ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB
Nanjing SAC Power Grid Automation Co., Ltd.
No. 11 Phoenix Road, Jiangning Development Zone
211100 Nanjing
China
Telephone: +86 25 51183000
Facsimile: +86 25 51183883
Customer hotline: 4008876268
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure
network. It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the
necessary measures (such as, but not limited to, installation of firewalls, application
of authentication measures, encryption of data, installation of anti virus programs,
etc.) to protect the product and the network, its system and interface included,
against any kind of security breaches, unauthorized access, interference, intrusion,
leakage and/or theft of data or information. ABB is not liable for any such damages
and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................6
Product documentation set............................................................6
Document revision history.............................................................6
Related documentation..................................................................7
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................8
Functions, codes and symbols......................................................8
REM615 1
Application Manual
Table of contents
2 REM615
Application Manual
Table of contents
Binary inputs................................................................................91
Optional light sensor inputs.........................................................93
Outputs.............................................................................................93
Outputs for tripping and controlling..............................................93
Outputs for signalling...................................................................94
IRF...............................................................................................95
Section 6 Glossary.........................................................................97
REM615 3
Application Manual
4
1YHT530017D05 B Section 1
Introduction
Section 1 Introduction
This manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.
REM615 5
Application Manual
Section 1 1YHT530017D05 B
Introduction
Maintenance
Engineering
Planning &
Installation
Operation
Quick start guide purchase
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual c
Communication protocol manual c
IEC 61850 Engineering guide
Point list manual
GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V1 EN
Figure 1: The intended use of documents during the product life cycle
6 REM615
Application Manual
1YHT530017D05 B Section 1
Introduction
1.4.1 Symbols
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
REM615 7
Application Manual
Section 1 1YHT530017D05 B
Introduction
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
To navigate between the options, use and .
HMI menu paths are presented in bold.
Select Main menu/Settings.
LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
8 REM615
Application Manual
1YHT530017D05 B Section 1
Introduction
REM615 9
Application Manual
Section 1 1YHT530017D05 B
Introduction
10 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
2.1 Overview
Re-engineered from the ground up, the 615 series has been designed to unleash the
full potential of the IEC 61850 standard for communication and interoperability
between substation automation devices. Once the standard configuration IED has
been given the application-specific settings, it can directly be put into service.
The 615 series IEDs support a range of communication protocols including IEC
61850 with GOOSE messaging, IEC 60870-5-103 and Modbus.
REM615 11
Application Manual
Section 2 1YHT530017D05 B
REM615 overview
The IED consists of two main parts: plug-in unit and case. The content depends on
the ordered functionality.
12 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
Rated values of the current and voltage inputs are basic setting parameters of the
IED. The binary input thresholds are selectable within the range 18176 V DC by
adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and
the plug-in unit.
REM615 13
Application Manual
Section 2 1YHT530017D05 B
REM615 overview
- 8 (14)2) 10 (13)2)
B 4 3
6/2 8 10
J 4 53) - 12 10
The LHMI is used for setting, monitoring and controlling the IED. The LHMI
comprises the display, buttons, LED indicators and communication port.
REF615
Overcurrent
Dir. earth-fault
Voltage protection
Phase unbalance
Thermal overload
Breaker failure
Disturb. rec. Triggered
CB condition monitoring
Supervision
Arc detected
Autoreclose shot in progr.
A070704 V3 EN
14 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
2.4.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.
3 4
A070705 V3 EN
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
REM615 15
Application Manual
Section 2 1YHT530017D05 B
REM615 overview
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs
can be configured with PCM600 and the operation mode can be selected with the
LHMI, WHMI or PCM600.
2.4.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With the push-buttons you can give open or close commands to
objects in the primary circuit, for example, a circuit breaker, a contactor or a
disconnector. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
A071176 V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
The WHMI allows accessing the IED via a Web browser. The supported Web
browser versions are Internet Explorer 7.0, 8.0 and 9.0.
16 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
Disturbance records
Phasor diagram
Single-line diagram
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A070754 V4 EN
Locally by connecting the laptop to the IED via the front communication port.
Remotely over LAN/WAN.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
REM615 17
Application Manual
Section 2 1YHT530017D05 B
REM615 overview
User audit trail is defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined usernames or user categories. The user
audit trail events are supported in IEC 61850-8-1, PCM600, LHMI and WHMI.
18 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
PCM600 Event Viewer can be used to view the audit trail events together with
normal events. Since only the administrator has the right to read audit trail,
authorization must be properly configured in PCM600. The audit trail cannot be
reset but PCM600 Event Viewer can filter data. Some of the audit trail events are
interesting also as normal process events.
REM615 19
Application Manual
Section 2 1YHT530017D05 B
REM615 overview
2.7 Communication
The IED supports a range of communication protocols including IEC 61850, IEC
60870-5-103 and Modbus. Operational information and controls are available
through these protocols. However, some communication functionality, for
example, horizontal communication between the IEDs, is only enabled by the IEC
61850 communication protocol.
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100Base-TX) or the fibre-
optic LC connector (100Base-FX).
