PL - 300 MULTIFUNCTION PROTECTION


INTRODUCTION
PL-3300 units are digital based multifunction protection The units are available in the following mechanical
relays that incorporate simultaneously in a single unit a great constructions:
number of protection functions that can be selected within
a set of options to create a solution adapted to any user's
needs. PL-3
300 Horizontal case:

Apart from the protection functions, they incorporate a wide


range of optional characteristics as listed below:

Reclosing unit: three-phase and by minimum frequency


Measurement
Communication features
Oscillography
Events
Fault reports
Fault locator

PL-3
300 Vertical case:
PL-3300 unit includes up to two rear communication ports
that allow:

To link the units to a Protection and Control Integrated


System, by means of various communication protocols
To access the status, historical data, and settings
information, locally and/or remotely through telephone
communications

PL-3300 control features allow it to be used as a bay control


in M.V. in small installations, when including command exe-
cution capabilities and automatisms.

PL-3
300 Integrated in TCP:
The innovations in PL-3
300 range of protection relays within
TEAM ARTECHE protection and control units are: Includes the same protection functions as PL-3 300 and
Unified rated currents (1A-5A) additionally incorporates enhanced control and local
Scale background: 200A automation functions of TCP units (see TCP catalogue).
It is applied as protection and control unit for medium and
Multiprotocol communications
high voltage bays.
Class 0,5 in I, V, and P measures
More digital inputs and outputs
IRIG-B synchronization input
Greater capacity and resolution of events reports,
faults reports, oscilloperturbographic recording and
measurement historical
Measurement of unit temperature
Aluminium box
Battery voltage measurement
6 setting tables
4 ANSI curves, 6 IEC/BSC curves, 1 definite time and
2 user programmable curves

2
FUNCTIONAL DESCRIPTION

PROTECTION FUNCTIONS
Phase overcurrent (3*50/51) and neutral overcurrent If the 67N unit is current polarized, the T9 transformer
(50N/51N) should measure the polarization current.

Protects the installations against phase to phase and phase


to earth faults, with instantaneous trips (2 levels) and timed
trips (programmable curves ANSI and IEC/BSC, and user
curves).

Phase directional overcurrent (67) and neutral directional


overcurrent (67N)

If the model includes directional overcurrent, the type of


polarization for phase and neutral directional can be The connection of units that polarize by V0 will vary upon
selected by setting: models, this voltage can be connected to T4, T5, T9 or
internally calculated.
67
Quadrature polarization
Sequence polarization
67N:
Polarization by V0
Polarization by V0, I0 (under request)
Sequence polarization

There are models of PL-3 300 that include a second


directional overcurrent unit.

3
Sensitive neutral overcurrent (50/51SN) Broken conductor (46BC)
Detects when a phase of the installation comes down and
Models with sensitive neutral unit are able to detect very protects bays against this anomaly.
resistive earth faults. For sensitive neutral measurement, it is
necessary to use a toroid transformer connected to Breaker failure (50BF)
transformer T5 or T4, depending on the model chosen.
If the model has directional overcurrent, the type of directio- Detects failures in breaker actuation, providing information
nal for this function can be chosen via setting: to other protection units so that these accelerate their trip.
angular The PL-3300 includes a three phase 50BF unit, and there are
watimetric models that include a single phase unit, monitoring each
I * cos f phase separately
I * sen f
Overvoltage (59), undervoltage (27) and voltage
unbalance (47)

There are models of PL-3 300 with the following voltage


functions: overvoltage, undervoltage and voltage
unbalance, that can be independently enabled or disabled
according to customer needs.

Overvoltage function acts against voltage increases that


could endanger the isolation and security of the protected
units.

