Sei sulla pagina 1di 78

Photo: HELUKABEL

Bus Cables HELUKABEL


Bus technology is being used in an increasing number of industrial applications. This technology can be applied in every branch in R
industry where process-control techniques are used. The enormous pressures of competitiveness and costs in all areas of process
control emphasise the need for even more rationalisation and greater efficency. The traditional method of parallel wiring for the
equipment and machines does not have the flexibility and thus constitutes a major factor in costs and time. The potential for saving
costs from internetworking the machinery by bus systems is very high. So as to keep the amount of cabling low, the information
from the master controller is sent over a bus network and is potentially available to all components in the system. Only those
components specifically addressed by the information can respond and process these signals. All types of cables and wires used in
all common bus systems are available from HELUKABEL.

R 86
Contents Bus Cables

Description Page
Industrial Ethernet HELUKAT 600IND S-STP, ROBUST........................................................................................................ R 89
Industrial Ethernet HELUKAT 600IND S-STP, SHIPLINE ...................................................................................................... R 90
Industrial Ethernet HELUKAT 600IND S-STP, ROBUSTFLEX ................................................................................................ R 91
Industrial Ethernet HELUKAT 500IND S-STP, 10GIG ........................................................................................................... R 92
Industrial Ethernet HELUKAT 250S S-FTP, Drag Chain ...................................................................................................... R 93
Industrial Ethernet HELUKAT 200IND S-FTP, ROBUSTFLEX ................................................................................................ R 94
Industrial Ethernet S-FTP, WK Industrial 105C ................................................................................................................ R 95
Industrial Ethernet HELUKAT 100S ECO S-FTP 4-core, Drag Chain .................................................................................. R 96
Industrial Ethernet HELUKAT 100S ECO S-FTP 4-pair, Drag Chain .................................................................................... R 97
Industrial Ethernet HELUKAT 200S S-FTP 4-core, Drag Chain .......................................................................................... R 98
Industrial Ethernet HELUKAT 200S S-FTP 4-pair, Drag Chain ........................................................................................... R 99
Industrial Ethernet HELUKAT 100T S-FTP Tordierex ....................................................................................................... R 100
Industrial Ethernet PROFInet Type A, xed installed + robust ........................................................................................ R 101
Industrial Ethernet PROFInet Type A, radiation resistant + armoured ........................................................................... R 102
Industrial Ethernet PROFInet Type B, hybrid ................................................................................................................... R 103
Industrial Ethernet PROFInet Type B, SHIPLINE + FESTOON............................................................................................. R 104
Industrial Ethernet PROFInet Type B and C, exible + high exible ............................................................................... R 105
Industrial Ethernet PROFInet Type C, Torsion .................................................................................................................. R 106
Probus L2, xed installation, indoor .............................................................................................................................. R 107
Probus L2, xed installation, outdoor or Industrial Area .............................................................................................. R 108
Probus L2, Direct Burial without + with Armouring ...................................................................................................... R 109
Probus L2, 7-wire............................................................................................................................................................ R 110
Probus L2, Drag Chain .................................................................................................................................................... R 111
Probus, ET200X + ECOFAST ............................................................................................................................................ R 112
Probus, SHIPLINE and High Temperature ...................................................................................................................... R 113
Probus DESINA-HYBRID-BUS ......................................................................................................................................... R 114
Probus L2, TORSION + FESTOON ..................................................................................................................................... R 115
Probus PA ....................................................................................................................................................................... R 116
Probus PA, armoured ..................................................................................................................................................... R 117
Probus PA, Long Distance .............................................................................................................................................. R 118
Probus SK, Indoor + Outdoor ......................................................................................................................................... R 119
Probus SK, FRNC + Industry ........................................................................................................................................... R 120
Probus SK, Drag Chain .................................................................................................................................................... R 121
FOUNDATION Fieldbus Basic .......................................................................................................................................... R 122
FOUNDATION Fieldbus Type A + gnge .......................................................................................................................... R 123
FOUNDATION Fieldbus Type A, armoured..................................................................................................................... R 124
FOUNDATION Fieldbus Type A ....................................................................................................................................... R 125
BUS Cables HMCB200, xed installed ............................................................................................................................... R 126
BUS Cables HMCB500, Drag Chain .................................................................................................................................... R 127
BUS Cables HMCB500S, Drag Chain .................................................................................................................................. R 128
BUS Cables HMCB800, Drag Chain .................................................................................................................................... R 129
BUS Cables USB S .............................................................................................................................................................. R 130
BUS Cables USB L............................................................................................................................................................... R 131
CAN-Bus 0,22 mm, xed installed .................................................................................................................................. R 132
CAN-Bus 0,22 mm, xed installed .................................................................................................................................. R 133
CAN-Bus, xed installed, 105C ........................................................................................................................................ R 134
CAN-Bus 0,34 mm, xed installed .................................................................................................................................. R 135
CAN-Bus 0,34 mm, xed installed .................................................................................................................................. R 136

R 87
Contents Bus Cables

Description Page
CAN-Bus 0,50 mm, xed installed .................................................................................................................................. R 137
CAN-Bus 0,50 mm, xed installed .................................................................................................................................. R 138
CAN-Bus 0,75 mm, xed installed .................................................................................................................................. R 139
CAN-Bus 0,25 mm, Drag Chain ....................................................................................................................................... R 140
CAN-Bus 0,34 mm Drag Chain, UL .................................................................................................................................. R 141
Interbus, xed installed .................................................................................................................................................... R 142
Interbus, xed installed, halogen-free ............................................................................................................................ R 143
Interbus Drag Chain .......................................................................................................................................................... R 144
Multibus I, high exible .................................................................................................................................................... R 145
Multibus II, high exible.................................................................................................................................................... R 146
ASI-Bus, EPDM ................................................................................................................................................................... R 147
ASI-Bus, PUR, UL/CSA ........................................................................................................................................................ R 148
ASI-Bus, TPE ...................................................................................................................................................................... R 149
ASI-Bus, TPE, UL/CSA......................................................................................................................................................... R 150
AS-Interface Electrical Cabinet FLIH ................................................................................................................................. R 151
Sensor-Aktor TPM ............................................................................................................................................................. R 152
DeviceNet PVC............................................................................................................................................................... R 153
DeviceNet FRNC ............................................................................................................................................................ R 154
DeviceNet CPE ............................................................................................................................................................... R 155
DeviceNet PUR, exible................................................................................................................................................. R 156
CC-Link-Bus PVC ............................................................................................................................................................... R 157
SafetyBUS, FRNC + PUR .................................................................................................................................................. R 158
LON BUS, H122 + Y116 ...................................................................................................................................................... R 159
EIB-Bus, 2-pairs PVC ......................................................................................................................................................... R 160
EIB-Bus, FRNC + PVC ........................................................................................................................................................ R 161
EIB-Bus ERD, PE ................................................................................................................................................................ R 162
KH-Bus, PVC + FRNC ......................................................................................................................................................... R 163

R 88
Industrial Ethernet
ROBUST 600IND
S-STP, Category 7

Type Industrial Area


Cable structure S-STP 4x2xAWG 23/1 PUR
Inner conductor diameter: Copper, bare (AWG 23/1)
Core insulation: Foam-skin-PE
Core colours: wh/bu, wh/og, wh/gn, wh/bn
Stranding element: Double core
Shielding 1: -
Shielding 2: Polyester foil, aluminium-lined
Screen 1 over stranding: Cu braid
Screen 2 over stranding: -
Outer sheath material: PUR
Cable external diameter: approx. 8,2 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
100 Ohm 20 ohm at 101 to 600 MHz
Loop resistance: 148 Ohm/km max.
Mutual capacitance: 43 nF/km nom.

Typical values
Frequency (MHz) 10 16 62,5 100 200 300 600
Attenuation (dB/100m) 5,6 7,1 13,9 17,5 25,2 32,1 44,9
Next (db) 100,0 100,0 96,0 94,0 88,0 84,0 73,0
ACR (db) 94,4 92,9 82,1 76,5 62,8 51,9 28,1

Technical data
Weight: approx. 62 kg/km
Min. bending radius for laying: 85 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 0,74 MJ/m
Copper weight: 34,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 7, Flame-retardant acc. to IEC 60332-1, Halogen-free acc. to 60754-2,
Corrosiveness acc. to EN50267-2-3, Oil-resistant

Application
HELUKAT 600IND data cables are used for harsh industrial applications. Mechanical characteristics are the steady against mineral oils, fats
and cooling lubricants. Also they are microben resistant and hydrolysis resistant. Electrically they are characterized by large performance
reserves and outstanding performance. They can be used to implement services such as Gigabit Ethernet, Fast Ethernet, Ethernet, ATM155,
FDDI, token ring 4/16 Mbit/s or ISDN absolutely trouble-free. The cables thus exceed the requirements for EN55022 Class B emission and
EN55024 immunity. So this serie has a superior electromagnetic compatibility qualification.

Part no. 801197, S-STP 4x2xAWG 23/1 PUR (S/FTP)


Dimensions and specifications may be changed without prior notice.

R 89
Industrial Ethernet
SHIPLINE 600IND
S-STP, Category 7

Cable structure S-STP 4x2xAWG 24/7 (stranded) FRNC


Inner conductor diameter: 0,61 mm
Conductor material: Copper, bare
Core insulation: Foam-skin-PE
Core colours: wh/bu, wh/og, wh/gn, wh/bn
Shielding 1: -
Screen over stranding element: Polyester foil, aluminium-lined
Screen 1 over stranding: Cu braid
Screen 2 over stranding: -
Outer sheath material: FRNC
Outer diameter: approx. 9,1 mm
Outer sheath colour: Grey similar to RAL 7035

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
100 Ohm 20 ohm at 101 to 600 MHz
Loop resistance: 164 Ohm/km max.
Mutual capacitance: 43 nF/km nom.
Rel. propagation velocity: 72 %

Typical values
Frequency (MHz) 10 16 62,5 100 200 600
Attenuation (dB/10m) 0,7 0,8 1,6 2,1 3,1 5,2
Next (db) 90,0 90,0 85,0 81,0 76,0 68,0
ACR (db) 89,3 89,2 83,4 78,9 72,9 62,8

Technical data
Weight: approx. 85 kg/km
Min. bending radius for laying: 85 mm
Operating temperature range min.: -20C
Operating temperature range max.: +75C
Caloric load, approx. value: 0,80 MJ/m
Copper weight: 36,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 7, Flame-retardant acc.
to IEC 60332-3, Smoke density acc. to IEC 61034, Halogen-free acc. to 60754-2, Corrosiveness
acc. to EN50267-2-3, Oil-resistant

Application R
This copper data cable, designed specifically for extreme industrial applications, is the ideal solution for Ethernet applications. Superior
transmission properties, suitable for use even under the most demanding conditions, certified by Germanischer Lloyd, that means suitable
for flexible marine and offshore applications.

Part no. 803382, S-STP 4x2xAWG 24/7 FRNC (S/FTP)


Dimensions and specifications may be changed without prior notice.

R 90
Industrial Ethernet
ROBUSTFLEX 600IND
S-STP, Category 7

Type Industrial Patch Cables


Cable structure S-STP 4x2xAWG 26/7 PUR
Inner conductor diameter: Copper, bare (AWG 26/7)
Core insulation: Foam-skin-PE
Core colours: wh/bu, wh/og, wh/gn, wh/bn
Stranding element: Double core
Shielding 1: -
Shielding 2: Polyester foil, aluminium-lined
Screen 1 over stranding: Cu braid
Screen 2 over stranding: -
Outer sheath material: PUR
Cable external diameter: approx. 6,4 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
100 Ohm 20 ohm at 101 to 600 MHz
Loop resistance: 290 Ohm/km max.
Mutual capacitance: 42 nF/km nom.

Typical values
Frequency (MHz) 10 16 62,5 100 200 600
Attenuation (db/10m) 0,8 1,1 2,2 2,8 4,0 7,4
Next (db) 80,0 80,0 75,0 72,0 68,0 61,0
ACR (db) 79,2 78,9 72,8 69,2 64,0 53,6

Technical data
Weight: approx. 48 kg/km
Min. bending radius for laying: 64 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 0,45 MJ/m
Copper weight: 28,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 7, Flame-retardant acc. to IEC 60332-1, Smoke density acc. to
IEC 61034, Halogen-free acc. to 60754-2, Corrosiveness acc. to EN50267-2-3, Oil-resistant, AWM 20963 (80C/30V)

Application
HELUKAT600 industry data cables were designed for high requirements in the industry (industrial ethernet) and other heavy-duty environments.
They are characterized by large performance reserves and outstanding performance. Mechanically they are also perfectly suited for rough
industrial environments due to their halogen-free PUR outer sheath. These line are manufacturable with common RJ45 plugs (industry and
office version), and also with some Sub-D and M12 plugs.

Part no. 802184, S-STP 4x2xAWG 26/7 PUR (S/FTP)


Dimensions and specifications may be changed without prior notice.

R 91
Industrial Ethernet
10GIG 500IND
S-STP, Category 6A

Cable structure 2x2x0.64 mm


Inner conductor diameter: 0,65 mm
Conductor material: Copper, bare
Core insulation: Foam-skin-PE
Core colours: whbu/bu, whog/og, whgn/gn, whbn/bn
Shielding 1: Polyester foil over stranded bundle
Inner sheath material: PVC
Screen over stranding element: Polyester foil, aluminium-lined
Total shielding: Foil + braid
Outer sheath material: PVC
Outer diameter: approx. 9,6 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
100 Ohm 20 Ohm at 101 to 500 MHz
Conductor resistance, max.: 59 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Loop resistance: 118 Ohm/km max.
Mutual capacitance: 72 nF/km nom.
Test voltage: 0,7 kV
Rel. propagation velocity: 62 %

Typical values
Frequency (MHz) 10 16 62,5 100 250 500
Attenuation (db/100m) 5,9 7,5 15,0 19,1 31,1 45,3
Next (dB) 60,3 57,2 48,4 45,3 39,3 34,3
PSNext (dB) 57,3 54,2 45,4 42,3 36,3 31,8

Technical data
Weight: approx. 115 kg/km
Min. bending radius for laying: 80 mm
Operating temperature range min.: -40C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,69 MJ/m
Copper weight: 44,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 6A,
Flame-retardant acc. to IEC 60332-3, CM 75C or PLTC

Application
R
Part no. 803693, INDUSTRIAL ETHERNET CAT.6A 10GIG
Dimensions and specifications may be changed without prior notice.

R 92
Industrial Ethernet
Drag Chain 250S
S-FTP, Category 6

Cable structure 4x2x0.15 mm (stranded)


Inner conductor diameter: 0,55 mm
Conductor material: Copper, tinned
Core insulation: PP
Core colours: whbu/bu, whog/og, whgn/gn, whbn/bn
Shielding 1: -
Inner sheath material: FRNC
Screen over stranding element: -
Total shielding: Foil + braid
Outer sheath material: PUR
Outer diameter: approx. 7,8 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
100 Ohm 20 Ohm bei 101 bis 250 MHz
Conductor resistance, max.: 140 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Loop resistance: 280 Ohm/km max.
Mutual capacitance: 52 nF/km nom.
Test voltage: 0,7 kV

Typical values
Frequency (MHz) 10 16 62,5 100 250
Attentuation (db/10m) 0,9 1,2 2,4 2,9 4,9
Next (db) 59,3 56,2 47,4 44,3 38,3
ACR (db) 58,4 55,0 45,0 41,4 33,4

Technical data
Weight: approx. 63 kg/km
Min. bending radius for laying: 60 mm
Operating temperature range min.: -30C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,35 MJ/m
Copper weight: 34,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 6, Flame-retardant acc.
to IEC 60332-1, UL 1581, Sec. 1080 (VW-1) and Sec. 1060 (FT-1)

Application
This copper data cable, designed specifically for extreme industrial applications, is the ideal solution for Ethernet Category 6 applications.
Superior transmission properties, suitable for use even under the most demanding conditions, designed for use in drag chains, fire-proof
and oil-resistant according to UL/CSA, the cable can also be used in the USA and Canada.

Part no. 803387, INDUSTRIAL ETHERNET CAT.6


Dimensions and specifications may be changed without prior notice.

R 93
Industrial Ethernet
ROBUSTFLEX 200IND
S-FTP, Category 5e

Type Industrial Patch Cables


Cable structure S-FTP 4x2xAWG 26/7 PUR
Inner conductor diameter: Copper, bare (AWG 26/7)
Core insulation: PO
Core colours: whbu/bu, whog/og, whgn/gn, whbn/bn
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Screen 1 over stranding: Polyester foil, aluminium-lined
Screen 2 over stranding: Cu braid
Outer sheath material: PUR
Cable external diameter: approx. 5,7 mm
Outer sheath colour: Grey similar to RAL 7035

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Loop resistance: 260 Ohm/km max.
Mutual capacitance: 47 nF/km nom.