For the correct operation of redundant loop topology, it is essential that the external
switches in the network support the RSTP protocol and that it is enabled in the
switches. Otherwise, connecting the loop topology can cause problems to the
network. The IED itself does not support link-down detection or RSTP. The ring
recovery process is based on the aging of the MAC addresses, and the link-up/link-
down events can cause temporary breaks in communication. For a better
performance of the self-healing loop, it is recommended that the external switch
furthest from the IED loop is assigned as the root switch (bridge priority = 0) and
the bridge priority increases towards the IED loop. The end links of the IED loop
can be attached to the same external switch or to two adjacent external switches. A
self-healing Ethernet ring requires a communication module with at least two
Ethernet interfaces for all IEDs.
20 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
Client A Client B
Network A
Network B
GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN
PRP specifies that each device is connected in parallel to two local area networks.
HSR applies the PRP principle to rings and to the rings of rings to achieve cost-
effective redundancy. Thus, each device incorporates a switch element that
forwards frames from port to port. The HSR/PRP option is available for REF615,
REM615, RET615 and REU615.
REM615 21
Application Manual
Section 2 1YHT530017D05 B
REM615 overview
PRP
Each PRP node, called a doubly attached node with PRP (DANP), is attached to
two independent LANs operated in parallel. These parallel networks in PRP are
called LAN A and LAN B. The networks are completely separated to ensure failure
independence, and they can have different topologies. Both networks operate in
parallel, thus providing zero-time recovery and continuous checking of redundancy
to avoid communication failures. Non-PRP nodes, called singly attached nodes
(SANs), are either attached to one network only (and can therefore communicate
only with DANPs and SANs attached to the same network), or are attached through
a redundancy box, a device that behaves like a DANP.
COM600
SCADA
22 REM615
Application Manual
1YHT530017D05 B Section 2
REM615 overview
HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the
two directions as two virtual LANs. For each frame sent, a node, DANH, sends two
frames, one over each port. Both frames circulate in opposite directions over the
ring and each node forwards the frames it receives, from one port to the other.
When the originating node receives a frame sent to itself, it discards that to avoid
loops; therefore, no ring protocol is needed. Individually attached nodes, SANs,
such as laptops and printers, must be attached through a redundancy box that acts
as a ring element. For example, a 615 series IED with HSR support can be used as
a redundancy box.
GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V1 EN
REM615 23
Application Manual
24
1YHT530017D05 B Section 3
REM615 standard configurations
REM615 25
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
Functionality A B C/J
Motor load jam protection
Motor start-up supervision
Phase reversal protection
Thermal overload protection for motors
Circuit breaker failure protection
Master trip, instance 1
Master trip, instance 2
Arc protection, instance 1 o o o
Arc protection, instance 2 o o o
Arc protection, instance 3 o o o
Control
Circuit-breaker control 6) 6) 6)
26 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
Functionality A B C/J
Three-phase voltage measurement -
Residual voltage measurement - -
Sequence voltage measurement -
Three-phase power and energy measurement -
RTD/mA measurement o o -
Frequency measurement -
= included, o = optional at the time of order
The external I/O modules binary inputs and outputs of can be used for the less time-
critical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the IEDs standard configuration.
The suitability of the IEDs binary outputs which have been selected for primary
device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.
REM615 27
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-4576631D-C686-454F-8CF0-DC654779B178 V1 EN
Figure 9: Drawing symbol used in the manual and the default connection of
the LED function blocks in the configurations
28 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-3B376A84-ACD8-4641-965F-1E83998849DC V1 EN
REM615 29
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-1596C4FB-2B52-431E-8CF8-F0D4E8797542 V1 EN
30 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-2A2AFE30-749F-4491-A5C1-1A3FB5DB73E1 V1 EN
Figure 12: Connection diagram for the B configuration (motor protection with
phase-to-earth voltage measurement)
REM615 31
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-0D4201D4-09AC-4FA2-9D09-1109DCCF11B5 V1 EN
32 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-F1C23E9E-B743-4CB1-A744-13281CD5E7DF V1 EN
REM615 33
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
Functional diagrams
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the outgoing feeder.
The functional diagrams are divided into sections with each section constituting
one functional entity. The external connections are also divided into sections. Only
the relevant connections for a particular functional entity are presented in each
section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used
several times in the configuration. To separate the blocks from each other, the IEC
61850 name, IEC symbol and ANSI function number are appended with a running
number, that is an instance number, from one upwards. If the block has no suffix
after the IEC or ANSI symbol, the function block has been used, that is,
instantiated, only once. The IEDs internal functionality and the external
connections are separated with a dashed line presenting the IEDs physical casing.