Isolated neutral overcurrent (67IN) Undervoltage function protects, those loads connected to
the line, which are sensitive to line voltage drops.
The high sensitivity and the directionality of this function
allows detecting earth faults for isolated neutral systems Voltage unbalance function protects the installation against
and very resistive earth faults. The isolated neutral current is the harmful effects of voltage unbalances, such as
measured using the same transformer as that used for the excessive warming in motors, current unbalances, etc.
sensitive neutral current measurement (see figure above).
Zero sequence overvoltage (59N)
Voltage controlled overcurrent (51V)
Protects against earth isolation failures in machines. Zero
Lowers the pickup level of the overcurrent unit depending sequence voltage can be obtained through an open delta
on the voltage level. This reduces the tripping time in case connection of the secondaries of three voltage transformers
of severe faults (with voltage fall). (see polarization by V0 of 67N) or calculated as the vectorial
sum of the three phase simple voltages.
Cold Load Pickup
Thermal image (49)
Avoids undesired trips produced by overcurrents at
connection time. Protect elements such as lines, transformers, etc, against
thermal overloads, calculating the temperature according to
Tap changer lock (50TCL) the present and recent load conditions of the protected
device.
Enables an independent current level to be set which can
be used for various automatisms, such as tap changer lock, Fuse failure (68FF)
to prevent the regulator from acting when the current is
enough to damage the tap changer. Detects if a fuse has blown up in the secondary circuit of the
voltage transformers. While detecting this situation,
Current unbalance (46) functions 51V, 27 and 59N will remain locked.

Protects the installation against unbalances in current as a


result of anomalies in the power system or unbalanced
loads.

4
Frequency unit (81 O, U, R) Zones and pilot protection (85)

Frequency units protect the Power System against loss of There are models of PL-3 300 that communicating with other
balance between generated and demanded power. terminals allow the next pilot protection schemes:
Permissive overreach
Permissive underreach
There are models of PL-3 300 with the following frequency Directional locking
functions: overfrequency and/or underfrequency and Directional unlocking
frequency rate of change, that can be enabled or disabled
independently via setting according to customer needs. Additional schemes:
ECO
There are 5 steps of frequency that can be programmed Inverse direction locking
independently as overfrequency or underfrequency,
allowing an underfrequency load shedding. To carry out these schemes, the instantaneous units of 67
and 67N have 3 zones with independent settings for each
The frequency rate of change unit has 4 steps, this allows zone. The direction of zones 1 and 2 is forwards and the
the disconnection of loads before reaching undesired zone 3 can be forwards or backwards.
frequency levels.
Breaker monitoring (74TC/CC)
Power protection (32)
Breaker supervision by pole. Statistic of number of
There are models of PL-3 300 with the following power breaker manoeuvres and breaker health monitoring by
functions, that can be independently enabled or disabled SkI2 counter
via setting according to customer needs: Possibility of supervision of 4 coils
Minimum active and apparent power (independent)
Maximum active and apparent power (independent) Protection functions locking feature
Reverse power
Each of the protection functions can be locked by a digital
The maximum and minimum power (active and apparent) input or logic function (see programmable logic).
units protect against excessive increases and decreases of
the generated power.

The reverse power protection acts against motorization of


the generator.

AUTOMATISMS
Syncrocheck (25) Recloser (79)

It is used to supervise the closing of a breaker with voltage PL-3300 units include a three-phase recloser and by
on both sides. The function enables the closing when the actuation of the underfrequency unit (for models with 81U
angle, frequency and magnitude in both sides comply with unit) which gives a reclosure possibility for each step of the
the set conditions. Synchrocheck function is made by 81U unit.
comparing voltages of phase B in both sides of the breaker.
The measurement of T7 is used against measurement of T9 The recloser also includes the option to enable the
or T5 connected to phase B of the other side of the sequence coordination function. Such sequence
breaker: coordination is applied when a number of units is installed
downstream and have a slow trip programmed with the last
reclosure. This function avoids the fast trip of the units that
are in a higher level, during the fast trip of the units that are
in the lower side.

High Current Lockout (HCL)

Provides a second instantaneous overcurrent unit at a


higher setting, so that its actuation does not produce
automatic reclosing.