Typical values
Frequency (MHz) 10 16 62,5 100 200
Attenuation (dB/10m) 0,8 1,1 2,4 2,9 4,3
Next (db) 58,0 56,0 45,0 43,0 37,0
ACR (db) 57,2 54,9 42,6 40,1 32,7

Technical data
Weight: approx. 44 kg/km
Min. bending radius for laying: 46 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 0,54 MJ/m
Copper weight: 24,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 5e, Flame-retardant acc. to IEC 60332-1, Smoke density acc. to
IEC 61034, Halogen-free acc. to 60754-2, Oil-resistant

Application
HELUKAT200 industry data cables were designed for high requirements in the industry (industrial ethernet) and other heavy-duty environments.
They are characterized by large performance reserves and outstanding performance. Mechanically they are also perfectly suited for rough
industrial environments due to their halogen-free PUR outer sheath. These lines are manufacturable with all common RJ45 plugs (industry R
and office version), and also with some Sub-D and M12 plugs.

Part no. 800068, S-FTP 4x2xAWG 26/7 PUR (SF/UTP)


Dimensions and specifications may be changed without prior notice.

R 94
Industrial Ethernet
WK Industrial 105C
S-FTP, Category 5e

Cable structure 2x2x0,75 mm (stranded)


Inner conductor diameter: 0,75 mm
Conductor material: Copper, tinned
Core insulation: XLPE ray cross-linking
Core colours: wh, ye, bu, og
Shielding 1: Polyester foil over stranded bundle
Inner sheath material: -
Screen over stranding element: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Outer sheath material: X-FRNC
Outer diameter: approx. 6,5 mm
Outer sheath colour: Black similar to RAL 9005

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 60 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Loop resistance: 120 Ohm/km max.
Mutual capacitance: 52 nF/km nom.
Test voltage: 2 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/100m) 6,3 8,0 16,5 21,3
Next (db) 70,0 65,0 55,0 50,0
ACR (db) 63,7 57,0 38,5 28,7

Technical data
Weight: approx. 64 kg/km
Min. bending radius for laying: 46 mm
Operating temperature range min.: -40C
Operating temperature range max.: +105C *
Caloric load, approx. value: 0,89 MJ/m
Copper weight: 34,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Category 5e, Halogen-free acc. to 60754-2,
Corrosiveness acc. to EN50267-2-3, UL-Syle 21281 80C/300V

Application
This copper data cable, designed specifically for extreme industrial applications, is the ideal solution for Ethernet applications. It guarantees
superior transmission properties. Cable with oil-resistant FRNC sheath and increased temperature resistance for use in the wind turbine and
similar sectors. Certified to UL, the cable can also be used in the USA and Canada.
* = with limited service life

Part no. 802293, INDUSTRIAL ETHERNET CAT.5e


Dimensions and specifications may be changed without prior notice.

R 95
Industrial Ethernet
DRAG CHAIN ECO 100S
S-FTP 4-Core, Category 5e

Type Drag chain applications


Cable structure 4x1x0.15 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 26/19)
Core insulation: PP
Core colours: whbl, bl, whor, or
Stranding element: Star quad
Shielding 1: Polyester foil over stranded bundle
Shielding 2: PETP fleece
Total shielding: Foil + braid
Outer sheath material: PUR
Cable external diameter: approx. 4,8 mm 0,3 mm
Outer sheath colour: Green

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Insulation resistance, min.: 0,15 GOhm x km
Loop resistance: 250 Ohm/km max.
Mutual capacitance: 51 nF/km nom.
Test voltage: 0,7 kV

Typical values
Frequency (MHz) 10 16 62,5 100 155
Attentuation (db/100m) 9,9 12,3 25,6 33,0 41,0
Next (db) 47,0 44,0 35,0 32,0 30,0

Technical data
Weight: approx. 30 kg/km
Min. bending radius for laying: 72 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 0,37 MJ/m
Copper weight: 17,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 5e, Flame-retardant acc. to IEC 60332-1, Halogen-free acc. to 60754-2,
Corrosiveness acc. to EN50267-2-3, AWM 20963 (80C/30V)

Application
This copper data cable, designed especially for heavy-duty industrial applications (Industrial Ethernet), is very well suited for manufacturing
of RJ45 and 15 or 9-Pin Sub-D plugs. With its PUR sheath, it is also suitable for the application in drag chains.
R
Part no. 82838, INDUSTRIAL ETHERNET CAT.5e
Dimensions and specifications may be changed without prior notice.

R 96
Industrial Ethernet
Drag chain ECO 100S
S-FTP 4-pair, Category 5e

Type Drag chain applications


Cable structure 4x2x0.15 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 26/19)
Core insulation: PP
Core colours: whbu/bu, whog/og, whgn/gn, whbn/bn
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: PETP fleece
Total shielding: Foil + braid
Outer sheath material: PUR
Cable external diameter: approx. 6,6 mm 0,2 mm
Outer sheath colour: Green

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Insulation resistance, min.: 0,15 GOhm x km
Loop resistance: 250 Ohm/km max.
Mutual capacitance: 48 nF/km nom.
Test voltage: 0,7 kV

Typical values
Frequency (MHz) 10 16 62,5 100 155
Attentuation (db/100m) 9,9 12,3 25,6 33,0 41,0
Next (db) 47,0 44,0 35,0 32,0 30,0

Technical data
Weight: approx. 56 kg/km
Min. bending radius for laying: 102 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 0,64 MJ/m
Copper weight: 31,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 5e, Flame-retardant acc. to IEC 60332-1, Halogen-free acc. to 60754-2,
Corrosiveness acc. to EN50267-2-3, AWM 20963 (80C/30V)

Application
This copper data cable, designed especially for heavy-duty industrial applications (Industrial Ethernet), is very well suited for manufacturing
of RJ45 and 15 or 9-Pin Sub-D plugs. With its PUR sheath, it is also suitable for the application in drag chains.

Part no. 82839, INDUSTRIAL ETHERNET CAT.5e


Dimensions and specifications may be changed without prior notice.

R 97
Industrial Ethernet
DRAG CHAIN 200S
S-FTP 4-Core, Category 5

Type Drag Chain Patch Cables


Cable structure S-FTP 4x1xAWG 24/19 PUR
Inner conductor diameter: Copper, bare (AWG 24/19)
Core insulation: PP
Core colours: wh/bn, gn/ye
Stranding element: Quad
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Screen 1 over stranding: Polyester foil, aluminium-lined
Screen 2 over stranding: Cu braid
Outer sheath material: PUR
Cable external diameter: approx. 6,2 mm 0,2 mm
Outer sheath colour: Green similar to RAL 6026

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Loop resistance: 156 Ohm/km max.
Mutual capacitance: 51 nF/km nom.

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/10m) 1,0 1,2 2,6 3,3
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 46,0 42,8 32,4 28,7

Technical data
Weight: approx. 54 kg/km
Min. bending radius for laying: 80 mm
Operating temperature range min.: -25C
Operating temperature range max.: +70C
Caloric load, approx. value: 0,944 MJ/m
Copper weight: 30,00 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 5, Flame-retardant acc. to IEC 60332-1, Halogen-free acc. to 60754-2,
Oil-resistant

Application
HELUKAT200T industry data cables were designed for the most extreme requirements in the industry (industrial ethernet) and other
heavy-duty environments. They are characterized by large performance reserves and outstanding performance, even under the most
extreme conditions. In addition, the thought-out mechanical construction even ensures applications in drag chains with high packing density. R
These lines are manufacturable with conventional Sub-D plugs or with various RJ45 plugs.

Part no. 800088, S-FTP 4x1xAWG 24/19 PUR (SF/UTP)


Dimensions and specifications may be changed without prior notice.

R 98
Industrial Ethernet
DRAG CHAIN 200S
S-FTP 4-Paar, Category 5

Type Drag Chain Patch Cables


Cable structure S-FTP 4x2xAWG 24/19 PUR
Inner conductor diameter: Copper, bare (AWG 24/19)
Core insulation: PE
Core colours: wh/bn, gn/ye, gy/pk, bu/rd
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Screen 1 over stranding: Polyester foil, aluminium-lined
Screen 2 over stranding: Cu braid
Outer sheath material: PUR
Cable external diameter: approx. 9,5 mm 0,2 mm
Outer sheath colour: Green similar to RAL 6026

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Loop resistance: 156 Ohm/km max.
Mutual capacitance: 51 nF/km nom.

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/10m) 1,0 1,2 2,6 3,3
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 46,0 42,8 32,4 28,7

Technical data
Weight: approx. 110 kg/km
Min. bending radius for laying: 115 mm
Operating temperature range min.: -25C
Operating temperature range max.: +70C
Caloric load, approx. value: 2,08 MJ/m
Copper weight: 54,30 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 5, Flame-retardant acc. to IEC 60332-1, Halogen-free acc. to 60754-2,
Oil-resistant

Application
HELUKAT200T industry data cables were designed for the most extreme requirements in the industry (industrial ethernet) and other
heavy-duty environments. They are characterized by large performance reserves and outstanding performance, even under the most
extreme conditions. In addition, the thought-out mechanical construction even ensures applications in drag chains with high packing density.
These lines are manufacturable with conventional Sub-D plugs or with various RJ45 plugs.

Part no. 81155, S-FTP 4x2xAWG 24/19 PUR (SF/UTP)


Dimensions and specifications may be changed without prior notice.

R 99
Industrial Ethernet
TORDIERFLEX 100T
S-FTP, Category 5

Type Torsion Patch Cables


Cable structure S-FTP 4x2xAWG 26/19 PUR
Inner conductor diameter: Copper, bare (AWG 26/19)
Core insulation: PO
Core colours: wh/bu, wh/og, wh/gn, wh/bn
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Screen 1 over stranding: Polyester foil copper, bare
Screen 2 over stranding: Cu braid
Outer sheath material: PUR
Cable external diameter: approx. 7,5 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Loop resistance: 260 Ohm/km max.
Mutual capacitance: 50 nF/km nom.

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/10m) 1,3 1,6 3,2 4,0
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 45,7 42,4 31,8 28,0

Technical data
Weight: approx. 63 kg/km
Min. bending radius for laying: 80 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 1,234 MJ/m
Copper weight: 29,50 kg/km

Norms
Acc. to ISO/IEC 11801, Acc. to EN 50173, Acc. to EIA/TIA 568-A, Category 5, Flame-retardant acc. to IEC 60332-1, Smoke density acc. to
IEC 61034, Halogen-free acc. to 60754-2, Oil-resistant, AWM 20963 (80C/30V)

Application
HELUKAT100T TORDIERFLEX data cables were designed for the most extreme requirements in the industry and other heavy-duty environments
in torsion applications. They are characterized by large performance reserves and outstanding performance, even under extreme conditions.
Long mechanical service life is also ensured due to a thought-out design. These lines are manufacturable with conventional Sub-D plugs or R
with various RJ45 plugs.

Part no. 800067, S-FTP 4x2xAWG 26/19 PUR (SF/UTP)


Dimensions and specifications may be changed without prior notice.

R 100
Industrial Ethernet
PROFInet Type A
fixed installed + robust

Type Fixed installation, indoor Industrial Area


Cable structure 2x2x0.64 mm 2x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: PE PE
Core colours: wh, ye, bu, og wh, ye, bu, og
Stranding element: Star quad Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC PVC
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PUR
Cable external diameter: approx. 6,5 mm 0,2 mm approx. 6,5 mm 0,2 mm
Outer sheath colour: Green similar to RAL 6018 Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 62 Ohm/km 62 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km 0,5 GOhm x km
Loop resistance: 124 Ohm/km max. 124 Ohm/km max.
Mutual capacitance: 50 nF/km nom. 50 nF/km nom.
Test voltage: 2 kV 2 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/100m) 5,2 6,9 15,0 19,5
Next (db) 70,0 65,0 55,0 50,0
ACR (db) 64,8 58,1 40,0 30,5

Technical data
Weight: approx. 67 kg/km approx. 64 kg/km
Min. bending radius for laying: 100 mm 46 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +80C +70C
Caloric load, approx. value: 0,34 MJ/m 0,91 MJ/m
Copper weight: 32,00 kg/km 32,00 kg/km

Norms
Applicable standards: PROFInet Guideline PROFInet Guideline
UL Style: CMG 75C PLTC FT4 -
CSA standard: CSA FT 4 -

Application
These copper data cables, designed especially for heavy-duty industrial applications, are very well suited for Ethernet applications. They
ensure superiour transmission properties and can be used even under most severe conditions. The line specified here correspond to the
PROFInet type A it is designed for normal (PVC) and robust (PUR) fixed installation applications.

Part no. 800653, PROFInet type A (SK) 801194, PROFInet type A (SK)
Dimensions and specifications may be changed without prior notice.

R 101
Industrial Ethernet
PROFInet Type A
radiation resistant + armoured

Type ray loaded areas Fixed installation,


outdoor
Cable structure 2x2x0.64 mm 2x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: XLPE ray cross-linking PE
Core colours: wh, ye, bu, og wh, ye, bu, og
Stranding element: Star quad Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: TPR ray cross-linking PVC
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Armouring: - Steel rib
Outer sheath material: PUR PE
Cable external diameter: approx. 6,5 mm 0,2 mm approx. 9,3 mm 0,5 mm
Outer sheath colour: Green similar to RAL 6018 Black

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 62 Ohm/km 62 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km 0,5 GOhm x km
Loop resistance: 124 Ohm/km max. 124 Ohm/km max.
Mutual capacitance: 50 nF/km nom. 50 nF/km nom.
Test voltage: 2 kV 2 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/100m) 5,2 6,9 15,0 19,5
Next (db) 70,0 65,0 55,0 50,0
ACR (db) 64,8 58,1 40,0 30,5

Technical data
Weight: approx. 63 kg/km approx. 124 kg/km
Min. bending radius for laying: 46 mm 93 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +80C +70C
Caloric load, approx. value: 0,29 MJ/m 2,14 MJ/m
Copper weight: 32,00 kg/km 31,00 kg/km

Norms R
Applicable standards: PROFInet Guideline PROFInet Guideline

Application
These copper data cables, designed especially for heavy-duty industrial applications are very well suited for Ethernet applications. They ensure
superiour transmission properties and can be used even under most severe conditions. The line specified here correspond to the PROFInet
type A and because of the special construction with cross-linked inner-jacket and PUR outer-jacket it is suitable for fixed installation applications
inside radiated areas and with the PVC inner-jacket/PE outer-jacket it is suitable for areas with rodent problems.

Part no. 801195, PROFInet type A (SK) 801650, PROFInet type A (SK)
Dimensions and specifications may be changed without prior notice.

R 102
Industrial Ethernet
PROFInet Type B
hybrid

Type Mobile use


Cable structure 2x2x0,75 mm (stranded)+ 4x1,5 mm
Inner conductor diameter 1: Copper, bare (AWG 22/7)
Inner conductor diameter 2: Copper, bare (AWG 16/84)
Core insulation 1: Foam-skin-PE
Core insulation 2: Foam-skin-PE
Core colours 1: wh, ye, bu, og
Core colours 2: Black
Stranding element 1: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Polyester foil
Outer sheath material: FRNC
Cable external diameter: approx. 10,3 mm 0,3 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 60 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Loop resistance: 120 Ohm/km max.
Mutual capacitance: 52 nF/km nom.
Test voltage: 2 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/100m) 6,3 8,0 16,5 21,3
Next (db) 50,0 47,0 38,0 35,0
ACR (db) 43,7 39,0 21,5 13,7

Technical data
Weight: approx. 153 kg/km
Min. bending radius for laying: 103 mm
Operating temperature range min.: -40C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,50 MJ/m
Copper weight: 94,00 kg/km

Norms
Applicable standards: PROFInet Guideline
UL Style: UL Style 21282

Application
This copper data cable, designed especially for heavy-duty industrial applications is very well suited for Ethernet applications. Ir ensures
superiour transmission properties and can be used even under most severe conditions. The line specified here corresponds the PROFInet
type, i.e. it is designed for flexible applications with integrated energoe cores.

Part no. 801651, PROFInet type B (SK)


Dimensions and specifications may be changed without prior notice.

