INSTRUCTION MANUAL FOR DYNA SM

_D

MICORPROCESSOR BASED TEMPERATURE TRANSMITTER

RTD/Thermocouple/mA
NEW From Cost-effective DYNA- inputs (linear/sq. rt)
Series Family Up to 4 Retransmission
Microprocessor based outputs 4-key membrane
Site Programmable-Program it, key board for programming
Fit it, Forget it! 24 VDC output to Power
Compact Size- 100 x 75 x 110 Transmitters
mm only

Introduction:
DYNA SM-D Temperature Transmitters are part of LECTROTEK
LTRON-Series Microprocessor based Process Measurement and
Control products. The instruments are innovative in terms of compact
size. and cost-effective, yet full featured in terms of ease of use,
programmability. It has full keyboard based operation for
programming inputs, ranges, decimal point, linear or square-root
input selection and calibration.

The DYNA SM-D accepts Pt-100 RTD, thermocouples, 4-20 mA (linear


or square-root) inputs. The instrument is compact and highly
functional fascia consists of a 4-digit 7-segment LED display and 4-key
membrane keyboard for programming/parameter selection purposes.

The enclosure is a 100 x 75 x 110 mm (W x H x D) sized engineering


plastic enclosure suitable for din rail mounting.

Unpacking, Installation:
Unpack the instrument and check for presence of this Operation
Manual, pair of clamps and physical damage if any. Report to the
dealer for any shortages or warranty service/replacement.
Install the instrument on the rail. Connect power supply as ordered
and marked on the instruments label. wire the instrument preferably
through an external fuse and a 0.5A MCB for protections against
shorts/over current protection. The instrument display comes on when
power on is done. In case of no display condition, check power supply
cord or connection point, In case of further difficulty please contact
dealer.
SPECIFICATIONS:
Inputs/ranges (site configurable) see table below
INPUT RANGES Resolutio
(default) n
Pt-100 RTD (3-wire) 000.0 to 0.1 o C
+400.0 o C
Fe-Const. Thermocouple 0 to 600 o C 1oC
(ANSI-J)
Cr-Al. Thermocouple (ANSI-K) 0 to 1200 o C 1oC
Pt-Pt-Rh 13% Thermocouple 0 to 1600 o C 1oC
(ANSI-R)
Pt-Pt-Rh 10% Thermocouple 0 to 1600 o C 1oC
(ANSI-S)
4-20 mA DC (linear/square -1999 to +9999 Up to 3
root) digits
Ambient temperature Correction automatic for thermocouple inputs
Accuracy +/- 0.25% FS +/- 1 digit
Display 4 digits, 7-segment LED, Red, in 14.2 mm
height
Keyboard 4-key membrane keyboard
Calibration From front keyboard, software based
Power Supply 100 - 260 Vac 50hz
Retransmission output Up to 4
Aux. Power Output 24 VDC, 30 mA output to power transmitters
(standard feature)
Wiring Screwed Maximum 2.5 mm wire size
Terminals
Enclosure Plastic, 100 x 75 x 110 mm (W x H x D), with
din-Rail mounting.
Environmental 0 to 50 o C
Ambient Temperature
Relative Humidity 90% RH max. Non-condensing

Common Terminology:
As abbreviations for commonly used instrument terms are referred to
in this manual, a definition of these as used for DYNA SM-D is given
below:
PV: Process Value such as the temperature or process variable under
measurement.
Programming:
As the instrument is a universal type, the default input programmed is
CR-AL..
The instruments can be operated in divided in 3 modes:
Operation Mode - This mode operates the DYNA SM-D
Configuration Mode - Use this mode to re-configure the
instruments input, ranges.
Calibration Mode - Use this mode to calibrate the instruments
inputs/output.
Output calibration Mode-all four outputs can be calibrated for
their values
Accordingly 0/4/20 Ma

Operation Mode KEYBOARD DISPLAY SHOWS


Normal Display Keyboard consists of 4
DYNA SM-D normally keys
displays the process S (Scroll 123.4 Process value
value on its 4-digit Forward)
display. In case
sensor/input is open or (Decrease)
not connected, display
shows OPEN. (Increase)

E (Scroll
Backward)
IMPORTANT NOTE: IN ALL SECTIONS, WHEN MULTIPLE KEY
FUNCTIONS ARE REQUIRED, THE FIRST KEY IS TO BE PRESSED
FIRST, AND KEEPING IT PRESSED, THE SECOND KEY HAS TO BE
THEN PRESSED, TO GO INTO THE PARTICULAR MODE. Eg.: When S
+ E key press instruction is given, Press S key first, and keeping
it pressed, press the E key, with another finger then release S key
and
Then release E key, to get into the Input calibration mode.