5
Programmable logic Special automatisms

The user can configure up to 15 logic signals, that can be The unit is provided by the following special automatisms:
assigned to output relays, LEDs, or inputs for protection Slack springs automatism: the unit watches the status of
functions blocking features. an input assigned as "slack springs". If this input is
active during a time longer than the one programmed in
setting "spring slack time" the output "open spring
motor" is generated, this input is used to trip the switch
of the spring tightening motor's power supply
Voltage presence: The automatism watches if the
average compound voltage is within particular values
and gives a control signal. When the average compound
voltage exceeds the presence threshold, the bit for the
control word is set to 1, and if it falls below the absence
threshold, that bit is set to 0
Close locking: If the circuit breaker is seen as closed, no
closing order is allowed from digital input, command,
pushbutton or recloser
Open locking: If the circuit breaker is seen as open, no
opening order is allowed from digital input, command or
pushbutton

Logic selectivity functions

Logic selectivity functions that lockout the trip, but not the
pick-up of the instantaneous overcurrent and isolated neu-
tral directional units, can be done.

DATA ACQUISITION FUNCTIONS


Measurements Events recording

The unit measures the following network parameters: The unit stores in non volatile memory the last 400 events,
Current for each phase (I) which can be retrieved from a PC, with the following data:
Neutral current (I) Date and time of the event
Phase to ground voltage in each phase (kV) Descriptive text of the event
Average phase to ground voltage (kV) Values of electrical parameters
Phase to phase voltage for each two phases (kV)
Average phase to phase voltage (kV)
Active power, three-phase and in each phase (MW)
Reactive power, three-phase and in each phase (MVAR)
Apparent power (MVA)
Power factor
Active energy counter (positive and negative)
Reactive energy counter (positive and negative)
Frequency (Hz)
Current maximeter and power, three-phase and in each
phase
Harmonics distortion factor in IA, IB,IC, and average
(in %)
Harmonics distortion factor in VA, VB, VC and average
(in %)

Additionally, the PL-3


300 presents:
Unit temperature measurement
Optionally: Battery voltage measurement. The battery
voltage measurement is executed using the units power
supply input

6
Fault records

The last 20 faults are stored in the non volatile memory, with
the following data:
Date and time of the fault pickup, beggining and end.
Prefault and fault values of electrical parameters
Duration and type of fault
Level of electrical parameters at the fault's ocurrence
time

Oscillograph data recorder

All the units have an oscillograph data recorder with the next
characteristics:
Each record comprises the samples from 9 analog
signals and the status of 32 selectable digital signals
32 samples per cycle
It is saved a maximum of 1200 cycles, and the number
of cycles per record is programmable (for example: if 60
cycles are selected, there will be 20 records of 60
cycles). The prefault is programmable by setting.
40 records of 30 cycles, 20 records of 60 cycles or 10
Demand maximeter
records of 120 cycles with programmable prefault, this
can be chosen via setting
The unit stores the maximum current value, plus the time
Configurable pickup
tag for the moment when it occurs.
Records in non volatile memory
The disturbances are collected and exported in COM-
Fault locator (FL)
TRADE format
There are models of PL-3 300 which have a fault locator unit.
This unit processes the information collected for each fault
and gives as a result of this calculation the distance to the
fault point. The distance is given in Km, %, miles,... and it
can be accesed via the display or the PC.

Time synchronization

Via communications
Via demodulated IRIG-B input

The unit has clock with backup battery.

Setting tables

The unit has 6 setting tables. The active table selection can
be made through the keyboard/display, command from the
protections console or digital input activation.
Historical reports

A queue of 4000 historical records is stored in the


non-volatile memory. Each record has currents, voltages
and maximum and minimum powers (active, reactive and
apparent), detected in a programmable time span.

7
MODELS
Non-d
directional PL-3
300 family (figure 1):

NB: 50/51 + 50/51N + 46 + 46BC + 50BF (3) +


74TC/CC

NC: NB model + 50/51SN + 49 + 51V + Cold Load


Pickup + 50TCL + 68FF

ND: NC model + 59 + 27 + 47 + 59N + 81O/U + 81R +


25

NE: ND model + FL

Figure 1
Directional PL-3
300 family (figure 2):

DB: 67 + 67N + 46 + 46BC + 50BF (3) + 74TC/CC

DC: DB model + 67SN + 67IN + 49 + 51V + Cold Load


Pickup + 50TCL + 68FF

DD: DC model + 59 + 27 + 47 + 81O/U + 81R + 25


nd
DE: DD model + 2 67/67N unit + 50BF ()

