Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
COMBUSTION
A Selas Heat Technology Company
www.webster-engineering.com
Throughout this manual, the following symbols are used to identify potential problems.
WARNING
This indicates a potential hazardous situation, which if not avoided, could result in personal injury or death.
CAUTION
This indicates a potentially hazardous situation, which if not avoided, could result in damage to the equipment.
WARNING
IF YOU SMELL GAS, OPEN WINDOW, EXTINGUISH ANY OPEN FLAMES, STAY AWAY FROM ELECTRICAL
SWITCHES, EVACUATE THE BUILDING AND IMMEDIATELY CALL THE GAS COMPANY.
IN ACCORDANCE WITH OSHA STANDARDS, ALL EQUIPMENT, MACHINES AND PROCESSES SHALL BE
LOCKED OUT PRIOR TO SERVICING.
IF THIS EQUIPMENT IS NOT INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MAN-
UFACTURERS INSTRUCTIONS, THIS PRODUCT COULD EXPOSE YOU TO SUBSTANCES IN FUEL OR FROM
FUEL COMBUSTION WHICH CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE
STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
IMPROPER SERVICING OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND
OPERATORS.
Date of Startup
Service Organization Information:
Company Name
Lead Technician
Address
Phone Number
C. Installation Page 19
1. General Considerations ......................... Page 19
2. Refractory Frontplate ............................. Page 20
3. Burner Mounting .................................... Page 20
4. Gas Piping .............................................. Page 21
5. General Oil Piping ................................. Page 22
6. Pressure Atomized Oil System................ Page 23
7. Air Atomized #2 Oil ................................ Page 24
8. Gas Pilot ................................................ Page 24
9. FGR Duct System ................................. Page 25
10. Draft and Stacks ................................... Page 27
11. Electrical System .................................... Page 28
THE INSTALLATION OF THE EQUIPMENT SHALL BE MAXIMUM 16738 8.4 120 150
IN ACCORDANCE WITH THE REGULATION OF AU-
THORITIES HAVING JURISDICTION, INCLUDING THE MINIMUM 2790 0.15 40 65
NATIONAL ELECTRICAL CODE, CSA STANDARDS 139
AND 140, THE CANADIAN NATIONAL ELECTRIC CODE, FUEL NATURAL GAS #2 OIL
Every attempt has been made to accurately reect the OIL NOZZLES (QTY) GPH @ 100 PSI (2) 24, (1) 22
burner construction, however, product upgrades and spe-
REQD GAS INLET PRESS 36 GAS BTU/CUFT
cial order requirements may result in differences between 1000
the content of this manual and the actual equipment. REQD OIL PUMP PRESS 300 PSI
CONTROL CIRCUIT 115 5 60 1 The electrical ratings of the burner are given, with the volt-
age, current load, frequency and phase (this will either be
BURNER MOTOR 460 20.1 60 3 15
single or 3-phase). For motors, the motor HP is listed.
OIL PUMP MOTOR 460 2.9 60 3 1.5
BOILER HP
PRESSURE, AIR or STEAM
200 200 HP
ATOMIZING
250 250 HP
MR Pressure atomizing
300 300 HP
MA Air atomizing
350 350 HP
400 400 HP
450 450 HP GAS TRAIN VENDOR
500 500 HP VGD Seimens
600 600 HP VGG Seimens
M Maxon
All Others
Blank
(ASCO) - (std)
MODULATION
HOUSING SIZE M Full modulation
5 5
7 7 FLAME SAFEGUARD
VENDOR DESIGNATION
RM7800L Honeywell
HOUSING M Mark AutoFlame - mini mark
ROTATION
SL Slant left MOTOR HORSEPOWER E110/EP170 Fireye
SR Slant right 50 5 HP 200 20 HP Nexus - N Fireye
V Vertical (std) 75 7.5 HP 250 25 HP LMV51-S Siemens
100 10 HP 300 30 HP LMV52-S Siemens
150 15 HP
This section describes the components of the HDS burner detailed review of how the components work as a sys-
line and provides some details on their application and tem and explain the overall operation of the burner.
operation. Other sections of this manual provide a more
Junction Box
Gas
Spuds Damper
Actuator
Mounting
Flange Air Damper
Oil Safety
Shutoff
Valves
Oil Supply
Combustion Pressure
Air Motor Gauge
Oil Metering
Gas Valve Gas Control Valve
Actuator Valve Oil Valve Oil Pressure
Actuator Switch
Figure B-1
HDSX General Arrangement, Left Side
(Shown With Optional Linkageless Control)
Scanner
Atomizing
Air Line
Ignition
Transformer
Oil Line
Windbox
Combustion
Air Motor
FGR Valve
FGR Adapter
Oil Pilot
Fan Inlet
Pilot Gas Connection Cone
Scanner Tube
Fuel Cam Fan
Fuel Cam
Scanner
Low Fire Damper Tube
Stop
Gas Control Valve
Combustion Air
Motor
Control Transformer
Burner Motor
Starter
Call for Heat Light
Alarm Buzzer
Alarm Light
Terminal Strip
Figure B-5
Control Panel (Gas Shown)
Fan
Blade
Figure B-6
Fan and Motor
Assembly
The windbox serves as the building block of the burner. It 3. Burner Drawer
requires good structural support to the boiler and oor to
The burner drawer contains the pilot, scanner, diffuser
handle the weight and movement of rotating components.
and oil gun. These components are all attached to the
Head Extension backplate. The burner drawer is removed as a complete
The head extension connects the ring head to the unit for adjustment and inspection. The burner drawer
windbox. It also allows different combinations of ring slides through the windbox, head extension and into the
heads to be used with different fan and windbox sizes. gas manifold. It is attached to the burner by bolting the
backplate to the windbox.
The head extension has an access door near the ring
head to simplify inspection, adjustments and maintenance.
This can also be used to simplify gas spud changes.
Air Damper
The air damper regulates the ow of air to the burner. It is
available in a multi-blade and single blade conguration.
The single blade damper has adjustable edge plates
that provide adjustment for leakage and a more linear Figure B-9 Burner Drawer Assembly
relationship of damper movement to ow. For high
The pilot, scanner, oil gun and diffuser position can be
turndown applications (greater than 6:1), seals are used
adjusted (in and out) by sliding the tube through the
on the blade ends of the single blade damper to improve
backplate. Setscrews are used to lock these tubes into
air turndown. The multi-blade damper uses rubber seals
position. The oil gun can be removed for inspection or
on the blade ends to improve sealing. On a single point
extended gas ring without removing the burner drawer.
positioning system (linkage), the damper shaft is connected
by linkage to the jackshaft. On a parallel positioning Diffuser
system (linkageless), the shaft is directly coupled to the The diffuser provides the directional control of the
actuator for the air damper. combustion air for mixing and combustion stability. The
diffuser uses a combination of outer swirl air and inner
The air damper mounts to the fan inlet and controls the
straight air. An inner ring is fastened to the diffuser in
air ow to the fan. On low NOx burners, the air damper
some applications.
is connected to the FGR adapter plate, so that the ue
gas can enter down-stream of the damper where there is
a negative pressure. If an optional silencer were used, it
would be mounted to the inlet of the air damper.