34 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
3.4.1 Applications
The standard configuration is mainly intended for comprehensive protection and
control functionality of circuit breaker controlled asynchronous motors. With
minor modifications this standard configuration can be applied also for contactor
controlled motors.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.4.2 Functions
Table 11: Functions included in the standard configuration A
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Non-directional earth-fault protection, low
EFLPTOC1 Io> (1) 51N-1 (1)
stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Negative-sequence overcurrent protection for
MNSPTOC1 I2>M (1) 46M (1)
motors, instance 1
Negative-sequence overcurrent protection for
MNSPTOC2 I2>M (2) 46M (2)
motors, instance 2
Loss of load supervision LOFLPTUC1 3I< 37
Motor load jam protection JAMPTOC1 Ist> 51LR
49,66,48,51L
Motor start-up supervision STTPMSU1 Is2t n<
R
Phase reversal protection PREVPTOC1 I2>> 46R
Thermal overload protection for motors MPTTR1 3Ith>M 49M
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Table continues on next page
REM615 35
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
36 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
REM615 37
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks
inside the IEDs standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorders parameter settings.
The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents. The signal marked with Io
represents the measured residual current via a core balance current transformer.
The functional diagrams describe the IEDs protection functionality in detail and
picture the factory set default connections.
38 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-4B8285F0-2C1E-4941-AD13-9C33AE5211CA V2 EN
Two overcurrent stages are offered for overcurrent and short-circuit protection. The
motor jam protection function (JAMPTOC1) is blocked by the motor startup
protection function. PHLPTOC1 can be used for overcurrent protection and
PHIPTOC1 for the short-circuit protection. The operation of PHIPTOC1 is not
blocked as default by any functionality and it should be set over the motor start
current level to avoid unnecessary operation.
GUID-E5E0B672-15AA-400F-8B14-45178C90EE6B V1 EN
REM615 39
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-C401D12B-45F4-4B40-A296-6C448F780878 V1 EN
The emergency start function (ESMGAPC1) allows motor startups although the
calculated thermal level or cumulative startup time counter are blocking the restart.
The emergency start is enabled for ten minutes after the selected binary input
(X120:BI1) is energized. On the rising edge of the emergency start signal:
Calculated thermal level in MPTTR1 is set slightly below the restart inhibit
level to allow at least one motor startup
Value of the cumulative startup time counter STTPMSU1 is set slightly below
the set restart inhibit value to allow at least one motor startup
Set start value of the MAPGAPC1 function is increased (or decreased)
depending on the Start value Add setting (only if the optional RTD/mA
module is included)
Alarm LED 11 is activated
A new emergency start cannot be made until the emergency start signal has been
reset and the emergency start time of ten minutes has expired.
The thermal overload protection function (MPTTR1) detects short- and long term
overloads under varying load conditions. When the emergency start request is
issued for the emergency start function, it activates the corresponding input of the
thermal overload function. When the thermal overload function has issued a restart
blocking, which inhibits the closing of the breaker when the machine is overloaded,
the emergency start request removes this blocking and enables the restarting of the
motor.
The restart inhibit is activated for a set period when a circuit breaker is opened.
This is called remanence voltage protection where the motor has damping
remanence voltage after circuit breaker opening. Reclosing after a too short period
40 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
of time can lead to stress for the machine and other apparatuses. The remanence
voltage protection waiting time can be set to a timer function TPSGAPC1.
GUID-CFEDD200-BAA6-4073-9D4A-F36C922F485C V1 EN
With the motor startup supervision function (STTPMSU1) the starting of the motor
is supervised by monitoring three-phase currents or the status of the energizing
circuit breaker of the motor.
The motor running time counter (MDSOPT1) provides history data since last
commissioning. The counter counts the total number of motor running hours and is
incremented when the energizing circuit breaker is closed. The alarm of the
runtime counter is connected to alarm LED 9.
REM615 41
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-43C1A121-BD26-41B2-B828-15F1F0EB00CB V2 EN
The negative-sequence protection and phase reversal protection are blocked if the
current circuit supervision detects failure in the current measuring circuit.
The loss of load situation is detected by LOFLPTUC. The loss of load situation can
happen, for example, if there is damaged pump or a broken conveyor.
42 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-BC48A3DA-E746-4198-8788-7307F5777F8B V1 EN
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.
CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping its own circuit breaker through the Master Trip 1
again. The TRBU output is used to give a backup trip to the circuit breaker feeding
upstream. For this purpose, the TRBU operate output signal is connected to the
output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-315C7C69-3A1C-4DE2-93FA-23B944DE38EC V1 EN
REM615 43
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
Motor cooling air temperature and motor bearing temperature can be measured
with inputs RTD4 (X130-13,14,12c) and RTD5 (X130-15,16,12c). The protection
functionality from these temperatures are provided by MAPGAPC2 and
MAPGAPC3 functions.
