat 4-pipe fan coil unit with 3-speed fan, Analog cooling valve
and N.C on/off heating valve for low voltage

Fresh Air Fan Airflow Direction Cooling Coil Heating Coil

DAMPER ANALOG 2 POSITION


COOLING VALVE HEATING VALVE

Return Air

VT8300

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


BO8 Out Time 0 = 15 Minute
BO8 AuxOut 0
Pipe no. 4
Seq. operation Cool-rht

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 29

VT8300 Mod. & On / Off Control

RH
BO8 - Aux Heat

V
UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M
BO4 - Fan H

RC (24 Vac)

C (Common)
HEATING VALVE COOLING VALVE
NC Com. 0-10 V 24V Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

FAN HI
13 14 15 16 17 18 19 20 21 22 23 24 FAN MED

FAN LO
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
Stand-by Mode (only available when PIR motion detector Remote wall mount or duct sensor ready.
sensor is used)
Can be configured for 2-pipe systems.
Setpoints revert to those defined by stand-by cooling and heating.
Can be configured to single or two speed fan.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and 3 universal inputs can be used and configured for advanced
cooling. functionality as required by the application.
Occupied Override Mode
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter.
On Call for Cool
Analog valve starts modulating based on cooling demand.
On Call for Heat
Heating valve opens.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
30 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB cooling only 2-pipe fan coil unit with 3-speed fan and 0-10VDC Analog cooling
valve for low voltage

Fan Airflow Direction Cooling Coil

ANALOG
COOLING VALVE

VT8300

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Pipe no. 2
Seq. operation Cool only

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 31

VT8300 Modulating Control

RH

BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L
BO3 - Fan M

BO4 - Fan H

RC (24 Vac)
C (Common)
COOLING VALVE
0-10 V 24V Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

FAN HI
13 14 15 16 17 18 19 20 21 22 23 24 FAN MED

FAN LO
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 193
UI 16
UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
Stand-by Mode (only available when PIR motion detector Remote wall mount or duct sensor ready.
sensor is used)
Can be configured for 4-pipe systems.
Setpoints revert to those defined by stand-by cooling and heating.
3 universal inputs can be used and configured for advanced
Unoccupied Mode
functionality as required by the application.
Setpoints revert to those defined by unoccupied heating and
cooling. Can be configured to two or three speed fan.
Occupied Override Mode
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat
Valve closes.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
32 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB cooling with reheat 2-pipe fan coil unit with 3-speed fan, 2-position valve and
electric reheat for low voltage

Fan Airflow Direction Cooling Coil Heating

2 POSITION ON / OFF DUCT


HEATER
COOLING VALVE

VT8300

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Control Type On/Off
BO8 Out Time 0 = 15 Minute
BO8 AuxOut 0
Pipe no. 2
Seq. operation Cool-rht
2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 33

VT8300 On / Off Control

RH

BO8 - Aux Heat

UO9 - Close Cool V

UO10 - Close Heat V


UO11 - Open Cool V

UO12 - Open Heat V


BO2 - Fan L
BO3 - Fan M

BO4 - Fan H
RC (24 Vac)

C (Common) COOLING VALVE


L IF NC IF NO Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

FAN HI
13 14 15 16 17 18 19 20 21 22 23 24 FAN MED

FAN LO
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
Setpoints revert to those defined by occupied cooling and heating. (see Appendix B for network wiring).
The changeover sensor sends supply air temperature to controller. Remote wall mount or duct sensor ready.
Stand-by Mode (only available when PIR motion detector Can be configured for 4-pipe systems.
sensor is used)
3 universal inputs can be used and configured for advanced
Setpoints revert to those defined by stand-by cooling and heating.
functionality as required by the application.
Unoccupied Mode
Can be configured to single or two speed fan.
Setpoints revert to those defined by unoccupied heating and
cooling.
2015 Viconcis Technologies. All rights reserved.

Occupied Override Mode


System reverts to occupied mode for duration determined by
ToccTime parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
34 Application Guide Fan Coil Unit Controller Series

VTR8300 and VT8300 as Zone Controllers


VT83x0U5xxxB heating only Analog valve actuator, 2 pipe
This section shows how the VTR8300 and VT8300 series Room Controllers are used as Zone Controllers.

Airflow Direction Heating Coil

ANALOG
HEATING VALVE

Configuration
Configuration Settings
Parameter Name

Fan menu ON-AUTO


Pipe no. 2
Seq. operation Heat only

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 35

VT8300 Modulating Control

RH

BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M
BO4 - Fan H

RC (24 Vac)

C (Common) HEATING VALVE


0-10 V 24V Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
During Occupied periods, the occupied heating and cooling (see Appendix B for network wiring).
setpoints are used. Remote wall mounted sensor or return air temperature
Stand-by Mode (only available when PIR motion detector sensor can be used instead of internal temperature sensor of
sensor is used) Controller.
When equipped with a PIR (Passive Infrared) accessory sensor 3 universal inputs can be used and configured for advanced
the Controller provides advanced active occupancy logic, which functionality as required by the application.
automatically switches occupancy levels from Occupied to Stand-by
Auxiliary electric reheat can be added if required by application.
to Unoccupied when no motion is detected in the room:
During PIR activated Stand-by periods, Stand-by heating and
2015 Viconcis Technologies. All rights reserved.

cooling setpoints are used


During PIR activated unoccupied periods, unoccupied-by
heating and cooling setpoints are used.