Oil Supply Pressure Gauge Figures B-17 and B-18 shows the components of typical air
This indicates the oil supply pressure from the pump. atomizing nozzles. The nozzle tip and swirler are lapped
together to form a perfect t and can only be used together
Oil Train as a matched set. Other air atomizing nozzles may have
The oil train contains the safety shut-off valves, pressure slightly different construction.
switches and other components that may be required
for the specic installation, insurance codes and local Figure B-17 Typical Small Air Atomizing Oil Nozzle
regulations and can vary greatly from burner to burner. Body Swirler
Oil trains tend to be designed for each application and a
unit specic oil train drawing is provided with each unit.
Details of the actual components are provided with each
burner.
Oil Safety Shutoff Valve Nozzle Tip
Each oil train has two shutoff valves. The valves can be
either solenoid or motorized type and can have an optional
POC (proof of closure) switch.
Spring
Low Oil Pressure Switch
This switch is set to a pressure below the expected oil
pressure and will trip if the oil pressure drops below this
level, shutting down the burner. Body Washer Tip
Swirler
Motor
Inlet Tube
Flexible
Hose Air
Supply Inlet Cone
Connection
Plastic Seal
Mounting Surface
Figure B-20 Large Air Compressor for Air Damper
FGR Control The burner may be equipped with single point positioning
Valve (linkage), multiple setting modulating motor or parallel
positioning system (linkageless). All of these systems
provide the basic fuel-air-ratio control required for good
combustion, however they can provide different features
Figure B-23 FGR Control Valve
and setup capabilities.
The FGR control valve modulates in conjunction with the
Modulating Control
fuel and air valves to provide different input rates. On a
The burner modulates to match the energy requirements
single point positioning system (linkage), it is connected
of the load. It does this by using a sensor that measures
to the jackshaft. With a parallel positioning system
the pressure or temperature of the system and a matching
(linkageless), an actuator is connected to the FGR control
sensor in the modulating motor that moves to match the
valve and modulated by electronic control to the desired
readings of the sensor.
position.
In some optional systems, a similar process is used with
FGR Shutoff Valve
an external control that provides a signal to the motor to
Single point positioning systems (linkage) require a
go to a certain rate. These systems may include multiple
separate FGR shut-off valve that prevents ow during
burner sequencing, outside temperature compensation
the purge cycle. The valve is driven by a motor to close
and numerous other control strategies.
the FGR line during the purge cycle. Parallel positioning
systems will modulate the control valve shut during purge Single Point Positioning (Linkage)
and do not require a shut-off valve. Single point positioning systems use a single modulating
Motor motor to vary the fuel input, air ow and other ow
changes like FGR and atomizing air ow. Linkage is used
to connect these ow control elements together to provide
a unied fuel-air-ratio control system. Other elements in
this system would typically include a jackshaft, fuel cam
and modulating motor.
Jackshaft
FGR Valve The jackshaft is a shaft that is used to tie the fuel, air
and FGR valves together with linkage, to provide a
uniform change in the ow as the burner modulates. A
modulating motor is used to drive the jackshaft, driven by
the requirement for heat in the system and as allowed to
Valve Stem operate by the ame safeguard.
Horizontal The jackshaft is a 3/4 shaft that rotates and is mounted
in bearing supports. This provides a common means of
modulating all of the valves from a single drive mechanism.
Drive Linkage The length can vary to meet overall dimensions and
individual drive arms are used to connect to each valve.
Fuel Cam
Figure B-24 FGR Shutoff Valve A fuel cam is a mechanical linkage that allows for small
fuel rate changes without changing the linkage setting.
The shutoff valve should be installed in the FGR duct
It can simplify the fuel-air-ratio adjustments during the
close to the boiler connection. The valve stem should
burner setup (Figure B-3 and B-4).
be horizontal, to prevent condensate from building in the
shaft bore, causing it to seize. Modulating Motor
HDS Manual Page 16 Section B - Component Descriptions
The jackshaft is driven by a modulating motor that rotates 90o something under 90o .
to modulate the burner input from minimum rate to maximum
rate. Linkage is used to connect the modulating motor to the This potentiometer is located in the control panel and is
jackshaft and the fuel cams along with connecting the fuel, adjusted at startup to provide the correct oil ring rate.
air and FGR control valves to the jackshaft. Parallel Positioning System (Linkageless)
The standard modulating motor has two internal proving The Posi-Control system is a parallel positioning system
switches. One switch, the Low Fire switch, proves the low (linkageless) that uses individual actuators for each
re position where the burner will light. This is also the control valve and a computer controller that directs each
position the modulating motor will travel to when the burner actuator to provide the input change from minimum to
shuts down. The second switch, the High Fire Purge switch, maximum capacity. The control provides more exibility
proves the high re purge position during pre-purge. in setting each fuel rate (Figures B-1 and B-2).
In the initial planning of the installation, several items must The location of the combustion air source must not create
be covered: a condition where the burner or vessel comes in contact
a. Prior to starting the installation, all the technical litera- with very cold air (under 40oF) or causes large uctuations
ture should be collected and reviewed to identify require- in combustion air temperature. Cold air can cause con-
ments. As a minimum, these should include the Installa- densation below 40oF in a standard burner and below 50oF
tion and Operating Manuals for the burner and vessel, the when equipped with FGR.
wiring diagrams, the fuel schematics and technical litera-
There should be no large variations in combustion air tem-
ture on supplied controls.
perature supplied to the burner. The burner can be adjust-
b. A general overview of the equipment should be made
ed to handle temperature variations of 30oF, but may not
prior to the installation. Check the location of access
be able to handle temperature swings of 50oF without com-
doors and insure that they will be able to function properly
bustion deterioration. In conditions where this can occur,
when all equipment is installed. The burner and control
some conditioning of the combustion air must be done by
panel should have sufcient clearance for the operator to
location, bafing or pre-heating of the air. Seasonal tune-
monitor, inspect and perform maintenance. A minimum
ups can also help cover the larger temperature swings.
clearance of 24 inches all around the burner should be
d. There are several people that should be notied before
provided for maintenance. The burner drawer and oil gun
starting, including the owners representative, the mechani-
is pulled out from the front of the burner and there needs
cal contractor, the electrical contractor, the service organi-
to be sufcient space for this activity. An HD5 requires 42
zation and the boiler manufacturer.
inches, an HD7 requires 46 inches and an HD9 requires
e. DO NOT USE TEFLON TAPE or compounds with Tef-
54 inches of clearance behind the backplate.
lon content as an oil or gas pipe sealant. Teon can cause
c. A source of combustion air must be provided for the
valves to fail creating a safety hazard. Warranties are nul-
burner. Local codes often determine minimum require-
lied and liability rests solely with installer when evidence
HDS Manual Page 19 Section C - Installation
of Teon is found. the frontplate is used to clamp the frontplate to the vessel.
f. Installer must clearly identify the main electrical power Bolts on the frontplate are used to clamp the burner to the
disconnect and the manual shutoff valve on the gas supply frontplate. High temperature berglass rope gaskets are
drop line to the burner. used to seal each connection.