GUID-1E213675-B75F-487A-A261-944E7BA4CAAD V1 EN
The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
44 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
DISTURBANCE RECORDER
RDRE1
PHLPTOC1_START BI#1 TRIGGERED LED7 (DR TRIGGERING)
PHIPTOC1_START BI#2
EFLPTOC1_START BI#3
EFHPTOC1_START BI#4
MPTTR1_ALARM BI#5
MPTTR1_BLK_RESTART BI#6
ESMGAPC1_ST_EMERG_ENA BI#7
STTPMSU1_MOT_STARTUP BI#8
STTPMSU1_LOCK_START BI#9
MNSPTOC1_START BI#10
MNSPTOC1_BLK_RESTART BI#11
MNSPTOC2_START BI#12
MNSPTOC2_BLK_RESTART BI#13
PREVPTOC1_START BI#14
MAPGAPC1_START BI#15
MAPGAPC2_START BI#16
MAPGAPC3_START BI#17
CCBRBRF1_TRRET BI#18
CCBRBRF1_TRBU BI#19
PHLPTOC1_OPERATE BI#20
PHIPTOC1_OPERATE BI#21
GUID-EBA6CFFB-7345-46D9-99BB-4C5B6A223574 V2 EN
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and 4 binary inputs are also connected.
REM615 45
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-B251A316-F624-40EE-9D97-8800DF260C1E V1 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) for Master Trip and TCSSCBR2 for PO4 (X100:20-24) for circuit
breaker closing. The trip circuit supervision 1 is blocked by the Master Trip
(TRPPTRC1) and the circuit-breaker open position signal. The trip circuit
supervision 2 is used for circuit breaker closing and therefore blocked when the
circuit breaker is closed. The trip circuit supervision alarm indication is connected
to LED 9.
The motor runtime counter alarm is connected also to the alarm LED 9.
46 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-5E7123DA-D09D-46BF-A768-3F5BDE5255AD V1 EN
The operate signals from the protections are connected to the trip output contact
PO3 (X100:15-19) via the corresponding Master Trip (TRPPTRC1). Open control
commands to the circuit breaker from the local or remote CBXCBR1-exe_op are
connected directly to the output PO3 (X100:15-19).
TRPPTRC1 provides the lockout/latching function, event generation and the trip
signal duration setting. If the lockout operation mode is selected, one binary input
can be reassigned to the RST_LKOUT input of the Master Trip to enable external
reset with a push button.
REM615 47
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-4688187D-B8F6-4E3C-AF8E-1CE48286E951 V1 EN
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the master trip logics. The open operation is always
enabled.
When the motor restart is inhibited, the BLK_CLOSE input is activated and
closing of the breaker is not possible. When all conditions of the circuit breaker
closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and
PO1 output (X100:6-7) is closed.
48 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
GUID-F9014930-199A-4AC2-92C1-EC7DAFDE19DE V1 EN
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
3.5.1 Applications
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
REM615 49
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
3.5.2 Functions
Table 17: Functions included in the standard configuration B
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Directional earth-fault protection, low stage,
DEFLPDEF1 Io> -> (1) 67N-1 (1)
instance 1
Three-phase undervoltage protection, instance 1 PHPTUV1 3U< (1) 27 (1)
Positive-sequence undervoltage protection,
PSPTUV1 U1< (1) 47U+ (1)
instance 1
Negative-sequence overvoltage protection,
NSPTOV1 U2> (1) 47O- (1)
instance 1
Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81 (1)
Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2) 81 (2)
Negative-sequence overcurrent protection for
MNSPTOC1 I2>M (1) 46M (1)
motors, instance 1
Negative-sequence overcurrent protection for
MNSPTOC2 I2>M (2) 46M (2)
motors, instance 2
Loss of load supervision LOFLPTUC1 3I< 37
Motor load jam protection JAMPTOC1 Ist> 51LR
49,66,48,51L
Motor start-up supervision STTPMSU1 Is2t n<
R
Phase reversal protection PREVPTOC1 I2>> 46R
Thermal overload protection for motors MPTTR1 3Ith>M 49M
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)
Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)
Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4)
Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5)
Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Table continues on next page
50 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
REM615 51
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
52 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks
inside the IEDs standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorders parameter settings.
The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents and 3U the three phase voltages.
The signal marked with Io represents the measured residual current via a core
balance current transformer.
The EFHPTOC protection function block for non-directional earth-faults uses the
calculated residual current originating from the measured phase currents.
REM615 53
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
The functional diagrams describe the IEDs protection functionality in detail and
picture the factory set default connections.
GUID-6A9ABC23-2E8A-40BF-B02C-057EF3BE2B6C V2 EN
Two overcurrent stages are offered for overcurrent and short-circuit protection. The
motor jam protection function (JAMPTOC1) is blocked by the motor startup
protection function. PHLPTOC1 can be used for overcurrent protection and
PHIPTOC1 for the short-circuit protection. The operation of PHIPTOC1 is not
blocked as default by any functionality and it should be set over the motor start
current level to avoid unnecessary operation.
Depending on the selected operation mode, the active setting group can be changed
either with a parameter or via binary input.
54 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-EB45D14C-DBE4-417B-A937-DBD71CC05563 V1 EN
The earth- fault protection is blocked when the short circuit protection
(PHIPTOC1) is started. The operation of the earth-fault protection functions is
connected to alarm LED 2.
GUID-3B5861E6-3BFE-43FF-AEE4-C6016BE4CDEE V1 EN
REM615 55
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-985FAB7A-91CD-4066-B405-D9C32FCA1447 V1 EN
The emergency start function (ESMGAPC1) allows motor startups although the
calculated thermal level or cumulative startup time counter are blocking the restart.