Unoccupied Mode
During unoccupied periods, the unoccupied heating and cooling
setpoints are used.
Occupied Override Mode
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.
On Call for Heat
The heating valve modulates from closed to open according to
demand.
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
36 Application Guide Fan Coil Unit Controller Series

VT83x0U5xxxB COOLing only Analog valve actuator, 2 pipe

Airflow Direction Cooling Coil

ANALOG
COOLING VALVE

Configuration
Configuration Settings
Parameter Name

Fan menu ON-AUTO


Pipe no. 2
Seq. operation Cool only

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 37

VT8300 Modulating Control

RH
BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M
BO4 - Fan H

RC (24 Vac)

C (Common) COOLING VALVE


0-10 V 24V Com.

1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
During Occupied periods, the occupied heating and cooling (see Appendix B for network wiring).
setpoints are used.
Remote wall mounted sensor or return air temperature
Stand-by Mode (only available when PIR motion detector sensor can be used instead of internal temperature sensor of
sensor is used)
Controller.
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which 3 universal inputs can be used and configured for advanced
automatically switches occupancy levels from Occupied to Stand-by functionality as required by the application.
to Unoccupied when no motion is detected in the room:
Auxiliary electric reheat can be added if required by application.
During PIR activated Stand-by periods, Stand-by heating and
cooling setpoints are used
2015 Viconcis Technologies. All rights reserved.

During PIR activated unoccupied periods, unoccupied-by


heating and cooling setpoints are used.
Unoccupied Mode
During unoccupied periods, the unoccupied heating and cooling
setpoints are used.
Occupied Override Mode
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.
On Call for Heat
The heating valve modulates from closed to open according to
demand.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
38 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB Heating coil with Tri-state floating valve actuator and PWM electric duct
heater

Airflow Direction Heating Coil On/Off Duct Heater

TRI-STATE
FLOATING VALVE

SSR
SOLID STATE RELAY
(R1810 WITH HEATSINK)

Configuration
Configuration Settings
Parameter Name

Fan menu ON-AUTO


Control Type Floating
BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Pipe no. 2
Seq. operation Heat-rht
2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 39

VT8300 Floating & PWM Control

RH

BO8 - Aux Heat


UO9 - Close Cool V

UO10 - Close Heat V

UO11 - Open Cool V


UO12 - Open Heat V
BO2 - Fan L

BO3 - Fan M

BO4 - Fan H
RC (24 Vac)

C (Common) PWM DUCT HEATER


SOLID STATE RELAY HEATING VALVE
L Close Open Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

24 Vac Transformer

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16

UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
During Occupied periods, the occupied heating and cooling (see Appendix B for network wiring).
setpoints are used.
Remote wall mounted sensor or return air temperature
Stand-by Mode (only available when PIR motion detector sensor can be used instead of internal temperature sensor of
sensor is used)
Controller.
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which 3 universal inputs can be used and configured for advanced
automatically switches occupancy levels from Occupied to Stand-by functionality as required by the application.
to Unoccupied when no motion is detected in the room:
During PIR activated Stand-by periods, Stand-by heating and
cooling setpoints are used
2015 Viconcis Technologies. All rights reserved.

During PIR activated unoccupied periods, unoccupied-by


heating and cooling setpoints are used.
Unoccupied Mode
During unoccupied periods, the unoccupied heating and cooling
setpoints are used.
Occupied Override Mode
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.
On Call for Heat
The proportional device will act as a first step and modulates from
0 to 100% capacity. The perimeter heater will operate as a second
step.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
40 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB heating with reheat, modulating duct heater, electric perimeter

Airflow Direction Two-stage Duct Heater

R820
SCR
PERIMETER HEATER

SSR
SOLID STATE RELAY
(R1810 WITH HEATSINK)

Configuration
Configuration Settings
Parameter Name

Fan menu ON-AUTO


BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Pipe no. 2
Seq. operation Heat-rht

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 41

VT8300 Mod. & PWM Control

RH

BO8 - Aux Heat


UO9 - Close Cool V

UO10 - Close Heat V

UO11 - Open Cool V


UO12 - Open Heat V
BO2 - Fan L
BO3 - Fan M

BO4 - Fan H
RC (24 Vac)
C (Common) PERMETER HEAT
SOLID STATE RELAY DUCT HEATER, SRC
L 0-10 V 24V Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

24 Vac Transformer

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16
UI 17

Sequence of Operation and Wiring Options


Occupied Mode Wireless adapter modules for BACnet models are available.
During Occupied periods, the occupied heating and cooling (see Appendix B for network wiring).
setpoints are used.
Remote wall mounted sensor or return air temperature
Stand-by Mode (only available when PIR motion detector sensor can be used instead of internal temperature sensor of
sensor is used)
Controller.
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which 3 universal inputs can be used and configured for advanced
automatically switches occupancy levels from Occupied to Stand-by functionality as required by the application.
to Unoccupied when no motion is detected in the room:
During PIR activated Stand-by periods, Stand-by heating and
cooling setpoints are used
2015 Viconcis Technologies. All rights reserved.