2. Refractory Frontplate A rope gasket is applied to full surface of the frontplate
mounting ange (it must cover the full face of the ange) to
The refractory front plate is used to adapt the burner to the seal the refractory front plate to the vessel (a spray adhe-
vessel. While the specic dimensions will vary with differ- sive can be used to hold the gasket in place temporarily).
ent vessel and burner congurations, all will be similar in The refractory frontplate is inserted into the furnace and
shape to that shown in Figure C-1. A mounting ange on clamped to the end of the furnace. The refractory must
45-60o 12 12 23.3
Minimum
1/4 Steel
Must Extend
2 Past
Figure C-1 Tubesheet
Refractory Frontplate
be centered in the furnace, so that the gap between the A rope gasket is applied to the burner mounting ange,
refractory and furnace is uniform. Clamp the frontplate to completely covering the ange (the 3/8 berglass gasket
the furnace with uniform tension on the bolts, starting with is provided with the burner). A ceramic insulation is placed
a low torque for all bolts and then repeating with higher on the end of the burner, as shown in Figure C-2. A spray
torque levels until tight. adhesive can be used to hold these in place prior to instal-
lation.
Pack the gap between the refractory and furnace with ce-
The burner is then inserted into the frontplate, centered
ramic blanket insulation (or ceramic rope) for at least 4
evenly (the 2 inch recess will center the burner) and
inches from the end of the refractory (Figure C-3). This
clamped into position. Clamp the burner to the frontplate
can be accomplished by reaching in from the center hole,
with uniform tension on the bolts, starting with a low torque
and placing the insulation between the refractory and fur-
for all bolts and then repeating with higher torque levels
nace, then pushing it in with a block.
until tight.
3. Burner Mounting
Normally
open vent
valve
Burner
The selection of the oil pipe line size is critical for proper 700-1000 1 1 1 2 2
operation of the system. For simple systems, Figure C-
Burner
Figure C7
Oil Pressure
Typical #2 Oil Field Piping Regulator
Oil Pump
Vacuum
Shutoff Valve Gauge
Strainer
Supply to Pump
Check Valve
(See Note) Shutoff Valve
Return to Tank
Note: Location of Check
Valve Varies with System.
Fuel Oil Tank Check Valve is Usually
Located as Close as Pos-
sible to Tank Outlet.
Gate Valve
Oil Pump #2 Check
Valve
Gate Valve
Vacuum Gauge
Boiler #2 Burner #2 Strainer
Oil Valve
Pressure Regulator Gate Valve
Check Valve
Supply
Figure C8
To Tank
Oil Piping, Multiple Burners Return
Gate Valve
Boiler 1 Boiler 2
Pressure Gauge
Check Valve
Burners
Figure C-9
Oil Schematic, Multiple Burners with Remote Oil Pumps
be 50% over the nozzle capacity. See section A for ratings. Long rad 90o elb
7.1 8.7 10 14 17 20 23 27
(rad = 8 x dia)
The general arrangement for this system is shown in Figure Mitered 45o
D-4. A supply and return line connection are required, along elbow
3 6 8 10 12 14 16 18
Drain
Line
Alternate
Construc-
tion Using
T
Eccentric
45o
10o Max
Figure C 14
Method of Connecting D
45o 45o
Breechings and Stacks
Damper
Breeching D
Page 27 Hold
on One
Plane
Cleanout
Motorized
Gas Pressure Shutoff Shutoff
Regulator Valve Manual Ball
Valve
Valve
L M M H
Customer Gas Burner FM & IRI - 5,000 to 12,5000 MBH
Supply
POC
Solenoid
Shutoff
Valve
L S M H
Customer Gas Burner U.L. - 12,501 to 12,600 MBH
Supply
POC
Pressure Test
Connection
Vent
Valve
L M M H
Customer Gas Burner FM & IRI - 12,501 to 12,600 MBH
Supply
POC POC
Gas Pressure
Regulator
(Intergral to
Shutoff Valve)
L M M H
Customer Gas Burner U.L., FM & IRI - >12,600 MBH
Supply
POC POC
Not Used on
U.L. System
Figure D-1
Typical Gas Train Arrangements
Figure D-1 shows the common gas trains arrangements lating. The two gas safety shutoff valves are either mo-
used on the HDS burner line. There may be other local torized or solenoid type and are controlled by the ame
or job site requirements that can alter the components in safeguard to provide safe control of the fuel ow.
addition to those outlined in this summary.
The gas control valve is a buttery valve used to control
All gas and oil systems for the HDS burner are full modu- the ow of gas from the low re to the high re input. The
HDS Manual Page 29 Section D - Fuel and Electrical Systems
buttery valve is driven by a fuel cam (linkage system) or the required ow to the burner with this available pressure.
a direct coupled actuator. There are different types of gas The job site supply pressures must be consistent with the
control valves used, which may use mechanical low re pressures listed on the burner material list.
stops and/or may be internally ported as a smaller size.
High turndown burners will require smaller valves with The regulated gas pressure is that pressure required to
higher pressure drops to provide adequate control at low overcome the pressure drops in the piping, ring head and
re. furnace pressure to deliver the required ow at high re.
Usually, one of the rst steps in setting up gas combustion
A vent valve is provided in some applications to allow gas is to adjust the regulator to get rated capacity. This regu-
that may leak past the rst valve to escape to a safe point lator is usually at the beginning of the train, but in some
of discharge. Vent valves are not used on propane cases, it can be integral to the second shutoff valve. The
fuels that are heavier than air or fuels that could be pressure drops and regulated pressures will be different in
toxic. these two designs.
A gas pressure regulator is used to provide a constant The manual valves are provided to lock out the fuel ow
supply pressure to the gas train and buttery control valve. during off times and during initial startup checkout. They
This constant pressure through a variable orice in the gas provide an added level of safety and can simplify mainte-
control valve obtains consistent gas ow rates. The regu- nance.
lator must be capable of operating through the full range of
ows and pressure with consistent and steady pressures. The gas piping can play a critical role in the operation of
The regulator may be located upstream of the safety shut- the system. Throughout the system, the piping must carry
off valves or integral with the second safety shutoff valve. the required ow without signicant loss of pressure. If
the drop is too high, there may not be enough pressure to
The high and low gas pressure switches are used to de- operate the burner a full capacity. This is especially true
tect an improper gas pressure situation and will prevent between the gas train and the burner, where the pressure
the burner from ring under these conditions. The low gas is lowest. The piping between the train and burner should
pressure switch is located near the supply of gas to the have a minimum number of elbows and / or turns to pre-
gas train, to detect a loss of supply pressure. The high vent high pressure drops.
gas pressure switch is located before the metering valve
to detect a surge in pressure to the burner. 2. Gas Pilot
The gas train is designed to work with the pressure avail- Figure D-2 show the typical gas pilot systems. Like the
able at the job site. This supply pressure generally refers gas trains above, they have the common components of
to the pressure available at the entrance to the gas train, a pressure regulator and shutoff valve. The gas line con-
which is the pressure supplied to the gas trains shown in nects upstream of the gas pressure regulator in the gas
Figure D-1. The supply pressure may vary depending on train.