The emergency start is enabled for ten minutes after the selected binary input
(X110:BI6) is energized. On the rising edge of the emergency start signal:
Calculated thermal level in MPTTR1 is set slightly below the restart inhibit
level to allow at least one motor startup
Value of the cumulative startup time counter STTPMSU1 is set slightly below
the set restart inhibit value to allow at least one motor startup
Set start value of the MAPGAPC1 function is increased (or decreased)
depending on the Start value Add setting (only if the optional RTD/mA
module is included)
Alarm LED 11 is activated
A new emergency start cannot be made until the emergency start signal has been
reset and the emergency start time of ten minutes has expired.
56 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
The thermal overload protection function (MPTTR1) detects short- and long term
overloads under varying load conditions. When the emergency start request is
issued for the emergency start function, it activates the corresponding input of the
thermal overload function. When the thermal overload function has issued a restart
blocking, which inhibits the closing of the breaker when the machine is overloaded,
the emergency start request removes this blocking and enables the restarting of the
motor.
The restart inhibit is activated for a set period when a circuit breaker is opened.
This is called remanence voltage protection where the motor has damping
remanence voltage after circuit breaker opening. Reclosing after a too short period
of time can lead to stress for the machine and other apparatuses. The remanence
voltage protection waiting time can be set to a timer function TPSGAPC1.
GUID-98C04C17-4412-42F9-A2C4-01A5A265D89B V1 EN
With the motor startup supervision function (STTPMSU1) the starting of the motor
is supervised by monitoring three-phase currents or the status of the energizing
circuit breaker of the motor.
REM615 57
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
The upstream blocking from the motor startup is connected to the output SO1
(X110:14-15-16). The output is used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.
The motor running time counter (MDSOPT1) provides history data since last
commissioning. The counter counts the total number of motor running hours and is
incremented when the energizing circuit breaker is closed. The alarm of the
runtime counter is connected to alarm LED 9.
GUID-806BFFC2-B2FB-4486-B52D-541A16C6123D V2 EN
58 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
The negative-sequence protection and phase reversal protection are blocked if the
current circuit supervision detects failure in the current measuring circuit.
The loss of load situation is detected by LOFLPTUC. The loss of load situation can
happen, for example, if there is damaged pump or a broken conveyor.
GUID-580ACE49-AA7C-4EF0-8146-A7307D9A31F4 V1 EN
GUID-0D0D3645-E20C-45BE-8E6F-EAC82CE7A27E V1 EN
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
REM615 59
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.
CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping its own circuit breaker through the Master Trip 1
again. The TRBU output is used to give a backup trip to the circuit breaker feeding
upstream. For this purpose, the TRBU operate output signal is connected to the
output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-15CA334D-6AE4-47EC-A5DF-E6D5D5E50F7D V1 EN
Motor cooling air temperature and motor bearing temperature can be measured
with inputs RTD4 (X130-13,14,12c) and RTD5 (X130-15,16,12c). The protection
functionality from these temperatures are provided by MAPGAPC2 and
MAPGAPC3 functions.
60 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-689B57C2-2301-4F0C-9587-6B68BA715A63 V1 EN
The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
REM615 61
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
DISTURBANCE RECORDER
RDRE1
PHLPTOC1_START BI#1 TRIGGERED LED7 (DR TRIGGERING)
PHIPTOC1_START BI#2
DEFLPDEF1_START BI#3
EFHPTOC1_START BI#4
MPTTR1_ALARM BI#5
MPTTR1_BLK_RESTART BI#6
ESMGAPC1_ST_EMERG_ENA BI#7
STTPMSU1_MOT_STARTUP BI#8
STTPMSU1_LOCK_START BI#9
MNSPTOC1_START BI#10
MNSPTOC1_BLK_RESTART BI#11
MNSPTOC2_START BI#12
MNSPTOC2_BLK_RESTART BI#13
PREVPTOC1_START BI#14
PHPTUV1_START BI#15
PSPTUV1_START BI#16
NSPTOV1_START BI#17
FRPFRQ1_START BI#18
FRPFRQ2_START BI#19
MAPGAPC1_START BI#20
MAPGAPC2_START BI#21
MAPGAPC3_START BI#22
CCBRBRF1_TRRET BI#23
CCBRBRF1_TRBU BI#24
PHLPTOC1_OPERATE BI#25
PHIPTOC1_OPERATE BI#26
JAMPTOC1_OPERATE BI#27
DEFLPDEF1_OPERATE OR BI#28
EFHPTOC1_OPERATE BI#29
PREVPTOC1_OPERATE BI#30
GUID-ABE44A03-A74A-4993-970D-34B953E27EED V2 EN
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and 8 binary inputs are also connected.