During PIR activated unoccupied periods, unoccupied-by


heating and cooling setpoints are used.
Unoccupied Mode
During unoccupied periods, the unoccupied heating and cooling
setpoints are used.
Occupied Override Mode
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.
On Call for Heat
The proportional device acts as a first step and modulates from 0
to 100% capacity. The perimeter heater operates as a second step.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
42 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB heating and cooling with changeover sensor and reheat, Analog valve
actuator, PWM duct heater and water sensor for changeover, 2 pipe

Airflow Direction Cooling / Heating Coil On/Off Duct Heater

2 POSITION
COOLING VALVE / HEATING VALVE

SSR
SOLID STATE RELAY
CHANGE OVER (R1810 WITH HEATSINK)
SENSOR

Configuration
Configuration Settings
Parameter Name

UI19 COS
Fan menu ON-AUTO
BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Pipe no. 2
Seq. operation Cool-rht
2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 43

VT8300 Mod. & PWM Control

RH

BO8 - Aux Heat

UO9 - Close Cool V


UO10 - Close Heat V

UO11 - Open Cool V


UO12 - Open Heat V
BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)
PWM DUCT HEATER
SOLID STATE RELAY HEATING VALVE
L 0-10 v 24 v Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

24 Vac Transformer

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24

CO SENSOR 10 k-2
BACnet REF

UI 20 - RS

Common
BACnet +

UI22 - SS
Common
BACnet -

SCOM
UI 19
UI 16

UI 17

Sequence of Operation and Wiring On Call for Heat


If supply water temperature is less than 75F (23.9C), the valve
Occupied Mode modulates from closed to open according to demand. If water
During Occupied periods, the occupied heating and cooling supply temperature is greater than 77F (25C), valve remains
setpoints are used. closed.
Stand-by Mode (only available when PIR motion detector On Call for Cool
sensor is used) If supply water temperature is higher than 77F (25C), valve
When equipped with a PIR (Passive Infrared) accessory sensor modulates from closed to open according to demand. If water
supply temperature is less than 75F (23.9C), valve remains
the Controller provides advanced active occupancy logic, which
closed. The duct heater operates as a second step.
automatically switches occupancy levels from Occupied to Stand-by
to Unoccupied when no motion is detected in the room:
Options
During PIR activated stand-by periods, stand-by heating and
2015 Viconcis Technologies. All rights reserved.

Wireless adapter modules for BACnet models are available.


cooling setpoints are used.
(see Appendix B for network wiring).
During PIR activated unoccupied periods, unoccupied-by
heating and cooling setpoints are used. Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Unoccupied Mode Controller.
During unoccupied periods, unoccupied heating and cooling
setpoints are used. 3 universal inputs can be used and configured for advanced
functionality as required by the application.
Occupied Override Mode
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
44 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB heating and cooling with changeover sensor and reheat, tri-state floating
actuator, PWM duct heater and water sensor for changeover, 2 pipe

Airflow Direction Cooling / Heating Coil On/Off Duct Heater

TRI-STATE
COOLING VALVE / HEATING VALVE

SSR
SOLID STATE RELAY
CHANGE OVER (R1810 WITH HEATSINK)
SENSOR

Configuration
Configuration Settings
Parameter Name

UI19 COS
Fan menu ON-AUTO
Control Type Floating
BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Pipe no. 2
Seq. operation Cool-rht 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 45

VT8300 Floating & PWM Control

RH

BO8 - Aux Heat

UO9 - Close Cool V

UO10 - Close Heat V

UO11 - Open Cool V

UO12 - Open Heat V


BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common) PWM DUCT HEATER


SOLID STATE RELAY HEATING VALVE
L Close Open Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

24 Vac Transformer

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24

CO SENSOR 10 k-2
BACnet REF

UI 20 - RS

Common
BACnet +

UI22 - SS
Common
BACnet -

SCOM
UI 19
UI 16

UI 17

Sequence of Operation and Wiring On Call for Heat


If supply water temperature is less than 75F (23.9C), valve
Occupied Mode modulates from closed to open according to demand. If water
During Occupied periods, occupied heating and cooling setpoints supply temperature is greater than 77F (25C), valve remains
are used. closed.
Stand-by Mode (only available when PIR motion detector On Call for Cool
sensor is used) If supply water temperature is higher than 77F (25C), valve
When equipped with a PIR (Passive Infrared) accessory sensor modulates from closed to open according to demand. If water
supply temperature is less than 75F (23.9C), valve remains
the Controller provides advanced active occupancy logic, which
closed. The duct heater operates as a second step.
automatically switches occupancy levels from occupied to stand-by
to unoccupied when no motion is detected in the room: Options
During PIR activated stand-by periods, stand-by heating and Wireless adapter modules for BACnet models are available.
2015 Viconcis Technologies. All rights reserved.

cooling setpoints are used. (see Appendix B for network wiring).