the operation of the unit, in which case a minimum and The gas pilot is positioned behind the diffuser, with the
maximum pressure are needed to dene the supply pres- pilot ame passing through the diffuser. The ame must
sure. The maximum pressure is the static pressure, or the be large enough to pass in front of the scanner tube for
pressure in the line when there is no ow. The leading the Flame Safeguard to detect the pilot ame and allow
components of the gas train are selected to operate up the burner to start. This also insures that there is sufcient
to these pressures. The minimum, or dynamic pressure pilot ame to ignite the main fuel.
is that pressure available when the unit is operating a full
rate, or the reduced pressure due to the ow in the line. The gas pilot can operate with either natural gas or pro-
The gas train is sized to this pressure, so that it can deliver pane. Different internal orices are used to regulate the
Manual 1/4
Gas Pressure Shutoff
Turn
Manual Ball Regulator Valve (Canada Application
Valve Only)
Valve
Customer Burner
For all Applications
Gas Supply Except IRI >12,5000 MBH
Optional
Low Oil Pres-
sure Switch Pressure Solenoid Solenoid
Gauge Valve Valve
Modulating Pressure
Check Oil Meter- Gauge
Check Relief Valve
Valve ing Valve
Valve
Return to Tank
(No Manual
Valves in This
Line) Note: Oil Pump shipped loose
Typical Field Supplied Items - By Others
for eld piping & mounting
Figure D-3
Pressure Atomized Oil Schematic
A standard oil pump provides oil at a pressure of about Two check valves are provided in the system downstream
300 psi to the nozzle. At high re, the bypass is closed of the nozzles to prevent the possible reverse ow of oil
or nearly closed and all of the pressure is available to the from the return line. One valve is located in the oil gun
oil nozzle for maximum ow. As the burner modulates to and the other is located on the burner piping.
low re, the oil metering valve is opened, causing some oil
to ow through the metering valve and to the return line. A strainer, manual valve and second check valve should
As the metering valve continues to open, more oil is by- be installed in the eld piping to allow proper operation of
passed and the ow through the nozzle continues to drop. the system (Figure D-3).
At high re, the pressure in the return line is about 150 psi. 4. Air Atomizing #2 Oil
At low re, this pressure drops to about 65 psi. Reducing
the pressure too low can result in poor atomization and a An air atomizing system uses compressed air to atomize
smoky re, which limits the turndown to about 3:1 to 4:1. the oil. The oil pump and oil pressure regulating valve are
On standard linkage systems, with combination gas, the optional and may be provided by others.
gas turndown will be about the same as the oil turndown, Figure D-4 shows a schematic of the air atomizing #2 oil
based on the air damper positions. Optional multi-point system. The oil nozzle has two inputs, oil and air. Oil is
modulation motors or parallel positioning systems can be supplied to the system at 125 PSIG. An optional remote
used to improve the turndown of gas ring on a combina- pump assembly may be used, or it can be provided by
tion burner. other systems. In either case, a backpressure regulator is
The oil pump is supplied as a separate assembly that in- required to provide a constant pressure to the system.
cludes the pump, backpressure regulator, motor, coupling, The oil metering valve regulates the ow of oil to the noz-
interconnecting housing and motor (Figure B-16). An op- zle and is used to vary the oil ow rate from low to high re.
tional gauge may also be provided. The motor starter for Modulation is obtained by a fuel cam (linkage system) or
the pump is included in the control panel. by a direct drive actuator.
The safety shutoff valves determine if the burner is al- An air compressor is used to supply air for atomization.
lowed to re on oil, as controlled by the ame safeguard The air compressor is provided as a separate assembly
system. These valves are the solenoid type except units and is eld piped to the burner. The compressor should be
over 89 GHP with FM or IRI insurance, where the valves located as close as possible to the burner to prevent loss
are motorized with POC (Proof of Closure) switches to of airow. Also, the piping should be done to minimize the
prove closed position prior to allowing the unit to operate. use of elbows and turns that result in pressure loss. The
The low oil pressure switch is used to prove sufcient oil following chart should be used to determine the minimum
supply to the burner. It is adjusted to a pressure that is size (Figure D-5).
below the minimum pressure expected at that location in
the system.
HDS Manual Page 31 Section D - Fuel and Electrical Systems
Safety
Air Filter Valve
Mufer
Air Low Atomizing (Modulating
Chamber Pressure or Fixed) Air
(200-350 Switch Bleed Valve
Bhp only) Gauge
Compressor Nozzle
Check
Shutoff Valves Valve Oil Gun Assembly
Modulating Oil Oil Gauge
(Sol. Operated)
Metering Valve Flexible
Ball Valve Metal Hoses
Rising Temp.
or Pressure
Burner Off 0% (Burner ON) (Burner OFF) (Burner OFF)
Figure D-8
Operating and Modulating Control
SCANNER
TUBE
Figure E-1
Burner Drawer Setup
4. Fuel, FGR and Air Control Figure E-3 shows the internal settings of the multiposi-
The fuel and air valves have initial positions set at the fac- tion modulation motor. Each adjustable cam setting is
tory. Differences in air density, fuel properties and supply related to an elecetrical connection (or circuit in motor).
pressure will require tuning of the burner. The initial posi- These circuit numbers are listed on the wiring diagram
tions of the air damper, FGR valve, gas valve and oil valve so that the low and high points of each fuel are identi-
should be adequate for initial startup, but must be checked ed. These would be adjusted independently to obtain
so that movement did not occur during shipment or instal- the input rates. The valves and linkage should operate
lation. If this is a linkage burner, the linkage should be ad- smoothly without strain or jerky actions. If this occurs,
justed to allow for modulation from low to high re, with each check for binding linkage and rod ends that are not with-
valve opening 45 to 90 degrees. This should be checked by in their range of motion and readjust as required.
12 Head 16 Head
Dim Initial Range Initial Range Description
A 1 1/4 - 1 1/2 1 1/4 - 1 1/2 Diffuser n to gas spud
B 1/2 No Adjust 1 No Adust Pilot to diffuser
Figure E-2 Burner Drawer
C 1 0 - 2 1 1/2 0 - 2 1/2 Oil nozzle to difusser Setup Dimensions
D 3 * 3 * Diffuser to gun tube
(See Figure E-1 for Dim)
E 1/8 No Adust 1/8 No Adjust Scanner tube to diffuser
F 2 1/2 No Adjust 2 1/2 No Adjust Pilot to scanner tube
G 1 1/2 0 - 3 1 1/2 0 - 3 Backplate to air straightner
H 30o Any Angle 30o Any Angle Straightner angle from vertical
* Must be behind nozzle tip and hold diffuser clamp
Cam
Return
Cam Set Screws Springs
ion
ire
it
hF
Pos
Hig ition
s Jack
Po
Fire
Shaft
Adjusting Screws
Low
Flexible Strip
Aluminum Strip
End Screws
Spring
End Screw
Adjusting Nut
Cam Follower
Retention Roller Washers
Plate
Roller Cam Follower
Figure E-5
Fuel Cam Adjustment
HDS Manual Page 36 Section E - Priliminary Adjustments
Raw Gas Tube A
ew
Vi
30o
Wire Mess
1/16
Tip of Electrode
Differential
Use Pressure
Screwdriver
to adjust
Regulator
Figure E 9
Main Gas Pressure Regulator Adjustment Figure E - 12 Low Oil and Atomizing Air Pressure
Switches
The low gas pressure switch (if provided) should be set
for an initial value of 50% below the lowest expected gas 10. Air Proving Switch
pressure. The high gas pressure switch (if provided) should The air proving switch has been adjusted at the factory for
be initially set at 50% above the highest valve expected at an initial setting. If this switch trips during initial startup,
that point. See section B for location of switches (Figure turn the adjustment screw ccw two full turns to reduce the
E-10). trip pressure setting (Figure E-13).