62 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-094B7351-E733-470F-B6CC-05B823DFA413 V1 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) for Master Trip and TCSSCBR2 for PO4 (X100:20-24) for circuit
breaker closing. The trip circuit supervision 1 is blocked by the Master Trip
(TRPPTRC1) and the circuit-breaker open position signal. The trip circuit
supervision 2 is used for circuit breaker closing and therefore blocked when the
circuit breaker is closed. The trip circuit supervision alarm indication is connected
to LED 9.
The motor runtime counter alarm is connected also to the alarm LED 9.
REM615 63
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-054B4BA5-8347-49AB-A007-7654D44093C3 V1 EN
The operate signals from the protections are connected to the trip output contact
PO3 (X100:15-19) via the corresponding Master Trip (TRPPTRC1). Open control
commands to the circuit breaker from the local or remote CBXCBR1-exe_op are
connected directly to the output PO3 (X100:15-19).
TRPPTRC1 provides the lockout/latching function, event generation and the trip
signal duration setting. If the lockout operation mode is selected, one binary input
can be reassigned to the RST_LKOUT input of the Master Trip to enable external
reset with a push button.
64 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-C93A3CD7-6E69-45F7-B9C0-8C1A1757E860 V1 EN
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the master trip logics. The open operation is always
enabled.
When the motor restart is inhibited, the BLK_CLOSE input is activated and
closing of the breaker is not possible. When all conditions of the circuit breaker
closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and
PO1 output (X100:6-7) is closed.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
REM615 65
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-81407556-CB01-49FE-AF4A-E29E29981A8E V1 EN
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
66 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
3.6.1 Applications
The standard configuration for motor protection with current and voltage based
protection and measurements functions is mainly intended for comprehensive
protection and control functionality of circuit breaker controlled asynchronous
motors. With minor modifications this standard configuration can be applied also
for contactor controlled motors.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.6.2 Functions
Table 23: Functions included in the standard configurations C and J
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Directional earth-fault protection, low stage,
DEFLPDEF1 Io> -> (1) 67N-1 (1)
instance 1
Three-phase undervoltage protection, instance 1 PHPTUV1 3U< (1) 27 (1)
Positive-sequence undervoltage protection,
PSPTUV1 U1< (1) 47U+ (1)
instance 1
Negative-sequence overvoltage protection,
NSPTOV1 U2> (1) 47O- (1)
instance 1
Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81 (1)
Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2) 81 (2)
Negative-sequence overcurrent protection for
MNSPTOC1 I2>M (1) 46M (1)
motors, instance 1
Negative-sequence overcurrent protection for
MNSPTOC2 I2>M (2) 46M (2)
motors, instance 2
Loss of load supervision LOFLPTUC1 3I< 37
Motor load jam protection JAMPTOC1 Ist> 51LR
Table continues on next page
REM615 67
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
68 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
REM615 69
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
LED Description
5 Motor restart inhibit
6 Breaker failure protection operate
7 Disturbance recorder triggered
8 Circuit breaker condition monitoring alarm
9 TCS, fuse failure, measuring circuit fault or runtime counter alarm
10 Arc protection operate
11 Emergency start enabled
Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.
The analog channels have fixed connections towards the different function blocks
inside the IEDs standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorders parameter settings.
70 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents and 3U the three phase voltages.
The signal marked with Io represents the measured residual current via a core
balance current transformer. The signal marked with Uo represents the measured
residual voltage via open-delta connected voltage transformers.
The EFHPTOC protection function block for non-directional earth-faults uses the
calculated residual current originating from the measured phase currents.
The functional diagrams describe the IEDs protection functionality in detail and
picture the factory set default connections.
GUID-34EB806B-FEEF-429D-B115-A52BBFB98B61 V2 EN
Two overcurrent stages are offered for overcurrent and short-circuit protection. The
motor jam protection function (JAMPTOC1) is blocked by the motor startup
protection function. PHLPTOC1 can be used for overcurrent protection and
PHIPTOC1 for the short-circuit protection. The operation of PHIPTOC1 is not
blocked as default by any functionality and it should be set over the motor start
current level to avoid unnecessary operation.
REM615 71
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
Depending on the selected operation mode, the active setting group can be changed
either with a parameter or via binary input.
GUID-D21A2FA0-A7EB-44BC-A25D-66B3A37F2DB1 V2 EN
The earth- fault protection is blocked when the short circuit protection
(PHIPTOC1) is started. The operation of the earth-fault protection functions is
connected to alarm LED 2.
72 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-62B6D44D-40BE-44C3-AC53-3C56199A52DC V2 EN
REM615 73
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-7DC9E12B-6E3F-4778-BD6A-1C6A04058FE7 V2 EN
The emergency start function (ESMGAPC1) allows motor startups although the
restart inhibit is activated. The emergency start is enabled for ten minutes after the
selected binary input (X120:BI1) is energized. On the rising edge of the emergency
start signal:
Calculated thermal level is set slightly below the restart inhibit level to allow
at least one motor startup
Value of the cumulative startup time counter STTPMSU1 is set slightly below
the set restart inhibit value to allow at least one motor startup
Set operate values of the temperature stages in MPTTR1 function is increased
by 10 percent
External restart inhibit signal (X100:PO1) is ignored
Alarm LED 11 is activated
The external restart inhibit signal is ignored for as long as the emergency start is
activated. A new emergency start cannot be made until the emergency start signal
has been reset and the emergency start time of 10 minutes has expired.
