PROTECTION RELAYS INPUT OUTPUT DETAILS

AL SHARIQ- RELAY INPUT OUTPUT & LED DETAILS

Binary Binary
Feeder Name Relay Designation Input Desicription
Input No OutPut No

1 CB Close 1
2 Earth Switch open 2
3 CB Close Pulse -Local/Scada 3
K55(7SJ8022) 4 CB Spring Charged 4
O/C & E/F & AR 5 AR IN - Local/Scada 5
RELAY 6 AR OUT - Local/Scada 6
7 AR RESET through Scada 7
8
LIVE
Outgoing

1 CB Close 1
2 CB Open 2
3 CB Close Pulse -Local/Scada 3
4 Earth Switch Close 4
K51(7SJ8022)
Aux Transformer 5 TCS Unhealthy 5
O/C & E/F
6 LVAC EMGY PB TRIP 6
7 CB Spring Charged 7
8
Aux Transformer O/C & E/F

PROTECTION RELAYS INPUT OUTPUT DETAILS

LIVE

1 CB Close 1
2 STAGE-1 CLOSE 2
3 STAGE-2 CLOSE 3
4 STAGE-3 CLOSE 4
K51(7SJ8022)
Capacitor Bank Feeder 5 STAGE-4 CLOSE 5
O/C & E/F
6 STAGE-5 CLOSE 6
7 Spare@TB ; X9-21,22 7
8
LIVE

1 CB Close 1
2 CB Open 2
3 Earth Switch Open 3
4 I/C CB - Service + Close 4
K27/59(7SJ8041)
Capacitor Bank Feeder U/V & O/V
PROTECTION RELAYS INPUT OUTPUT DETAILS
K27/59(7SJ8041)
Capacitor Bank Feeder 5 CAPACTOR Bank iso DOOR OPEN 5
U/V & O/V
6 VT MCB ON -F25A 6
7 Spare@TB ; X9-9,10 7
8
LIVE

1 VT MCB ON +Line Voltage Healthy (KVTS) 1


2 CB Close 2
3 33KV CB Close 3
K67(7SJ8041) 4 33KV CB Open 4
Directional 5 AC/DC MCB TRIP 5
O/C & E/F 6 B/C CB Close in Service Position 6
7 B/C CB Open in Service Position 7
8
LIVE
Incomer

1 CB Open 1
2 Earth Switch Close 2
3 CB in Local 3
4 CB in Scada 4
K51(7SJ8021) SBEF 5 Spare@TB ; X3-31,32 5
6 Spare@TB ; X3-33,34 6
7 Spare@TB ; X3-35,36 7
8
LIVE

1 CB Open 1
2 CB Close 2
3 33KV CB Close 3
4 33KV CB Open 4
K64(7SJ8022) REF 5 TCS Unhealthy 5

Incomer
PROTECTION RELAYS INPUT OUTPUT DETAILS
K64(7SJ8022) REF
6 I/C BET Close 6
7 I/C BET Open 7
8
LIVE
Incomer
1 I/C 1 VT + Bus A VT Status 1
2 Interlock ON selector switch 2
3 Bypass ON selector switch 3
4 Sync Block (I/C F24B & B/C F25D) 4
K25(7SJ8041) 5 Synch ON switch 5
SYNCH
6 Synch O/R switch 6
7 Trip Relay Operated 7
8
LIVE

1 CB Close 1
2 CB Spring Charged 2
3 TCS Unhealthy 3
4 CB in Local 4
K51(7SJ8022)
Bus Coupler 5 CB in Scada 5
O/C & E/F
6 BET ON (both Bus A&B) 6
7 Spare@TB ; X3-31,32 7
8
LIVE

1 Synch ON From Local/Scada 1


2 Synch O/R From Local/Scada 2
3 B/C Interlock ON 3
4 B/C Bypass ON 4
K25(7SJ8041)
Bus Coupler 5 VT Healthy (Bus A & Bus B +I/C-1 + I/C-2) 5
SYNCH
6 Trip Relay Operated 6
7 Sync Block (Bus A-F25E & Bus B -F24D) 7
8
Bus Coupler SYNCH

