Client : SEC-EOA Riyadh Power Plant # 10 "

Contractor: BEMCO 10721026/00'


Sub Cont:
Orifice Plate Verification Report Form No: TS-I4002
Dtae: 13/02/09 Rev: 0
Tag No. : Type :
Make : P&ID No :
Line Size : Plate Dia(D) :
Plate Thickness : Bore Dia(d) :
Plate Material : Service :
Location : Date of Calibration :

Verification as per Data sheet :


Yes No
Tag no is correct :
Plate Thickness is correct :
Plate material is correct :
Bore dia is correct :
Plate dia is correct :
Vent / Drain holes are correct :

Test Equipment Used


Equip.Make
Equip.Model No
Equip.Sl.No
Equip.Calibration Certification No
Equip.Calibration Validity
Remarks

Company SUB CONTRACTOR ARABIAN BEMCO SEC

Signature

Name

Date
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
Verification of Thermowell Form No: TS-I4003
Dtae: 13/02/09 Rev: 0

Tag No. : Name/ Appln :


Flange rating : Type :
End connection : Make :
Insertion Length : Service

Verification as per Data sheet :


Yes No
Tag no is correct :
Thermowell length is correct :
Process connection is correct :
Material is correct :
Thermoelement length is
:
correct

Test Equipment Used


Equip.Make
Equip.Model No
Equip.Sl.No
Equip.Calibration Certification No
Equip.Calibration Validity
Remarks

Company SUB CONTRACTOR ARABIAN BEMCO SEC

Signature

Name

Date
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO

Sub Cont:
INSTRUMENT CALIBRATION REPORT FOR
Form No: TS-I4004
TEMPERATURE ELEMENT
Dtae: 13/02/09 Rev: 0

NAME/APPLN :
TAG NO. : AREA/LOCATION :

TYPE : MAKE :

MODEL NO : RANGE :

P & ID NO. : SERVICE :

DATA SHEET REF : DATE OF CALIBRATION :

INST. SERIAL NO :

PRE-CALIBRATION INSPECTION :
TAG NUMBER CORRECT : YES / NO COMPLIANCE WITH SPECS. : YES / NO

GENERAL CONDITION SATISFACTORY : YES / NO INPUT RANGE :

BODY MATERIAL CORRECT : YES / NO OUTPUT RANGE :

AMBIENT CONDITION: FIELD/LAB ______________

TEST EQUIPMENT USED :


EQUIPMENT TYPE : RANGE :

EQUIPMENT SERIAL NO. : ACCURACY :

MAKE / MODEL : CALIBRATION DATE :

CERTIFICATE NO. : RE-CALIBRATION DUE :

INPUT OUTPUT IN Ohm/Mv % ERROR REMARKS

% Deg C OBSERVED EXPECTED

REMARKS :

SUB CONTRACTOR ARABIAN BEMCO SEC

SIGN

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO

Sub Cont:
INSTRUMENT CALIBRATION REPORT
(TRANSMITTERS) Form No: TS-I4005

Dtae: 13/02/09 Rev: 0


TAG NO. : INSTRUMENT DESCRIPTION :__________________________
TYPE : AREA/LOCATION :__________________________
MAKE/MODEL : CALIBRATION RANGE: :__________________________
P & ID NO. : SPECIFIED ACCURACY: :__________________________
DATA SHEET REF. : SERVICE DESCRIPTION: :__________________________
INST. SERIAL NO : DATE OF CALIBRATION: :_______________________

PRE-CALIBRATION INSPECTION :
TAG NUMBER CORRECT SAFETY PROTECTION :
GENERAL CONDITION SATISFACTION INPUT CALIBRATION RANGE :
COMPLIANCE WITH SPECIFICATION OUTPUT CALIBRATION RANGE :
ZERO ELEVATION /SUPRESSION (IN ENGG. UNIT) :
AMBIENT CONDITION : FIELD / LAB. TEMP. : HUMIDITY :