DF: DE model + FL

Figure 2
PL-3 300 for distributed generator interconnection family
(figure 2):

IB: 50/51 + 67N + 46 + 46BC + 50BF (3) + 74TC/CC


+ 68FF + 59 + 27 + 47 + 59N + 81O/U + 81R + 25 +
32 + 79 + 79 (81U) + High Current Lockout

IC: IB model + 49 + 51V + Cold Load Pickup + 50TCL


nd
+ 2 67/67N unit

PL-3
300 for distribution centres family:
Figure 3
CR: /51 + 50/51N + 46 + 46BC + 50BF (3) + 74TC/CC
+ 49 + 79 + High Current Lockout

All models incorporate the following special automatisms: slack springs automatisms, voltage presence, open locking and
close locking.

8
SETTING RANGES (6 tables)
Phase and neutral overcurrent units (indep.) Phase and neutral High current lockout units (independent)
Setting Range Step Setting Range Step
Timed unit (A) 0.1-200 0.01 Activation trip number 1-4 1
Instanatenous unit (A) 0.1-200 0.01 Pickup (A) 0.1-200 0.01
Sensitive neutral overcurrent unit Additional time (s) 0-60 0.01
Ajuste Rango Paso Voltage controlled overcurrent unit
Timed unit (A) 0.005-10 0.001 Setting Range Step
Instantaneous unit (A) 0.005-10 0.001 Control voltage (V) 10-200 0.1
Isolated neutral overcurrent unit Thermal image unit
Setting Range Step Setting Range Step
Low current (A) 0.005-1 0.001 Nominal current (A) 0.2-100 0.1
High current (A) 0.005-1 0.001 Alarm threshold (%) 80-100 1
Low voltage (V) 0.5-60 0.1 Heating ratio (min.) 3-60 1
High voltage (V) 0.5-60 0.1 Cooling ratio (min.) 3-180 1
First trip timming (s) 0-60 0.01 Underfrequency and Overfrequency units
Directional unit Setting Range Step
Setting Range Step Type of frequency Max./Min
Phase angle 0-359 1 Frequency (Hz) 45-65 0.01
Neutral angle 0-359 1 Definite time (s) 0-60 0.01
Minimum polarization voltage (V) 1.0-15.0 0.1 Minimum supervision voltage (V) 40-200 1
Broken conductor unit Frequency rate of change unit
Setting Range Step Setting Range Step
Pickup (I2/I1) 0.1-0.5 0.01 Supervision frequency (Hz) 45-65 0.01
Definite time (s) 0.05-300 0.01 Minimum current (A) 0-100 0.1
df/dt pickup (Hz/s) 0.2-5 0.1
Current unbalance unit Additional time (s) 0-2 0.01
Setting Range Step
Timed pickup (A) 0.1-200 0.01 Maximum active and apparent power units (independent)
Instantaneous pickup (A) 0.1-200 0.01 Setting Range Step
HI-Set (%) 1-200 1
Breaker failure unit Timing (s) 0-60 0.01
Setting Range Step
LO-Set (%) 1-200 1
Phase restore (A) 0.1-200 0.01
Timing (s) 0-100 0.1
Neutral restore (A) 0.1-200 0.01
Definite time (s) 0-60.00 0.01 Minimum active and apparent power units (independent)
Setting Range Step
Pilot protection schemes Pickup (%) 1-200 1
Setting
Timing (s) 0-60 0.01
Type selection Permissive overreach
Permissive underreach Reverse power unit
Directional lock Setting Range Step
Directional unlock HI-Set (%) 1-200 1
Setting Range Step Timing (s) 0-60 0.01
RTP input dropout time 0-1.00 0.01 LO-Set (%) 1-200 1
Block additional time 0-1.00 0.01 Timing (s) 0-100 0.1
Loss of guard delay 0-0.20 0.01 Recloser
ECO enable YES/NO Setting Range Step
Minimum RTP delay for ECO 0-9.9 0.1 Number of closures 0-4 1
Reverse directional lock enable YES/NO 1st closure time for phase to phase faults (s) 0.05-100 0.01
Reverse directional lock definite time 0-9.9 0.1 2nd closure time for phase to phase faults (s) 1-600 1
Overvoltage and undervoltage units (independent) 3rd closure time for phase to phase faults (s) 1-600 1
Setting Range Step 4th closure time for phase to phase faults (s) 1-600 1
Timed unit (V) 10-200 0.1 1st closure time for phase to earth faults (s) 0.05-90 0.1
Instantaneous unit (V) 10-200 0.1 2nd closure time for phase to earth faults (s) 1-600 1
3rd closure time for phase to earth faults (s) 1-600 1
Zero sequence overvoltage unit 4th closure time for phase to earth faults (s) 1-600 1
Setting Range Step
Security time for phase to phase faults (s) 1-600 1
Timed unit (V) 2-200 0.1
Security time for phase to earth faults (s) 1-600 1
Instantaneous unit (V) 2-200 0.1
Security time after manual closure (s) 1-600 1
Voltage unbalance unit Dead time for Vref (s) 1-600 1
Setting Range Step
Timed pickup (V2/V1) 0.1-0.5 0.01 Minimum frequency recloser
Setting Range Step
Definite time (s) 0-600 0.01 Min. frequency conditions to reclose YES/NO
Additional time (s) 0-60 0.01 Min. frequency value for reclosing (Hz) 45-65 0.01
Time characteristics Reclosing time (s) 1-1000 1
Setting Security time (s) 1-300 1
Curve type Definite time Synchrocheck
Inverse BSC Setting Range Step
Very Inverse BSC Minimum voltage side A (V) 10-200 1
Extremely Inverse BSC Minimum voltage side B (V) 10-200 1
Inverse short time BSC Enable "if not A and not B" YES/NO
Inverse long time BSC Enable "if not A and B" YES/NO
Inverse ANSI Enable "if A and not B" YES/NO
Very Inverse ANSI Voltage difference enable YES/NO
Extremely Inverse ANSI Voltage difference (V) 2-90 1
Moderately inverse time ANSI Frequency difference enable YES/NO
User curve (USAR1 or USAR2) Frequency difference (Hz) 0.05-2 0.01
Relapse with disc emulation option Angle difference enable YES/NO
Setting Range Step Angle difference () 5-50 1
Time index 0.05-30 0.01 Checking time (s) 0-100 1
Definite time (s) 0-600 0.01
Inst. addit. time (s) 0-60 0.01 Note: All the units have an enable setting.