During PIR activated unoccupied periods, the unoccupied-by
Remote wall mounted sensor or return air temperature
heating and cooling setpoints are used.
sensor can be used instead of internal temperature sensor of
Unoccupied Mode Controller.
During Unoccupied periods, unoccupied heating and cooling 3 universal inputs can be used and configured for advanced
setpoints are used.
functionality as required by the application.
Occupied Override Mode
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
46 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB heating and cooling with changeover sensor and reheat, Analog 0-10 Vdc air
damper actuator, PWM duct heater and air sensor for changeover, 2 pipe

Airflow Direction Analog Damper On/Off Duct Heater

CHANGE OVER DAMPER


SENSOR

SSR
SOLID STATE RELAY
(R1810 WITH HEATSINK)

Configuration
Configuration Settings
Parameter Name

UI19 COS
Fan menu ON-AUTO
BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Prop. band Default value 3.0. Range = 3.0 to 10.
Pipe no. 2
Seq. operation Cool-rht 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 47

VT8300 Mod. & On / Off Control

RH

BO8 - Aux Heat


OU9 - Close Cool V

UO10 - Close Heat V

UO11 - Open Cool V

UO12 - Open Heat V


BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)

C (Common) PWM DUCT HEATER


SOLID STATE RELAY ZONE DAMPER ACTUATOR
L 0-10 v 24 v Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

24 Vac Transformer

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24

CO SENSOR 10 k-2
BACnet REF

UI 20 - RS
Common
BACnet +

UI22 - SS
Common
BACnet -

SCOM
UI 19
UI 16
UI 17

Sequence of Operation and Wiring On Call for Heat


If supply water temperature is higher than 77F (25C), valve
Occupied Mode modulates from closed to open according to demand. If water
During Occupied periods, occupied heating and cooling setpoints supply temperature is less than 75F (23.9C), valve remains
are used. closed. The duct heater operates as a second step.
Stand-by Mode (only available when PIR motion detector On Call for Cool
sensor is used) If supply air temperature is less than 75F (23.9C), damper
When equipped with a PIR (Passive Infrared) accessory sensor modulates from closed to open according to demand. If water
supply temperature is greater than 77F (25C), damper remains
the Controller provides advanced active occupancy logic, which
closed.
automatically switches occupancy levels from occupied to stand-by
to unoccupied when no motion is detected in the room: Options
During PIR activated stand-by periods, stand-by heating and Wireless adapter modules for BACnet models are available.
2015 Viconcis Technologies. All rights reserved.

cooling setpoints are used. (see Appendix B for network wiring).


During PIR activated unoccupied periods, the unoccupied-by
Remote wall mounted sensor or return air temperature
heating and cooling setpoints are used.
sensor can be used instead of internal temperature sensor of
Unoccupied Mode Controller.
During unoccupied periods, unoccupied heating and cooling
setpoints are used. 3 universal inputs can be used and configured for advanced
functionality as required by the application.
Local Override
The controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
48 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB heating and cooling with changeover sensor and reheat, floating air damper
actuator, PWM duct heater and supply air sensor for changeover, 2 pipe

Airflow Direction Floating Damper On/Off Duct Heater

CHANGE OVER DAMPER


SENSOR

SSR
SOLID STATE RELAY
(R1810 WITH HEATSINK)

Configuration
Configuration Settings
Parameter Name

UI19 COS
Fan menu ON-AUTO
Control Type Floating
BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Pipe no. 2
Seq. operation Cool-rht 2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 49

VT8300 Floating & PWM Control

RH

BO8 - Aux Heat


UO9 - Close Cool V

UO10 - Close Heat V


UO11 - Open Cool V
UO12 - Open Heat V
BO2 - Fan L
BO3 - Fan M

BO4 - Fan H
RC (24 Vac)
C (Common) PWM DUCT HEATER
SOLID STATE RELAY ZONE DAMPER ACTUATOR
L Close Open Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

24 Vac Transformer

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24

CO SENSOR 10 k-2
BACnet REF

UI 20 - RS
Common
BACnet +

UI22 - SS
Common
BACnet -

SCOM
UI 19
UI 16
UI 17

Sequence of Operation and Wiring On Call for Heat


If supply water temperature is higher than 77F (25C), valve
Occupied Mode modulates from closed to open according to demand. If water
During Occupied periods, occupied heating and cooling setpoints supply temperature is less than 75F (23.9C), valve remains
are used. closed. The duct heater operates as a second step.
Stand-by Mode (only available when PIR motion detector On Call for Cool
sensor is used) If supply air temperature is less than 75F (23.9C), damper
When equipped with a PIR (Passive Infrared) accessory sensor modulates from closed to open according to demand. If water
supply temperature is greater than 77F (25C), damper remains
the Controller provides advanced active occupancy logic, which
automatically switches occupancy levels from occupied to stand-by closed.
to unoccupied when no motion is detected in the room:
Options
During PIR activated stand-by periods, stand-by heating and
Wireless adapter modules for BACnet models are available.
2015 Viconcis Technologies. All rights reserved.

cooling setpoints are used.