Adjusting
Panel
Knob
Adjusting
Screw
Removable
Cover
Air Proving
Switch
The cam is used to adjust the intermediate fuel rate with 4. FGR Adjustments
the low and high re settings done by the linkage connec- Flue gas is recirculated back into the burner to reduce
tions. The intermediate rates can be adjusted by turning the the ame temperature, which reduces the NOx level.
adjusting screws in the clockwise direction to increase fuel High quantities of ue gas result in lower NOx levels,
input and decrease the % O2 level in the ue gases. Turn- but can also result in ame instability if there is too
ing the adjustment screws counterclockwise will decrease much FGR. Natural gas fuel can handle larger quanti-
fuel input and increase % O2 in the ue gases. ties of ue gas than oil and can have much lower NOx
The following guidelines should be used for adjusting the levels as a result. Generally, the NOx levels only apply
cam: to gas ring and oil ring is not adjusted for NOx levels.
a. When adjusting the screws, the adjacent screws must There may be exceptions to this, and the orders details
also be adjusted to provide a smooth contour from screw to should be reviewed to identify any special combustion
screw. When complete, the exible strip between the adjust- requirements.
ing screws and the roller must come in contact with each Dual fuel units may need additional adjustments and
screw, providing a smooth transition from low re to high compensation to handle the different FGR rates be-
re. tween natural gas and #2 fuel oil. Units that require
b. The end screws (or nuts) can be adjusted to hold the strip gas NOx levels above about 45 ppm can operate with
against the screws, but should not deform the strip. the same quantity of FGR on both fuels and no ad-
c. There should be no upsets in the prole, where the ex- ditional controls or adjustments are needed. Burners
HDS Manual Page 41 Section F - Startup and Operating Instructions
equipped with Posi-Control can be adjusted for individual air inch head (identied with the letter C in the model
and FGR settings on both fuels and can easily handle these number).
variations, even with lower NOx levels. Linkage burners op- Mark the angle position of the straightner tube (Dim.
erating at 30 ppm NOx (natural gas) are equipped with a H, Figure E-1) and measure its distance out from the
potentiometer in the control panel that will allow the shut-off backside to the end of the tube (Dim. A, Figure F-2).
valve to partially open and allows a small amount of FGR to Mark the distance of the oil gun tube from the back-
ow when ring oil. This keeps the oil inputs close to the gas plate.
input (lower FGR rates increases the combustion air rate). Mark the distance of the scanner to the backplate (Dim
The oil combustion is generally better when FGR is used at C, Figure F-2).
low rates resulting is a lower NOx level. Linkage levels with Mark the distance of the gas pilot line to the backplate
NOx levels under 30 ppm will also use a multiple modulation (Dim D, Figure F-2).
motor to provide separate gas and oil low re andhigh re
positions. a. To adjust the air straightner position, (not available
on the 20 inch head). This is usually done to improve
Linkage dual fuel units may also be equipped with the op- low re ame shape, to obtain more uniform ame ap-
tional multiple set point (Landis) modulation motor in addition pearance.
to the above potentiometer. This motor allows for different Loosen the two set screws located on the square boss
low and high re settings on gas vs oil to obtain the correct welded to the backplate.
airow for each fuel and optimize the turndown on gas. Loosen the two setscrews in the straightner, locking
the straightner to the oil gun tube.
The quantity of recirculated ue gas can be adjusted with the Adjust the straightner tube, moving in, out or rotate the
inlet tube on the FGR line. To reduce the quantity of FGR, tube to obtain the best combustion.
push the tube into the FGR line (loosen the two set screws Tighten the four screws from the above steps.
to adjust the position of the tube, and tighten when done). b. To adjust the diffuser to gas spud dimension:
Moving the tube into the air stream will increase the quantity Measure the dimension from the backplate to the end
of FGR. An access cover is provided opposite the FGR line of the oil gun tube. This dimension, along with the intial
for this adjustment. position measured in gure F-2 will determine the limit
On a dual fuel unit, the natural gas should be done rst to of the adjustment. For example, if the diffuser is 1 inch
properly set the FGR inlet tube. Once gas is setup, oil can behind the diffuser, then it can be adjusted in 3/4 inch or
be set. out 1/2 inch to stay within the limits of 1/4 inch to 1 1/2
inch diffuser to gas spud dimension.
For dual fuel linkage systems, the following guidelines Loosen the two setscrews locking the straightner tube
should be used: to the oil gun tube.
A 60 ppm system can be adjusted with the same FGR rate Loosen the two setscrews locking scanner tube to the
on both fuels. The FGR control valve is set on gas and oil backplate. Move the scanner in the maximum amount
follows that setting. adjustment, (3/4 inch in our example) and temporarily
A 30 ppm system uses the FGR limiting potentiometer lock in place.
(located in the control panel) to obtain a partial ow of FGR Loosen the two setscrews locking the pilot gas line to
when ring oil. The FGR control valve is set when ring the backplate. Pull the pilot out the maximum amount
gas. The FGR limiting potentiometer is adjusted to improve allowed in the diffuser movement (1/2 inch in our ex-
combustion but not cause instability. The combustion needs ample).
to be checked at several ring rates. Adjust the diffuser by moving the oil gun tube in and
Under 30 ppm, separate gas and oil operating pointsare out the amount determined above. Do not rotate the
established in the modulating motor. Parallel positioning tube or the alignment of the components could be upset.
