From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Size
Equipment Equipment Runs Core
(Sq.mm)

FROM NEW SWITCHGEAR


635 KVA DIESEL GENERATOR-1 MCC - LV SWG
1 HOTTF-1 DG01-MCC-PC-01
(HO1-DEG-0101) SYN PANEL (H01-MCC-01)
Trench 1 4 240

636 KVA DIESEL GENERATOR-1 MCC - LV SWG


2 HOTTF-1 DG01-MCC-PC-02
(HO1-DEG-0101) SYN PANEL (H01-MCC-01)
Trench 1 4 240

MCC - LV SWG CRUDE TRANSFER PUMP -1


3 HOTTF-1 MCC-1102A-PC-01
(H01-MCC-01) (H01 - G - 1102A)
Trench 1 3 16

MCC - LV SWG CRUDE TRANSFER PUMP -1


4 HOTTF-1 MCC-1102B-PC-01
(H01-MCC-01) (H01 - G - 1102B)
Trench 1 3 16

MCC - LV SWG CRUDE TRANSFER PUMP -1


5 HOTTF-1 MCC-1102C-PC-01
(H01-MCC-01) (H01 - G - 1102C) STAND BY
Trench 1 3 16

MCC - LV SWG CRUDE TRANSFER PUMP -2


6 HOTTF-1 MCC-1106A-PC-01
(H01-MCC-01) (H01-G-1106A)
Trench 1 3 16

MCC - LV SWG CRUDE TRANSFER PUMP -2


7 HOTTF-1 MCC-1106B-PC-01
(H01-MCC-01) (H01-G-1106B)
Trench 1 3 16

MCC - LV SWG WASH WATER PUMP


8 HOTTF-1 MCC-1602A-PC-01
(H01-MCC-01) (H01-G-1602A)
Trench 1 3 25

MCC - LV SWG WASH WATER PUMP


9 HOTTF-1 MCC-1602B-PC-01
(H01-MCC-01) (H01-G-1602B)
Trench 1 3 25

MCC - LV SWG COMPACT ELECTROSTATIC COALESCER


10 HOTTF-1 MCC-1103-PC-01
(H01-MCC-01) (H01-G-1103)
Trench 1 3 6

MCC - LV SWG OFF SPEC PUMP


11 HOTTF-1 MCC-1204-PC-01
(H01-MCC-01)
Trench 1 3 6

MCC - LV SWG NITROGEN GENERATOR


12 HOTTF-1 MCC-PC-0101
(H01-MCC-01) (PACKAGE LOAD)
Trench 1 3 240

MCC - LV SWG
13 HOTTF-1 MCC-PC-0102A
(H01-MCC-01)
BOILER LOAD-1 Trench 1 3 16

MCC - LV SWG
14 HOTTF-1 MCC-PC-0102B
(H01-MCC-01)
BOILER LOAD-2 Trench 1 3 16
PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Size
Equipment Equipment Runs Core
(Sq.mm)

MCC - LV SWG
15 HOTTF-1 MCC-PC-0102C
(H01-MCC-01)
BOILER LOAD-3 Trench 1 3 16

MCC - LV SWG
16 HOTTF-1 MCC-PC-0103
(H01-MCC-01)
AIR COMPRESSOR UNIT-1 Trench 1 3 16

MCC - LV SWG
17 HOTTF-1 MCC-PC-0104
(H01-MCC-01)
TO AC UPS UNIT Trench 1 3 6

MCC - LV SWG
18 HOTTF-1 MCC-PC-0105-01
(H01-MCC-01)
TO SEPERATOR - 03 Trench 1 5 16

MCC - LV SWG
19 HOTTF-1 MCC-PC-0105-02
(H01-MCC-01)
TO SEPERATOR - 03 Trench 1 5 16

MCC - LV SWG
20 HOTTF-1 MCC-PC-0106
(H01-MCC-01)
EXISITNG LOW VOLTAGE SWITCHGEAR Trench 1 4 240

MCC - LV SWG
21 HOTTF-1 MCC-PC-0107
(H01-MCC-01)
OPERATOR CABIN Trench 1 3 16

MCC - LV SWG
22 HOTTF-1 MCC-PC-0108
(H01-MCC-01)
PORTABLE CABIN OFFICE Trench 1 3 16

FROM EXISITING SWITCHGEAR

23 HOTTF-1 MCC-PC-0108 EXISITING SWITCHGEAR TO EXISITING LIGHT AND SMALL POWER DB Trench 1 4 16

TO EXISITING LIGHT AND SMALL


24 HOTTF-1 JB-LPDB-PC-01
POWER DB
LIGHTING JUNCTION BOX-1 Trench 1 4 16

25 HOTTF-1 LIGHTING JUNCTION BOX-1 TO ALL LIGHT FITTING _ 1 3 2.5

26 HOTTF-1 MCC-PC-0109 EXISITING SWITCHGEAR ANTISCALANT Trench 1 3 6

27 HOTTF-1 MCC-PC-0110 EXISITING SWITCHGEAR H2S SCAVENGER Trench 1 3 6


PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Size
Equipment Equipment Runs Core
(Sq.mm)