(see Appendix B for network wiring).
During PIR activated unoccupied periods, the unoccupied-by
heating and cooling setpoints are used. Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Unoccupied Mode
During unoccupied periods, unoccupied heating and cooling Controller.
setpoints are used. 3 universal inputs can be used and configured for advanced
Local Override functionality as required by the application.
The Controller reverts back to the occupied mode as specified by a
configuration timer when a local override is requested at Controller.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
50 Application Guide Fan Coil Unit Controller Series
VT83x0U5xxxB cooling and reheat, Analog 0-10 vdc air damper actuator, Analog duct heater
and electric perimeter

Airflow Direction Modulating Damper Modulating Duct Heater

DAMPER

PERIMETER HEATER

SSR
SOLID STATE RELAY
(R1810 WITH HEATSINK)

Configuration
Configuration Settings
Parameter Name

Fan menu ON-AUTO


BO8 Out Time 1 = 10 Second
BO8 AuxOut 0-Heat
Pipe no. 4
Seq. operation Cl/ht-rht

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 51

VT8300 Modulating & PWM Control

RH
BO8 - Aux Heat

OU9 - Close Cool V


UO10 - Close Heat V
UO11 - Open Cool V
UO12 - Open Heat V
BO2 - Fan L

BO3 - Fan M
BO4 - Fan H
RC (24 Vac)

C (Common)
ZONE DAMPER
PERMETER HEAT COOLING ONLY
SOLID STATE RELAY DUCT HEATER, SRC ACTUATOR
L 0-10 V 24V Com. 0-10 V 24V Com.

S
1 2 3 4 5 6 7 8 9 10 11 12

FCU Low-voltage
TERMINAL BLOCK

COMM ON

24 VAC

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF

UI 20 - RS
BACnet +

UI22 - SS
Common
Common
BACnet -

UI 19
UI 16
UI 17

Sequence of Operation and Wiring On Call for Heat


The damper remains closed. The proportional heater acts as a first
Occupied Mode step and modulate from 0 to 100% capacity. The perimeter heater
During Occupied periods, occupied heating and cooling setpoints operates as a second step.
are used. On Call for Cool
Stand-by Mode (only available when PIR motion detector The damper modulates from closed to open according to demand.
sensor is used)
When equipped with a PIR (Passive Infrared) accessory sensor Options
the Controller provides advanced active occupancy logic, which Wireless adapter modules for BACnet models are available.
automatically switches occupancy levels from occupied to stand-by (see Appendix B for network wiring).
to unoccupied when no motion is detected in the room:
Remote wall mounted sensor or return air temperature
During PIR activated stand-by periods, stand-by heating and sensor can be used instead of internal temperature sensor of
2015 Viconcis Technologies. All rights reserved.

cooling setpoints are used. Controller.


During PIR activated unoccupied periods, the unoccupied-by
heating and cooling setpoints are used. 3 universal inputs can be used and configured for advanced
functionality as required by the application.
Unoccupied Mode
During unoccupied periods, unoccupied heating and cooling
setpoints are used.
Local Override
The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
52 Application Guide Fan Coil Unit Controller Series

VT8300 Mixed-voltage Applications


Applications in this section make use of the SC1300 and SC2300 mixed-voltage relays.
VT8350U5xxxB and SC1300 120 VDC RELAY Heating/cooling 4-pipe fan coil unit with high voltage
3-speed fan, and 0-10 VDC Analog valves and dehumidification sequence for low voltage

High Voltage Fan Airflow Direction Cooling Coil Heating Coil

ANALOG ANALOG
COOLING VALVE HEATING VALVE

VT8300

SC1300

Power supply
120 vac

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Pipe no. 4
Seq. operation Cool / Heat

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 53

VT8300 Mix Voltage 120 volts

RH

BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

1 2 3 4 5 6 7 8 9 10 11 12

HEATING VALVE COOLING VALVE


0-10v 24v Com. 0-10v 24v Com.

SC1300

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF
+

UI 20 - RS
-

UI22 - SS
Common
Common

High Voltage Fan


BACnet

BACnet

UI 19
UI 16

UI 17

FAN HI

FAN MED

FAN LO
Power supply
120 Vac
COMM ON

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
The changeover sensor sends supply air temperature to controller. Dehumidification only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Stand-by Mode (only available when PIR motion detector
sensor is used) Dehumidification disabled if room temperature falls below low
Setpoints revert to those defined by stand-by cooling and heating. ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and Reheat disabled if cooling demand reaches 100%.
cooling.
Options
Occupied Override Mode
2015 Viconcis Technologies. All rights reserved.