The thermal overload protection function (MPTTR1) detects short- and long term
overloads under varying load conditions. When the emergency start request is
issued for the emergency start function, it activates the corresponding input of the
thermal overload function. When the thermal overload function has issued a restart
blocking, which inhibits the closing of the breaker when the machine is overloaded,
the emergency start request removes this blocking and enables the restarting of the
motor.
74 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
The restart inhibit is activated for a set period when a circuit breaker is opened.
This is called remanence voltage protection where the motor has damping
remanence voltage after circuit breaker opening. Reclosing after a too short period
of time can lead to stress for the machine and other apparatuses. The remanence
voltage protection waiting time can be set to a timer function TPSGAPC1.
GUID-BAC6545B-0B21-499C-8930-85C6C9C66E6F V2 EN
With the motor startup supervision function (STTPMSU1) the starting of the motor
is supervised by monitoring three-phase currents or the status of the energizing
circuit breaker of the motor.
The upstream blocking from the motor startup is connected to the output SO1
(X110:14-15-16). The output is used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.
The motor running time counter (MDSOPT1) provides history data since last
commissioning. The counter counts the total number of motor running hours and is
REM615 75
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
incremented when the energizing circuit breaker is closed. The alarm of the
runtime counter is connected to alarm LED 4.
GUID-47B67152-61E5-4948-9EAC-EDE15641C455 V2 EN
The negative-sequence protection and phase reversal protection are blocked if the
current circuit supervision detects failure in the current measuring circuit.
The loss of load situation is detected by LOFLPTUC. The loss of load situation can
happen, for example, if there is damaged pump or a broken conveyor.
76 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-7399FB0E-9383-4BF7-A3B4-BD32C885065E V1 EN
Two frequency protection stages (FRPFRQ1 and PFRQ2) are offered. These
functions are used to protect the motor against abnormal power system frequency.
GUID-927D00F3-76C3-4BDD-85EC-88B93E4B8AA1 V1 EN
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.
CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping its own circuit breaker through the Master Trip 1
REM615 77
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
again. The TRBU output is used to give a backup trip to the circuit breaker feeding
upstream. For this purpose, the TRBU operate output signal is connected to the
output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-39A636D3-54CF-4425-9552-322889A5CE40 V2 EN
The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
78 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-D7ADBE62-2DF3-476B-A008-3A589207E81E V2 EN
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and 4 binary inputs are also connected.
REM615 79
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-AC0AE2D0-1238-4D03-88AA-57D310CED5B7 V2 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) for Master Trip and TCSSCBR2 for PO4 (X100:20-24) for circuit
breaker closing. The trip circuit supervision 1 is blocked by the Master Trip
(TRPPTRC1) and the circuit-breaker open position signal. The trip circuit
supervision 2 is used for circuit breaker closing and therefore blocked when the
circuit breaker is closed. The trip circuit supervision alarm indication is connected
to LED 9.
The motor runtime counter alarm is connected also to the alarm LED 9.
80 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
GUID-6CBC044E-6D85-424A-AA6C-FF72590D1F1F V2 EN
The operate signals from the protections are connected to the trip output contact
PO3 (X100:15-19) via the corresponding Master Trip (TRPPTRC1). Open control
commands to the circuit breaker from the local or remote CBXCBR1-exe_op are
connected directly to the output PO3 (X100:15-19).
TRPPTRC1 provides the lockout/latching function, event generation and the trip
signal duration setting. If the lockout operation mode is selected, one binary input
can be reassigned to the RST_LKOUT input of the Master Trip to enable external
reset with a push button.
REM615 81
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-B622B909-E854-4539-BBD9-D6F295867CDF V2 EN
There are three disconnector status blocks (DCSXSWI13) available in the IED.
The remaining two not described in the functional diagram are available in
PCM600 for connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.
The binary inputs 7 and 8 (X110:1-13) are designed for the position indication of
the line-side earthing switch.
82 REM615
Application Manual
1YHT530017D05 B Section 3
REM615 standard configurations
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector or breaker truck and earth-switch position statuses and the statuses
of the Master Trip logics and gas pressure alarm and circuit-breaker spring
charging. The OKPOS output from the DCSXSWI block defines if the
disconnector or the breaker truck is definitely either open (in test position) or close
(in service position). This, together with the open earth-switch and non-active trip
signal, activates the close-enable signal to the circuit breaker control function
block. The open operation is always enabled.
When the motor restart is inhibited, the BLK_CLOSE input is activated and
closing of the breaker is not possible. When all conditions of the circuit breaker
closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and
PO1 output (X100:6-7) is closed.
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
REM615 83
Application Manual
Section 3 1YHT530017D05 B
REM615 standard configurations
GUID-9F82AC98-808F-4820-BB71-A48445FAC7B4 V2 EN
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
84 REM615
Application Manual
1YHT530017D05 B Section 4
Requirements for measurement transformers
The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection settings of the IED should be defined in accordance with
the CT performance as well as other factors.
