Sei sulla pagina 1di 2

DSEGenset

DSE7410/20 MKII SPECIFICATIONS

DC SUPPLY

AUTO START & AUTO MAINS FAILURE


CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute
CONTROL MODULES CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing
DSE7420 MKII supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


DSE7410 MKII 510 mA at 12 V, 240 mA at 24 V

MAXIMUM STANDBY CURRENT


330 mA at 12 V, 160 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

GENERATOR&MAINS(UTILITY)
VOLTAGERANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCYRANGE
KEY FEATURES 2 configurable volt-free relay Compatible with a wide range of 3.5 Hz to 75 Hz
4-Line back-lit LCD text display outputs CAN engines, including tier 4
Multiple Display Languages 6 configurable analogue/digital engine support MAGNETIC PICKUP
VOLTAGE RANGE
Five key menu navigation inputs J1939-75 support & CAN alarm +/- 0.5 V to 70 V
LCDalarm indication Support for 0 V to 10 V & 4 mA to ignore function
Heated display option available 20 mA sensors Uses DSE Configuration Suite PC FREQUENCY RANGE
10,000 Hz (max)
Customisable power-up text and Support for 3 k resistive sensors Software for simplified
images 8 configurable digital inputs configuration INPUTS
DSENet expansion compatibility Configurable 5 stage dummy load Licence-free PC software DIGITAL INPUTS A TO H
Data logging facility upto 20 and load shedding outputs IP65 rating (with supplied gasket) Negative switching

parameters CAN, MPU and alternator offers increased resistance to water ANALOGUE INPUTS A, B, E & F
Internal PLC editor frequency speed sensing in one ingress Configurable as:
Protections disable feature variant Modules can be integrated into Negative switching digital input
0 V to 10 V sensor
Fully configurable via PC using Real time clock building management systems 4 mA to 20 mA sensor
USB, RS232, RS485 and ethernet Manual and automatic fuel pump (BMS) using MODBUS RTU & TCP Resistive sensor
communication control Configurable CAN parameters to
ANALOGUE INPUTS C & D
Front panel configuration with Engine pre-heat and post-heat read and display CAN information
Configurable as:
multi-level PINprotection functions from external CAN devices. Negative switching digital input
Power save mode Engine run-time scheduler Resistive sensor
3 phase generator sensing and Engine idle control for starting & KEY BENEFITS
OUTPUTS
protection stopping Automatically transfers between OUTPUT A & B (FUEL & START)
3 phase mains (utility)sensing and Fuel usage monitor and low fuel mains (utility) and generator 15 A DC at supply voltage
protection (DSE7420 MKIIonly) level alarms (DSE7420 MKll only) for
OUTPUTS C & D
Automatic load transfer control Simultaneous use of RS232, convenience. 8 A AC at 250 V AC (Volt-free)
(DSE7420 MKIIonly) RS485 & ethernet communication Hours counter provides accurate
Generator current and power ports information for monitoring and AUXILIARY OUTPUTS E, F, G, H, I & J
monitoring (kW, kvar, kVA, pf) True dual mutual standby using maintenance periods 2 A DC at supply voltage
Mains current and power RS232 or RS485 for accurate User-friendly set-up and button DIMENSIONS
monitoring (kW, kvar, kVA, pf) hours balancing. layout for ease of use OVERALL
(DSE7420 MKII only) MODBUS RTU & TCP support with Multiple parameters are monitored 245 mm x 184 mm x 51 mm
9.6 x 7.2 x 2.0
kW and kvar overload and reverse configurable MODBUS pages. & displayed simultaneously for full
power alarms SNMP GET, SET and TRAP support visibility PANEL CUT-OUT
Over current protection built in. The module can be configured to 220 mm x 160 mm
Unbalanced load protection Advanced SMS messaging suit a wide range of applications for 8.7 x 6.3