9
TECHNICAL CHARACTERISTICS
Power supply Frequency
24-4
48 Vdc Programmable system frequency 50 or 60 Hz
Range 18-60 Vdc Operating range fn 5Hz
Ripple over 48 Vdc 20 % over rated
125-2
220 Vdc Communication ports
Range 86-280Vdc Front communication port
Ripple over 220 Vcc 20 % over rated Connector RS232 DTE 9 pin female D type
Burden 8W mn Cable length 3 m max.
18W max Baud rate 300-38400 bps
Isolation No
Current circuits Rear communication port types (COM-1
1 and COM-2
2)
Thermal capacity for phase/neutral current (UNIFIED RATED CURRENT 5/1A) RS232
Continuous 20 A Connector RS232 DTE9 pin female D type
For 1 sec. 500 A Type of cable Shielded
For cycle 1250 A Cable length 15 m max.
Burden for In = 5A <0,35 VA Isolation 500 V
Burden for In = 1A <0,02 VA RS485
Thermal capacity for sensitive neutral and isolated neutral current Connector RS485 DTE9 pin female D type
Continuous 20 A Type of cable Shielded crossed
For 1sec. 500 A Cable length 1000 m max.
Burden for In = 1A <0,02 VA Isolation 500 V
Burden for In = 0,25A <0,002 VA Glass F.O.
Connector G.F.O. ST
Voltage circuits Wavelength 820 nm
Thermal capatity Allowed attenuation 8db with 62,5/125 mm
Continuous 2 Vn glass F.O.
For 1 min. 3,5 Vn Multimode glass F.O. 62,5 /125 mm
Burden for 63,5V 0,015 VA Maximum distance 1,25 Km
Burden for 100V 0,027 VA Plastic F.O.
Programmable voltages: Simple or compound (only for pin type terminals) Connector P.F.O. Standard of HP
Programmable phase order: ABC or CBA Wavelength 660nm
Allowed attenuation 24,7 db with 1mm
Closed Terminals for current and voltage input (optional) plastic
Terminal pitch 9,5 mm cable 22 db with
200 mm silica cable
Digital inputs and outputs without extension board Maximum distance 115 m with 1mm low
Inputs number 8 losses plastic cable
Outputs number 7 1,9 Km with 200 mm
silica cable
Digital inputs and outputs with extension board
Inputs number 17 IRIG-B B
Outputs number 14 Input type Demodulated
Input level TTL
Optoisolated digital inputs Cable type 2 shielded wires
Voltage range 18-60 Vdc Isolation 500V
Inactive below 15 Vdc
Voltage range 86-280 Vdc Accuracies
Inactive below 60 Vdc Class 0,5 for V, I and P (untill 120% rated) for unified rated current 5/1A
Burden <3 mA Accuracy in the protections range 3%
Curves operating accuracy 5% or 30 ms (the
Output contacts higher of both)
Trip relays: Relays 1 to 6 (and 8 to 13)
Carry 8A Battery voltage monitoring (optional):
Make (0,5s) 30 A 24-4
48 Vdc
Breaking capacity (L/R=40 ms) Range 18 to 60 Vdc
220 Vdc 0,2 A 125-2
220 Vdc
125 Vdc 0,3 A Range 86 to 280 Vdc
48 Vdc 0,5 A
Resistive breaking capacity Environmental characteristics
220Vdc 0,5A Operating Temperature -10C to 55C
125 Vdc 1A Extended operating Temperature (optional) -20C to 75C
48 Vdc 3A Storage Temperature -40C to 85C
Actuating time O8 ms Relative humidity Untill 95% without
Auxiliary relay: Relay 7 (and 14) condensation
Carry: 10 A
Make (0,5s) 30A Mechanical characteristics
Breaking capacity (L/R=40ms) Weight 2,8 Kg
125 Vdc 0,25 A Approx. weight with packing and docum. 3,8 Kg
48 Vdc 0,5 A Front IP IP40
Resistive breaking capacity Optional front IP IP52
220 Vdc 0,15 A
125 Vdc 0,4 A
48 Vdc 2A
Actuating time O8 ms

