JINDAL INDIA THERMAL POWER LIMITED

Inspected By : Sri Rajech Sonker , Sri B C Mohapatra, Sri Abit Panigrahi,Sri


DATE:- 14.09.2017
Bidyadhar Barik, Sri K.Kishan, Sri Rajesh Kumar

Safety Inspection Report TG Cable Gallery,0m


Deptt./ Section Brief description of the
Sl. No. Area Photographs if any Responsibility Target Date
Exact Location unsafe condition

1 2 3 4 5 6 7

Unit#1
Electrical socket found
1 Cable 0 meter EMD
in hanging condition.
gallery,

Power cables are


found in hanging
Unit#1 condition, need
2 Cable 0 meter dressing.Poor EMD
gallery illumination
observed inside the
cable gallery

Power cables are


Unit#1
found in hanging
3 Cable 0 meter EMD
condition, need
gallery
dressing.

Unit#1
Poor housekeeping
4 Cable 0 meter EMD
observed.
gallery
Deptt./ Section Brief description of the
Sl. No. Area Photographs if any Responsibility Target Date
Exact Location unsafe condition

1 2 3 4 5 6 7

Unit#1 Power cables are


5 Cable 0 meter found kept in EMD
gallery haphazard manner.

Unit#1 Fall ceiling material


6 Cable 0 meter found stored in cable CIVIL
gallery gallery.

Unit#1 Bundle of cables kept


7 Cable 0 meter on cable tray, need EMD
gallery removal.

Fall ceiling material


0 meter outside
8 Unit#1 found stored in cable CIVIL
cable gallery
gallery.
Deptt./ Section Brief description of the
Sl. No. Area Photographs if any Responsibility Target Date
Exact Location unsafe condition

1 2 3 4 5 6 7

Unit#2 Flammabkle materials


9 Cable 0 meter are stored on cable EMD
gallery tray at many locations.

Unit#2 Unused cable tray


10 Cable 0 meter found kept on fire EMD
gallery sprinkler line.

Power cables are


Unit#2
found in hanging
11 Cable 0 meter EMD
condition, need
gallery
dressing.

Unit#2
Unused electrical DB
12 Cable 0 meter EMD
found on the walkway
gallery
Deptt./ Section Brief description of the
Sl. No. Area Photographs if any Responsibility Target Date
Exact Location unsafe condition

1 2 3 4 5 6 7

Unit#2 Water accumulation


13 Cable 0 meter found inside the cable CIVIL
gallery gallery.

Naked power cable


Unit#2
insereted without top
14 Cable 0 meter EMD
plug and another board
gallery
in open condition.

Oil drums should be


15 Unit#2 ,0m MOT wall kept at a safe distance TMD
from the electrrical DB.

Sprinkler line not


Cable commissioned.Pipe
16 0 meter BOP
gallery found in open
condition.