TRANSMITTER DETAILS :

COMMUNICATION
TYPE OUTPUT FORM FAIL SAFE DIRECTION
MODE
SMART ANALOG LINEAR BURNOUT UPSCALE FAIL TO UPSCALE
ANALOG DIGITAL SQRT BURNOUT DOWNSCALE FAIL TO DOWNSCALE
HART SPECIAL BURNOUT LAST GOOD VALUE UNDEFINED

TEST EQUIPMENT USED :


EQUIPMENT TYPE : RANGE :
EQUIP. SERIAL NO. : ACCURACY :
MAKE : : CALIBRATED DATE :
CERTIFICATE NO. : CALIBRATION DUE DATE :

RESULT :

% OF CALIBRATED EXPECTED OUTPUT %


ACTUAL INPUT ACTUAL OUTPUT % ERROR REMARKS
SPAN OR mA

0%

25%

50%

75%

100%

75%

50%

25%

0%

REMARKS :

SUB CONTRACTOR ARABIAN BEMCO SEC

SIGN

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO

Sub Cont:
SWITCH CALIBRATION REPORT ( PS/TS/LS-DPS ) Form No: TS-I4006

Date: 13/02/09 Rev: 0


TAG NO : _______________________ INSTRUMENT DESCRIPTION: __________________________
TYPE : _______________________ AREA/LOCATION : _________________________
MAKE / MODEL : _______________________ CALIBRATION RANGE : __________________________
P & ID NO : _______________________ SPECIFIED ACCURACY : __________________________
DATA SHEET NO & PAGE :____________________ SERVICE DESCRIPTION : _________________________
INSTRUMENT SERIAL NO :____________________ DATE OF CALIBRATION : __________________________

PRE- CALIBRATION INSPECTION :


VALVE FUNCTION CORRECTLY Y/N OPENING TIME : ______________ Sec
VALVE ACCUMULATOR FITTED Y/N CLOSING TIME : ______________ Sec
OPERATION OF ACCUMULATOR CHECKED Y/N ACCUMULATOR PRE CHARGE TO : _______ BAR
VALVE ACTION ON AIR / POWER FAILURE : FAIL OPEN / FAIL CLOSE

ZERO ELEVATION / SUPRESSION ( IN ENGG UNITS ) : __________________

AMBIENT CONDITION : FIELD / LAB TEMP : ________ HUMIDITY :___________

VALVE DETAILS :
COMMUNICATION
TYPE MODE OUTPUT FORM
SMART ANALOG LINEAR
ANALOG DIGITAL SQRT
HART SPECIAL

TEST EQUIPMENT :
TYPE OF EQPT MAKE MODEL # SERIAL # CERT NO CAL DATE EXP DATE

RESULTS :
INPUT % ACTUAL INPUT ACTUAL OUTPUT EXPECTED OUTPUT % ERROR REMARKS

0
25
50
75
100
75
50
25
0

REMARKS :

SUBCONTRACTOR BEMCO SEC

SIGN

NAME
DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO

Sub Cont:
LOCAL INSTRUMENT CALIBRATION REPORT (
PG/TG/LG ) Form No: TS-4007
Date: 13/02/09 Rev: 0
TAG NO : _______________________ INSTRUMENT DESCRIPTION: ___________________________
TYPE : _______________________ AREA/LOCATION : _________________________
MAKE / MODEL : _______________________ CALIBRATION RANGE : __________________________
P & ID NO : _______________________ SPECIFIED ACCURACY : __________________________
DATA SHEET NO & PAGE :____________________ SERVICE DESCRIPTION : _________________________
INSTRUMENT SERIAL NO :____________________ DATE OF CALIBRATION : __________________________