10
MAN-M
MACHINE INTERFACE Rear port's programmable communication protocols

The communications protocol for the first rear port (COM-1)


The PL-3 300 units allow the communication and dialogue is always Procome. The protocol of the second rear port
with the user through the associated peripherals: (COM-2), If exists, is programmable.
The user can choose via setting out of the next communi-
Keyboard-d
display cations protocols: Procome, DNP 3.0, MODBUS,
IEC 870-5-101.

SOFTWARE
TEAM ARTECHE uses the SIPCON Protections programm,
developed for PCs running under WINDOWS. This
programm allows clear and simple dialogue with the unit for
access to the information stored in it and for setting as
Featuring: necessary.
2 line 16 character LCD with programmable language:
spanish/english All the configuration accesses are password protected to
16 key keyboard prevent tampering by unauthorized personnel.
Optical signalling: 7 programmable red LEDs and 1 two-
colour status LED The outstanding features of the SIPCON Protections
4 signalled push-buttons with programmable functiona- programm include the following:
lity. The functionality of these push-buttons are chosen Authomatic detection of the unit which it is in dialogue
by setting: with
a- Deactivated Unit status display via status screens
b- Functionality programmable by the user Presentation and modification of settings
c- Programmed as indicated below Filling and presentation of all information stored by the
relay for its later study in higher levels: events, historical
data, faults, etc.
Breaker closure with signalled LED
SIPCON Protections is compatible with the software used
Breaker open with signalled LED in TEAM ARTECHE's Integrated Protection and Control
System, and can be incorporated into them as just one
more functional module.
Breaker control: Local/Remote with signalling LED

Maneuver permission

When you select the four push-buttons to have


programmable functionality, the keys of the keyboard can
also be programmed to carry out commands, which are set
by the user.

