Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
AbstractThis paper presents a simple method for voltage sta- work, or tending to one [15],[18], to indicate voltage instability
bility assessment by reducing the bus impedance matrix of a net- had occurred. However, they only indicate the critical buses and
work into its two-bus equivalent model at a referred bus. Closed- do not yield information on the causes and effects of voltage in-
form equations of the equivalent model could then be derived to
facilitate an equivalent nodal analysis at the referred bus to de- stability.
termine its voltage stability limit. The method was also shown to On the causes and effects of voltage instability, identication
have parallels with the well-accepted modal analysis of the Jaco- of critical system locations to undertake appropriate types of re-
bian matrix. These include dening geometric indices to identify medial measure is a practical planning and operation concern.
critical buses and participation factors to quantify contribution of This had motivated works such as [8][10] which were based
network elements to their criticality. The method however does not
require post power ow solution processing of the Jacobian matrix; on a widely accepted method [7] that exploited the modal prop-
such computational advantage may make it suitable for online ap- erties of the full system model.
plications. The IEEE 300-bus system was tested with the method Taking cognizance of the emphasis by previous works
which was shown to be valid and computationally robust and ef- [1][18] for a simple and computationally efcient system
cient. model that also offers full facility to develop practical aspects
Index TermsEffective distance to collapse, equivalent nodal for voltage stability assessment, a method which incorporates
analysis, reduced bus impedance matrix, voltage stability. both these features is proposed in this work. Thus, this paper
presents a method which reduces the bus impedance matrix of a
network into its two-bus equivalent model at a referred bus, to
I. INTRODUCTION
facilitate an equivalent nodal analysis to determine its voltage
stability limit. The method is deemed to be simple and fast
0885-8950 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
(6)
(12)
where is the minor of the th diagonal element of . where and
. is the MVA load at the th bus, and are
D. Relationship Between Modal and Nodal Approaches respectively its active and reactive load components. is
The relationship between the modal and nodal voltage sensi- the equivalent MVA load at the th bus, and are
tivity indices can be shown using the Leibniz formula for block respectively its equivalent active and reactive load components
matrices [20] on and to obtain (the asterisk denotes conjugate quantities).
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
Fig. 1. Two-bus equivalent model of the -bus power system at the th re-
ferred bus.
(13)
If is taken as the reference vector, it is seen that (13) is the Fig. 2. th bus voltage prole surface dened by (16).
power equation of a classical two-bus power system as shown
in Fig. 1. Thus (13) represents the two-bus equivalent model of
the -bus power system seen from the th bus. Accordingly, where is the maximum equivalent load that can in-
, , and as dened in (12) are therefore the equiva- crease along a constant line on the voltage prole surface,
lent voltage source, equivalent load, and Thevenin impedance of for example, point 4 in Fig. 2. For ,
the two-bus equivalent model, and they represent the aggregate is infeasible since it would then not be on the voltage prole
effect of all voltage sources, loads, and impedances distributed surface. Thus all the tuples is the edge
in the -bus power system to be felt at the th bus. Separating line of the voltage prole surface, which constitutes the th bus
(13) into its real and imaginary parts gives voltage point-of-collapse (POC) boundary. Equation (18) is also
the equation of the projection of this boundary onto the
(14) plane; it therefore describes the th bus voltage stability
(15) boundary condition on this plane. It is further shown that the
nodal voltage sensitivity of the two-bus equivalent model at the
Summing the square of (14) and (15), and simplifying yields
th bus, or called the equivalent nodal voltage sensitivity, also
becomes innite at the boundary condition of (18). For this pur-
pose, the partial and total differential of the th bus voltage
with respect to the equivalent load can be derived from
(16)
(16) as
Equation (16) represents the voltage prole surface of the th
(20)
bus as a function of its equivalent MVA load and voltage
source ;an example is shown in Fig. 2. The th bus voltage
is therefore constrained on this surface described by (16) as the
(21)
operating point changes, for example, the power ow path in
Fig. 2. At a particular operating point, the corresponding
and can be computed from its power ow solution according where
to (12), and the th bus voltage magnitude is related according
to (16) as
(18)
Thus the equivalent nodal voltage sensitivity also becomes in-
may be interpreted as the effective load at the th bus; it nite at the boundary condition of (18).
represents the effectiveness of the equivalent load at this Since the innitesimal increment of , are independent
bus. variables, then
At the boundary condition of (18), i.e., , the
th bus voltage is determined from (17) as
(19)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
Thus
(23)
(26)
(30)
(29) (32)
As seen from (29), these contributions are the proportions of and noting that and , ,
the th bus load to the corresponding th bus equivalent load, where is the th branch admittance.