(linkageless) systems allow all of the valves to be positioned When the best position is found, lock into place with the
independently for each fuel. For this reason, the setup se- two setscrews on the air straightner tube.
quence can be more exible. Determine the change in the diffuser position and
5. Burner Drawer Adjustments move the scanner and gas pilot line to the same rela-
tive point. For example, if the new diffuser position is
The burner drawer has several adjustments built into the 1/2 inch in from the original setting, then the pilot and
design that allow the combustion to be tuned during opera- scanner tube would each be positioned 1/2 inch closer
tion. While this can simplify the combustion tunng process, to the backplate to maintain their same relationship to
care must be used to retain the relative position of other the diffuser.
components during this sequence. If these adjustments are Tighten the setscrews on the pilot line and scanner
required, follow the sequence listed to perform the adjust- tube.
ments. c. To adjust the oil nozzle to diffuser position:
Lossen the two setscrews locking the oil gun lines to
Before any adjustments are made, the position of each com- the aluninum end cap of the oil gun.
ponent must be marked. A felt tip pen or a combination of Adjust the oil nozzle to obtain the best combustion.
masking tape and another type of pen can be used. Watch for spray back on the diffuser when the gun is
NOTE: There is no external air straightner tube on the 20
HDS Manual Page 42 Section F - Startup and Operating Instructions
Straightner Tube
A
Set Screws
B
Oil Gun
Tube Set
Screws
Oil Line
Set Screws
Oil Gun Tube
Scanner Tube
Scanner Tube Set
Screws D
Gas Pilot
C
Tube Set
Screws
Figure F-2
Drawer Assembly Adjusments
pulled too far back. The ame may appear good but carbon Combination burners, ring both gas and oil, require
will quickly develop on the diffuser. some compromises in the setup because they share
Tighten the two setscrews on the oil tubes locking it into common controls for both fuels. In this case, linkage
position. units must have the gas input adjusted to match the oil
inputs because there is little exibility in adjusting the oil
If the burner drawer needs to be removed for better access rates. Oil will be setup rst and will set the air damper
to components, follow the following steps: positions to support the low and high re oil inputs. Fol-
low the procedure outlined in section 11 to complete the
a. Disconnect the scanner by screwing it off of the scanner oil setup. Then setup the gas input as dened in section
tube. In some cases, the scanner simply pulls out, with a 10, using the air damper positions dened by oil, and ad-
spring tension. Secure the scanner so that it is protected justing the gas input to match the air damper settings.
from shock.
b. Disconnect the gas pilot line. Move the pilot line so the If the burner is equipped with an optional multiple set-
drawer can be pulled out without interference. point modulating motor or parallel postioning, the low
c. If equipped with oil, disconnect the oil lines, and move and high re rates, as well as lightoff rates, can be set
them out of the way to allow the drawer to be pulled. independently for each fuel. In this case, the gas is ad-
d. Disconnect the ignition cable from the transformer. It is justed rst, to set the air damper locations for gas ring,
attached with a thumb screw nut. as dened in Section 10. Once gas is set, oil is setup as
e. Loosen and remove the nuts on the burner drawer. dened in Section 11, except that the multipoint modu-
f. Pull the drawer out, holding the drawer centered in the lating damper motor is adjusted to bring the low re air
opening to prevent it from hanging up while being pulled setting to match the oil needs.
out. There are several different options available that can al-
g. Set the drawer down horizontally, do not set it on the dif- ter the exact setup details, and these must be evaluated
fuser as it may atten some ns or change positions. prior to startup so that the procedures can be adjusted
To re-install the burner drawer, simply work the procedure accordingly. The procedures given are for linkage sys-
in reverse. tems. Parallel positioning (linkageless) systems allow
for much more exibility in the fuel, air and FGR settings
6. Single Fuel Setups on each fuel, and can be tuned to better match each fu-
els needs. The setup details for linkageless controls will
Single fuel burners can be adjusted following the procedures follow the same general sequence, but differ in specics
outlined in Section 10 for gas ring; Section 11 for pressure for setting the valve positions.
atomized oil and Section 12 for Air atomized #2 oil.
8. Combination Gas and Air Atomized #2 Oil
The procedures for each of the systems (linkage, cams,
FGR) must be completely understood and followed as part Combination burners, ring both gas and oil, require
of the setup process. some compromises in the setup because they share
common controls for both fuels. Air atomized #2 oil r-
7. Combination Gas and Pressure Atomized Oil ing can have turndowns and air damper positions very
NOTE: The listed manifold pressure is only an ap- With a gauge or manometer at the same location as the
proximate value and can vary with operating condi- high gas pressure switch, modulate the burner to deter-
tions and normal tolerances. The fuel ow rate must mine the ring rate with the highest gas pressure.
be measured to obtain an accurate input value. At the highest gas pressure,adjust the high gas pressure
setting down until the switch opens and causes the burner
r. Adjust the air damper to obtain the correct O2 level.
to shutdown.
s. If equipped with FGR, adjust the NOx level to be about
From the scale reading of the switch,adjust the setting to
10% below any guaranteed NOx performance. A balance
a pressure that is 10% higher then the shutdown pressure.
of the FGR control valve and air damper are required to
For example, if the switch opened at 10 inches as indi-
obtain the nal result, as each can impact the other. If
cated on the high gas pressure switch, the switch should
the FGR valve does not travel at least 50 degrees, the
be adjusted to a reading of 11 inches.
FGR inlet tube should be readjusted (pushed into the FGR
Remove the gauge or manometer and plug the open-
pipe).
ing.
t. Modulate the burner to low re, adjusting the O2 level
Cycle the burner on and off to determine if the limit works
as the burner modulates.
properly.
u. Adjust the low re input, using the fuel cam and air
If the limit causes nuisance shutdowns because of small
damper adjustments. The linkage may need to be read-
pressure changes during startup, increase the pressure
justed to obtain the correct relationship between the fuel
setting an additional 5%.
valve and air damper. (Figure F-1)
z. The burner should be operating at low re to adjust
v. Re-adjust the midre points for the correct O2 level.
the air proving switch. Turn the adjusting screw cw (in)
w. If equipped with FGR, adjust the NOx levels at low
until the burner trips out (shutdown caused by the air ow
and midre rates to be about 10% under the guaranteed
switch). Turn the adjustment screw ccw (out) 1 1/2 turns
levels.
from the point of shutdown. Check the operation at higher
x. Adjust the low gas pressure switch to be 10% below the
rates.
lowest expected gas pressure.
With a guage or manometer at the same location as the 10. Pressure Atomized Oil Setup
low gas pressure switch, modulate the burner to deter-
The pressure atomized oil system has a limited range of
mine the ring rate with the lowest gas pressure.
adjustment for low and high re, dictated by the operation
At the lowest gas pressure,adjust the low gas pressure
of the oil nozzle. The combustion air and FGR must be
setting up until the switch breaks and causes the burner
adjusted to match these rates.
to shutdown.
From the scale reading of the switch,adjust the setting to If the burner is equipped with FGR, and is a linkage sys-
a pressure that is 10% lower than the shutdown pressure. tem, the type of FGR control must be determined prior
For example, if the switch opened at 10 inches as indi- to starting. If this is a dual fuel burner, the FGR rate is
cated on the low gas pressure switch, the switch should determined by the NOx performance on gas. A 60 ppm
be adjusted to a reading of 9 inches. burner will operate with the same FGR rate on gas and oil.
Remove the gauge or manometer and plug the open- A 30 ppm unit will use the limiting potentiometer to slightly
ing. reduce the FGR rate on oil ring. For Oil only combustion,
Cycle the burner on and off to determine if the limit works the NOx level will be given on the burner detail sheet, and
properly. should be used to set the FGR control valve.