PROTECTION RELAYS INPUT OUTPUT DETAILS

LIVE

1 VT MCB FAIL 1

2 CB Open 2
3 CB Close 3
4 Line E/S Close 4
5 DEF Send 5
6 TCS-1 Unhealthy 6
7 TCS-2 Unhealthy 7
F87C/21(7SD52) 8 SPARE 8
33KV CRP Line Differential 9
10
11
12
13
14
15

16
PROTECTION RELAYS INPUT OUTPUT DETAILS

1 CB Open 1
2 CB Close 2
3 Line E/S Close 3
4 Spring Un Charged 4
5 TCS-1&2 Unhealthy 5
6
F87T(7UT6131) 7
Transformer 8
Differential
LIVE

1 VT MCB Block 1
2 CB Open 2
33KV CRP 3 CB Close 3
4 Line E/S Close 4
F59N(7SJ8041) NDR
5 Spring Un Charged 5
6 TCS-1 Unhealthy 6
7 TCS-2 Unhealthy 7
8

LIVE

1 VT MCB Fail 1
2 CB Open 2
3 CB Close 3
4 Line E/S Close 4
F67/67N,F50/51 5 Spring Un Charged 5
(7SJ8041) Dir O/C &
E/F
PROTECTION RELAYS INPUT OUTPUT DETAILS
F67/67N,F50/51
(7SJ8041) Dir O/C &
E/F 6 TCS-1 Unhealthy 6
7 TCS-2 Unhealthy 7
8

LIVE
PROTECTION RELAYS INPUT OUTPUT DETAILS

PUT OUTPUT & LED DETAILS

Output Desicription LED Description

AR Local out to Scada@TB ; X8-10,11 1


TRIP RELAY RESET COMM FROM IEC 2
CB Open Command From IEC 3
OC&EF to CB Direct Trip 4
OC&EF to CB Master Trip 5
CB Close Command From IEC 6
CB AR CLOSE 7
O/C & E/F to Scada@TB ; X8-14,15 8
Relay Faulty to scada @TB ;X8-12,13

Spare@TB ; X51-1,2 1
TRIP RELAY RESET COMM FROM IEC 2
CB Close Command From IEC 3
CB Open Command From IEC 4
OC&EF to CB Direct Trip 5
OC&EF to CB Master Trip 6
O/C to scada @TB ;X8-9,10 7
E/F to scada @TB ;X8-11,12 8
PROTECTION RELAYS INPUT OUTPUT DETAILS

Relay Faulty to scada @TB ;X8-7,8

TRIP RELAY RESET COMM FROM IEC 1


Spare@TB ; X51-1,2 2
CB Close Command From IEC 3
CB Open Command From IEC 4
OC&EF to CB Direct Trip 5
OC&EF to CB Master Trip 6
O/C to Scada@TB ; X8-11,12 7
E/F to Scada@TB ; X8-13,14 8
Relay Faulty to scada @TB ;X8-9,10

Spare@TB ; X27-1,3 1
Spare@TB ; X27-4,6 2
CB Closing Interlock 3
27&59 Trip to CB Direct Trip 4
PROTECTION RELAYS INPUT OUTPUT DETAILS

27&59 Trip to CB Master Trip 5


27 Trip to scada @TB ;X8-17,18 6
59 Trip to scada @TB ;X8-19,20 7
Bus No Voltage to I/C BET Closing CKT 8
Relay Faulty to scada @TB ;X8-7,8

Dead LINE Voltage to Solenoid E/S Interlock 1


Direc O/C Trip to scada @TB ;X8-30,31 2
67/67N Trip to CB Direct Trip 3
67/67N Trip to CB Master Trip 4
67/67N Trip to 33KV Annunciator 5
67/67N Trip to 33KV Trip Coil 2 6
67/67N Trip to 33KV CB - 86 7
Direc E/F Trip to scada @TB ;X8-32,33 8
Relay Faulty to scada @TB ;X8-22,23

SBEF Trip to scada @TB ;X8-14,15 1


Spare 2
CB Close 3
CB Trip through scada 4
SBEF Trip to CB Direct Trip 5
SBEF Trip to CB Master Trip 6
SBEF Trip to 33KV Annunciator 7
TRIP RELAY RESET COMM FROM IEC 8
Relay Faulty to scada @TB ;X8-24,25