and are thus measures of participation of the th bus loads in The numerator terms of comprise only the th branch
the load stress at the th bus. The participation depends on the admittances and th bus shunt admittance (the cofac-
th bus load's transfer impedance and voltage tors are independent of these admittances); each thus represents
weights, which are respectively analogous to the mode shape the admittance contribution to . Its proportion
and excitation weights of the Jacobian eigenmodes in [7]. Thus of represents the participation of the th branch
the transfer impedance and voltage weights may also be called admittance in the th Thevenin admittance; thus
the th bus impedance shape and load voltage excitation. The
impedance shape represents the electrical connectivity or ability
of the th load to participate in the load stress at the th bus,
while the load voltage excitation represents the intensity of this
participation. Together they represent the degree of participa- (33)
tion of the th bus load at the th bus. It is also seen that the
Using (31) and (32) in (33) yields
impedance shape depends only on the transfer impedance and
not on the bus loading. (34)
B. Generator Participation Factors Similar to the treatment of the generator participation factors,
As seen in (12), the equivalent voltage source at the th the scalar participation factor is dened as
bus comprises the sum of the voltage source contribution by
every generator, which is a vector product of the generator cur-
rent and transfer impedance between the generator terminal bus
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
(35)
TABLE I
EDC RANKING OF CRITICAL BUSES
TABLE II
PARTICIPATION FACTORS FOR LOAD STRESS AT BUS 113
Fig. 9. IEEE 300-bus test system used for the case study.
TABLE III the adaptive scheme is consistently faster than the xed scheme
COMPUTATION TIMES FOR NODAL AND MODAL METHODS for all the buses computed. Although the rela-
tive speed gains vary widely, i.e., between 13% and 69%, this is
rather due to Tf than Ta being inconsistent and still an average
relative speed gain of 32% is achieved. The relative speed gain
would be even higher if a smaller load step, say 20 MW, was
used for the xed scheme. Moreover, Tn is extremely fast when
compared to Tm, i.e., Tm/Tn being between 80 and 100 times.
Thus the proposed method is deemed to be computationally effi-
cient. Thirdly, the differences between the POC loads computed
using the adaptive (Pa) and xed (Pf) scheme are less than 5.5%
for all the buses analyzed, implying that the adaptive scheme is
contrast, a single large load at bus 17 (561 MW) or bus 20 (595 fairly accurate despite taking larger load steps than the xed
MW) still have low participation factors (0.0018 and scheme.
, respectively) due to their small impedance shapes with
respect to bus 113 (0.00151 and correspondingly). X. CONCLUSIONS
To demonstrate the computational efciency of the pro-
posed method, the POC load for the 10 weakest buses in This paper had presented a simple method for voltage sta-
Table I were computed using the adaptive scheme outlined in bility assessment by reducing the bus impedance matrix of a net-
Section VIII-A and also the xed scheme with an arbitrary work to facilitate an equivalent nodal analysis at a referred bus
30-MW load step increase. The total power ow time taken to determine its voltage stability limit. It was also shown that the
for a POC load computation run using each respective scheme method could identify critical buses and quantify contribution of
are denoted as Ta (adaptive) and Tf (xed), respectively. The network elements to their criticality, through use of geometric
nodal (EDC) and modal (minimum eigenvalue) indices were indices and participation factors, respectively. The method is
also computed at each load step (after power ow converged) potentially suitable for online applications since it uses only
of a POC load computation run using the adaptive scheme, and the power ow solution to compute these quantities. The IEEE
the total time taken are denoted as Tn (nodal) and Tm (modal), 300-bus system was tested with the method which was shown
respectively. The power ow and indices were computed using to be valid, reliably robust, computationally efcient, and accu-
MATLAB running on an Intel processor, 1.7 GHz, 4 GB rate. Consequently the method could be developed into a useful
RAM personal computer. The computation results are given in planning and operation tool.
Table III.