PRE- CALIBRATION INSPECTION


TAG NUMBER CORRECT Y/N COMPLIANCE WITH SPECIFICATION: _____________
GENERAL CONDITION SATISFACTORY Y/N INPUT CALIBRATION RANGE : ______________
BODY MATERIAL CORRECT Y/N OUTPUT CALIBRATION RANGE : ______________
NAME PLATE AVAILABLE Y/N ACCURACY : ______________
INITIAL / FINAL TIMER SETTING Y/N
ZERO ELEVATION / SUPRESSION ( IN ENGG UNITS ) : __________________

AMBIENT CONDITION : FIELD / LAB TEMP : ________ HUMIDITY :___________

TEST EQUIPMENT USED :

TYPE OF EQPT MAKE MODEL # SERIAL # CERT NO CAL DATE EXP DATE

TEST RESULTS :

INPUT % APPLIED INPUT BAR INSTRUMENT READING % ERROR REMARKS

deg c
deg C
0
25
50
75
100
75
50
25
0

REMARKS :

SUBCONTRACTOR BEMCO SEC / SAUD CONSULT

SIGN
NAME
DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont: INSTRUMENT LOOP TEST SHEET - PRESSURE /
LEVEL / FLOW / TEMPERATURE TRANSMITTER / Form No: TS-I4008
OTHER TRANSMITTERS Dtae: 13/02/09 Rev: 0
INSTRUMENT KKS NO : ___________________________________
INSTRUMENT DESCRIPTION : ___________________________________
SERVICE : ___________________________________
REFERENCE P&I DIAGRAM : ___________________________________
REFERENCE LOOP DIAGRAM : ___________________________________
MANUFACTURER : ___________________________________
TYPE : ___________________________________
MODEL : ___________________________________
RANGE : ___________________________________
INPUT SIGNAL : ___________________________________

CABLE CONTINUITY TEST/ IR TEST OK NA

DOUBLE/TRIPLE MEASUREMENT OK NA

DISCREPANCY OK NA

TREND OK NA

TOTALIZER OK NA

MEASURE TRANSMITTER DCS MEASURE TRANSMITTER DCS


INPUT OUTPUT INDICATION INPUT OUTPUT INDICATION

0% 75%
25% 50%
50% 25%
75% 0%
100%
OVER RANGE
UNDER RANGE

STATIC HEAD CORRECTION (PRESSURE TRANSMITTERS) ..mm of liquid column

THRESHOLDS
SET ERROR SWITCHING VALUE
THRESHOL LOGIC
% During During DEAD BAND ALARM
DS Value FUNCTION
Meas. Percentage Increase Decrease
INVALID SIGNAL
MAX 2
MAX 1
MIN 1
MIN 2

REMARKS:

SUBCONTRACTOR ARABIAN BEMCO SEC / SAUD CONSULT


SIGNATURE

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
INSTRUMENT LOOP TEST SHEET - RTD Form No: TS-I4009
Dtae: 13/02/09 Rev:
INSTRUMENT DESCRIPTION : ___________________________________
SERVICE : ___________________________________
K.K.S.NUMBER : ___________________________________
REFERENCE P&I DIAGRAM : ___________________________________
REFERENCE LOOP DIAGRAM : ___________________________________
MANUFACTURER : ___________________________________
TYPE : ___________________________________
MODEL : ___________________________________
RANGE ___________________________________
INPUT SIGNAL : RTD PT-100(

CABLE CONTINUITY TEST / IR TEST OK NA

DOUBLE/TRIPLE MEASUREMENT OK NA

DISCREPANCY OK NA

TREND OK NA

TOTALIZER OK NA

0
RESISTANCE VALUE DCS INDICATION C
0
100 =0 C

THRESHOLDS
SET ERROR SWITCHING VALUE
LOGIC
THRESHOLDS % Meas. During During DEAD BAND ALARM
Value FUNCTION
Range Percentag Increase Decrease
INVALID SIGNAL
MAX 2
MAX 1
MIN 1
MIN 2

REMARKS:

