FEATURES
Easy and quick installation
No separate linkage and adjustments required
Low power consumption
Force-limiting end stops
Manual operation knob
0(2)~10 Vdc or 0(4)~20mA input signal selectable
Position feedback signal
Direct/ Reverse action adjustable
Stroke position on signal failure selectable
Corrosion-resistant design
Maintenance-free
ML7421A ML7421B
SPECIFICATIONS
Safety
Protection class III as per EN60730-1
Protection standard IP54 as per EN60529
Flame retardant housing V0 as per UL94
(with metal cable gland)
Material
Cover ABS-FR
Yoke and Base Aluminum diecast
1 ECC-CDA-VA02-DEC-2010-V01-EN
Wiring
2
Wiring terminals 1.5 mm
Cable entry M20.
Additional knock-out
For PG11
Table 1. Selection
Model Number ML7421A1032 ML7421B1023
power consumption 14 VA 14 VA
signal input 0(2) Vdc Actuator stem retracted. Two-way valve:open, three-way valve port A-AB:closed
signal input 10 Vdc Actuator stem extended. Two-way valve:closed, three-way valve port A-AB:open
Factory setting; can be reversed by pressing the right-hand pushbutton (W3) located on the PCB (see Fig. 1).
ECC-CDA-VA02-DEC-2010-V01-EN 2
Input Signal Output Signal "POSITION"
The Vdc or mA input signal is selected by shifting jumper plug An analog output signal 2...10 Vdc POSITION is available
W4 (see Fig.2). The factory setting of W4 is Vdc. No exter- which represents the actuator position. It can be used for
nal resistor for mA input signal is necessary. remote indication.
When the actuator stem is fully extended, the output signal is
10 Vdc.
Input Signal Range
The range of the analog input signal Y (Vdc or mA) can be
selected by changing the position of jumper plug W2 (Fig. 1). Y-Signal Override
The factory set is at 0~10Vdc. To override the Y-signal, input 1 and 2 (see Fig. 3) must be
connected as follows:
Direction of Action Stem extended: 24V at input 1; input 2 not connected
The direction of action can be selected by changing the posi- Stem reacted: 24V at input 2; input 1 not connected.
tion of jumper plug W3(Fig. 1). The factory setting is: stem 24 Vac power and ground must be permanently connected.
extends at increasing signal (direct acting).
NOTE: Jumper plugs W1, W2, W3 and W4 are accessible
after the cover has been removed. ( see Fig. 2).
Input Signal Failure
In case of a signal input e.g. a broken wire, the actuator will
run to one of the three positions (possible only if W4 has been
W2 W3 W4 set to the V position):
0%: actuator stem position for 0(2) Vdc
50%: actuator stem in central position
100%: actuator stem in position for 10 Vdc
2...10 V 0...10 V 10 V 10 V mA V The factory setting of W1 is 50%.
4...20 mA 0...20 mA 20 mA 20 mA
Accessories
W1 W4= W3= W4= W3= Auxiliary Switches
The actuators can be equipped on-site with an auxiliary switch
V 10V, 20mA V 10V, 20mA unit with two switches. Their switching points are adjustable
Y Y over the full length of the actuator stroke. The switches can be
I MO I MO used to switch pumps or provide remote indication of any
0 100
stroke position. A cable gland PG11 is delivered with the unit.
Part number: 43191680-002
100 I MO I MO 0
High-Temperature Kit
I MO I MO (for application 150 medium temperature)
Fig. 2. Effects of jumper plugs W1, W2, W3, W4
stroke 20 mm 38mm
3 ECC-CDA-VA02-DEC-2010-V01-EN
DIMENSIONS
178x (178)
64
178x (178)
64
430
360
326
301
additional
knock-out for
264
cable fitting:
239
18.9 (PG11)
204
additional
knock-out for
142
cable fitting:
18.9 (PG11)
WIRING
0...10 V / 0...20 mA 10 V / 20 mA
2...10 V / 4...20 mA 10 V / 20 mA
W2 W3
210 V
position
0(2)...10 V
Y 0(4)...20 mA
24 V
M 24 V
} 24 V~ 1 2 3 4 5 6
24 V~
S1 S2
1
2 Auxiliary switches
W1 W4 24 Vac / 5(3) A
V mA
% 0 0 Fig. 6. Accessories
50 0
100 0
ECC-CDA-VA02-DEC-2010-V01-EN 4