It is rstly seen from Table III that Ta are fairly consistent, REFERENCES
averaging 25 s, for all the buses computed. This implies that the [1] A. Tiranuchit and R. J. Thomas, A posturing strategy against voltage
adaptive scheme is reliably robust since a representative number stabilities in electric power systems, IEEE Trans. Power Syst., vol. 3,
no. 1, pp. 8793, Feb. 1986.
of buses with different network locations, voltage levels, and [2] P. Kessel and H. Glavitsch, Estimating the voltage stability of a power
types of stability boundary were analyzed. Secondly, system, IEEE Trans. Power Del., vol. 1, no. 3, pp. 346354, Jul. 1986.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
[3] A. Tiranuchit et al., Towards a computational feasible on-line voltage [14] L. C. P. da Silva, V. F. da Costa, and W. Xu, Preliminary results on
stability index, IEEE Trans. Power Syst., vol. 3, no. 2, pp. 669675, improving the modal analysis technique for voltage stability assess-
May 1988. ment, in Proc. IEEE Power Eng. Soc. Summer Meeting, 2000, vol. 3,
[4] N. Flatabo, R. Ognedal, and T. Carlsen, Voltage stability condition in pp. 19461950.
a power system calculated by sensitivity methods, IEEE Trans. Power [15] I. Musirin and T. K. A. Rahman, On-line voltage stability based con-
Syst., vol. 5, no. 4, pp. 12861293, Nov. 1990. tingency ranking using fast voltage stability index, in Proc. IEEE PES
[5] R. A. Schlueter et al., Methods for determining proximity to voltage Transmission and Distribution Conf. Exhib. 2002: Asia-Pacific, Oct.
collapse, IEEE Trans. Power Syst., vol. 6, no. 1, pp. 285292, Feb. 2002, vol. 2, pp. 11181123.
1991. [16] G. Verbi and F. Gubina, A new concept of voltage-collapse protec-
[6] C. A. Canizares et al., Point of collapse methods applied to AC/DC tion based on local phasors, IEEE Trans. Power Del., vol. 19, no. 2,
power systems, IEEE Trans. Power Syst., vol. 7, no. 2, pp. 673683, pp. 576581, Apr. 2004.
May 1992. [17] I. mon et al., Local voltage stability index using Tellegan's theorem,
[7] B. Gao, G. K. Morrison, and P. Kundur, Voltage stability evalua- IEEE Trans. Power Syst., vol. 21, no. 3, pp. 12671275, Aug. 2006.
tion using modal analysis, IEEE Trans. Power Syst., vol. 7, no. 4, pp. [18] S. Corsi and G. N. Taranto, A real-time voltage instability identi-
15291542, Nov. 1992. cation algorithm based on local phasor measurements, IEEE Trans.
[8] P. Kundur, K. Morison, and B. Gao, Practical considerations Power Syst., vol. 23, no. 3, pp. 12711279, Aug. 2008.
in voltage stability assessment, Int. J. Elect. Power Energy [19] H. A. D. Lee and G. Andersson, Analysis of voltage and power inter-
Syst.Special Issue on Voltage Stability and Collapse, vol. 15, no. 4, actions in multi-infeed HVDC systems, IEEE Trans. Power Del., vol.
pp. 205215, 1993. 28, no. 2, pp. 816823, Apr. 2013.
[9] W. Xu, Y. Mansour, and P. G. Harrington, Planning methodologies [20] M. Brookes, The Matrix Reference Manual, 2011 [Online]. Available:
for voltage stability limited power systems, Int. J. Elect. Power En- http://www.ee.imperial.ac.uk/hp/staff/dmb/matrix/intro.html
ergy Syst.Special Issue on Voltage Stability and Collapse, vol. 15, [21] Power System Test Case Archive [Online]. Available: https://www.ee.
no. 4, pp. 221228, 1993. washington.edu/research/pstca/
[10] Y. Mansour et al., SVC placement using critical modes of voltage
instability, IEEE Trans. Power Syst., vol. 9, no. 2, pp. 757763, May
1994.
[11] P. A. Lf and G. Andersson, Fast calculation of a voltage stability
index, IEEE Trans. Power Syst., vol. 7, no. 1, pp. 5464, Feb. 1992. Denis Hau Aik Lee (M'1988) was born in Kuching, Malaysia. He received the
[12] B. V. Ramana et al., A two bus equivalent method for determination of B.Eng. degree from the National University of Singapore in 1984 and the Ph.D.
steady-state voltage stability limit of a power system, Int. J. Computat. degree from the Royal Institute of Technology, Stockholm, Sweden, in 1998.
Eng. Res., vol. 2, no. 2, pp. 428434, Mar.Apr. 2012. Currently he is employed with the Sarawak Electricity Supply Corporation,
[13] G. B. Jasmon and L. H. C. C. Lee, Stability of loadow techniques for an electricity utility of the Sarawak Energy Berhad group of companies in
distribution system voltage stability analysis, IEE Proc. C, vol. 138, Sarawak, East Malaysia. His technical interests include power system stability,
no. 6, pp. 479484, Nov. 1991. dynamics, and control, and ac/dc interactions in HVDC systems.