SUBCONTRACTOR ARABIAN BEMCO SEC / SAUD CONSULT


SIGNATURE

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
INSTRUMENT LOOP TEST SHEET - DCS DIGITAL
Form No: TS-I4010
INPUT SIGNALS ( SWITCHES )
Dtae: 13/02/09 Rev: 0
INSTRUMENT DESCRIPTION : ___________________________________
SERVICE : ___________________________________
K.K.S.NUMBER : ___________________________________
REFERENCE P&I DIAGRAM : ___________________________________
REFERENCE LOOP DIAGRAM : ___________________________________
MANUFACTURER : ___________________________________
TYPE : ___________________________________
MODEL : ___________________________________
RANGE : ___________________________________
ALARM SET POINT : ___________________________________

CABLE CONTINUITY TEST / IR TEST OK NA

DOUBLE /TRIPLE MEASUREMENT OK NA

DISCREPANCY OK NA

THRESHOLDS
SET ERROR SWITCHING VALUE
DEAD LOGIC
THRESHOLDS % Meas. During During ALARM
Value BAND FUNCTION
Range Percentage Increase Decrease
INVALID SIGNAL
MAX 2
MAX 1
SEE RELEVANT CALIBRATION CERTIFICATE FROM I&C LABORATORY
MIN 1
MIN 2

SHORT CIRCUIT
WIRE BREAK

REMARKS:

SUBCONTRACTOR ARABIAN BEMCO SEC / SAUD CONSULT

SIGNATURE

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
INSTRUMENT LOOP TEST SHEET- MOTOR
Form No: TS-I4011
OPERATED VALVE
Dtae: 13/02/09 Rev: 0

INSTRUMENT DESCRIPTION : ___________________________________

SERVICE : ___________________________________

K.K.S.NUMBER : ___________________________________

REFERENCE P&I DIAGRAM : ___________________________________

REFERENCE LOOP DIAGRAM : ___________________________________

MANUFACTURER : ___________________________________

TYPE : ___________________________________

SERIAL NUMBER : ___________________________________

FULL STROKE TIME OPEN / CLOSE : ________/________ Sec.

RUNNING TIME MONITORING : _________________ Sec.

OPEN : _________________ Nm
CLOSED : _________________ Nm

OK N/A
CABLE CONTINUITY TEST / IR TEST
OPEN POSITION CLOSE POSITION
VALVE LIMIT SWITCH
LIMIT
CLOSING ON TORQUE
LIMIT
OPENING ON TORQUE

TRIP INTERLOCK

RELEASE INTERLOCK

OPERATION FROM LOCAL PANEL OPEN CLOSE

OPERATION FROM LOCAL OPEN CLOSE


RUN
ALARMS ELECTRICAL FAILURE LIMIT SWITCH DISCREPANCY TIME

STATUS INDICATION ON DCS NA OPEN CLOSE FAULT

REMARKS:

SUBCONTRACTOR ARABIAN BEMCO SEC

SIGNATURE

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
INSTRUMENT LOOP TEST SHEET - PNEUMATIC
Form No: TS-I4012
VALVES
Dtae: 13/02/09 Rev: 0

INSTRUMENT DESCRIPTION : ___________________________________

SERVICE : ___________________________________

K.K.S.NUMBER : ___________________________________

REFERENCE P&I DIAGRAM : ___________________________________

REFERENCE LOOP DIAGRAM : ___________________________________

LOCAL PANEL NAME : ___________________________________

MANUFACTURER : ___________________________________

TYPE : ___________________________________

SOLENOID TYPE : ___________________________________

POWER SUPPLY : ___________________________________

FULL STROKE TIME OPEN / CLOSE : ________/________ Sec.