R 103
Industrial Ethernet
PROFInet Typ B
SHIPLINE + FESTOON

Type Marine and Offshore FESTOON


Cable structure 2x2x0,75 mm (stranded) 2x2x0.75 mm (stranded)
Inner conductor diameter: Copper, tinned (AWG 22/7) Copper, tinned (AWG 22/7)
Core insulation: PP PE
Core colours: wh, ye, bu, og wh, ye, bu, og
Stranding element: Star quad Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: FRNC PVC
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: FRNC PVC
Cable external diameter: approx. 6,5 mm 0,4 mm approx. 6,5 mm 0,2 mm
Outer sheath colour: Green similar to RAL 6018 Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz 100 Ohm 5 %
Conductor resistance, max.: 60 Ohm/km 60 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km 0,5 GOhm x km
Loop resistance: 120 Ohm/km max. 120 Ohm/km max.
Mutual capacitance: 52 nF/km nom. 52 nF/km nom.
Test voltage: 2 kV 0,7 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/100m) 6,0 7,6 16,0 21,0
Next (db) 70,0 65,0 55,0 50,0
ACR (db) 64,0 57,4 39,0 29,0

Technical data
Weight: approx. 68 kg/km approx. 68 kg/km
Min. bending radius for laying: 46 mm 50 mm
Operating temperature range min.: -40C -10C
Operating temperature range max.: +70C +80C
Caloric load, approx. value: 0,45 MJ/m 1,20 MJ/m
Copper weight: 32,00 kg/km 32,00 kg/km

Norms
Applicable standards: PROFInet Guideline PROFInet Guideline
UL Style: CMG 75C PLTC FT4 CMG 75C or PLTC or AWM 21694 600V
CSA standard: CSA FT 4 CSA FT 4 R
Application
This copper data cable, designed especially for heavy-duty industrial applications is very well suited for Ethernet applications. It ensures
superiour transmission properties and can be used even under most severe conditions. The lines specified here corresponds the PROFInet
type B and are certified by the Germanische Lloyd (SHIPLINE), i.e. designed for flexible marine and offshore applications and Festoon
applications.

Part no. 802185, PROFInet type B (SK) 803295, PROFInet type B (SK)
Dimensions and specifications may be changed without prior notice.

R 104
Industrial Ethernet
PROFInet Type B + C
flexible + high flexible

Type Mobile use Drag chain applications


Cable structure 2x2x0,75 mm (stranded) 2x2x0.75 mm (stranded)
Inner conductor diameter: Copper, tinned (AWG 22/7) Copper, tinned (AWG 22/7)
Core insulation: PE PE
Core colours: wh, ye, bu, og wh, ye, bu, og
Stranding element: Star quad Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC FRNC
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PUR
Cable external diameter: approx. 6,5 mm 0,2 mm approx. 6,5 mm 0,2 mm
Outer sheath colour: Green similar to RAL 6018 Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 62 Ohm/km 60 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km 0,5 GOhm x km
Loop resistance: 124 Ohm/km max. 120 Ohm/km max.
Mutual capacitance: 52 nF/km nom. 52 nF/km nom.
Test voltage: 2 kV 0,7 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (dB/100m) 6,0 7,6 16,0 21,0
Next (db) 70,0 65,0 55,0 50,0
ACR (db) 64,0 57,4 39,0 29,0

Technical data
Weight: approx. 67 kg/km approx. 61 kg/km
Min. bending radius for laying: 46 mm 50 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,32 MJ/m 0,85 MJ/m
Copper weight: 32,00 kg/km 32,00 kg/km

Norms
Applicable standards: PROFInet Guideline PROFInet Guideline
UL Style: CMG 60C or PLTC or AWM 20201 CMX 75C (shielded)
CSA standard: CSA FT 4 -

Application
This copper data cable, designed especially for heavy-duty industrial applications is very well suited for Ethernet applications. Ir ensures
superiour transmission properties and can be used even under most severe conditions. The lines specified here corresponds the PROFInet
types B and C, i.e. they are designed for flexible and highly flexible applications, such as drag chains.

Part no. 800654, PROFInet type B (SK) 800655, PROFInet type C (SK)
Dimensions and specifications may be changed without prior notice.

R 105
Industrial Ethernet
PROFInet Type C
Torsion

Type Torsional applications


Cable structure 2x2x0,75 mm (stranded)
Inner conductor diameter: Copper, tinned (AWG 22/19)
Core insulation: Foam-skin-PE
Core colours: wh, ye, bu, og
Stranding element: Star quad
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Outer sheath material: PUR
Cable external diameter: approx. 6,5 mm 0,2 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 60 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Loop resistance: 120 Ohm/km max.
Mutual capacitance: 52 nF/km nom.
Test voltage: 0,7 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (db/100m) 7,6 10,0 26,5 41,0
ELFEXT (db) 43,8 39,7 24,0 20,0

Technical data
Weight: approx. 54 kg/km
Min. bending radius for laying: 46 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 0,45 MJ/m
Copper weight: 32,00 kg/km

Norms
Applicable standards: PROFInet Guideline
UL Style: AWM Style 21161 80C

Application
This copper data cable, designed especially for heavy-duty industrial applications is very well suited for Ethernet applications. Ir ensures
superiour transmission properties and can be used even under most severe conditions. The lines specified here corresponds the PROFInet R
types C, i.e. they are designed for torsion applications, such as roboter arms.

Part no. 802186, PROFInet type C (SK)


Dimensions and specifications may be changed without prior notice.

R 106
BUS Cables
Profibus L2
Indoor

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2x0.64 mm 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 7,8 mm 0,2 mm approx. 7,8 mm 0,2 mm
Outer sheath colour: Grey similar to RAL 7001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 110 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 30 nF/km nom. 30 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 2,5 dB/km 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km 38,4 kHz < 4,0 dB/km
4 MHz < 22,0 dB/km 4 MHz < 22,0 dB/km
16 MHz < 42,0 dB/km 16 MHz < 42,0 dB/km

Technical data
Weight: approx. 69 kg/km approx. 69 kg/km
Min. bending radius for laying: 120 mm 120 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,99 MJ/m 0,99 MJ/m
Copper weight: 24,00 kg/km 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMX 75C (shielded) CMX 75C (shielded)
CSA standard: CSA FT1 CSA FT1

Application
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the
information exchange between different automation systems as well as for communication with the connected decentralized field units,
serial field bus systems are used. The types mentioned here are suitable for indoor laying and are equipped with a special PVC sheath.

Part no. 80384, Profibus L2 81448, Profibus L2


Dimensions and specifications may be changed without prior notice.

R 107
BUS Cables
PROFIBUS L2 Outdoor + Industry
Outdoor + Industry

Type Fixed installation, Industrial Area


outdoor
Cable structure 1x2x0.64 mm 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PE PUR
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 8,0 mm 0,4 mm
Outer sheath colour: Black similar to RAL 9005 Petrol similar to RAL 5018

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 110 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 30 nF/km nom. 30 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 2,5 dB/km 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km 38,4 kHz < 4,0 dB/km
4 MHz < 22,0 dB/km 4 MHz < 22,0 dB/km
16 MHz < 42,0 dB/km 16 MHz < 42,0 dB/km

Technical data
Weight: approx. 64 kg/km approx. 67 kg/km
Min. bending radius for laying: 120 mm 120 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 2,26 MJ/m 1,52 MJ/m
Copper weight: 24,00 kg/km 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170

Application
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the
information exchange between different automation systems as well as for communication with the connected decentralized field units,
serial field bus systems are used. The types mentioned here are suitable for outdoor laying (PE sheath) and industry laying (PUR sheath).
R
Part no. 80792, Profibus L2 81186, Profibus L2
Dimensions and specifications may be changed without prior notice.

R 108
BUS Cables
Profibus L2 Direct Burial
without + with Armouring

Type Underground laying Underground laying


Cable structure 1x2x0.64 mm 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE Cell PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC PE
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Armouring: - Steel band
Outer sheath material: PE PE
Cable external diameter: approx. 10,0 mm 0,2 mm approx. 10,6 mm 0,3 mm
Outer sheath colour: Black similar to RAL 9005 Black similar to RAL 9005

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1 GOhm x km 5 GOhm x km
Loop resistance: 114 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 30 nF/km nom. 30 nF/km nom.
Nominal voltage: - 250 V
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 2,5 dB/km 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km 38,4 kHz < 4,0 dB/km
3 MHz < 22,0 dB/km 4 MHz < 22,0 dB/km
20 MHz < 42,0 dB/km 16 MHz < 42,0 dB/km

Technical data
Weight: approx. 92 kg/km approx. 132 kg/km
Min. bending radius for laying: 180 mm 190 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 2,657 MJ/m 2,40 MJ/m
Copper weight: 24,00 kg/km 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170

Application
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the
information exchange between different automation systems as well as for communication with the connected decentralized field units,
serial field bus systems are used. The above mentioned type is suitable for underground installation and is equipped with a special PVC/PE
sheath.

Part no. 82824, Profibus ERD 802177, Profibus L2


Dimensions and specifications may be changed without prior notice.

R 109
BUS Cables
Profibus L2
7-wire

Type Mobile use


Cable structure 1x2x0.64 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/7)
Core insulation: Foam-skin-PE
Core colours: rd, gn
Stranding element: 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Outer sheath material: PVC
Cable external diameter: approx. 7,8 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 %
Conductor resistance, max.: 86,7 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 110 Ohm/km max.
Mutual capacitance: 30 nF/km nom.
Test voltage: 1,5 kV
Attenuation: 9,6 kHz < 3,0 dB/km
38,4 kHz < 5,0 dB/km
4 MHz < 26,0 dB/km
16 MHz < 55,0 dB/km

Technical data
Weight: approx. 75 kg/km
Min. bending radius for laying: 120 mm
Operating temperature range min.: -20C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,20 MJ/m
Copper weight: 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571

Application
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the
information exchange between different automation systems as well as for communication with the connected decentralized field units,
serial field bus systems are used. With his cord design, the type mentioned here is suitable for laying in regular mobile applications and is R
equipped with a special PVC sheath.

Part no. 800648, Profibus L2


Dimensions and specifications may be changed without prior notice.

R 110
BUS Cables
Profibus L2
Drag Chain

Type Drag chain applications Drag chain applications


Cable structure 1x2x0.64 mm (stranded) 1x2x0.64 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/19) Copper, bare (AWG 24/19)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PUR PUR
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 8,0 mm 0,4 mm
Outer sheath colour: Petrol similar to RAL 5018 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 82 Ohm/km 82 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 164 Ohm/km max. 164 Ohm/km max.
Mutual capacitance: 30 nF/km nom. 30 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 3,0 dB/km 9,6 kHz < 3,0 dB/km
38,4 kHz < 5,0 dB/km 38,4 kHz < 5,0 dB/km
4 MHz < 25,0 dB/km 4 MHz < 25,0 dB/km
16 MHz < 52,0 dB/km 16 MHz < 52,0 dB/km

Technical data
Weight: approx. 65 kg/km approx. 65 kg/km
Min. bending radius for laying: 60 mm 60 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +60C +60C
Caloric load, approx. value: 1,52 MJ/m 1,52 MJ/m
Copper weight: 25,00 kg/km 25,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170

Application
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the
information exchange between different automation systems as well as for communication with the connected decentralized field units,
serial field bus systems are used. The above mentioned types are suitable for drag chains (stranded).

Part no. 81003, Profibus L2 80267, Profibus L2


Dimensions and specifications may be changed without prior notice.

R 111
BUS Cables
Profibus
ET200X + ECOFAST

Type Drag chain applications Drag chain applications


Cable structure 1x2x0.65 mm + 1x2x0.65 mm +
3x1x0.75 mm (stranded) 4x1x1.5 mm (stranded)
Inner conductor diameter 1: Copper, bare (AWG 22/19) Copper, bare (AWG 24/19)
Inner conductor diameter 2: Copper, bare (AWG 18/24) Copper, bare (AWG 18/84)
Core insulation 1: Foam-skin-PE Foam-skin-PE
Core insulation 2: PVC TPM
Core colours 1: rd, gn rd, gn
Core colours 2: bk, bu, gnye bk, bk, bk, bk
Stranding element 1: Double core 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: Foil + braid Foil + braid
Total shielding: Polyester foil -
Outer sheath material: PUR TPU
Cable external diameter: approx. 9,5 mm 0,5 mm approx. 11,0 mm 0,3 mm
Outer sheath colour: Petrol similar to RAL 5018 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 15 %
Conductor resistance, max.: 84 Ohm/km 89,9 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 168 Ohm/km max. 179 Ohm/km max.
Mutual capacitance: 30 nF/km nom. 30 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 3,0 dB/Km 9,6 kHz 3,0 dB/km
38,4 kHz < 5,0 dB/Km 38,4 kHz 5,0 dB/km
4 MHz < 25,0 dB/Km 4 MHz 30,0 dB/km
16 MHz < 52,0 dB/Km 16 MHz 60,0 dB/km

Technical data
Weight: approx. 105 kg/km approx. 159 kg/km
Min. bending radius for laying: 140 mm 165 mm
Operating temperature range min.: -5C -20C
Operating temperature range max.: +60C +60C
Caloric load, approx. value: 1,973 MJ/m 2,835 MJ/m
Copper weight: 46,00 kg/km 90,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: AWM Style 20351 UL Style 20233 R
Application
The Profibus-ET200X and Profibus ECOFAST lines used in the area of process automation. These BUS systems are a very economical solution
for the cell and field area. For the information exchange between different automation systems as well as for communication with the
connected decentralized field units, serial field bus systems are used. The series ET200X and DESINA hybrid are characterized by a special
construction with data and power supply in one cable. These types are suited for the application in drag chains and similar mobile applications.

Part no. 82913, Profibus L2 800044, Profibus L2


Dimensions and specifications may be changed without prior notice.

R 112
Bus Cables
Profibus
SHIPLINE and High Temperature

Type Marine and Offshore High temperature areas


Cable structure 1x2x0.75 mm (stranded) 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/7) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE XLPE ray cross-linking
Core colours: rd, gn rd, gn
Stranding element: Double core 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle -
Inner sheath material: FRNC -
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: X-FRNC FEP
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 7,2 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1,6 GOhm x km 1,6 GOhm x km
Loop resistance: 110 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 29 nF/km nom. 28 nF/km nom.
Nominal voltage: 60 V 250 V
Test voltage: 1 kV 3,6 kV
Attenuation: 9,6 kHz < 2,5 dB/Km 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/Km 38,4 kHz < 4,0 dB/km
4 MHz < 22,0 dB/Km 4 MHz < 22,0 dB/km
16 MHz < 42,0 dB/Km 16 MHz < 42,0 dB/km

Technical data
Weight: approx. 84 kg/km approx. 64 kg/km
Min. bending radius for laying: 80 mm 52 mm
Operating temperature range min.: -25C -50C
Operating temperature range max.: +80C +180C
Caloric load, approx. value: 1,26 MJ/m 0,30 MJ/m
Copper weight: 35,00 kg/km 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170

Application
The series SHIPLINE and HIGH TEMPERATURE are used to interconnect Profibus components. For the information exchange between different
automation systems as well as for communication with the connected decentralized field units, serial field bus systems are used. The lines
described here are designed for Marine and Offshore applications or the use in extreme temperature ranges.

Part no. 802178, Profibus SHIPLINE 802179, Profibus high temperature


Dimensions and specifications may be changed without prior notice.

R 113
BUS Cables
DESINA-HYBRID-BUS

Type Hybrid Bus Cable


Cable structure 4x1.5 mm + 2xPOF
Conductor material Copper, bare, KL.6 = extra fine wire
Core insulation: TPM
Polymer optical fibre: 4x POF 980/1000
Core colours: Black
Core identification: Numbers
Total shielding: PETP fleece
Outer sheath material: TPU
Cable external diameter: approx. 8,8 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Conductor resistance, max.: 13,7 Ohm/km
Insulation resistance, min.: 0,5 GOhm x km
Test voltage: 3 kV

Optical characteristic
Fibre attenuation: 230 dB/km max. at 650 nm

Technical data
Weight: approx. 120 kg/km
Min. bending radius for laying: 130 mm
Operating temperature range min.: -20C
Operating temperature range max.: +80C
Copper weight: 60,00 kg/km

Norms
Applicable standards: Detail specification for DESINA

Application
The DESINA Cu/POF hybrid field bus cables combines signal lines made of plastic fibre-optic conductors and copper cables. The use of these
transmission systems significantly reduces the number of different cables in a planned bus installation in machine tools operations. The
main applications of these cables are in mobile applications in machine construction.

Part no. 81713, DESINA HYBRID BUS


Dimensions and specifications may be changed without prior notice.