Allows:
Displaying of inputs, measurements, date and time,
statistical data and last fault
Displaying and modification of active table, settings,
inputs, outputs and LEDs allocation, except the
programmable logic and the oscillograph data recorder

Communications: Local and remote

The units has:


1 RS232 front serial port, for direct connection to a PC
1 or 2 rear serial outputs for connection to a PC, modem
or Integrated Protection and Control System. The rear
terminals can be: RS232, RS485, glass F.O. or plastic
F.O.

11
PIN TYPE TERMINALS
Rear board example

Vertical Model

Horizontal Model

12
CONNECTIONS DIAGRAMM PL-3
300 PIN TYPE TERMINALS
Interconnection example

13
CLOSED TERMINALS (for analog inputs)
Rear board example

Vertical Model

Horizontal Model

14
CONNECTIONS DIAGRAMM PL-3
300 CLOSED TERMINALS
Interconnection example

15
PL300 IN BOX DIMENSIONS
HORIZONTAL

VERTICAL

16
PL300 IN TCP DIMENSIONS

PL300 PIN TYPE TERMINALS IN TCP

17
QUALITY POLICY
Since it was founded, TEAM ARTECHE has committed itself
to complying with the guideline laid out in its quality policy,
oriented towards the continuous improvement of its
products and services in each and every one of its activities,
in order to obtain complete client satisfaction.

The ISO 9001 international certificate shows that the


desing, manufacturing and service provided by TEAM
ARTECHE follow the most secure and stringent control and
supervision procedures.

Every unit manufactured by TEAM ARTECHE is designed to


operate under severe electrical substation and industrial
plant conditions, complying with the most exigent
electromagnetic, environmental and mechanical tests, thus
incorporating the CE mark of electromagnetic compliance.

STANDARDS AND TESTS


Electrical
Immunity to electrostatic discharges IEC 61000-4-2 Class IV
Immunity to fast transient bursts IEC 61000-4-4 Class IV
Immunity to voltage pulses (surges) IEC 61000-4-5 Class IV
Immunity to 1MHz damped wave IEC 61000-4-12 Class III
Measurement of insulation resistance IEC-255-5
Measurement of dielectric rigidity IEC-255-5 Class III
Measurement of insulation with voltage pulses IEC 255-5 Class III
Microcuts IEC 60870-2-1

Electromagnetic
Measurement of radiated electromagnetic interference EN55011 Class A, group 1
Immunity to radiated radiofrequency fields IEC 61000-4-3 Class III
Immunity to conducted radiofrequency signals IEC 61000-4-6 Class III
Immunity to 50Hz magnetic fields IEC 61000-4-8

Mechanical
Vibration IEC 255-21-1 Class I
Shock and bump IEC 255-21-2 Class I

Environmental
Damp heat IEC 68-2-3 (+70C, 93% relative humidity)
Dry heat IEC 68-2-2 (+85C)
Cold IEC 68-2-1 (-40C)
Change of temperature IEC 68-2-14 (-20/+70C, 2 of 4 hours cycle)

18
SELECTION TABLE
Continuous improvement of its products i s TEAM ARTECHEs one of the
main objetives, consequently, this catalogues information, can be modified
without previous advise. To get a completer information, consult the manual or
PL300 MODEL contanct our sales department.