System reverts to occupied mode for duration determined by Wireless adapter modules for BACnet models are available.
ToccTime parameter. (see Appendix B for network wiring).
On Call for Cool Remote wall mount or duct sensor ready.
Cooling valve opens to maintain room temperature. Heating valve Can be configured for 2-pipe systems.
closes. Dehumidification enabled.
3 universal inputs can be used and configured for advanced
On Call for Heat functionality as required by the application.
Heating valve opens to maintain room temperature. Cooling valve
closes. Dehumidification disabled. Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
54 Application Guide Fan Coil Unit Controller Series
VT8350U5xxxB and SC2300 240 VDC RELAY Heating/cooling 4-pipe fan coil unit with high voltage
3-speed fan, and 0-10 VDC Analog valves and dehumidification sequence for low voltage

High Voltage Fan Airflow Direction Cooling Coil Heating Coil

ANALOG ANALOG
COOLING VALVE HEATING VALVE

VT8300

SC2300

Power supply
240 vac

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Pipe no. 4
Seq. operation Cool / Heat

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 55

VT8300 Mix Voltage 240 volts

RH

BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

1 2 3 4 5 6 7 8 9 10 11 12

HEATING VALVE COOLING VALVE


0-10v 24v Com. 0-10v 24v Com.

SC2300

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF
+

UI 20 - RS
-

UI22 - SS
Common
Common

High Voltage Fan


BACnet

BACnet

UI 19
UI 16

UI 17

FAN HI

FAN MED

FAN LO
Power supply
240 Vac
COMM ON

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
Dehumidification only allowed in COOL mode, or if cooling is
The changeover sensor sends supply air temperature to controller.
enabled in AUTO mode.
Stand-by Mode (only available when PIR motion detector
Dehumidification disabled if room temperature falls below low
sensor is used)
ambient lockout temperature, which is cooling setpoint minus
Setpoints revert to those defined by stand-by cooling and heating.
configuration defined deadband value.
Unoccupied Mode
Reheat disabled if cooling demand reaches 100%.
Setpoints revert to those defined by unoccupied heating and
cooling.
Options
Occupied Override Mode
2015 Viconcis Technologies. All rights reserved.

Wireless adapter modules for BACnet models are available.


System reverts to occupied mode for duration determined by
(see Appendix B for network wiring).
ToccTime parameter.
Remote wall mount or duct sensor ready.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve Can be configured for 2-pipe systems.
closes. Dehumidification enabled. 3 universal inputs can be used and configured for advanced
On Call for Heat functionality as required by the application.
Heating valve opens to maintain room temperature. Cooling valve Universal input can be configured for changeover sensor.
closes. Dehumidification disabled.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
56 Application Guide Fan Coil Unit Controller Series
VT8350U5xxxB and SC1300 120 VDC RELAY Heating/cooling 4-pipe fan coil unit with High Voltage
3-speed fan, tri-state floating valves and dehumidification sequence for low voltage

High Voltage Fan Airflow Direction Cooling Coil Heating Coil

TRI-STATE TRI-STATE
FLOATING VALVE FLOATING VALVE

VT8300

SC1300

Power supply
120 vac

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Control Type Floating
Pipe no. 4
Seq. operation Cool / Heat

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 57

VT8300 Floating Control Mix Voltage

RH

BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

1 2 3 4 5 6 7 8 9 10 11 12

HEATING VALVE COOLING VALVE


Open Close Com. Open Close Com.

SC1300

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF
+

UI 20 - RS
-

UI22 - SS
Common
Common

High Voltage Fan


BACnet

BACnet

UI 19
UI 16

UI 17

FAN HI

FAN MED

FAN LO
Power supply
120 Vac
COMM ON

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
Dehumidification is only allowed in COOL mode, or if cooling is
Stand-by Mode (only available when PIR motion detector
enabled in AUTO mode.
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating. Dehumidification is disabled if room temperature falls below low
ambient lockout temperature, which is the cooling setpoint minus
Unoccupied Mode
the configuration defined deadband value.
Setpoints revert to those defined by unoccupied heating and
cooling. Reheat disabled if cooling demand reaches 100%.
Occupied Override Mode
Options
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve Remote wall mount or duct sensor ready.
closes. Can be configured for 2-pipe systems with changeover.
On Call for Heat 3 universal inputs can be used and configured for advanced
Heating valve opens to maintain room temperature. Cooling valve functionality as required by the application.
closes.
Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
58 Application Guide Fan Coil Unit Controller Series
VT8350U5xxxB and SC2300 240 VDC RELAY Heating/cooling 4-pipe fan coil unit with High Voltage
3-speed fan, tri-state floating valves and dehumidification sequence for low voltage

High Voltage Fan Airflow Direction Cooling Coil Heating Coil

TRI-STATE TRI-STATE
FLOATING VALVE FLOATING VALVE

VT8300

SC2300

Power supply
240 vac

Configuration
Configuration Settings
Parameter Name

Fan menu L-M-H-A


Control Type Floating
Pipe no. 4
Seq. operation Cool / Heat

2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 59

VT8300 Floating Control Mix Voltage

RH

BO8 - Aux Heat

UO11 - Analog Heat

UO12 - Analog Cool


BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

1 2 3 4 5 6 7 8 9 10 11 12

HEATING VALVE COOLING VALVE


Open Close Com. Open Close Com.