R 114
BUS Cables
Profibus L2
TORSION + FESTOON

Type Torsional applications Mobile use


Cable structure 1x2x0.80 mm (stranded) 1x2x0.65 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 22/19) Copper, bare (AWG 24/19)
Core insulation: Foam-skin-PE Cell PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + filler 2 cores + 2 fillers stranded together
Shielding 1: - Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PUR PVC
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 8,0 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Petrol similar to RAL 5018

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 49 Ohm/km 66,5 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1,6 GOhm x km
Loop resistance: 98 Ohm/km max. 133 Ohm/km max.
Mutual capacitance: 29 nF/km nom. 28 nF/km nom.
Test voltage: 3,6 kV 2 kV
Attenuation: 9,6 kHz < 3,0 dB/km 9,6 kHz 3,0 dB/km
38,4 kHz < 5,0 dB/km 38,4 kHz 4,0 dB/km
4 MHz < 25,0 dB/km 4 MHz 25,0 dB/km
16 MHz < 51,0 dB/km 16 MHz 49,0 dB/km

Technical data
Weight: approx. 66 kg/km approx. 64 kg/km
Min. bending radius for laying: 100 mm 40 mm
Operating temperature range min.: -25C -40C
Operating temperature range max.: +75C +60C
Caloric load, approx. value: 0,89 MJ/m 1,09 MJ/m
Copper weight: 32,00 kg/km 23,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMX 75C (shielded) CMG 75C or CL2 or AWM 20201 600V
CSA standard: - CSA FT 4

Application
The series TORSION and FESTOON are used to interconnect Profibus BUS components. This BUS system is a very economical solution for the
field area. For the information exchange between different automation systems as well as for communication with the connected decentralized
field units, serial field bus systems are used. The lines described here are designed torsionable or hanging movable construction. Areas such
as robot applications and/or garland suspension are easily realized.

Part no. 800109, Profibus L2 800649, Profibus L2


Dimensions and specifications may be changed without prior notice.

R 115
BUS Cables
Profibus PA

Type Hazardous areas Non-hazardous areas


Cable structure 1x2x1.0/2.55 mm 1x2x1.0/2.55 mm
Inner conductor diameter: Copper, bare (AWG 18/1) Copper, bare (AWG 18/1)
Core insulation: PE PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 7,6 mm 0,2 mm approx. 7,6 mm 0,2 mm
Outer sheath colour: Blue Black

Electrical data
Characteristic impedance: 100 Ohm 20 % 100 Ohm 20 %
Conductor resistance, max.: 22 Ohm/km 22 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 44 Ohm/km max. 44 Ohm/km max.
Mutual capacitance: 55 nF/km nom. 55 nF/km nom.
Nominal voltage: 300 V 300 V
Test voltage: 2,5 kV 2,5 kV
Attenuation: 39 kHz 3,0 dB/km 39 kHz 3,0 dB/km

Technical data
Weight: approx. 76 kg/km approx. 76 kg/km
Min. bending radius for laying: 140 mm 140 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,95 MJ/m 0,95 MJ/m
Copper weight: 44,00 kg/km 44,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571 UL Style 2571

Application
This Profibus PA line is used in the area of process automation, among other things in the chemical industry. This cable is an economical
solution for the cell and field area. For the information exchange between different automation systems as well as for communication with
the connected decentralized field units, serial field bus systems are used. The above mentioned types are suitable for ex (and ATEX/ Class
II, EX-i/ EN 60079-14) and not-ex installation and are equipped with a special PVC-sheath.

Part no. 82835, Profibus PA 82836, Profibus PA


R
Dimensions and specifications may be changed without prior notice.

R 116
Bus Cables
Profibus PA
armoured

Type Hazardous areas Non-hazardous areas


Cable structure 1x2x1.0/2.55 mm 1x2x1.0/2.55 mm
Inner conductor diameter: Copper, bare (AWG 18/1) Copper, bare (AWG 18/1)
Core insulation: PE PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC PVC
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Armouring: Steel band Steel band
Outer sheath material: PVC PVC
Cable external diameter: approx. 10,2 mm 0,2 mm approx. 10,2 mm 0,2 mm
Outer sheath colour: Blue Black

Electrical data
Characteristic impedance: 100 Ohm 15 % 100 Ohm 15 %
Conductor resistance, max.: 22 Ohm/km 22 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 44 Ohm/km max. 44 Ohm/km max.
Mutual capacitance: 55 nF/km nom. 55 nF/km nom.
Nominal voltage: 300 V 300 V
Test voltage: 2,5 kV 2,5 kV
Attenuation: 39 kHz 3,0 dB/km 39 kHz 3,0 dB/km

Technical data
Weight: approx. 170 kg/km approx. 170 kg/km
Min. bending radius for laying: 200 mm 200 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,95 MJ/m 1,95 MJ/m
Copper weight: 45,00 kg/km 45,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170

Application
This Profibus PA line is used in the area of process automation, among other things in the chemical industry. This cable is an economical
solution for the cell and field area. For the information exchange between different automation systems as well as for communication with
the connected decentralized field units, serial field bus systems are used. The above mentioned types are suitable for ex and not-ex installation
where rodent infestation is to be expected and therefore equipped with a metal armouring and a double PVC-sheath.

Part no. 802180, Profibus PA 802181, Profibus PA


Dimensions and specifications may be changed without prior notice.

R 117
BUS Cables
Profibus PA
Long Distance

Type Hazardous areas Non-hazardous areas


Cable structure 1x2x1.6/3.2 mm 1x2x1.6/3.2 mm
Inner conductor diameter: Copper, bare (AWG 16/7) Copper, bare (AWG 16/7)
Core insulation: PE PE
Core colours: rd, gn rd, gn
Stranding element: 2 cores + 2 fillers stranded together 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 9,5 mm 0,5 mm approx. 9,5 mm 0,5 mm
Outer sheath colour: Blue Black

Electrical data
Characteristic impedance: 100 Ohm 20 % 100 Ohm 20 %
Conductor resistance, max.: 24 Ohm/km 24 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 48 Ohm/km max. 48 Ohm/km max.
Mutual capacitance: 60 nF/km nom. 60 nF/km nom.
Nominal voltage: 300 V 300 V
Test voltage: 1 kV 1 kV
Attenuation: 39 kHz 2,7 dB/km 39 kHz 2,7 dB/km

Technical data
Weight: approx. 110 kg/km approx. 110 kg/km
Min. bending radius for laying: 75 mm 75 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,57 MJ/m 1,57 MJ/m
Copper weight: 62,00 kg/km 62,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571 UL Style 2571

Application
This Profibus PA line is used in the area of process automation, among other things in the chemical industry. This cable is an economical
solution for the cell and field area. For the information exchange between different automation systems as well as for communication with
the connected decentralized field units, serial field bus systems are used. The types mentioned here are suitable for ex and not-ex installation
and are equipped with a special PVC-sheath.
R
Part no. 800650, Profibus PA 800715, Profibus PA
Dimensions and specifications may be changed without prior notice.

R 118
BUS Cables
Profibus SK
Indoor + Outdoor

Type Fixed installation, indoor Fixed installation,


outdoor
Cable structure 1x2x0.64 mm 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: Double core Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC PE
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PE
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 8,0 mm 0,4 mm
Outer sheath colour: Violet similar to RAL 4001 Black similar to RAL 9005

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 110 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 35 nF/km nom. 35 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 2,5 dB/km 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km 38,4 kHz < 4,0 dB/km
4,0 MHz < 22,0 dB/km 4 MHz < 22,0 dB/km
16,0 MHz < 42,0 dB/km 16 MHz < 42,0 dB/km

Technical data
Weight: approx. 79 kg/km approx. 65 kg/km
Min. bending radius for laying: 120 mm 120 mm
Operating temperature range min.: -40C -20C
Operating temperature range max.: +80C +70C
Caloric load, approx. value: 1,068 MJ/m 1,451 MJ/m
Copper weight: 24,00 kg/km 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMG 75C or CL3 or AWM 21694 600V -
CSA standard: CSA FT 4 -

Application
The application of these Profibus SK cables are in the cell and field area, just as for conventional types. The great advantage of this new
system is the quick connection of the cable to the respective plugs. This type of processing also avoids errors. The above mentioned types
are suitable for indoor- or outdoor installation and are equipped with a special PVC or PE sheath.

Part no. 81903, Profibus SK 81904, Profibus SK


Dimensions and specifications may be changed without prior notice.

R 119
BUS Cables
Profibus SK
FRNC + Industry

Type Fixed installation, indoor Industrial Area


Cable structure 1x2x0.64 mm 1x2x0.64 mm
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 22/1)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: Double core Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: FRNC PE
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: FRNC PUR
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 8,0 mm 0,4 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 55 Ohm/km 55 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 110 Ohm/km max. 110 Ohm/km max.
Mutual capacitance: 35 nF/km nom. 35 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 2,5 dB/km 9,6 kHz < 2,5 dB/km
38,4 kHz < 4,0 dB/km 38,4 kHz < 4,0 dB/km
4 MHz < 22,0 dB/km 4 MHz < 22,0 dB/km
16 MHz < 42,0 dB/km 16 MHz < 42,0 dB/km

Technical data
Weight: approx. 73 kg/km approx. 71 kg/km
Min. bending radius for laying: 160 mm 120 mm
Operating temperature range min.: -25C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,203 MJ/m 1,574 MJ/m
Copper weight: 24,00 kg/km 24,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CM 750C (shielded) AWM Style 20236 AWM I/II A/B 80C 30V FT1
CSA standard: - CSA FT1

Application
The application of these Profibus SK cables are in the cell and field area, just as for conventional types. The great advantage of this new R
system is the quick connection of the cable to the respective plugs. This type of processing also avoids errors. The types mentioned here
are suitable for indoor laying (special FRNC sheath) and heay industry laying (PUR sheath).

Part no. 81501, Profibus SK 81905, Profibus SK


Dimensions and specifications may be changed without prior notice.

R 120
BUS Cables
Profibus SK
Drag Chain

Type Drag chain applications Drag chain applications


Cable structure 1x2x0.64 mm (stranded) 1x2x0.64 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/19) Copper, bare (AWG 24/19)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: rd, gn rd, gn
Stranding element: Double core Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Inner sheath material: PVC PVC
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PUR PUR
Cable external diameter: approx. 8,0 mm 0,4 mm approx. 8,0 mm 0,4 mm
Outer sheath colour: Petrol similar to RAL 5018 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 Ohm 10 % 150 Ohm 10 %
Conductor resistance, max.: 84 Ohm/km 84 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 168 Ohm/km max. 168 Ohm/km max.
Mutual capacitance: 35 nF/km nom. 35 nF/km nom.
Test voltage: 1,5 kV 1,5 kV
Attenuation: 9,6 kHz < 3,0 dB/km 9,6 kHz < 3,0 dB/km
38,4 kHz < 5,0 dB/km 38,4 kHz < 5,0 dB/km
4 MHz < 25,0 dB/km 4 MHz < 25,0 dB/km
16 MHz < 52,0 dB/km 16 MHz < 52,0 dB/km

Technical data
Weight: approx. 70 kg/km approx. 70 kg/km
Min. bending radius for laying: 60 mm 60 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,53 MJ/m 1,53 MJ/m
Copper weight: 25,00 kg/km 25,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMX 75C (shielded) CMX 75C (shielded)
CSA standard: CSA FT1 CSA FT1

Application
The application of these Profibus SK cables are in the cell and field area, just as for conventional types. The great advantage of this new
system is the quick connection of the cable to the respective plugs. This type of processing also avoids errors. The above mentioned types
are suitable for drag chains (stranded).

Part no. 81906, Profibus SK 801659, Profibus SK


Dimensions and specifications may be changed without prior notice.

R 121
BUS Cables
FOUNDATION Fieldbus
Basic

Type process automation


Cable structure 1x2x1.1/2,55-100 LI
Inner conductor diameter: Copper, bare (AWG 18/7)
Core insulation: PO
Core colours: or, bl
Stranding element: 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Drain wire: yes
Outer sheath material: PVC
Cable external diameter: approx. 8,0 mm 0,3 mm
Outer sheath colour: Orange

Electrical data
Characteristic impedance: 100 Ohm 20 Ohm
Conductor resistance, max.: 22 Ohm/km
Insulation resistance, min.: 5 GOhm x km
Loop resistance: 44 Ohm/km max.
Mutual capacitance: 60 nF/km nom.
Nominal voltage: 300 V
Test voltage: 1,5 kV
Attenuation: 39 kHz 3,4 dB/km

Technical data
Weight: approx. 85 kg/km
Min. bending radius for laying: 80 mm
Operating temperature range min.: -40C
Operating temperature range max.: +80C
Caloric load, approx. value: 1,22 MJ/m
Copper weight: 45,00 kg/km

Norms
Applicable standards: Foundation Fieldbus Spec. FF-816-1.4
UL Style: CMG 75C PLTC FT4
CSA standard: CSA FT 4

Application
The FOUNDATION Fieldbus is an open and neutral fieldbus standard which is primarily oriented on the requirements of process automation.
It is a functionally complete fieldbus solution for areas like temperature transmitters, pressure transmitters or valve actuators. Today we R
distinguish between the specification H1 (31,25 kbit/s) and HSE (100Mbit/s). Branches like the petrochemical, chemical or the food- and
beverage industry see the advantages and use the FOUNDATION fieldbus technology.

Part no. 803354, Foundation Fieldbus Basic


Dimensions and specifications may be changed without prior notice.

R 122
BUS Cables
FOUNDATION Fieldbus
Type A + gnye

Type process automation


Cable structure 1x2x1.1/2,85-100 LI + 1x0,8 gnye
Inner conductor diameter 1: Copper, bare (AWG 18/41)
Inner conductor diameter 2: Copper, bare (AWG 18/41)
Core insulation 1: XLPE ray cross-linking
Core insulation 2: PVC
Core colours 1: bu, bn
Core colours 2: gn/ye
Stranding element 1: Double core
Shielding 1: -
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Drain wire: yes
Outer sheath material: PVC
Cable external diameter: approx. 7,9 mm 0,3 mm
Outer sheath colour: Yellow

Electrical data
Characteristic impedance: 100 Ohm 20 Ohm
Conductor resistance, max.: 24 Ohm/km
Insulation resistance, min.: 2 GOhm x km
Loop resistance: 48 Ohm/km max.
Mutual capacitance: 65 nF/km nom.
Nominal voltage: 300 V
Test voltage: 1,5 kV
Attenuation: 39 kHz 3,4 dB/km

Technical data
Weight: approx. 84 kg/km
Min. bending radius for laying: 60 mm
Operating temperature range min.: -25C
Operating temperature range max.: +105C
Caloric load, approx. value: 1,00 MJ/m
Copper weight: 49,00 kg/km

Norms
Applicable standards: Foundation Fieldbus Spec. FF-816-1.4
UL Style: CMG 105 or CL3 FT4
CSA standard: CSA FT 4

Application
The FOUNDATION Fieldbus is an open and neutral fieldbus standard which is primarily oriented on the requirements of process automation.
It is a functionally complete fieldbus solution for areas like temperature transmitters, pressure transmitters or valve actuators. Today we
distinguish between the specification H1 (31,25 kbit/s) and HSE (100Mbit/s). Branches like the petrochemical, chemical or the food- and
beverage industry see the advantages and use the FOUNDATION fieldbus technology.

Part no. 801191 ,Foundation Fieldbus FF A


Dimensions and specifications may be changed without prior notice.

R 123
BUS Cables
FOUNDATION Fieldbus
Type A armoured

Type process automation


Cable structure 1x2x1.1/2,85-100 LI + 1x0,8 gnye, armoured
Inner conductor diameter 1: Copper, bare (AWG 18/41)
Inner conductor diameter 2: Copper, bare (AWG 18/41)
Core insulation 1: XLPE ray cross-linking
Core insulation 2: PVC
Core colours 1: bu, bn
Core colours 2: gn/ye
Stranding element 1: Double core
Shielding 1: -
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Polyester foil, aluminium-lined
Drain wire: yes
Armouring: Steel shaft
Outer sheath material: PVC
Cable external diameter: approx. 12,3 mm 0,3 mm
Outer sheath colour: Yellow

Electrical data
Characteristic impedance: 100 Ohm 20 Ohm
Conductor resistance, max.: 24 Ohm/km
Insulation resistance, min.: 2 GOhm x km
Loop resistance: 48 Ohm/km max.
Mutual capacitance: 65 nF/km nom.
Nominal voltage: 300 V
Test voltage: 1,5 kV
Attenuation: 39 kHz 3,4 dB/km

Technical data
Weight: approx. 187 kg/km
Min. bending radius for laying: 130 mm
Operating temperature range min.: -25C
Operating temperature range max.: +105C
Caloric load, approx. value: 1,65 MJ/m
Copper weight: 110,00 kg/km

Norms
Applicable standards: Foundation Fieldbus Spec. FF-816-1.4
UL Style: CMG 105C or PLTC FT4 Sun Res
CSA standard: CSA FT 4
R
Application
The FOUNDATION Fieldbus is an open and neutral fieldbus standard which is primarily oriented on the requirements of process automation.
It is a functionally complete fieldbus solution for areas like temperature transmitters, pressure transmitters or valve actuators. Today we
distinguish between the specification H1 (31,25 kbit/s) and HSE (100Mbit/s). Branches like the petrochemical, chemical or the food- and
beverage industry see the advantages and use the FOUNDATION fieldbus technology.