If the limit causes nuisance shutdowns because of small a. Place the burner switch in the OFF position.
pressure drops during startup, reduce the pressure setting b. Place the Auto-Manual switch in the manual position.
an additional 5%. If this is a combination fuel burner, make sure the fuel se-
y. Adjust the high gas pressure switch to be 10% above lector switch is on OIL.
the highest expected gas pressure. c. Place the manual ame control potentiometer in the
HDS Manual Page 45 Section F - Startup and Operating Instructions
min (low re) position. added turbulence but not high enough to impact ame sta-
d. Turn the electrical power for the burner, boiler and re- bility. A balance of the FGR control valve and air damper
lated components on. are required to obtain the nal result, as each can impact
e. Verify that the oil metering valve is nearly opened (the the other. If this is a 30 ppm system, the FGR limiting pot
valve will be closed at high re). should be adjusted to reduce the FGR rate for stable com-
f. Turn the burner switch on. This will start the blower mo- bustion, with the FGR control valve set when ring gas. If
tor and initiate the purge cycle. this is a 60 ppm system, no adjustment is necessary.
g. When the prepurge sequence is complete and the low o. Modulate the burner to low re, adjusting the O2 level
re start switch is made, the pilot valve will open and the as the burner modulates.
pilot ame should be visible through the burner sight port. p. Adjust the low re input, using the fuel cam and air
h. When the pilot ame is established, the ame safe- damper adjustments. If the burner is equipped with FGR,
guard will energize the main oil valves (indicated with the adjust the NOx level according to the type of system (limit-
Fuel Valve Light), and the burner should ignite at low re. ing potentiometer or matching gas).
This operation of the main fuel valves must be visually q. Re-adjust the midre points for the correct O2 levels.
checked by observing the valve stem moving up with a The linkage may need to be readjusted to obtain the cor-
motorized valve or hearing the clicking noise from a sole- rect relationship between the fuel valve and air damper.
noid valve. (Figure F-1)
NOTE: If the burner is not operating as indicated, follow r. If equipped with FGR, adjust the NOx levels at low and
the troubleshooting steps to determine the problem and midre rates to be about 10% under the guaranteed levels
corrective action. or as required for the gas ring.
i. The main ame may not light on the rst attempt, be- s. The burner should be operating at low re to adjust
cause it must ll the oil lines before providing oil to the the air proving switch. Turn the adjusting screw cw (in)
nozzle. Press the reset button on the ame safeguard to until the burner trips out (shutdown caused by the air ow
restart the burner. switch). Turn the adjustment screw ccw (out) 1 turns
WARNING from the point of shutdown. Check the operation at higher
DO NOT ATTEMPT TO START THE BURNER WHEN rates.
EXCESS OIL HAS ACCUMULATED, WHEN THE UNIT t. Adjust the oil pressure switch to trip and shutdown the
IS FULL OF VAPOR, OR WHEN THE COMBUSTION burner at a pressure that is 10% lower than the supply oil
CHAMBER IS HOT. pressure.
j. After a few seconds, the combustion analyzer should 11. Air Atomized, #2 oil Setup
have an accurate reading of the O2 in the stack. The O2 The air atomized oil system has the potential for a large
level should be between 4% and 8%, and the nozzle oil turndown range similar to gas and has the potential to be
pressure should be between 50 and 70 PSIG. Do not at- adjusted to different low re rates. See the burner name-
tempt to ne tune combustion until the high re has been plate for details on actual rates for this burner.
set. If the burner is equipped with FGR and is a linkage sys-
If the burner is equipped with FGR, the FGR control valve tem, the type of FGR control must be determined prior to
should be set for the approximate NOx level required. starting. If this is a dual fuel burner, the FGR rate is deter-
1. Turning the cam screw in will add fuel, making it richer mined by the NOx performance on gas. A 60 ppm burner
and reducing the O2 level. will operate with the same FGR rate on gas and oil. A 30
2. Turning the cam screw out will reduce the fuel input, ppm unit will use the limiting potentiometer to slightly re-
increasing the O2 level. duce the FGR rate on oil ring. For Oil only combustion,
3. The air damper should be positioned for the correct the NOx level will be given on the burner detail sheet, and
low re settings. should be used to set the FGR control valve.
k. Operate the burner until the boiler is warmed up, and a. Place the burner switch in the OFF position.
near the operating pressure or temperature. b. Place the Auto-Manual switch in the manual position.
l. Increase the ring rate, using the manual potentiometer, If this is a combination fuel burner, make sure the fuel se-
while monitoring and adjusting the O2 level. Adjust the lector switch is on OIL.
cam as needed to reach the high re input. c. Place the manual ame control potentiometer in the
If the burner is equipped with FGR, adjust the FGR control min (low re) position.
valve as required to maintain the NOx level. d. Turn the electrical power for the burner, boiler and re-
m. At high re (end of the modulating motor travel), ad- lated components on.
just the high re input (open or close the fuel valve) to e. Verify that the oil metering valve is at the nearly closed
match the maximum input listed on the rating label. The position.
fuel metering valve should be nearly closed (or closed) at f. Turn the burner switch on. This will start the blower mo-
this point and the nozzle pressure should be about 150 tor and initiate the purge cycle.
PSIG (return line). g. When the prepurge sequence is complete and the low
n. If equipped with FGR, adjust the NOx level to be about re start switch is made, the pilot valve will open and the
10% below any guaranteed NOx performance or if perfor- pilot ame should be visible through the burner sight port.
mance guarantee exists adjust the FGR to provide some h. When the pilot ame is established, the ame safeguard
Page 46 Section F - Stratup and Operating Instructionsl
HDS Manual
will energize the main oil valves (indicated with the Fuel the other. If this is a 30 ppm system, the FGR limiting
Valve Light), and the burner should ignite at low re. This pot should be adjusted to reduce the FGR rate for stable
operation of the main fuel valves must be visually checked combustion, with the FGR control valve set when ring
by observing the valve stem moving up with a motorized gas. If this is a 60 ppm system, no adjustment is neces-
valve or hearing the clicking noise from a solenoid valve. sary.
NOTE: If the burner is not operating as indicated, follow the o. Modulate the burner to low re, adjusting the O2 level
troubleshooting steps to determine the problem and correc- as the burner modulates.
tive action. p. Adjust the low re input, using the fuel cam and air
WARNING damper adjustments.
DO NOT ATTEMPT TO START THE BURNER WHEN q. If the burner is equipped with FGR, adjust the NOx
EXCESS OIL HAS ACCUMULATED, WHEN THE UNIT level according to the type of system (limiting potentiom-
IS FULL OF VAPOR, OR WHEN THE COMBUSTION eter or matching gas).
CHAMBER IS HOT. r. Re-adjust the midre points for the correct O2 levels.
The linkage may need to be readjusted to obtain the cor-
i. After a few seconds, the combustion analyzer should rect relationship between the fuel valve and air damper.
have an accurate reading of the O2 in the stack. The O2 See Figure F-1.
level should be between 4% and 8% (see Figure F-3 for O2 s. If equipped with FGR, adjust the NOx levels at low
rates), and the nozzle oil press should be between 5 and 15 and midre rates to be about 10% under the guaranteed
PSIG (see Figure F-4). Do not attempt to ne tune combus- levels or as required for the gas ring.
tion until the high re input has been set. t. The burner should be operating at low re to adjust
If the burner is equipped with FGR, the FGR control valve the air proving switch. Turn the adjusting screw cw (in)
or limiting potentiometer should be set for the approximate until the burner trips out (shutdown caused by the air
NOx level required. ow switch). Turn the adjustment screw ccw (out) 1
Turning the cam screw in will add fuel, making it richer turns from the point of shutdown. Check the operation
and reducing the O2 level. at higher rates.