SC2300

13 14 15 16 17 18 19 20 21 22 23 24
BACnet REF
+

UI 20 - RS
-

UI22 - SS
Common
Common

High Voltage Fan


BACnet

BACnet

UI 19
UI 16

UI 17

FAN HI

FAN MED

FAN LO
Power supply
240 Vac
COMM ON

Sequence of Operation and Wiring On Demand for Dehumidification


Dehumidification is achieved via cooling coil using heating coil for
Occupied Mode
reheat if necessary.
Setpoints revert to those defined by occupied cooling and heating.
Dehumidification is only allowed in COOL mode, or if cooling is
Stand-by Mode (only available when PIR motion detector
enabled in AUTO mode.
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating. Dehumidification is disabled if room temperature falls below low
ambient lockout temperature, which is the cooling setpoint minus
Unoccupied Mode
the configuration defined deadband value.
Setpoints revert to those defined by unoccupied heating and
cooling. Reheat disabled if cooling demand reaches 100%.
Occupied Override Mode
Options
System reverts to occupied mode for duration determined by
2015 Viconcis Technologies. All rights reserved.

ToccTime parameter. Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve Remote wall mount or duct sensor ready.
closes. Can be configured for 2-pipe systems with changeover.
On Call for Heat 3 universal inputs can be used and configured for advanced
Heating valve opens to maintain room temperature. Cooling valve functionality as required by the application.
closes.
Universal input can be configured for changeover sensor.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
60 Application Guide Fan Coil Unit Controller Series

Appendix A - Passive infra-red Sensor specifications


Passive Infra-Red Sensor Sequence of Operation

Initially, the Controller is in Stand-by mode and Stand-by setpoints are used for the Controller. When the Passive
Infra-Red (PIR) sensor detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer
is reset. The Occupied setpoints are used for this operation.
If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room
switches to Stand-by mode and Stand-by setpoints are used. While in Stand-by mode, if no motion is detected
for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and
uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion switches the room back to
Occupied mode.

Typical Detection Pattern for PIR Lens

Horizontal Angles (Typical) Vertical Angle (Typical)

Recommended installation Transverse motion: 4-5 ft/s / 1.5 m/s


height for PIR sensor:
4 - 5 ft. / 1.2-1.5 m

Sensor Ranges
A = 20 ft. / 6.1 m
40O
B = 14 ft. / 4.3 m
C = 11 ft. / 3.4 m A Center 30O

20O 20O

B B
20O 20O
C C

Center

Energy Savings
Typical Savings of 10-30%
85 50%
80
75
70
40%
65
60
Saving Percentage
Energy Usage (KWh)

55
PIR can maximize your
50 30%
2015 Viconcis Technologies. All rights reserved.

energy saving from


45
10-30% by adjusting
40
temperature set points in
35 20%
unoccupied zones during
30
scheduled periods. 25
20
10%
15
10
5
0 0%
0 2 4 6 8 10 12 14 16 18 20 22 24
Time of Day (EST)
Typical Consumption PIR Thermostat Consumption Savings

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 61

Appendix B - optional network SET-UP

BACnet Communication Wiring Wireless Communication

BACnet +
thermostat -
1 ref

BACnet +
thermostat -
2 ref

BACnet +
thermostat -
3 ref

Notes:
Wiring should be daisy chained
Always respect polarity No communication wires required
If using 2 conductors and shielded wires, connect
shield of each feed together on back of Controller
Only ground shield at one location. Do not connect
shield to reference terminal

Appendix C - schematic of controllers occupancy sequence of operation


Setpoints

26.5C
80F
Unoccupied cool
24.5C
76F
Stand-by cool
22C 22C
72F Deadband Deadband 72F
Occupied cool
Deadband
Occupied heat
70F 70F
21C 21C
Stand-by heat Stand-by 66F
time 19C
2015 Viconcis Technologies. All rights reserved.

Unoccupied heat Unoccupied


time 62F
16.5C
Time

Movement detected Into Stand-by mode Into Unoccupied Next movement


- - mode detected
Stand-by timer reset Unoccupied timer reset

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
62 Application Guide Fan Coil Unit Controller Series

Appendix D - VTR8300 controller and SC3000 relay pack


Product Overview
The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit
thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet MSTP or
wireless ZigBee Pro networked models.
No previous building automation training is required for installation and commissioning process, and
installation can be completed in approximately fifteen minutes.
The SC3000 Series Line Voltage Switching Transformer Relay Pack Controllers are designed for silent control
of typical high voltage fan coil device loads (90 - 277 VAC multi-voltages). It uses advanced microprocessor-
based circuitry with a built-in transformer that eliminates all typical required peripheral components when
automating a Fan Coil unit with traditional building automation systems.
The SC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the
control of a single master VTR83XX Terminal Equipment Controller.
A single VTR83XX Terminal Equipment Controller can control up to 10 x SC3000 Series Relay Packs as they
are line-powered units.
The unit locally contains all relay outputs for fan switching and valve control, and models are also available
for extra monitoring/control inputs of the Fan Coil Units.