Part no. 801192, Foundation Fieldbus FF A


Dimensions and specifications may be changed without prior notice.

R 124
BUS Cables
FOUNDATION Fieldbus
Type A

Type process automation


Cable structure 1x2x1.1/2,85-100 LI
Inner conductor diameter: Copper, bare (AWG 18/41)
Core insulation: XLPE ray cross-linking
Core colours: bu, bn
Stranding element: Double core
Shielding 1: -
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Drain wire: yes
Outer sheath material: PVC
Cable external diameter: approx. 7,9 mm 0,3 mm
Outer sheath colour: Yellow

Electrical data
Characteristic impedance: 100 Ohm 20 Ohm
Conductor resistance, max.: 24 Ohm/km
Insulation resistance, min.: 2 GOhm x km
Loop resistance: 48 Ohm/km max.
Mutual capacitance: 65 nF/km nom.
Nominal voltage: 300 V
Test voltage: 1,5 kV
Attenuation: 39 kHz 3,4 dB/km

Technical data
Weight: approx. 89 kg/km
Min. bending radius for laying: 60 mm
Operating temperature range min.: -40C
Operating temperature range max.: +105C
Caloric load, approx. value: 1,05 MJ/m
Copper weight: 42,00 kg/km

Norms
Applicable standards: Foundation Fieldbus Spec. FF-816-1.4
UL Style: CMG 105 or CL3 FT4
CSA standard: CSA FT 4

Application
The FOUNDATION Fieldbus is an open and neutral fieldbus standard which is primarily oriented on the requirements of process automation.
It is a functionally complete fieldbus solution for areas like temperature transmitters, pressure transmitters or valve actuators. Today we
distinguish between the specification H1 (31,25 kbit/s) and HSE (100Mbit/s). Branches like the petrochemical, chemical or the food- and
beverage industry see the advantages and use the FOUNDATION fieldbus technology.

Part no. 801193, Foundation Fieldbus FF A


Dimensions and specifications may be changed without prior notice.

R 125
BUS Cables
HMCB200
fixed installed

Type Fixed installation, indoor


Cable structure 2x2x0,22 mm
Inner conductor diameter: Copper, bare (AWG 22/7)
Core insulation: Foam-skin-PE
Core colours: gn, ye, pk, bu
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Outer sheath material: PVC
Cable external diameter: approx. 6,8 mm 0,15 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 87,6 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 175 Ohm/km max.
Mutual capacitance: 50 nF/km nom.
Test voltage: 0,5 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (db/100m) 8,0 10,0 20,0 27,0
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 39,0 34,0 15,0 5,0

Technical data
Weight: approx. 71 kg/km
Min. bending radius for laying: 100 mm
Operating temperature range min.: -20C
Operating temperature range max.: +70C
Caloric load, approx. value: 0,92 MJ/m
Copper weight: 35,00 kg/km

Norms
UL Style: AWM Style 2502 AWM I/II A/B 80C 30V FT1

Application
These signal cables, designed specifically for use in heavy-duty industries, are the ideal solution for MOTION-CONNECT 200, 500 and 800 series
applications. They guarantee superior transmission properties and can be used under the most severe conditions. The cable cited here R
conforms to HMCB200 for fixed installation.

Part no. 802471, HMCB200


Dimensions and specifications may be changed without prior notice.
* Drive Cliq is registered trademark from Siemens AG.

R 126
BUS Cables
HMCB500
Drag Chain

Type Drag chain applications


Cable structure 2x2xAWG26 + 1x2xAWG22
Inner conductor diameter 1: Copper, bare (AWG 26/7)
Inner conductor diameter 2: Copper, bare (AWG 22/7)
Core insulation 1: PO
Core insulation 2: PO
Core colours 1: gn, ye, pk, bu
Core colours 2: rd, bk
Stranding element 1: Double core
Shielding 1: -
Shielding 2: -
Total shielding: Foil + braid
Outer sheath material: PUR
Cable external diameter: approx. 6,9 mm 0,1 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 135 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 270 Ohm/km max.
Mutual capacitance: 50 nF/km nom.
Test voltage: 0,5 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (db/100m) 13,0 16,0 32,0 40,0
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 34,0 28,0 3,0 -8,0

Technical data
Weight: approx. 61 kg/km
Min. bending radius for laying: 70 mm
Operating temperature range min.: -20C
Operating temperature range max.: +60C
Caloric load, approx. value: 0,97 MJ/m
Copper weight: 35,00 kg/km

Norms
UL Style: AWM Style 20236 AWM I/II A/B 80C 30V FT1

Application
These signal cables, designed specifically for use in heavy-duty industries, are the ideal solution for MOTION-CONNECT 200, 500 and 800 series
applications. They guarantee superior transmission properties and can be used under the most severe conditions. The cable cited here
conforms to HMCB500 for highly-flexible applications inside motor drives.

Part no. 802472, HMCB500


Dimensions and specifications may be changed without prior notice.
* Drive Cliq is registered trademark from Siemens AG.

R 127
BUS Cables
HMCB500S
Drag Chain

Type Drag chain applications


Cable structure 2x2xAWG24 + 1x2xAWG22
Inner conductor diameter 1: Copper, bare (AWG 24/7)
Inner conductor diameter 2: Copper, tinned (AWG 22/19)
Core insulation 1: Foam-skin-PE
Core insulation 2: PE
Core colours 1: gn, ye, pk, bu
Core colours 2: rd, bk
Stranding element 1: Double core
Shielding 1: -
Shielding 2: -
Total shielding: Foil + braid
Outer sheath material: PVC
Cable external diameter: approx. 7,0 mm 0,15 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 90 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 180 Ohm/km max.
Mutual capacitance: 50 nF/km nom.
Test voltage: 0,5 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (db/100m) 10,0 12,0 23,0 30,0
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 37,0 36,0 12,0 2,0

Technical data
Weight: approx. 72 kg/km
Min. bending radius for laying: 125 mm
Operating temperature range min.: 0C
Operating temperature range max.: +60C
Caloric load, approx. value: 0,00 MJ/m
Copper weight: 38,00 kg/km

Norms
UL Style: AWM Style 2502 AWM I/II A/B 80C 30V FT1 R
CSA standard: CSA FT1

Application
These signal cables, designed specifically for use in heavy-duty industries, are the ideal solution for MOTION-CONNECT 200, 500 and 800 series
applications. They guarantee superior transmission properties and can be used under the most severe conditions. The cable cited here
conforms to HMCB500 for flexible applications inside motor drives for distances up to 100m.

Part no. 803672, HMCB500S


Dimensions and specifications may be changed without prior notice.
* Drive Cliq is registered trademark from Siemens AG.

R 128
BUS Cables
HMCB800
Drag Chain

Type Drag chain applications


Cable structure 2x2x0,15 mm + 1x2x0,38mm
Inner conductor diameter 1: Copper, bare (AWG 26/19)
Inner conductor diameter 2: Copper, tinned (AWG 22/19)
Core insulation 1: PO
Core insulation 2: PO
Core colours 1: gn, ye, pk, bu
Core colours 2: rd, bk
Stranding element 1: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Foil + braid
Outer sheath material: TPE
Cable external diameter: approx. 7,0 mm 0,15 mm
Outer sheath colour: Green similar to RAL 6018

Electrical data
Characteristic impedance: 100 Ohm 15 ohm at 1 to 100 MHz
Conductor resistance, max.: 135 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 270 Ohm/km max.
Mutual capacitance: 50 nF/km nom.
Test voltage: 0,5 kV

Typical values
Frequency (MHz) 10 16 62,5 100
Attenuation (db/100m) 13,0 16,0 32,0 40,0
Next (db) 47,0 44,0 35,0 32,0
ACR (db) 34,0 28,0 3,0 -8,0

Technical data
Weight: approx. 72 kg/km
Min. bending radius for laying: 105 mm
Operating temperature range min.: -20C
Operating temperature range max.: +60C
Caloric load, approx. value: 0,91 MJ/m
Copper weight: 42,00 kg/km

Norms
UL Style: AWM Style 20236 AWM I/II A/B 80C 30V FT1

Application
These signal cables, designed specifically for use in heavy-duty industries, are the ideal solution for MOTION-CONNECT 200, 500 and 800 series
applications. They guarantee superior transmission properties and can be used under the most severe conditions. The cable cited here
conforms to HMCB800 for highly-flexible applications.

Part no. 802473, HMCB800


Dimensions and specifications may be changed without prior notice.
* Drive Cliq is registered trademark from Siemens AG.

R 129
BUS Cables
USB Bus S

Type Drag chain applications


Cable structure 1x2xAWG28 + 1x2xAWG20
Inner conductor diameter 1: Cu VAG + steel core (AWG 28/19)
Inner conductor diameter 2: Copper, tinned (AWG 20/37)
Core insulation 1: FEP
Core insulation 2: PO
Core colours 1: wh, gn
Core colours 2: rd, bk
Stranding element 1: 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Foil + braid
Outer sheath material: PUR
Cable external diameter: approx. 5,0 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 90 Ohm 15 %
Conductor resistance, max.: 232 Ohm/km
Insulation resistance, min.: 0,1 GOhm x km
Loop resistance: 464 Ohm/km max.
Mutual capacitance: 54 nF/km nom.
Test voltage: 0,5 kV

Typical values
Frequency (MHz) 10 16 62,5 100 200 300 400
Attenuation (db/100m) 12,1 15,4 31,0 39,7 60,2 76,2 99,7

Technical data
Weight: approx. 45 kg/km
Min. bending radius for laying: 50 mm
Operating temperature range min.: -20C
Operating temperature range max.: +60C
Caloric load, approx. value: 0,49 MJ/m
Copper weight: 30,00 kg/km

Norms
Applicable standards: USB-Standard 2.0

Application
These USB cables, designed specifically for use in heavy-duty industries, are the ideal solution for highly-flexible applications such as drag
chains and camera technology. They guarantee superior transmission properties. The cable cited here can be used up to a maximum cable
length of 5m.
R
Part no. 802469, USB S
Dimensions and specifications may be changed without prior notice.

R 130
BUS Cables
USB Bus L

Type Drag chain applications


Cable structure 1x2xAWG24 + 1x2xAWG20
Inner conductor diameter 1: Copper, bare (AWG 24/19)
Inner conductor diameter 2: Copper, tinned (AWG 20/37)
Core insulation 1: PO
Core insulation 2: PO
Core colours 1: wh, gn
Core colours 2: rd, bk
Stranding element 1: 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Foil + braid
Outer sheath material: PUR
Cable external diameter: approx. 5,8 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 90 Ohm 15 %
Conductor resistance, max.: 140 Ohm/km
Insulation resistance, min.: 0,1 GOhm x km
Loop resistance: 280 Ohm/km max.
Mutual capacitance: 50 nF/km nom.
Test voltage: 0,5 kV

Typical values
Frequency (MHz) 10 16 62,5 100 200 300
Attenuation (db/100m) 8,5 10,2 21,3 27,3 41,5 53,3

Technical data
Weight: approx. 56 kg/km
Min. bending radius for laying: 75 mm
Operating temperature range min.: -35C
Operating temperature range max.: +70C
Caloric load, approx. value: 0,57 MJ/m
Copper weight: 34,00 kg/km

Norms
Applicable standards: USB-Standard 2.0

Application
These USB cables, designed specifically for use in heavy-duty industries, are the ideal solution for highly-flexible applications such as drag
chains and camera technology. They guarantee superior transmission properties and can be used even under the most severe conditions.
The cable cited here can be used up to a maximum cable length of 10m.

Part no. 802470, USB L


Dimensions and specifications may be changed without prior notice.

R 131
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2x0.22 mm (stranded) 4x1x0.22 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/7) Copper, bare (AWG 24/7)
Core insulation: Cell PE Cell PE
Core colours: wh/bn wh, bn, gn, ye
Stranding element: Double core Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 5,4 mm 0,2 mm approx. 6,9 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 87 Ohm/km 87 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 174 Ohm/km max. 174 Ohm/km max.
Mutual capacitance: 58 nF/km nom. 58 nF/km nom.
Nominal voltage: 30 V 30 V
Test voltage: 1,5 kV 1,5 kV

Technical data
Weight: approx. 41 kg/km approx. 60 kg/km
Min. bending radius for laying: 81 mm 107 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,574 MJ/m 1,234 MJ/m
Copper weight: 17,00 kg/km 21,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571 UL Style 2571

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 81286, CAN BUS 81287, CAN BUS


Dimensions and specifications may be changed without prior notice. R

R 132
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor


Cable structure 2x2x0.22 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/7)
Core insulation: Cell PE
Core colours: wh/bn, gn/ye
Stranding element: 2 cores + 2 fillers stranded together
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Cu braid, tinned
Outer sheath material: PVC
Cable external diameter: approx. 7,5 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 %
Conductor resistance, max.: 87,6 Ohm/km
Insulation resistance, min.: 5 GOhm x km
Loop resistance: 174 Ohm/km max.
Mutual capacitance: 40 nF/km nom.
Nominal voltage: 30 V
Test voltage: 1,5 kV

Technical data
Weight: approx. 60 kg/km
Min. bending radius for laying: 113 mm
Operating temperature range min.: -25C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,13 MJ/m
Copper weight: 32,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571
CSA standard: CSA FT1

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 82509, CAN BUS


Dimensions and specifications may be changed without prior notice.

R 133
BUS Cables
CAN Bus
fixed installed, 105C

Type Industrial Area


Cable structure 2x2xAWG 24/19mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/19)
Core insulation: XLPE ray cross-linking
Core colours: wh/bn, gn/ye
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Cu braid, tinned
Outer sheath material: PUR
Cable external diameter: approx. 8,4 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 %
Conductor resistance, max.: 87,2 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 84 Ohm/km max.
Mutual capacitance: 42 nF/km nom.
Nominal voltage: 600 V
Test voltage: 2,5 kV

Technical data
Weight: approx. 80 kg/km
Min. bending radius for laying: 126 mm
Operating temperature range min.: -40C
Operating temperature range max.: +105C *
Copper weight: 40,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL/CSA 21223 80C, 600V

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system. Cable
with oil-resistant FRNC sheath and increased temperature resistance for use in the wind turbine and similar sectors. Certified to UL, the
cable can also be used in the USA and Canada.
* = with limited service life
R
Part no. 801982, CAN BUS
Dimensions and specifications may be changed without prior notice.

R 134
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2x0.34 mm (stranded) 4x1x0.34 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 22/7) Copper, bare (AWG 22/7)
Core insulation: Cell PE Cell PE
Core colours: wh/bn wh/bn, gn/ye
Stranding element: Double core Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 6,5 mm 0,2 mm approx. 8,0 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 57,5 Ohm/km 57,5 Ohm/km
Insulation resistance, min.: 5 GOhm x km 5 GOhm x km
Loop resistance: 115 Ohm/km max. 115 Ohm/km max.
Mutual capacitance: 40 nF/km nom. 40 nF/km nom.
Nominal voltage: 30 V 30 V
Test voltage: 2 kV 2 kV

Technical data
Weight: approx. 54 kg/km approx. 77 kg/km
Min. bending radius for laying: 98 mm 120 mm
Operating temperature range min.: -25C -25C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,109 MJ/m 1,179 MJ/m
Copper weight: 23,00 kg/km 30,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571 UL Style 2571

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 801572, CAN BUS 801573, CAN BUS


Dimensions and specifications may be changed without prior notice.

R 135
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor


Cable structure 2x2x0.34 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 22/7)
Core insulation: Foam-skin-PE
Core colours: wh/bn, gn/ye
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Cu braid, tinned
Outer sheath material: PVC
Cable external diameter: approx. 8,5 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 %
Conductor resistance, max.: 55,4 Ohm/km
Insulation resistance, min.: 5 GOhm x km
Loop resistance: 110 Ohm/km max.
Mutual capacitance: 40 nF/km nom.
Nominal voltage: 250 V
Test voltage: 1,5 kV

Technical data
Weight: approx. 85 kg/km
Min. bending radius for laying: 130 mm
Operating temperature range min.: -40C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,32 MJ/m
Copper weight: 46,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMX 75C (shielded)
CSA standard: CSA FT1

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 803344, CAN BUS R


Dimensions and specifications may be changed without prior notice.