The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary
current to the rated primary current. For example, a protective current transformer
of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For
protective current transformers, the accuracy class is designed by the highest
permissible percentage composite error at the rated accuracy limit primary current
prescribed for the accuracy class concerned, followed by the letter "P" (meaning
protection).
Table 29: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error at Phase displacement at rated primary Composite error at
rated primary current rated accuracy limit
current (%) minutes centiradians primary current (%)
5P 1 60 1.8 5
10P 3 - - 10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if
there are accuracy requirements for the metering functions (current metering,
power metering, and so on) of the IED.
REM615 85
Application Manual
Section 4 1YHT530017D05 B
Requirements for measurement transformers
The CT accuracy primary limit current describes the highest fault current
magnitude at which the CT fulfils the specified accuracy. Beyond this level, the
secondary current of the CT is distorted and it might have severe effects on the
performance of the protection IED.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy
limit factor (Fn) and is proportional to the ratio of the rated CT burden and the
actual CT burden.
Sin + Sn
Fa Fn
Sin + S
A071141 V1 EN
The nominal primary current I1n should be chosen in such a way that the thermal
and dynamic strength of the current measuring input of the IED is not exceeded.
This is always fulfilled when
The saturation of the CT protects the measuring circuit and the current input of the
IED. For that reason, in practice, even a few times smaller nominal primary current
can be used than given by the formula.
86 REM615
Application Manual
1YHT530017D05 B Section 4
Requirements for measurement transformers
The factor 0.7 takes into account the protection IED inaccuracy, current
transformer errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the
high set stage overcurrent protection is defined. The operate time delay caused by
the CT saturation is typically small enough when the overcurrent setting is
noticeably lower than Fa.
When defining the setting values for the low set stages, the saturation of the CT
does not need to be taken into account and the start current setting is simply
according to the formula.
With definite time mode of operation, the saturation of CT may cause a delay that
is as long as the time the constant of the DC component of the fault current, when
the current is only slightly higher than the starting current. This depends on the
accuracy limit factor of the CT, on the remanence flux of the core of the CT, and
on the operate time setting.
With inverse time mode of operation, the delay should always be considered as
being as long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the
AC component of the fault current should not saturate the CT less than 20 times the
starting current. Otherwise, the inverse operation time can be further prolonged.
Therefore, the accuracy limit factor Fa should be chosen using the formula:
The Current start value is the primary pickup current setting of the IED.
The following figure describes a typical medium voltage feeder. The protection is
implemented as three-stage definite time non-directional overcurrent protection.
REM615 87
Application Manual
Section 4 1YHT530017D05 B
Requirements for measurement transformers
A071142 V1 EN
The maximum three-phase fault current is 41.7 kA and the minimum three-phase
short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is
calculated to be 59.
The start current setting for low-set stage (3I>) is selected to be about twice the
nominal current of the cable. The operate time is selected so that it is selective with
the next IED (not visible in the figure above). The settings for the high-set stage
and instantaneous stage are defined also so that grading is ensured with the
downstream protection. In addition, the start current settings have to be defined so
that the IED operates with the minimum fault current and it does not operate with
the maximum load current. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (I>>>)
in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the
criteria given by the current transformer selection formula is fulfilled and also the
IED setting is considerably below the Fa. In this application, the CT rated burden
could have been selected much lower than 10 VA for economical reasons.
88 REM615
Application Manual
1YHT530017D05 B Section 5
IED physical connections
5.1 Inputs
REM615 89
Application Manual
Section 5 1YHT530017D05 B
IED physical connections
X130-11 Common1)
X130-12 Common2)
X130-13 RTD4 (AI6), +
X130-14 RTD4 (AI6), -
X130-15 RTD5 (AI7), +
X130-16 RTD5 (AI7), -
X130-17 RTD6 (AI8), +
X130-18 RTD6 (AI8), -
90 REM615
Application Manual
1YHT530017D05 B Section 5
IED physical connections
Binary inputs of slot X110 are available with configurations B and J and optional
for A and C.
REM615 91
Application Manual
Section 5 1YHT530017D05 B
IED physical connections
92 REM615
Application Manual
1YHT530017D05 B Section 5
IED physical connections
The IED is provided with connection sockets X13, X14 and X15
only if the optional communication module with light sensor inputs
has been installed. If the arc protection option is selected when
ordering an IED, the light sensor inputs are included in the
communication module.
5.2 Outputs
REM615 93
Application Manual
Section 5 1YHT530017D05 B
IED physical connections
Output contacts of slot X130 are available in the optional BIO module BIOB02A
for configuration B.
94 REM615
Application Manual
1YHT530017D05 B Section 5
IED physical connections
Terminal Description
X130-16 SO3, common
X130-17 SO3, NO
X130-18 SO3, NC
5.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of
the protection IED. Under normal operating conditions, the IED is energized and
the contact is closed (X100/3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the output contact drops off and the
contact closes (X100/3-4).