Typical Fan Coil Unit Set-up

Typical Fan Coil Unit


H C
1 Tx/Rx
2 7 Vdc
Power
3 Com Supply

SC3404E5000
4 RUI 1
Electrical
5 SCom
6 RBI 2 WHITE
90-277 Vac - 50/60 Hz
Cabinet
C C
1/2HP + 5A Max Comb. or
7 SS 13A+ 5A Max Comb
Amb. Temp. 50oC
BLACK
8 RS FAN
RED
LOW
9 Heat - 1/2 HP
or 13A FAN
Max MED BLUE
10 Heat +
FAN
BROWN
HIGH
5A
Max
COOL YELLOW

1 Tx/Rx
2 7 Vdc
Power
3 Com Supply

4 RUI 1
5 SCom xxx-xxxx-xx

6 RBI 2 90-277 Vac - 50/60 Hz


WHITE
1/2HP + 5A Max Comb. or
7 SS 13A+ 5A Max Comb
Amb. Temp. 50oC
BLACK
8 RS FAN
RED
LOW
9 Heat - 1/2 HP
or 13A FAN
Max MED BLUE
10 Heat +
FAN
BROWN
HIGH
5A
Max
COOL YELLOW

Low Voltage Connections


to VTR8300 Controller

2015 Viconcis Technologies. All rights reserved.

Daisy Chained Mixed Daisy Chained


Topology and Star Topology

Star Topology

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
Application Guide Fan Coil Unit Controller Series 63

Appendix E - sed series wireless Sensors


Wireless ZigBee Pro Motion Sensors and Door/Window Switch
Wireless door switches used with an onboard or remote PIR sensor provide advanced local occupancy routines allowing for increased
energy savings during occupied hours without sacrificing occupant comfort.
Wireless window switches are used to monitor exterior windows or patio/balcony doors when opened to prevent unnecessary energy
consumption.
Fan Coil Terminal Equipment Controllers with SED Series ZigBee Pro wireless switches can be used in stand-alone mode, or with
integration to a central management system, to allow for advanced functions such as central reservation and occupancy functions.
Up to twenty SED-WIN or SED-DOR ZigBee wireless switches can be used with a VTR8300 or VT8300 Room Controller
Up to ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a VTR8300 or VT8300
Room Controller
Note that if a ZigBee wireless window switch is used, the VT8300 Room Controller cannot also use a remote PIR motion sensor, whether
wired or wireless. Using one or more wireless remote PIR motion sensors means that a wired PIR motion sensor cannot be used, and
vice versa.
The SED Series sensors are factory delivered with batteries and are ready to be installed, configured, and used right out of the box. Due
to the extremely small current consumption of the sensors, the expected battery life is approximately 10 years, which is equivalent to the
battery shelf life.
No tools are required for commissioning or servicing the ZigBee devices. A simple interface on the devices with an on-board LED and
hidden switch provides all required functions for local interaction. The VT8300 user interface has screens used to pair and configure
ZigBee devices (SED-WMS, SED-CMS, or SED-WDS only). Local information for battery life and connectivity (heartbeat) are also
displayed through the ZigBee Pro wireless network.
For more information about using the SED-WIN and SED-DOR switches, consult the SED-WIN / SED-DOR Wireless Door and
Window Switch Installation Guide.
For more information about using the SED-WDS, SED-WMS and SED-CMS wireless switches and sensors, consult the Pairing VT8000
Series Room Controllers with ZigBee Sensors Installation Guide and Procedure.

Model Selection

Window Switch Door Switch

Door switch SED-DOR-P-5045

Window switch SED-WIN-P-5045

Door/window switch SED-WDS-P-5045

Wall mounted
SED-WMS-P-5045
motion sensor
Ceiling mounted
SED-CMS-P-5045
motion sensor
2015 Viconcis Technologies. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015
64 Application Guide Fan Coil Unit Controller Series

LED LED LED

SED-WIN
SED-CMS SED-DOR
SED-WMS SED-WDS

LED

Hidden Hidden Hidden


switch switch switch

Hidden
switch
Appendix F: Terminal Correspondence
The terminals of an VT8300 are identified differently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7000
series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller
with a VT8300 Room Controller.

VT7000 VT8300
Terminal name Terminal ID Terminal name Terminal ID
Binary Input 1 BI1 Universal Input 16 UI16
2015 Viconcis Technologies. All rights reserved.

Binary Input 2 BI2 Universal Input 17 UI17


Universal Input 3 UI3 Universal Input 19 UI19
Sensor Common Scom Terminal 18 Common COM
Remote Sensor RS Universal Input 20 UI20 - RS
Sensor Common Scom Terminal 21 Common COM
Mix/Supply Sensor MS Universal Input 22 UI22 - SS

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150
028-0444-00 www.viconics.com | sales@viconics.com January 2015