R 136
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2x0.50 mm (stranded) 4x1x0.50 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 20/7) Copper, bare (AWG 20/7)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: wh/bn wh, bn, gn, ye
Stranding element: Double core Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 7,0 mm 0,2 mm approx. 8,5 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 37 Ohm/km 37 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 74 Ohm/km max. 74 Ohm/km max.
Mutual capacitance: 50 nF/km nom. 65 nF/km nom.
Test voltage: 1,5 kV 1,5 kV

Technical data
Weight: approx. 69 kg/km approx. 100 kg/km
Min. bending radius for laying: 105 mm 128 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,09 MJ/m 1,64 MJ/m
Copper weight: 30,00 kg/km 45,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571 UL Style 2571

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 800571, CAN BUS 800685, CAN BUS


Dimensions and specifications may be changed without prior notice.

R 137
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor


Cable structure 2x2x0.50 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 20/7)
Core insulation: Foam-skin-PE
Core colours: wh/bn, gn/ye
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Cu braid, tinned
Outer sheath material: PVC
Cable external diameter: approx. 9,5 mm 0,2 mm
Outer sheath colour: Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 %
Conductor resistance, max.: 34,4 Ohm/km
Insulation resistance, min.: 5 GOhm x km
Loop resistance: 68 Ohm/km max.
Mutual capacitance: 40 nF/km nom.
Nominal voltage: 250 V
Test voltage: 1,5 kV

Technical data
Weight: approx. 116 kg/km
Min. bending radius for laying: 150 mm
Operating temperature range min.: -40C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,62 MJ/m
Copper weight: 60,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMX 75C (shielded)
CSA standard: CSA FT1

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 803722, CAN BUS R


Dimensions and specifications may be changed without prior notice.

R 138
BUS Cables
CAN Bus
fixed installed

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2x0.75 mm (stranded) 4x1x0.75 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 18/19) Copper, bare (AWG 18/19)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: wh/bn wh/bn, gn/ye
Stranding element: Double core Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PVC PVC
Cable external diameter: approx. 8,7 mm 0,3 mm approx. 8,8 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 15 % 120 Ohm 15 %
Conductor resistance, max.: 27,5 Ohm/km 27,5 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 55 Ohm/km max. 55 Ohm/km max.
Mutual capacitance: 42 nF/km nom. 42 nF/km nom.
Nominal voltage: 300 V 300 V
Test voltage: 1,5 kV 1,5 kV

Technical data
Weight: approx. 101 kg/km approx. 112 kg/km
Min. bending radius for laying: 110 mm 120 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,67 MJ/m 1,76 MJ/m
Copper weight: 40,00 kg/km 58,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: UL Style 2571 UL Style 2571
CSA standard: CSA FT1 CSA FT1

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The above mentioned types are suitable for fixed laying in indoor applications. This is also a very economical solution of a BUS system.

Part no. 803383, CAN BUS 803384, CAN BUS


Dimensions and specifications may be changed without prior notice.

R 139
BUS Cables
CAN Bus
Drag Chain

Type Drag chain applications Drag chain applications


Cable structure 1x2x0.25 mm (stranded) 4x1x0.25 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 24/19) Copper, bare (AWG 24/19)
Core insulation: PE PE
Core colours: wh/bn wh, bn, gn, ye
Stranding element: Double core Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PUR PUR
Cable external diameter: approx. 6,2 mm 0,3 mm approx. 6,5 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 85 Ohm/km 85 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 170 Ohm/km max. 170 Ohm/km max.
Mutual capacitance: 50 nF/km nom. 50 nF/km nom.
Test voltage: 1,5 kV 1,5 kV

Technical data
Weight: approx. 40 kg/km approx. 45 kg/km
Min. bending radius for laying: 90 mm 95 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,798 MJ/m 0,943 MJ/m
Copper weight: 18,00 kg/km 25,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The lines specified here are designed for highly flexible applications. This is also a very economical solution of a BUS system.

Part no. 81911, CAN BUS, highly flexible 81912, CAN BUS, highly flexible
Dimensions and specifications may be changed without prior notice.

R 140
Bus Cables
CAN Bus
Drag Chain, UL

Type Drag chain applications Drag chain applications


Cable structure 1x2x0.34 mm (stranded) 4x1x0.34 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 22/43) Copper, bare (AWG 22/43)
Core insulation: Foam-skin-PE Foam-skin-PE
Core colours: wh/bn wh/bn, gn/ye
Stranding element: 2 cores + 2 fillers stranded together Star quad
Shielding 1: - -
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: PUR PUR
Cable external diameter: approx. 6,9 mm 0,3 mm approx. 7,5 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 15 % 120 Ohm 15 %
Conductor resistance, max.: 56 Ohm/km 56 Ohm/km
Insulation resistance, min.: 5 GOhm x km 5 GOhm x km
Loop resistance: 170 Ohm/km max. 170 Ohm/km max.
Mutual capacitance: 40 nF/km nom. 40 nF/km nom.
Nominal voltage: 250 V 250 V
Test voltage: 1,5 kV 1,5 kV

Technical data
Weight: approx. 54 kg/km approx. 64 kg/km
Min. bending radius for laying: 70 mm 75 mm
Operating temperature range min.: -30C -30C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,20 MJ/m 1,20 MJ/m
Copper weight: 30,00 kg/km 42,00 kg/km

Norms
Applicable standards: Profibus acc. to DIN 19245 T3 and EN50170 Profibus acc. to DIN 19245 T3 and EN50170
UL Style: CMX 444 CMX 444

Application
The CAN bus series (control area network) is a variable field bus system. In the area of automation technology, complex controllers and
control units are networked. Industries, such as the textile or construction machine industry and the medical technology, use this series.
The lines specified here are designed for highly flexible applications where also a UL Certificate is required.

Part no. 802182, CAN BUS, highly flexible 802339, CAN BUS, highly flexible
Dimensions and specifications may be changed without prior notice.

R 141
BUS Cables
I-BUS
fixed installed

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 3x2x0.22 mm 3x2x0.22 mm +
3x1.0 mm
Inner conductor diameter: Copper, bare (AWG 24/7) Copper, bare (AWG 24/7)
Inner conductor diameter 2: - Copper, bare (AWG 17/56)
Core insulation: PE PE
Core insulation 2: - PE
Core colours: wh/bn, gn/rd, ye/gn wh/bn, gn/rd, ye/gn
Core colours 2: - bu, rd, gnye
Stranding element: Double core Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, bare Cu braid, bare
Outer sheath material: PVC PVC
Cable external diameter: approx. 7,0 mm 0,3 mm approx. 8,0 mm 0,3 mm
Outer sheath colour: Pastel turquoise similar to RAL 6034 Pastel turquoise similar to RAL 6034

Electrical data
Characteristic impedance: 100 Ohm 15 Ohm 100 Ohm 15 Ohm
Conductor resistance, max.: 96 Ohm/km 96 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 192 Ohm/km max. 192 Ohm/km max.
Mutual capacitance: 60 nF/km nom. 60 nF/km nom.
Test voltage: 1 kV 1 kV
Attenuation: 256 kHz < 1,5 dB/100m 256 kHz < 3,0 dB/100m
772 kHz < 2,4 dB/100m 772 kHz < 4,8 dB/100m
1 MHz < 2,7 dB/100m 1 MHz < 5,2 dB/100m
4 MHz < 5,2 dB/100m 4 MHz < 10,4 dB/100m
10 MHz < 8,4 dB/100m 10 MHz < 16,8 dB/100m
16 MHz < 11,2 dB/100m 16 MHz < 22,4 dB/100m
20 MHz < 11,9 dB/100m 20 MHz < 23,8 dB/100m

Technical data
Weight: approx. 70 kg/km approx. 96 kg/km
Min. bending radius for laying: 110 mm 120 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 1,20 MJ/m 1,31 MJ/m
Copper weight: 35,00 kg/km 68,00 kg/km

Norms R
Applicable standards: interbus specification 2.0, IEC61158 interbus specification 2.0, IEC61158
UL Style: UL Style 2571 UL Style 2571

Application
Interbus-S is an inexpensive way to network sensors and actuators with all standard automation instruments. The twisted two-core conductor
is used as a standard transfer medium. This bus system replaces the expensive parallel cabling for the different signal types in the lower
levels of automation technique and combines the cables in a single bus cable. Interbus components are connected with this long-distance
BUS cable.

Part no. 80778, I-BUS 81202, I-BUS


Dimensions and specifications may be changed without prior notice.

R 142
BUS Cables
I-BUS
fixed installed, halogenfree

Type Fixed installation, indoor


Cable structure 3x2x0.22 mm
Inner conductor diameter: Copper, bare (AWG 24/7)
Core insulation: PE
Core colours: wh/bn, gn/rd, ye/gn
Stranding element: Double core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, bare
Outer sheath material: PE
Cable external diameter: approx. 7,0 mm 0,3 mm
Outer sheath colour: Pastel turquoise similar to RAL 6034

Electrical data
Characteristic impedance: 100 Ohm 15 Ohm
Conductor resistance, max.: 96 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 192 Ohm/km max.
Mutual capacitance: 50 nF/km nom.
Test voltage: 1 kV
Attenuation: 256 kHz < 1,5 dB/100m
772 kHz < 2,4 dB/100m
1 MHz < 2,7 dB/100m
4 MHz < 5,2 dB/100m
10 MHz < 8,4 dB/100m
16 MHz < 11,2 dB/100m
20 MHz < 11,9 dB/100m

Technical data
Weight: approx. 67 kg/km
Min. bending radius for laying: 110 mm
Operating temperature range min.: -25C
Operating temperature range max.: +60C
Caloric load, approx. value: 1,10 MJ/m
Copper weight: 35,00 kg/km

Norms
Applicable standards: interbus specification 2.0, IEC61158

Application
Interbus-S is an inexpensive way to network sensors and actuators with all standard automation instruments. The twisted two-core conductor
is used as a standard transfer medium. This bus system replaces the expensive parallel cabling for the different signal types in the lower
levels of automation technique and combines the cables in a single bus cable. Interbus components are connected with this long-distance
BUS cable. The cable with halogenfree jacket is used for outdoor applications and in the food-industry.

Part no. 81557, I-BUS


Dimensions and specifications may be changed without prior notice.

R 143
BUS Cables
I-BUS
Drag Chain

Type Drag chain applications Drag chain applications


Cable structure 3x2x0.25 mm 3x2x0.25 mm +
3x1.0 mm
Inner conductor diameter: Copper, bare (AWG 24/19) Copper, bare (AWG 24/19)
Inner conductor diameter 2: - Copper, bare (AWG 17/65)
Core insulation: PE PE
Core insulation 2: - PE
Core colours: wh/bn, gn/rd, ye/gn wh/bn, gn/rd, ye/gn
Core colours 2: - bu, rd, gnye
Stranding element: Double core Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, bare Cu braid, tinned
Outer sheath material: PUR PUR
Cable external diameter: approx. 7,6 mm 0,3 mm approx. 8,6 mm 0,3 mm
Outer sheath colour: Pastel turquoise similar to RAL 6034 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 100 Ohm 15 Ohm 100 Ohm 15 Ohm
Conductor resistance, max.: 96 Ohm/km 96 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 192 Ohm/km max. 192 Ohm/km max.
Mutual capacitance: 60 nF/km nom. 60 nF/km nom.
Test voltage: 1 kV 1 kV
Attenuation: 256 kHz < 1,5 dB/100m 256 kHz < 3,0 dB/100m
772 kHz < 2,4 dB/100m 772 kHz < 4,8 dB/100m
1 MHz < 2,7 dB/100m 1 MHz < 5,2 dB/100m
4 MHz < 5,2 dB/100m 4 MHz < 10,4 dB/100m
10 MHz < 8,4 dB/100m 10 MHz < 16,8 dB/100m
16 MHz < 11,2 dB/100m 16 MHz < 22,4 dB/100m
20 MHz < 11,9 dB/100m 20 MHz < 23,8 dB/100m

Technical data
Weight: approx. 63 kg/km approx. 92 kg/km
Min. bending radius for laying: 90 mm 100 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,937 MJ/m 1,227 MJ/m
Copper weight: 36,00 kg/km 70,00 kg/km

Norms R
Applicable standards: interbus specification 2.0, IEC61158 interbus specification 2.0, IEC61158

Application
Interbus-S is an inexpensive way to network sensors and actuators with all standard automation instruments. The twisted two-core conductor
is used as a standard transfer medium. This bus system replaces the expensive parallel cabling for the different signal types in the lower
levels of automation technique and combines the cables in a single bus cable. Interbus components are connected with this long-distance
BUS cable. The above mentioned types are suitable for drag chain application.

Part no. 81203, I-BUS 82696, I-BUS


Dimensions and specifications may be changed without prior notice.

R 144
BUS-Cables
Multibus I, high exible

Type Multibus I, 15 cores high exible


Cable structure
Probus: 1 x 2 x AWG 22 mm2 (Foam-Skin PO/rd/gn)
DeviceNetTM: 2 x 2 x AWG 22 mm2 (Foam-Skin PO/wh/bn, ye/gn)
Interbus: 2 x 2 x 0,25 (Foam-Skin PO/ gn/pk, ye/gn)
Power cores: 4 x 1 x 1,0 mm2 (PO/rd, bl, bu, bn)
Protective earth core: 1,0 mm2 (PO/gnye)
Stranding: Single cores totaly stranded together and lled with plastic elements
Total shielding: PP vlies
Outer sheath material: PUR, halogenfree
Cable external diameter: app. 14,7 mm
Outer sheath colour: violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 + -15 Ohm (Probus)
120 + -12 Ohm (DeviceNetTM)
100 + -15 Ohm (Interbus)
Conductor resistance: <= 20 Ohm/km (power cores + protection core)
<= 70 Ohm/km (Probus)
<= 70 Ohm/km (DeviceNetTM)
<= 80 Ohm/km (Interbus)
Insulation resistance: >= 500 Mohm x km (at 20 C)
Mutual capacitance: 30 pF/m nominal (Probus)
40 pF/m nominal (DeviceNetTM)
50 pF/m nominal (Interbus)
Testvoltage: 2500 V (core/ core)
1500 V (core/ screen)

Mechanical data
Bending radius single: <= 70 mm
Bending radius repeated: <= 110 mm
Tensile strength static: 300 N
Tensile strength dynamic: 140 N
Oil resistance: Diesel, Biodiesel, ASTM-l 1, ASTM-l 2, Vitam EHF, Biohydran
Flame resistance: HD 405.1, IEC 60332-1, VW1/ FT1 acc. C-UL
FCKW free: yes
Self extinguishable: yes
Other attributes: PVC free, free of lacquer wetting disturbing substances, siliconfree,
resistant against PVC exibiliser and cable fat RB1

Thermal attributes
Operating temperature range: - 40 C to + 80 C
Laying temperature range: - 30 C to + 80 C

Norms Probus standard, DeviceNetTM standard, Interbus standard

UL-Style VW1/ FT1 acc. C-UL

Application Drag chains, torsion applications (according HELU specikation)

Part no. 801652, Multibus I, 15 cores

R 145
BUS-Cables
Multibus II, high exible

Type Multibus II, 15 cores high exible


Cable structure
Probus: 1 x 2 x 0,34 mm2 (Foam-Skin PO/rd/gn)
DeviceNetTM: 4 x 2 x 0,34 mm2 (Foam-Skin PE/ye, or, wh, bu-ye, or, wh, bu)
Power cores 1: 2 x 1,0 mm2 (PO/rd, bl)
Power cores 2: 2 x 1,5 mm2 (PO/bu, bn)
Protective earth core: 1,5 mm2 (PO/gnye)
Stranding: Single cores totaly stranded together and lled with plastic elements
Total shielding: PP vlies
Outer sheath material: PUR, halogenfree
Cable external diameter: app. 15,0 mm
Outer sheath colour: violet similar to RAL 4001

Electrical data
Characteristic impedance: 150 + -15 Ohm (Probus)
100 + -15 Ohm (PROFInet)
Conductor resistance: <= 20 Ohm/km (power cores + protection core)
<= 70 Ohm/km (Probus)
<= 62 Ohm/km (PROFInet)
Insulation resistance: >= 500 Mohm x km (at 20 C)
Mutual capacitance: 30 pF/m nominal (Probus)
40 pF/m nominal (PROFInet)
Testvoltage: 2500 V (core/ core)
1500 V (core/ screen)

Mechanical data
Bending radius single: <= 70 mm
Bending radius repeated: <= 110 mm
Tensile strength static: 300 N
Tensile strength dynamic: 140 N
Oil resistance: Diesel, Biodiesel, ASTM-l 1, ASTM-l 2, Vitam EHF, Biohydran
Flame resistance: HD 405.1, IEC 60332-1, VW1/ FT1 acc. C-UL
FCKW free: yes
Self extinguishable: yes
Other attributes: PVC free, free of lacquer wetting disturbing substances, siliconfree,
resistant against PVC exibiliser and cable fat RB1
R
Thermal attributes
Operating temperature range: - 40 C to + 80 C
Laying temperature range: - 20 C to + 80 C

Norms Probus standard, PROFInet standard


UL-Style VW1/ FT1 acc. C-UL
Application Drag chains, torsion applications (according HELU specication)
Part no. 804115, Multibus II, 15 cores

R 146
BUS Cables
A-BUS
EPDM

Type Actuator Sensor Interface Actuator Sensor Interface


Cable structure 2x1.5 mm 2x1.5 mm
Inner conductor: Copper, tinned Copper, tinned
Core insulation: Rubber compound Rubber compound
Core colours: bu, bn bu, bn
Shielding 1: - -
Shielding 2: - -
Total shielding: - -
Outer sheath material: EPDM EPDM
Outer sheath colour: Yellow similar to RAL 1023 Black similar to RAL 9005

Electrical data
Conductor resistance, max.: 13,7 Ohm/km 13,7 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 27 Ohm/km max. 27 Ohm/km max.
Nominal voltage: 32 V 48 V
Test voltage: 1 kV at 15 min. 1 kV at 15 min.