Independent earth fault protection (additional external modem user flexibility MAXIMUM PANEL THICKNESS
Breaker control via fascia buttons required) PLC editor allows user configurable 8 mm
Fuel and start outputs configurable Start & stop capability via SMS functions to meet user specific 0.3
when using CAN messaging application requirements. STORAGE TEMPERATURE RANGE
6 configurable DC outputs 3 configurable maintenance alarms -40C to +85 C
-40 F to +185 F

RELATED MATERIALS OPERATING TEMPERATURE RANGE


TITLE PART NO. NON-HEATED DISPLAY VARIANT
-30C to +70 C
DSE7410 MKII & DSE7420 MKII Installation Instructions 053-191 -22 F to +158 F
DSE7410 MKII & DSE7420 MKII Operator Manual 057-263
DSE7410 MKII & DSE7420 MKII Configuration Suite PC Manual 057-262 HEATED DISPLAY VARIANT
-40 C to +70 C
-40 F to +158 F
DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA
Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-203/10/16 (1) US
DSEGenset

DSE7410/20 MKII ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO START & AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment

CONTROL MODULES BS EN 61000-6-4


EMC Generic Emission Standard for
the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE7410 MKII is an Auto Start Both modules are compatible with The modules also feature SNMP
Control Module and the DSE7420 electronic (CAN) and non-electronic functionality for connection to SNMP TEMPERATURE
MKII is an Auto Mains (Utility) Failure (magnetic pick-up/alternator sensing) systems. BS EN 60068-2-1
Ab/Ae Cold Test -30 C
Control Module suitable for a wide engines and offer an extensive BS EN 60068-2-2
variety of single, diesel or gas, gen-set number of flexible inputs, outputs The modules can be easily configured Bb/Be Dry Heat +70 C
applications. and extensive engine protections so using the DSE Configuration Suite PC
VIBRATION
the system can be easily adapted to software. Selected front panel editing BS EN 60068-2-6
Monitoring an extensive number of meet the most demanding industry is also available. Ten sweeps in each of three major axes
engine parameters, the modules will requirements. 5 Hz to 8 Hz at +/-7.5 mm,
display warnings, shutdown and 8 Hz to 500 Hz at 2 gn
engine status information on the The extensive list of features includes HUMIDITY
back-lit LCD screen, illuminated LEDs, enhanced event and performance BS EN 60068-2-30
remote PC and via SMS text alerts monitoring, remote communications & Db Damp Heat Cyclic 20/55 C
at 95% RH 48 Hours
(with external modem). PLC functionality. BS EN 60068-2-78
Cab Damp Heat Static 40 C
The DSE7420 MKII will also monitor Dual mutual standby is now available at 93% RH 48 Hours
the mains (utility) supply. The modules on both the DSE7410 MKII &
SHOCK
include USB, RS232, RS485 and DSE7420 MKII using RS232 or RS485 BS EN 60068-2-27
Ethernet ports as well as dedicated communications. This provides Three shocks in each of three major axes
DSENet terminals for system for a simpler and more convenient 15 gn in 11 mS
expansion. installation with more advanced DEGREES OF PROTECTION
features such as true hours balancing. PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
DSE2130 MODBUS
DSE2131 MODEM PC ETHERNET
DSE2133
DSE2152 CAN
DSE2157 8 6 6
DSE2510/20
DSE2548 232 485

DSENET RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS INPUT STOP SUPPLY 8-35V

DEUTZ

DSE7410/20 MKII ISUZU


PERKINS
CATERPILLAR
MTU
VOLVO
7
CUMMINS
SCANIA
OTHER
AND MORE

MAINS (UTILITY) N/C VOLT FREE GENERATOR/ N/O VOLT FREE GENERATOR CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT LOAD CURRENT OUTPUT SENSING ALTERNATOR OUTPUTS ENGINES &
DSE7420 MKII ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS VOLTS
D+
W/L +

1ph 1 1ph 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E/N N

ISSUE 1

Potrebbero piacerti anche