Turning the cam screw out will reduce the fuel input, in- FIGURE F-4
creasing the O2 level. Typical Atomizing Air Pressure
The air damper should be positioned for the correct low
re settings.
% Rate Minimum
The atomizing air pressure can be adjusted using the air
bleed valve. 10 5 - 15
j. Operate the burner until the boiler is warmed up, and 15 7 - 20
near the operating pressure or temperature. 20 10 - 25
k. Increase the ring rate, using the manual potentiome-
ter, while monitoring and adjusting the O2 level. Adjust the 30 12 - 30
cam, oil pressure and atomizing air pressure as needed to 40 15 - 35
reach the high re input. 50 20 - 40
l. If the burner is equipped with FGR, adjust the FGR con-
100 25 - 60
trol valve or potentiometer as required to maintain the NOx
level.
m. At high re (end of the modulating motor travel), adjust
the high re input to match the maximum input listed on the 12. Operating Control Adjustments
rating label. Using a ow meter, the fuel input may be mea-
The operating controls must be adjusted to properly cycle
sured using the following equation,
the burner ON and OFF and provide modulation. See
Oil GPH = Section E-11 for details. The controls should not force
[Gal end Gal start] x [3600 sec/hr] / the burner into rapid ON-OFF cycles, as this will cause
[measured sec] premature failure of the motor and operating equipment.
The operating control must be adjusted to provide the
Where Gal end = meter gallons at end of test
ON pressure or temperature desired. It must allow the
Gal start = gallons at start of the test
burner to come on and start before the temperature or
Measured sec = measured time of test
pressure drops into the modulating range. The OFF
GPH = Gallons of oil per hour
pressure or temperature must be sufciently above the
n. If equipped with FGR, adjust the NOx level to be about ON point to allow a reasonable run time.
10% below any guaranteed NOx performance or if perfor- The modulating control must be adjusted to start modu-
mance guarantee exists adjust the FGR to provide some lation at some reasonable point below the ON tempera-
added turbulence but not high enough to impact ame sta- ture or pressure and provide modulation to high re at
bility. A balance of the FGR control valve and air damper the lowest temperature or pressure.
are required to obtain the nal result, as each can impact
6. FGR Systems
Technician
Annual As
Seasonal
Required
Operator
Monthly
Trained
Weekly
Annual
Burner
Boiler
Daily
This graph shows the relationship between excess air, %Oxygen and %CO2, which is typically obtained from a
ue gas analyzer. The values are based on a dry reading, where the ue gas is extracted and cooled before the
analysis if done.
% Oxygen
% CO2 (gas)
% Oxygen and % CO2 (dry)
% Excess Air
2 No Ignition Lack of fuel, no gas pressure, closed fuel valve Check fuel supply and valves
(spark, no ame) No voltage to pilot solenoid Check electrical connections
Defective pilot solenoid valve Replace
Incorrect location of pilot Check location of pilot
Improper raw gas tube position Check location of raw gas tube
Improperly positioned electrodes Recheck dimensions
Too much combustion air ow Check air damper position
3 Pilot not detected Scanner tube not positioned correctly Check location of scanner tube
(ame present) Scanner tube dirty Clean scanner tube
Scanner or amplier faulty Replace
Pilot improperly positioned Check pilot position
Incorrect gas pressure to pilot Readjust pressure
Combustion air ow rate too high Readjust damper
4 No main gas ame Weak scanner signal Clean scanner lens and tube
(pilot OK) Damper or fuel control valve setting incorrect Readjust
Fuel valve(s) not opening Check wiring to valves
5 No main oil ame Weak scanner signal Clean scanner lense and tube
(pilot OK) Damper or fuel control valve setting incorrect Readjust
Fuel valve(s) not opening Check wiring to valves
Oil nozzle or line obstructed Check nozzle and lines, clean
No atomizing air pressure Check compressor wiring
Compressor pressure too low or high Readjust
Burner not level, oil is draining into vessel Check level, adjust as required.
6 Burner stays at low re Manual pot in low re position (low re hold) Readjust to high re position
Manual-auto switch in wrong position Change position of switch
Modulating Control Check wiring or replace
Loose linkage Readjust and tighten
Binding linkage or valve Readjust or replace
7 Burner shuts down Loose electrical connection Check and tighten connections
during operation Loss of fuel supply Replenish fuel supply
Limit switch breaks (opens) Readjust limit switch
8 Burner does not start Main disconnect switch is open Close switch
Loose electrical connection Check electrical connections
Operating controls are tripped Check and reset operating limits
High or low fuel pressure Check fuel supply - reset switches
10 Gas combustion noise Input too low for burner components Check input, compare to rating label
(rumbling) Improper excess air Readjust excess air
Fluxuating gas pressure (regulator not holding pressure) Check regulator pressure and supply
High stack draft (especially at low re) Stabalize draft
Diffuser not in optimum position Adjust diffuser position in or out
Poor air ow distribution (off center ame) Adjust air straightner blade
11 Oil combustion smoking Oil nozzle dirty or plugged Clean oil nozzle
Improper excess air Readjust excess air
Input too low for burner components Check input, compare to rating label
High stack draft (especially at low re) Stabalize draft
Incorrect nozzle position Adjust the nozzle to diffuser position
Fluxuating oil pressures (regulator not holding) Check regulator pressure and oil supply
Poor air ow distribution (off center ame) Adjust air straightner blade
Too much FGR (if equipped) Reduce FGR rate
13 Fuel-Air-Ratios have changed Linkage wear Check linkage and tighten all joints
over time Fuel cam screws have moved Replace fuel cam
Air damper seal worn Replace air damper seals
Fuel lines plugged Check and clean lines, strainers & lters
Fuel control valve worn Replace fuel control valve
Gas orices or gas manifold plugged Clean and/or replace
Combustion air temperature changed Retune burner
Draft condition changed Check draft and outlet damper
Vessel plugged Clean vessel
Plugged or leaky FGR valve Clean / repair
14 Cannot obtain capacity on Wrong spring range in regulator Install higher spring range
gas Too many elbows before control valve Rework piping to reduce elbows
Gas line too small, high pressure drop Use larger pipe size
Supply pressure lower then stated Increase supply pressure
Supply pressure drops too low at high re Use larger gas line sizes / orice in
service regulator
Regulator too small for ow and pressure Change regulator
17 Cannot obtain NOx levels on Inlet tube in wrong position Adjust inlet tube to center of fan inlet
gas Taper FGR valve to be full open
FGR valve not full open Adjust FGR valve to full open
FGR valve full of condensate Clean duct and add drains
FGR duct not directed to ue stream Add angle cut in center of stack
FGR line too small Check sizing, use ttings with less drop
Operating on propane, not natural gas Resize FGR for propane operation
Shutoff valve is not full open Check FGR shutoff valve position
NOTES