Technical data
Weight: approx. 70 kg/km approx. 70 kg/km
Min. bending radius for laying: 30 mm 30 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +85C +85C
Caloric load, approx. value: 0,975 MJ/m 0,975 MJ/m
Copper weight: 31,00 kg/km 31,00 kg/km

Norms
Applicable standards: ASI standard ASI standard

Application
AS components are interconnected with this special system cable. With the AS interface, the cable assembly from the control system to the
sensor/actuator is not needed. The AS interface is the field bus system that transmitts both data and power in one single cable. With fast
contacting in penetration technique, the possibility of errors in cabling is largely reduced. The special outer jacket provides protection against
bio-oil, grease, and refrigerant lubricants, and the cable is therefore even suitable for applications in wet surroundings, in machinery and
plant construction, as well as in the machine tool and automotive industry.

Part no. 80824, A-BUS EPDM 80825, A-BUS EPDM


Dimensions and specifications may be changed without prior notice.

R 147
BUS Cables
A-BUS
PUR, UL/CSA

Type Actuator Sensor Interface Actuator Sensor Interface


Cable structure 2x1.5 mm 2x1.5 mm
Inner conductor: Copper, tinned Copper, tinned
Core insulation: PO PO
Core colours: bu, bn bu, bn
Shielding 1: - -
Shielding 2: - -
Total shielding: - -
Outer sheath material: PUR PUR
Outer sheath colour: Yellow similar to RAL 1023 Black similar to RAL 9005

Electrical data
Conductor resistance, max.: 13,7 Ohm/km 13,7 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 27 Ohm/km max. 27 Ohm/km max.
Nominal voltage: 32 V 48 V
Test voltage: 1 kV at 15 min. 1 kV at 15 min.

Technical data
Weight: approx. 64 kg/km approx. 64 kg/km
Min. bending radius for laying: 30 mm 30 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +80C +80C
Caloric load, approx. value: 0,965 MJ/m 0,965 MJ/m
Copper weight: 31,00 kg/km 31,00 kg/km

Norms
Applicable standards: ASI standard ASI standard
UL Style: AWM Style 20549/10493 AWM Style 20549/10493
CSA standard: CSA FT2 CSA FT2

Application
AS components are interconnected with this special system cable. With the AS interface, the cable assembly from the control system to the
sensor/actuator is not needed. The AS interface is the field bus system that transmitts both data and power in one single cable. With fast
contacting in penetration technique, the possibility of errors in cabling is largely reduced. The special outer jacket provides protection against
oil, grease, and refrigerant lubricants, and the cable is therefore even suitable for applications in wet surroundings, in machinery and plant
construction, as well as in the machine tool and automotive industry. The PUR variant is suitable for heavy-duty industrial environments.
These types are certified for the American market (UL 1581, FT2) through the use of special materials.

Part no. 82434, A-BUS PUR 82822, A-BUS PUR


Dimensions and specifications may be changed without prior notice. R

R 148
BUS Cables
A-BUS
TPE

Type Actuator Sensor Interface Mobile use


Cable structure 2x1.5 mm 2x1.5 mm
Inner conductor: Copper, tinned Copper, tinned
Core insulation: TPE TPE
Core colours: bu, bn bu, bn
Shielding 1: - -
Shielding 2: - -
Total shielding: - -
Outer sheath material: TPE TPE
Outer sheath colour: Yellow Black

Electrical data
Conductor resistance, max.: 13,7 Ohm/km 13,7 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 27 Ohm/km max. 27 Ohm/km max.
Nominal voltage: 32 V 32 V
Test voltage: 1,5 kV at 15 min. 1,5 kV at 15 min.

Technical data
Weight: approx. 70 kg/km approx. 70 kg/km
Min. bending radius for laying: 24 mm 24 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +105C +105C
Caloric load, approx. value: 1,10 MJ/m 1,10 MJ/m
Copper weight: 31,00 kg/km 31,00 kg/km

Norms
Applicable standards: ASI standard ASI standard

Application
AS components are interconnected with this special system cable. With the AS interface, the cable assembly from the control system to the
sensor/actuator is not needed. The AS interface is the field bus system that transmitts both data and power in one single cable. With fast
contacting in penetration technique, the possibility of errors in cabling is largely reduced. The special outer jacket provides protection against
many oils, grease, and refrigerant lubricants, and the cable is therefore even suitable for applications in wet surroundings, in machinery and
plant construction, as well as in the machine tool and automotive industry.

Part no. 801846, A-BUS TPE 801847, A-BUS TPE


Dimensions and specifications may be changed without prior notice.

R 149
BUS Cables
A-BUS
TPE, UL/CSA

Type Actuator Sensor Interface Mobile use


Cable structure 2x1.5 mm 2x1.5 mm
Inner conductor: Copper, tinned Copper, tinned
Core insulation: TPE TPE
Core colours: bu, bn bu, bn
Shielding 1: - -
Shielding 2: - -
Total shielding: - -
Outer sheath material: TPE TPE
Outer sheath colour: Yellow Black

Electrical data
Conductor resistance, max.: 13,7 Ohm/km 13,7 Ohm/km
Insulation resistance, min.: 1 GOhm x km 1 GOhm x km
Loop resistance: 27 Ohm/km max. 27 Ohm/km max.
Nominal voltage: 32 V 48 V
Test voltage: 1,5 kV at 15 min. 1,5 kV at 15 min.

Technical data
Weight: approx. 70 kg/km approx. 70 kg/km
Min. bending radius for laying: 24 mm 24 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +105C +105C
Caloric load, approx. value: 1,10 MJ/m 1,10 MJ/m
Copper weight: 31,00 kg/km 31,00 kg/km

Norms
Applicable standards: ASI standard ASI standard
UL Style: 21439 nach UL 758 21439 nach UL 758
CSA standard: CSA FT2 CSA FT2

Application
AS components are interconnected with this special system cable. With the AS interface, the cable assembly from the control system to the
sensor/actuator is not needed. The AS interface is the field bus system that transmitts both data and power in one single cable. With fast
contacting in penetration technique, the possibility of errors in cabling is largely reduced. The special outer jacket provides protection against
many oils, grease, and refrigerant lubricants, and the cable is therefore even suitable for applications in wet surroundings, in machinery and
plant construction, as well as in the machine tool and automotive industry. These variations are certified for the American market (UL 1581,
FT2) through the use of special materials.

Part no. 801954, A-BUS UL 801955, A-BUS UL


Dimensions and specifications may be changed without prior notice. R

R 150
BUS Cables
AS-Interface
Electrical Cabinet FLIH

Type Fixed installation, indoor


Cable structure 2x0,86/ 2,5
Inner conductor: Copper, tinned
Shielding 1: -
Shielding 2: -
Total shielding: -
Outer sheath material: FRNC
Outer sheath colour: Yellow

Electrical data
Characteristic impedance: 105 Ohm 35 Ohm
Conductor resistance, max.: 23 Ohm/km
Insulation resistance, min.: 0,01 GOhm x km
Loop resistance: 46 Ohm/km max.
Nominal voltage: 300 V
Test voltage: 2 kV at 15 min.

Technical data
Weight: approx. 24 kg/km
Min. bending radius for laying: 15 mm
Operating temperature range min.: -25C
Operating temperature range max.: +70C
Caloric load, approx. value: 0,30 MJ/m
Copper weight: 20,00 kg/km

Norms
Applicable standards: ASI standard
UL Style: UL-Style 2440 (80C/300V)

Application
AS components are interconnected with this special system cable. With the AS interface, the cable assembly from the control system to the
sensor/actuator is not needed. The AS interface is the field bus system that transmitts both data and power in one single cable. With fast
contacting in penetration technique, the possibility of errors in cabling is largely reduced. This type is especially constructed for cabling
inside electrical cabinets.

Part no. 802183, AS-Interface FLIH


Dimensions and specifications may be changed without prior notice.

R 151
BUS Cables
SENSOR-AKTOR
TPM

Type Sensor Actuator Cable


Cable structure 4x0.34 mm
Inner conductor diameter: Copper, bare (AWG 22/43)
Core insulation: PP
Core colours: wh, bu, bk, bn
Stranding element: Star quad
Shielding 1: -
Shielding 2: PETP fleece
Total shielding: -
Outer sheath material: TPM
Cable external diameter: approx. 4,7 mm 0,2 mm
Outer sheath colour: Black

Electrical data
Conductor resistance, max.: 60 Ohm/km
Insulation resistance, min.: 1 GOhm x km
Loop resistance: 120 Ohm/km max.
Test voltage: 1,5 kV

Technical data
Weight: approx. 29 kg/km
Min. bending radius for laying: 75 mm
Operating temperature range min.: -25C
Operating temperature range max.: +60C
Caloric load, approx. value: 0,505 MJ/m
Copper weight: 15,00 kg/km

Norms
UL Style: AWM Style 21198/ 1049

Application
All Sensors and actuators (such as proximity switches, magnet valves) in a field are installed with these special cables, whereby particular
attention is paid to the corrosive environmental conditions. Due to the decentralisation of control and electro-technical function groups,
connected directly to the components in the field, significant savings potentials are realized. The main applications of these cables are in
machine construction.

Part no. 81712, sensor actuator


Dimensions and specifications may be changed without prior notice.

R 152
BUS Cables
DeviceNet
PVC

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2xAWG18 + 1x2xAWG24 +
1x2xAWG15 1x2xAWG22
Inner conductor diameter 1: Copper, tinned (AWG 18/19) Copper, tinned (AWG 24/19)
Inner conductor diameter 2: Copper, tinned (AWG 15/19) Copper, tinned (AWG 22/19)
Core insulation 1: Foam-skin-PE Foam-skin-PE
Core insulation 2: PVC PVC
Core colours 1: light bu, wh light bu, wh
Core colours 2: rd, bk rd, bk
Stranding element 1: Double core Double core
Shielding 1: - -
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Copper shifting, tinned
Drain wire: yes yes
Outer sheath material: PVC PVC
Cable external diameter: approx. 12,2 mm 0,3 mm approx. 6,9 mm 0,3 mm
Outer sheath colour: Grey Grey

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 22,6 Ohm/km 90 Ohm/km
Insulation resistance, min.: 0,2 GOhm x km 0,2 GOhm x km
Loop resistance: 45 Ohm/km max. 180 Ohm/km max.
Mutual capacitance: 39,8 nF/km nom. 39,8 nF/km nom.
Test voltage: 2 kV 2 kV
Attenuation: 125 kHz < 0,42 dB/100m 125 kHz < 0.95 dB/100m
500 kHz < 0,81 dB/100m 500 kHz < 1.64 dB/100m

Technical data
Weight: approx. 192 kg/km approx. 67 kg/km
Min. bending radius for laying: 190 mm 110 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +80C +80C
Caloric load, approx. value: 2,92 MJ/m 0,91 MJ/m
Copper weight: 85,00 kg/km 35,00 kg/km

Norms
Applicable standards: ODVA DeviceNet ODVA DeviceNet
UL Style: CMG 75C PLTC FT4 CMG 75C PLTC FT4
CSA standard: CEC: CMG FT4 CSA FT 4

Application
DeviceNet is a bus system developed by Allen Bradley (Rockwell Automation). These cables are used to interconnect various industrial
devices, such as SPS controls or limit switches. The special characteristic of this bus system is that a data pair and a power supply pair are
integrated in one cable. These cables with PVC sheath are designed for fixed installation.

Part no. 800683, DeviceNet PVC 800684, DeviceNet PVC


Dimensions and specifications may be changed without prior notice.

R 153
BUS Cables
DeviceNet
FRNC

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2xAWG18 + 1x2xAWG24 +
1x2xAWG15 1x2xAWG22
Inner conductor diameter 1: Copper, tinned (AWG 18/19) Copper, tinned (AWG 24/19)
Inner conductor diameter 2: Copper, tinned (AWG 15/19) Copper, tinned (AWG 22/19)
Core insulation 1: Cell PE Cell PE
Core insulation 2: Cell PE Cell PE
Core colours 1: light bu, wh light bu, wh
Core colours 2: rd, bk rd, bk
Stranding element 1: Double core Double core
Shielding 1: - -
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Drain wire: yes yes
Outer sheath material: FRNC FRNC
Cable external diameter: approx. 12,2 mm 0,3 mm approx. 6,9 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 22,6 Ohm/km 90 Ohm/km
Insulation resistance, min.: 0,2 GOhm x km 0,2 GOhm x km
Loop resistance: 45 Ohm/km max. 180 Ohm/km max.
Mutual capacitance: 39 nF/km nom. 39,8 nF/km nom.
Test voltage: 2 kV 2 kV
Attenuation: 125 kHz < 0.42 dB/100m 125 kHz < 0.95 dB/100m
500 kHz < 0.81 dB/100m 500 kHz < 1.64 dB/100m

Technical data
Weight: approx. 195 kg/km approx. 70 kg/km
Min. bending radius for laying: 190 mm 110 mm
Operating temperature range min.: -25C -25C
Operating temperature range max.: +80C +80C
Caloric load, approx. value: 2,73 MJ/m 0,82 MJ/m
Copper weight: 85,00 kg/km 34,00 kg/km

Norms
Applicable standards: ODVA DeviceNet ODVA DeviceNet
UL Style: CL2 CMG CL2 CMG
CSA standard: CEC: CMG FT4 CEC: CMG FT4 R
Application
DeviceNet is a bus system developed by Allen Bradley (Rockwell Automation). These cables are used to interconnect various industrial
devices, such as SPS controls or limit switches. The special characteristic of this bus system is that a data pair and a power supply pair are
integrated in one cable. These cables with FRNC sheath are designed for fixed installation.

Part no. 800681, DeviceNet FRNC 800682, DeviceNet FRNC


Dimensions and specifications may be changed without prior notice.

R 154
BUS Cables
DeviceNet
CPE

Type Fixed installation, indoor Fixed installation, indoor


Cable structure 1x2xAWG18 + 1x2xAWG24 +
1x2xAWG15 1x2xAWG22
Inner conductor diameter 1: Copper, tinned (AWG 18/19) Copper, tinned (AWG 24/19)
Inner conductor diameter 2: Copper, tinned (AWG 15/19) Copper, tinned (AWG 22/19)
Core insulation 1: PE PE
Core insulation 2: PE PVC
Core colours 1: light bu, wh light bu, wh
Core colours 2: rd, bk rd, bk
Stranding element 1: Double core Double core
Shielding 1: - -
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Drain wire: yes yes
Outer sheath material: CPE CPE
Cable external diameter: approx. 12,0 mm 0,3 mm approx. 7,0 mm 0,3 mm
Outer sheath colour: Yellow Yellow

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 22,6 Ohm/km 90 Ohm/km
Insulation resistance, min.: 0,2 GOhm x km 0,2 GOhm x km
Loop resistance: 45 Ohm/km max. 180 Ohm/km max.
Mutual capacitance: 39 nF/km nom. 39 nF/km nom.
Test voltage: 2 kV 2 kV
Attenuation: 125 kHz < 0,43 dB/100m 125 kHz < 0,95 dB/100m
500 kHz < 0,82 dB/100m 500 kHz < 1,64 dB/100m

Technical data
Weight: approx. 195 kg/km approx. 70 kg/km
Min. bending radius for laying: 190 mm 110 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +60C +60C
Caloric load, approx. value: 2,73 MJ/m 0,82 MJ/m
Copper weight: 71,20 kg/km 28,10 kg/km

Norms
Applicable standards: ODVA DeviceNet ODVA DeviceNet
UL Style: CMG PLTC CL2 CMG
CSA standard: CEC: CMG FT4 CEC: CMG FT4

Application
DeviceNet is a bus system developed by Allen Bradley (Rockwell Automation). These cables are used to interconnect various industrial
devices, such as SPS controls or limit switches. The special characteristic of this bus system is that a data pair and a power supply pair are
integrated in one cable. These cables are designed for fixed installation.