MODEL
PL300 Non directional NB
NC
ND
NE
PL300 Directional DB
DC
DD
TRANSFORMER ARRANGEMENT
DE
DF
T4 T5 T9
PL300 Interconnection IB
IC Model NB IN
PL300 Distribution center CR
BOX TYPE
Model NC IN I SN
Horizontal H
Vertical V
TCP integrated Note 5 T Model ND* IN I SN VSYNC V0 calculated
POWER SUPPLY
18-60 Vdc Y Model ND* I SN V0 VSYNC IN calculated
86-280 Vdc Z
ANALOG INPUTS TERMINALS Same transformer arrangement as
Model NE*
Pin type Standard terminals 1 model ND
Closed terminals 2
EXTENSION MODULE Model DB IN V0
No module 0
9 DIs (6 indepen.) + 7 DOs (3 indepen.) 1
Model DB +
current polarized IN V0 I0
DIGITAL INPUTS VOLTAGE 67N
Range: 18-60 Vdc Y
Range: 86-280 Vdc Z Model DC IN I SN V0
REAR COMMUNICATION PORTS
Model DC +
GFO Programmable Protocol A current polarized IN I SN I0 V0 calculated
PFO Programmable Protocol B 67N*
RS232 Programmable Protocol C Model DC +
current polarized I SN V0 I0 IN calculated
RS485 Programmable Protocol D 67N*
GFO (COM-2) + GFO (COM-1) Note 1 E
PFO (COM-2) + PFO (COM-1) Note 1 F Model DD* IN I SN VSYNC V0 calculated
RS232 (COM-2) + RS232 (COM-1) Note 1 G
RS485 (COM-2) + RS232 (COM-1) Note 1 H Model DD* I SN V0 VSYNC IN calculated
GFO (COM-2) + RS232 (COM-1) Note 1 I
Internal communication for TCP Note 5 T Model DD +
current polarized I SN I0 VSYNC IN and V0 calculated
SPECIAL FUNCTIONS AND AUTOMATISMS 67N
No functions 0
Same transformer arrangement as
79 + 79 (81U) + HCL (included in models IB, IC and CR) Note 2 1 Model DE* model DD
85 (only for directional PL-300 models) 2
Model DE +
79 + 79 (81U) + HCL + 85 (only for directional PL-300 models) Note 2 3 current polarized Same transformer arrangement as
model DD + current polarized 67N
Battery voltage measurement and extended operating temperature 67N
None 0 Same transformer arrangement as
Model DF* model DD
Battery voltage measurement 1
Extended operating temperature 2 Model DF +
current polarized Same transformer arrangement as
Battery voltage measurement and extended operating temp. 3
model DD + current polarized 67N
Current polarized 67N Note 4 67N
No 0
Model IB IN V0 VSYNC
Yes 1
V0 or I N calculation Model IB +
None 0 current polarized IN I0 VSYNC V0 calculated
67N*
V0 calculated 1
Model IB +
IN calculated Note 3 2 current polarized V0 I0 VSYNC IN calculated
Both (only for models DD + current polarized 67N, 3 67N*
DE + current polarized 67N, DF + current polarized 67N) Same transformer arrangement as
Model IC
model IB
If you want to have a printed manual with your relay, tell our sales departament. Model IC +
current polarized Same transformer arrangement as
Specify also the language you want fot the manual (spanish or english). model IB + current polarized 67N
67N*

Model CR IN

Note 1: For models with 2 communications ports the communication protocol of the port COM-2 is programmable and the one of the port COM-1 is always Procome
protocol.
Note 2: The unit 79 (81U) is only for models with function 81U.
Note 3: For models marked with an * in the transformer arrangement table.
Note 4: Only for models with 67N and T9 = I0
Note 5: When T box type is selected, the rear communication option to select must be T: Internal communication for TCP.

19
Derio Bidea, 28 48100 MUNGIA - VIZCAYA - SPAIN
Tel.: + 34 - 94 601 89 00 Fax: + 34 - 94 601 89 01
E-mail: teamarteche@teamarteche.com
www.teamarteche.com

For further information, please contact :


TM

C&S Protection & Control Ltd.


44, Okhla Indl. Estate, New Delhi-110020, Ph.: 011-55602414, 26319465-66 Fax: 011-55602413 email: cspc@controlsindia.com

Marketing Office : DELHI : Ph.: 55602414, 26319465-66 Fax : 55602413 CHANDIGARH : Ph. 2776154, 2776151, 2726153 Fax: 2726154
KOLKATA : Ph. 24549607-08 Fax: 24549371 MUMBAI : Ph.: 24114727-28 Fax : 24126631 PUNE : Ph.: 5444822-824, Fax: 5410820,
AHMEDABAD : Ph.: 65841425, 6589132 Fax : 6589132 BANGALORE : Ph.: 5586147, 5323582, 5594939 Fax: 5582796,
CHENNAI : Ph.: 26426475, 26426572 Fax: 26411972 HYDERABAD : Ph.: 27813003, 55332304 Fax: 27812987

Potrebbero piacerti anche