RTD/Thermocouple/mA
NEW From Cost-effective DYNA- inputs (linear/sq. rt)
Series Family Up to 4 Retransmission
Microprocessor based outputs 4-key membrane
Site Programmable-Program it, key board for programming
Fit it, Forget it! 24 VDC output to Power
Compact Size- 100 x 75 x 110 Transmitters
mm only
Introduction:
DYNA SM-D Temperature Transmitters are part of LECTROTEK
LTRON-Series Microprocessor based Process Measurement and
Control products. The instruments are innovative in terms of compact
size. and cost-effective, yet full featured in terms of ease of use,
programmability. It has full keyboard based operation for
programming inputs, ranges, decimal point, linear or square-root
input selection and calibration.
Unpacking, Installation:
Unpack the instrument and check for presence of this Operation
Manual, pair of clamps and physical damage if any. Report to the
dealer for any shortages or warranty service/replacement.
Install the instrument on the rail. Connect power supply as ordered
and marked on the instruments label. wire the instrument preferably
through an external fuse and a 0.5A MCB for protections against
shorts/over current protection. The instrument display comes on when
power on is done. In case of no display condition, check power supply
cord or connection point, In case of further difficulty please contact
dealer.
SPECIFICATIONS:
Inputs/ranges (site configurable) see table below
INPUT RANGES Resolutio
(default) n
Pt-100 RTD (3-wire) 000.0 to 0.1 o C
+400.0 o C
Fe-Const. Thermocouple 0 to 600 o C 1oC
(ANSI-J)
Cr-Al. Thermocouple (ANSI-K) 0 to 1200 o C 1oC
Pt-Pt-Rh 13% Thermocouple 0 to 1600 o C 1oC
(ANSI-R)
Pt-Pt-Rh 10% Thermocouple 0 to 1600 o C 1oC
(ANSI-S)
4-20 mA DC (linear/square -1999 to +9999 Up to 3
root) digits
Ambient temperature Correction automatic for thermocouple inputs
Accuracy +/- 0.25% FS +/- 1 digit
Display 4 digits, 7-segment LED, Red, in 14.2 mm
height
Keyboard 4-key membrane keyboard
Calibration From front keyboard, software based
Power Supply 100 - 260 Vac 50hz
Retransmission output Up to 4
Aux. Power Output 24 VDC, 30 mA output to power transmitters
(standard feature)
Wiring Screwed Maximum 2.5 mm wire size
Terminals
Enclosure Plastic, 100 x 75 x 110 mm (W x H x D), with
din-Rail mounting.
Environmental 0 to 50 o C
Ambient Temperature
Relative Humidity 90% RH max. Non-condensing
Common Terminology:
As abbreviations for commonly used instrument terms are referred to
in this manual, a definition of these as used for DYNA SM-D is given
below:
PV: Process Value such as the temperature or process variable under
measurement.
Programming:
As the instrument is a universal type, the default input programmed is
CR-AL..
The instruments can be operated in divided in 3 modes:
Operation Mode - This mode operates the DYNA SM-D
Configuration Mode - Use this mode to re-configure the
instruments input, ranges.
Calibration Mode - Use this mode to calibrate the instruments
inputs/output.
Output calibration Mode-all four outputs can be calibrated for
their values
Accordingly 0/4/20 Ma
E (Scroll
Backward)
IMPORTANT NOTE: IN ALL SECTIONS, WHEN MULTIPLE KEY
FUNCTIONS ARE REQUIRED, THE FIRST KEY IS TO BE PRESSED
FIRST, AND KEEPING IT PRESSED, THE SECOND KEY HAS TO BE
THEN PRESSED, TO GO INTO THE PARTICULAR MODE. Eg.: When S
+ E key press instruction is given, Press S key first, and keeping
it pressed, press the E key, with another finger then release S key
and
Then release E key, to get into the Input calibration mode.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
P N E + 24V
1 0 0 -2 6 4 V
-D
1 3
2 4
U N IV E R S A L S IG N A L
IS O L A T O R /R E P E A T E R
TC+ -
+OP3- +OP2- +OP1- m A RTD
+
COM A B OP4
-
Rs485 4 -2 0 m A 4 -2 0 m A 4 -2 0 m A 4 -2 0 m A IN P U T
+ - R B G
20 21 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38