Part no. 81907, DeviceNet CPE 81908, DeviceNet CPE


Dimensions and specifications may be changed without prior notice.

R 155
BUS Cables
DeviceNet
PUR, flexible

Type Drag chain applications Drag chain applications


Cable structure 1x2xAWG18 + 1x2xAWG24 +
1x2xAWG15 1x2xAWG22
Inner conductor diameter 1: Copper, tinned (AWG 18/40) Copper, tinned (AWG 24/19)
Inner conductor diameter 2: Copper, tinned (AWG 15/84) Copper, tinned (AWG 22/19)
Core insulation 1: Cell PE Cell PE
Core insulation 2: Cell PE Cell PE
Core colours 1: light bu, wh light bu, wh
Core colours 2: rd, bk rd, bk
Stranding element 1: Double core Double core
Shielding 1: - -
Shielding 2: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned Cu braid, tinned
Drain wire: yes yes
Outer sheath material: PUR PUR
Cable external diameter: approx. 12,0 mm 0,3 mm approx. 7,0 mm 0,3 mm
Outer sheath colour: Violet similar to RAL 4001 Violet similar to RAL 4001

Electrical data
Characteristic impedance: 120 Ohm 10 % 120 Ohm 10 %
Conductor resistance, max.: 22,6 Ohm/km 90 Ohm/km
Insulation resistance, min.: 0,2 GOhm x km 0,2 GOhm x km
Loop resistance: 45 Ohm/km max. 45 Ohm/km max.
Mutual capacitance: 39,8 nF/km nom. 39,8 nF/km nom.
Test voltage: 2 kV 2 kV
Attenuation: 125 kHz < 0,41 dB/100m 125 kHz < 0,95 dB/100m
500 kHz < 0,82 dB/100m 500 kHz < 1,64 dB/100m

Technical data
Weight: approx. 185 kg/km approx. 68 kg/km
Min. bending radius for laying: 61 mm 35 mm
Operating temperature range min.: -40C -40C
Operating temperature range max.: +80C +80C
Caloric load, approx. value: 2,54 MJ/m 0,76 MJ/m
Copper weight: 90,00 kg/km 35,00 kg/km

Norms
Applicable standards: ODVA DeviceNet ODVA DeviceNet
UL Style: CMX 75C CL2X CMX 75C CL2X

Application R
DeviceNet is a bus system developed by Allen Bradley (Rockwell Automation). These cables are used to interconnect various industrial
devices, such as SPS controls or limit switches. The special characteristic of this bus system is that a data pair and a power supply pair are
integrated in one cable. These cables with PUR sheath are designed for highly flexible applications.

Part no. 81909, DeviceNet PUR 81910, DeviceNet PUR


Dimensions and specifications may be changed without prior notice.

R 156
BUS Cables
CC-Link BUS
PVC

Type Fixed installation, indoor


Cable structure 3x0.5 mm
Inner conductor diameter: Copper, bare (AWG 20/7)
Core insulation: Cell PE
Core colours: wh, bu, ye
Stranding element: Triple core
Shielding 1: Polyester foil over stranded bundle
Shielding 2: Polyester foil, aluminium-lined
Total shielding: Cu braid, tinned
Drain wire: yes
Outer sheath material: PVC
Cable external diameter: approx. 7,7 mm 0,3 mm
Outer sheath colour: Red

Electrical data
Characteristic impedance: 110 Ohm 15 Ohm
Conductor resistance, max.: 37,8 Ohm/km
Insulation resistance, min.: 10 GOhm x km
Loop resistance: 75 Ohm/km max.
Mutual capacitance: 60 nF/km nom.
Test voltage: 2 kV
Attenuation: 1 MHz < 16,0 dB/100m
5 MHz < 35,0 dB/100m

Technical data
Weight: approx. 77 kg/km
Min. bending radius for laying: 120 mm
Operating temperature range min.: -40C
Operating temperature range max.: +70C
Caloric load, approx. value: 1,10 MJ/m
Copper weight: 40,00 kg/km

Norms
Applicable standards: CC-Link Specification 1.10
UL Style: CM 75C or PLTC

Application
The CC link (control and communication link) is a field bus system that is used in the area of testing, sensors and actuators. The main target
market is Asia, but the USA and Great Britain also rely more and more on CC link. As an option, a version with power supply cores is available.
It is used particularly in channels.

Part no. 800497, CC-Link communications cable


Dimensions and specifications may be changed without prior notice.

R 157
BUS Cables
SafetyBUS
FRNC + PUR

Type Fixed installation, indoor Drag chain applications


Cable structure 3x0,75 mm (stranded) 3x0,75 mm (stranded)
Inner conductor diameter: Copper, bare (AWG 18/24) Copper, bare (AWG 18/24)
Core insulation: PP PP
Core colours: wh, bn, gn wh, bn, gn
Stranding element: Triple core Triple core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Cu braid, tinned Cu braid, tinned
Outer sheath material: FRNC PUR
Cable external diameter: approx. 7,5 mm 0,3 mm approx. 7,5 mm 0,3 mm
Outer sheath colour: Yellow similar to RAL 1003 Yellow similar to RAL 1003

Electrical data
Characteristic impedance: 110 Ohm 10 Ohm 110 Ohm 10 Ohm
Conductor resistance, max.: 26 Ohm/km 26 Ohm/km
Insulation resistance, min.: 0,2 GOhm x km 0,2 GOhm x km
Loop resistance: 52 Ohm/km max. 52 Ohm/km max.
Mutual capacitance: 45 nF/km nom. 45 nF/km nom.
Nominal voltage: 250 V 250 V
Test voltage: 3 kV 3 kV
Attenuation: 1 MHz < 1,6 dB/Km 1 MHz < 1,6 dB/Km
5 MHz < 3,4 dB/Km 5 MHz < 3,4 dB/Km
10 MHz < 5,6 dB/Km 10 MHz < 5,6 dB/Km
16 MHz < 7,5 dB/Km 16 MHz < 7,5 dB/Km

Technical data
Weight: approx. 68 kg/km approx. 65 kg/km
Min. bending radius for laying: 60 mm 60 mm
Operating temperature range min.: -25C -40C
Operating temperature range max.: +80C +80C
Caloric load, approx. value: 0,72 MJ/m 0,76 MJ/m
Copper weight: 50,00 kg/km 50,00 kg/km

Norms
Applicable standards: abutted at SafetyBUS p technical guidelines abutted at SafetyBUS p technical guidelines
copper wires 1.0 copper wires 1.0

Application
SafetyBUS p is an open bus system for the serial transfer of safety-related data. It is based on the CAN (Controller Area Network) protocol.
From this technology benefit the users in several areas like the automotive industry or the process automation. The above mentioned types R
are suitable for fixed installations and as well as for drag chains (PUR).

Part no. 800651, SafetyBus p 800652, SafetyBus p


Dimensions and specifications may be changed without prior notice.

R 158
BUS Cables
LON BUS
H112 + Y116

Type Fixed installation, indoor Mobile use


Cable structure 1x2xAWG 22/1 1x2xAWG 16/19
Inner conductor diameter: Copper, bare (AWG 22/1) Copper, bare (AWG 16/19)
Core insulation: PE PVC
Core colours: wh, bu wh, bk
Stranding element: Double core Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Polyester foil, aluminium-lined -
Drain wire: yes -
Outer sheath material: FRNC PVC
Cable external diameter: approx. 4,4 mm 0,3 mm approx. 7,0 mm 0,4 mm
Outer sheath colour: White Grey

Electrical data
Characteristic impedance: 100 Ohm 10 % 85 Ohm 15 %
Conductor resistance, max.: 57 Ohm/km 15,8 Ohm/km
Insulation resistance, min.: 5 GOhm x km 0,02 GOhm x km
Loop resistance: 114 Ohm/km max. 31 Ohm/km max.
Mutual capacitance: 45 nF/km nom. 10 nF/km nom.
Nominal voltage: 125 V 300 V
Test voltage: 0,7 kV 2 kV

Technical data
Weight: approx. 24 kg/km approx. 71 kg/km
Min. bending radius for laying: 35 mm 85 mm
Operating temperature range min.: -20C -20C
Operating temperature range max.: +75C +80C
Caloric load, approx. value: 0,337 MJ/m 1,25 MJ/m
Copper weight: 11,00 kg/km 30,00 kg/km

Application
The LON bus (Local Operating Network) is a system used in building automation systems. It has the great advantage that it allows usage of
different transmission media. It is used in the interior as hard wiring (H122) and as patch cable (Y116) and must be made in accordance with
DIN EN 50090-2-2 (VDE 0892 Part 2-2:1997-06).

Part no. 802187, LON H122 802188, LON Y116


Dimensions and specifications may be changed without prior notice.

R 159
BUS Cables
E-BUS
PVC

Type 2-pairs 2-pairs


Cable structure 2x2x0.8 mm 2x2x0.8 mm
Inner conductor: Copper, bare Copper, bare
Core insulation: PVC PVC
Core colours: wh, ye, rd, bk wh, ye, rd, bk
Stranding element: Star quad Star quad
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Drain wire: yes yes
Outer sheath material: PVC PVC
Cable external diameter: approx. 6,6 mm 0,3 mm approx. 6,6 mm 0,3 mm
Outer sheath colour: Blue Lilac similar to RAL 4005 Green similar to RAL 6010

Electrical data
Characteristic impedance: 100 Ohm 100 Ohm
Conductor resistance, max.: 73,2 Ohm/km 73,2 Ohm/km
Insulation resistance, min.: 0,1 GOhm x km 0,1 GOhm x km
Loop resistance: 146 Ohm/km max. 146 Ohm/km max.
Mutual capacitance: 100 nF/km nom. 100 nF/km nom.

Technical data
Weight: approx. 54 kg/km approx. 54 kg/km
Min. bending radius for laying: 95 mm 95 mm
Operating temperature range min.: -30C -30C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,90 MJ/m 0,90 MJ/m
Copper weight: 25,00 kg/km 25,00 kg/km

Norms
Applicable standards: EIB standard EIB standard

Application
The E-bus cable is used for the transmission of bus signals for intelligent systems in buildings. The cables ensure perfect communication in
accordance with EIB regulations (European installation bus). They can be layed over, in, or below the plaster, in pipes and pipe ducts, in dry,
moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun. Wiring together with high-power
supply cables is possible without limitation. The EIB bus can be used to control lighting, blinds, heating, ventilation, indicator boards, etc.

Part no. 81081, E-BUS 81663, E-BUS


Dimensions and specifications may be changed without prior notice.
R

R 160
BUS Cables
E-BUS
FRNC + PVC

Type 2-pairs 4-pairs


Cable structure 2x2x0.8 mm 4x2x0.8 mm
Inner conductor: Copper, bare Copper, bare
Core insulation: PE PVC
Core colours: wh, ye, rd, bk wh, ye, rd, gn, bu, bn, wh, wh
Stranding element: Star quad Double core
Shielding 1: Polyester foil over stranded bundle Polyester foil over stranded bundle
Shielding 2: - -
Total shielding: Polyester foil, aluminium-lined Polyester foil, aluminium-lined
Drain wire: yes yes
Outer sheath material: FRNC PVC
Cable external diameter: approx. 6,6 mm 0,3 mm approx. 8,2 mm 0,4 mm
Outer sheath colour: Blue Lilac similar to RAL 4005 Blue Lilac similar to RAL 4005

Electrical data
Characteristic impedance: 100 Ohm 100 Ohm
Conductor resistance, max.: 73,2 Ohm/km 73,2 Ohm/km
Insulation resistance, min.: 0,1 GOhm x km 0,1 GOhm x km
Loop resistance: 146 Ohm/km max. 146 Ohm/km max.
Mutual capacitance: 100 nF/km nom. 100 nF/km nom.

Technical data
Weight: approx. 54 kg/km approx. 92 kg/km
Min. bending radius for laying: 95 mm 120 mm
Operating temperature range min.: -30C -30C
Operating temperature range max.: +70C +70C
Caloric load, approx. value: 0,58 MJ/m 1,37 MJ/m
Copper weight: 25,00 kg/km 41,00 kg/km

Norms
Applicable standards: EIB standard EIB standard

Application
The E-bus cable is used for the transmission of bus signals for intelligent systems in buildings. The cables ensure perfect communication in
accordance with EIB regulations (European installation bus). They can be layed over, in, or below the plaster, in pipes and pipe ducts, in dry,
moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun. Wiring together with high-power
supply cables is possible without limitation. The EIB bus can be used to control lighting, blinds, heating, ventilation, indicator boards, etc.

Part no. 80826, E-BUS 81077, E-BUS


Dimensions and specifications may be changed without prior notice.

R 161
BUS Cables
E-BUS DIRECT BURIAL
PE, ERD

Type Underground laying


Cable structure 2x2x0.8 mm
Inner conductor: Copper, bare
Core insulation: PE
Core colours: wh, ye, rd, bk
Stranding element: Star quad
Shielding 1: Polyester foil over stranded bundle
Shielding 2: -
Total shielding: Polyester foil, aluminium-lined
Outer sheath material: PE
Cable external diameter: approx. 8,8 mm 0,3 mm
Outer sheath colour: Black similar to RAL 9005

Electrical data
Characteristic impedance: 100 Ohm
Conductor resistance, max.: 73,2 Ohm/km
Insulation resistance, min.: 5 GOhm x km
Loop resistance: 146 Ohm/km max.
Mutual capacitance: 55 nF/km nom.
Test voltage: 0,8 kV

Technical data
Weight: approx. 75 kg/km
Min. bending radius for laying: 130 mm
Operating temperature range min.: -20C
Operating temperature range max.: +70C
Caloric load, approx. value: 2,00 MJ/m
Copper weight: 25,00 kg/km

Norms
Applicable standards: EIB standard

Application
The E-bus cable is used for the transmission of bus signals for intelligent systems in buildings. The cables ensure perfect communication in
accordance with EIB regulations (European installation bus). They can be layed over, in, or below the plaster, in pipes and pipe ducts, in dry,
moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun. Wiring together with high-power
supply cables is possible without limitation. The EIB bus can be used to control lighting, blinds, heating, ventilation, indicator boards, etc.

Part no. 802800, E-BUS BURIAL


Dimensions and specifications may be changed without prior notice.
R

R 162
BUS Cables
KH-BUS
PVC + FRNC

Type Hospital-Bus Hospital-Bus


Cable structure 2x1.5mm (stranded) + 2x1.5mm (stranded) +
2x2x0.60 mm (solid) 2x2x0.60 mm (solid)
Inner conductor, power core: Copper, bare Copper, bare
Inner conductor, data core: Copper, tinned Copper, tinned
Core insulation, power core: PVC PVC
Core insulation, data core: PE PE
Core colours, power core: rd, bu rd, bu
Core colours, data core: gn/ye, gy/pk gn/ye, gy/pk
Stranding element, data core: Double core Double core
Shielding, data pair: PP foil + aluminium-lined foil + PP foil PP foil + aluminium-lined foil + PP foil
Drain wire: yes yes
Outer sheath material: PVC FRNC
Cable external diameter: approx. 8,0 mm 0,3 mm approx. 8,0 mm 0,3 mm
Outer sheath colour: Green similar to RAL 6001 Green similar to RAL 6001

Electrical data
Insulation resistance, min.: 0,02 GOhm x km 0,02 GOhm x km
Mutual capacitance: 70 nF/km nom. 70 nF/km nom.
Test voltage: 2 kV 2 kV

Technical data
Weight: approx. 90 kg/km approx. 93 kg/km
Min. bending radius for laying: 120 mm 120 mm
Operating temperature range min.: -30C -30C
Operating temperature range max.: +80C +80C
Caloric load, approx. value: 1,01 MJ/m 0,86 MJ/m
Copper weight: 53,00 kg/km 53,00 kg/km

Application
For computer-based patient calling systems, easy and quick installation is an important factor. Therefore a 6-core bus cable is used to connect
the components of the calling system. This cable is used for the transmission of power, data, and voice.

Part no. 81085, KH-BUS 81447, KH-BUS


Dimensions and specifications may be changed without prior notice.

R 163

Potrebbero piacerti anche