Spare@TB ; X64-1,3 1
Spare@TB ; X64-4,6 2
REF Trip to CB Direct Trip 3
REF Trip to CB Master Trip 4
REF Trip to 33KV Annunciator 5
PROTECTION RELAYS INPUT OUTPUT DETAILS

64R Trip to 33KV Trip Coil2 6


64R Trip to 33KV CB Master Trip 7
REF Trip to scada @TB ;X8-12,13 8
Relay Faulty to scada @TB ;X8-26,27

Spare@TB ; X25-1,3 1
Spare@TB ; X25-4,6 2
Synch ON - CB Closing Interlock 3
Synch O/R - CB Closing Interlock 4
Sync ON to scada @TB ;X8-46,47 5
Sync O/R to scada @TB ;X8-48,49 6
Synch ON Command From IEC 7
Synch O/R Command From IEC 8
Relay Faulty to scada @TB ;X8-28,29

TRIP RELAY RESET COMM FROM IEC 1


Spare@TB ; X51-1,3 2
CB Close Command From IEC 3
CB Open Command From IEC 4
O/C& E/FTrip to CB Direct Trip 5
O/C& E/F Trip to CB Master Trip 6
O/C Trip to scada @TB ;X8-16,17 7
E/F Trip to scada @TB ;X8-18,19 8
Relay Faulty to scada @TB ;X8-22,23

Spare@TB ; X25-1,2 1
Spare@TB ; X25-3,5 2
Synch ON - CB Closing Interlock 3
Synch O/R - CB Closing Interlock 4
Sync ON to scada @TB ;X8-10,11 5
Sync O/R to scada @TB ;X8-12,13 6
Synch ON Command From IEC 7
Synch O/R Command From IEC 8
PROTECTION RELAYS INPUT OUTPUT DETAILS

Relay Faulty to scada @TB ;X8-24,25

Current Differential Operated to Scada@TB-XS-1,21 1

Distance Operated to Scada@TB-XS-1,22 2


FO Communication Fail to Scada@TB-XS-1,23 3
CB Open Command From IEC 4
F87L/21 Trip to Trip Coil-2 5
Remote End Switch Close to Annunciator 6
CB Close Command From IEC 7
FO Communication Fail to Annunciator 8
Distance Operated to Annuncitor 9
Current Differential Operated to Annunciator 10
Spare 11
Spare 12
F87L/21 Trip to 86 13
Spare@ TB-XU-3,4 14
Spare@ TB-XU-5,6
Relay Faulty to Scada@TB-XS-1,17 & Annucitator & Spare XU-
11,12
PROTECTION RELAYS INPUT OUTPUT DETAILS

F87T Trip to 86 1
F87T Trip to K12 2
Spare 3
Spare 4
Spare 5
F87T Trip to Trip Coil-2 6
F87T InterTrip to 11KV 86 7
F87T InterTrip to 11KV CB Direct Trip 8
Relay Faulty to Scada@TB-XS-1,17 & Annucitator & Spare XU- 9
11,12
10
11
12
13
14

F59N Direct Trip to Trip Coil-2 1


F59N Trip to 86 2
NDR Trip to Annunciator 3
NDR Trip to Scada@TB-XS-1,20 4
Spare@ TB-XU-7,8 5
Spare@ TB-XU-9,10 6
Spare 7
Spare
Relay Faulty to Scada@TB-XS-1,17 & Annucitator & Spare XU-
11,12

F67/67N,F50/51 Trip to Trip Coil-2 1


DEF Signal Send to F87L Relay 2
F67/67N,F50/51 Trip to 86 3
F67/67N Trip to 11KV CB Master Trip 4
F67/67N Trip to 11KV CB Direct Trip 5
PROTECTION RELAYS INPUT OUTPUT DETAILS

F67/67N Trip to Annunciator 6


Dir O/C &E/F Trip to Scada@TB-XS-1,19 7
Spare@ TB-XU-1,2
Relay Faulty to Scada@TB-XS-1,17 & Annucitator & Spare XU-
11,12