Always sequence of operation should be:-1) configuration mode


2) calibration mode 3) output calibration mode

Configuration Mode Keyboard Operation Display Shows


(sequentially)
What is its function? Step1: Press S + E Display shows ZERO.
In this mode the user keys. mA input (linear mA
can change DC)
instruments input, Step2: Press S + Display shows input
resolution (decimal keys. type
point), To get into this For eg. rtd/CrAL..
mode press Step3: Press or ).
S + E keys first. keys to select desired
Press S + input.
together. Eg.: rtd
Instrument Display shows rngH
shows the input Step4: Press S key to Display shows rngL
configured at select RANGE HI.
present. Step5: Press S key to
By using , select RANGE LO Display shows Dp
keys select Step6: Press S key to
required input. select decimal point Display shows 002.0
Get out of the Step7:Press or (pv)
mode by keys to select desired
pressing S+E dp Display shows SrnO
keys again. Step8: Press S key to
select serial-number Display shows 0001
Step9: Press S key to
select
Step10:Press or
keys to select
desired serial number
Input Calibration Keyboard Operation Display Shows
Mode
What is input Connect required Example given below
calibration mode? calibration source is for an RTD input
In this mode user can ( RTD/mA/mV) at the configured
check or re-calibrate input terminals. DYNA SM-D
the DYNA SM-D at 1. Press S + E keys. Connect R to
site. Display terminal 35.
To get into this mode, shows ZErO. Connect B to
press 1. S + E keys 2. Press E key to see terminal 36.
first. input at Connect G to
2. Press E key ZERO calibration terminal 37
successively to side.
select ZERO, SPAN, 3. Press OR keys ZErO (Zero side input
AMBIENT (for T/C to adjust errors if calibration).
input is configured). any. 000.3 (Pt-100 input at
3. Get out of the mode 4. Press E, displays 100 with an error of
by SPAn. 0.3)
pressing S + E keys 5. Repeat calibration 000.0 (0.3 error
again. for corrected)
SPAN, give full span
input SPAn (Span side input
and adjust error by calibration)
OR keys. 402.0 (Pt-100
resistance for 400 o C)
400.0 (after adjusting
4. Press E key error)
successively to
select ZERO, SPAN, Example given below
AMBIENT (for T/C 6. Press S + E keys. is for CR-AL
input is configured). Display thermocouple
5. Get out of the mode shows ZErO. input configured
by 7. Press E key to see Connect TC+ to
pressing S + E keys input at terminal 35.
again ZERO calibration Connect TC- to
side. terminal 36.
8. Press OR keys SHORT TERMINALS
to adjust errors if 36 AND 37
any.
9. Press E, displays Feed absolute mV of
SPAn. respective
10. Repeat calibration thermocouples
for At zero side and
SPAN, give full span span side
input Foe ex;- feed 2.02
and adjust error by Mv for cr-al
OR keys. thermocouple for
zero side. And 48.82
mV for span side.

Output Calibration Keyboard Operation Display Shows


Mode

What is output Step 1: Connect a Example given below


calibration mode? DMM at the DYNA is for an RTD input
In this mode user can SM-DS s output configured ..
calibrate all the four terminals 30and31, to
DYNA SM-D isolated read the re- 0CH1(Zero side
re-transmission signal transmission output1 output calibration).
output to 0-20 ma/4-20 Step 2: Press S+ 4CH1(4mA output
mA. Keys together calibration).
Step 3: press E
To get into this mode, Step4:Press OR
press 1. S + Keys to adjust mA
keys first. output to 4mA. 20CH1(Span side
Step 5: Press E Key output calibration)
to display span side).
Step 6: Press OR .
Keys to adjust mA 0CH2(Zero side
output to 20mA. output calibration).
2 Press S key again to 4CH2(4mA output
go to Repeat same calibration).
Output calibration of procedure as above to
next Output that is calibrate OUTPUT
OUTPUT 2 2.connect DMM to
measure current 20CH2(Span side
output between output calibration)
terminals28 and 29
3. Get out of the mode Similarly connect
by DMM Between
pressing S + terminal 26 and 27
keys again. For OUTPUT 3.
.connect DMM to
measure current
output between
terminal 24and 25 for
OUTPUT 4.

CONNECTION DIAGRAM:- SHORT TERMINALS 36 AND 37 FOR


TC INPUT

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
P N E + 24V
1 0 0 -2 6 4 V
-D

1 3

2 4

U N IV E R S A L S IG N A L
IS O L A T O R /R E P E A T E R

TC+ -
+OP3- +OP2- +OP1- m A RTD
+
COM A B OP4
-
Rs485 4 -2 0 m A 4 -2 0 m A 4 -2 0 m A 4 -2 0 m A IN P U T
+ - R B G
20 21 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38