CABLE CONTINUITY TEST / IR TEST OK N/A

POWER FAIL POSITION OPEN CLOSE

AIR FAIL POSITION OPEN CLOSE

VALVE OPERATION FROM LOCAL CONTROL PANEL OPEN CLOSE

STATUS INDICATION ON DCS NA OPEN CLOSE FAULT

REMARKS:

SUBCONTRACTOR ARABIAN BEMCO SEC

SIGNATURE

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
Instrument Loop Test - Solenoid Valve Form No: TS-I4013
Dtae: 13/02/09 Rev: 0

INSTRUMENT DESCRIPTION : ___________________________________

SERVICE : ___________________________________

K.K.S.NUMBER : ___________________________________

REFERENCE P&I DIAGRAM : ___________________________________

REFERENCE LOOP DIAGRAM : ___________________________________

LOCAL PANEL NAME : ___________________________________

MANUFACTURER : ___________________________________

TYPE : ___________________________________

SOLENOID TYPE : ___________________________________

POWER SUPPLY : ___________________________________

CABLE CONTINUITY TEST / IR TEST OK N/A

OPERATION FROM LOCAL PANEL OPEN CLOSE

POWER FAIL POSITION OPEN CLOSE

STATUS INDICATION ON DCS NA OPEN CLOSE FAULT

REMARKS:

SUBCONTRACTOR ARABIAN BEMCO SEC

SIGNATURE

NAME

DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO

Sub Cont:
SWITCH CALIBRATION REPORT ( PS/TS/LS-DPS ) Form No: TS-I4014

Date: 13/02/09 Rev: 0


TAG NO : _______________________ INSTRUMENT DESCRIPTION :______________________
TYPE : _______________________ AREA/LOCATION : ___________________
MAKE / MODEL : _______________________ OVERRANGE : __________________________
P & ID NO : _______________________ PROOF RANGE :_________________________
INSTRUMENT SERIAL NO :____________________ DIFFERENTIAL ADJUSTABLE :_________________________
SET VALUE :________________ DIFFERENTIAL VALUE :__________________________
SERVICE :________________ DATE OF CALIBRATION :___________________________
DATA SHEET NO & PAGE :____________________

PRE- CALIBRATION INSPECTION :


TAG NUMBER CORRECT Y/N SAFETY PROTECTION : ______________
GENERAL CONDITION SATISFACTORY Y/N INPUT CALIBRATION RANGE : ______________
COMPLIANCE WITH SPECIFICATION Y/N
AMBIENT CONDITION : FIELD / LAB TEMP : ________ HUMIDITY :___________

OPEN ON RISING H SWITCH SET ___________ RESET ____________


CLOSE ON FALLING
OPEN ON RISING H H SWITCH SET ___________ RESET ____________
CLOSE ON FALLING
TEST EQUIPMENT USED :
TYPE OF EQPT MAKE MODEL # SERIAL # CERT NO CAL DATE EXP DATE

RESULTS :
NO CONTACT NC CONTACT DEAD BAND CABLE CORE

REMARKS :

SUBCONTRACTOR ARABIAN BEMCO SEC / SAUD CONSULT

SIGN

NAME
DATE
Client : SEC-EOA
Riyadh Power Plant # 10 " 10721026/00'
Contractor: BEMCO
Sub Cont:
TRUMENT & CONTROL CABLE MEGGER / CONTINUITY TEST REPOForm No: TS-I4001

Dtae: 13/02/09 Rev: 0

PANEL / JB No .: AREA/LOCATION .: REPORT No.:

DRWG. REF. NO .: APPLIED VOLTAGE .: DATE.:

CABLE SCREEN/
ITEM CONDUCTOR TO CONDUCTOR TO CONDUCTOR SHIELD TO CONTINUITY
CABLE NO. CABLE TYPE/SIZE FROM TO LENGTH - SHIELD TO REMARKS
NO. CONDUCTOR SHIELD TO ARMOUR SHIELD TEST
Mtrs ARMOUR

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TYPE OF INSTRUMENT : Remarks:

INSTRUMENT NO/SR. NO. :

INSTRUMENT MAKE/MODEL :

CALIBRATION CERTIFICATE NO. :

INSTRUMENT CALIBRATION DATE/DUE :

SUB CONTRACTOR ARABIAN BEMCO SEC

Name

Signature

Date