28 HOTTF-1 MCC-PC-0111 EXISITING SWITCHGEAR DE MULSIFER Trench 1 3 6

29 HOTTF-1 MCC-PC-0112 EXISITING SWITCHGEAR DIESEL INJECTION Trench 1 3 6

30 HOTTF-1 MCC-PC-0113 EXISITING SWITCHGEAR ANTI FOAM Trench 1 3 6

31 HOTTF-1 MCC-PC-0114 EXISITING SWITCHGEAR O2 SCAVENGER Trench 1 3 6

32 HOTTF-1 MCC-PC-0115-01 EXISITING SWITCHGEAR TO SEPERATOR 01 & 02 Trench 1 5 16

33 HOTTF-1 MCC-PC-0115-02 EXISITING SWITCHGEAR TO SEPERATOR 01 & 02 Trench 1 5 16

CONTROL CABLE
MCC - LV SWG CRUDE TRANSFER PUMP -1
34 HOTTF-1 MCC-1102A-CC-LCS-01
(H01-MCC-01) (H01 - G - 1102A) - LCS
Trench 1 5 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -1


35 HOTTF-1 MCC-1102A-CC-ES-01
(H01-MCC-01) (H01 - G - 1102A) - EMERGENCY STOP
Trench 1 3 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -1


36 HOTTF-1 MCC-1102B-CC-LCS-01
(H01-MCC-01) (H01 - G - 1102B) - LCS
Trench 1 5 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -1


37 HOTTF-1 MCC-1102B-CC-ES-01
(H01-MCC-01) (H01 - G - 1102B) - EMERGENCY STOP
Trench 1 3 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -1


38 HOTTF-1 MCC-1102C-CC-LCS-01
(H01-MCC-01) (H01 - G - 1102C) - LCS
Trench 1 5 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -1


39 HOTTF-1 MCC-1102C-CC-ES-01
(H01-MCC-01) (H01 - G - 1102C) - EMERGENCY STOP
Trench 1 3 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -2


40 HOTTF-1 MCC- 1106A-CC-LCS-01
(H01-MCC-01) (H01-G-1106A) - LCS
Trench 1 5 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -2


41 HOTTF-1 MCC-1106A-CC-ES-01
(H01-MCC-01) (H01-G-1106A) - EMERGENCY STOP
Trench 1 3 2.5
PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Size
Equipment Equipment Runs Core
(Sq.mm)

MCC - LV SWG CRUDE TRANSFER PUMP -2


42 HOTTF-1 MCC- 1106B-CC-LCS-01
(H01-MCC-01) (H01-G-1106B) - LCS
Trench 1 5 2.5

MCC - LV SWG CRUDE TRANSFER PUMP -2


43 HOTTF-1 MCC- 1106B-CC-ES-01
(H01-MCC-01) (H01-G-1106B) - EMERGENCY STOP
Trench 1 3 2.5

MCC - LV SWG WASH WATER PUMP


44 HOTTF-1 MCC-1602A-CC-LCS-01
(H01-MCC-01) (H01-G-1602A) - LCS
Trench 1 5 2.5

MCC - LV SWG WASH WATER PUMP


45 HOTTF-1 MCC-1602A-CC-ES-01
(H01-MCC-01) (H01-G-1602A) - EMERGENCY STOP
Trench 1 3 2.5

MCC - LV SWG WASH WATER PUMP


46 HOTTF-1 MCC-1602B-CC-LCS-01
(H01-MCC-01) (H01-G-1602B) - LCS
Trench 1 5 2.5

MCC - LV SWG WASH WATER PUMP


47 HOTTF-1 MCC-1602B-CC-ES-01
(H01-MCC-01) (H01-G-1602B) - EMERGENCY STOP
Trench 1 3 2.5

MCC - LV SWG
48 HOTTF-1 MCC-1204-CC-LCS-01
(H01-MCC-01)
OFF SPEC PUMP-LCS Trench 1 5 2.5

MCC - LV SWG
49 HOTTF-1 MCC-1204-CC-ES-01
(H01-MCC-01)
OFF SPEC PUMP-EMERGENCY STOP Trench 1 3 2.5
PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Volta
Size
Equipment Equipment Runs Core Type Gra
(Sq.mm)
(KV

FROM NEW SWITCHGEAR


635 KVA DIESEL GENERATOR-1 MCC - LV SWG
1 HOTTF-1 DG01-MCC-PC-01
(HO1-DEG-0101) SYN PANEL (H01-MCC-01)
Trench 1 4 240 Cu/XLPE/PVC/GSWA/PVC 0.6

636 KVA DIESEL GENERATOR-1 MCC - LV SWG


2 HOTTF-1 DG01-MCC-PC-02
(HO1-DEG-0101) SYN PANEL (H01-MCC-01)
Trench 1 4 240 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG CRUDE TRANSFER PUMP -1


3 HOTTF-1 MCC-1102A-PC-01
(H01-MCC-01) (H01 - G - 1102A)
Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG CRUDE TRANSFER PUMP -1


4 HOTTF-1 MCC-1102B-PC-01
(H01-MCC-01) (H01 - G - 1102B)
Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG CRUDE TRANSFER PUMP -1


5 HOTTF-1 MCC-1102C-PC-01
(H01-MCC-01) (H01 - G - 1102C) STAND BY
Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG CRUDE TRANSFER PUMP -2


6 HOTTF-1 MCC-1106A-PC-01
(H01-MCC-01) (H01-G-1106A)
Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG CRUDE TRANSFER PUMP -2


7 HOTTF-1 MCC-1106B-PC-01
(H01-MCC-01) (H01-G-1106B)
Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG WASH WATER PUMP


8 HOTTF-1 MCC-1602A-PC-01
(H01-MCC-01) (H01-G-1602A)
Trench 1 3 25 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG WASH WATER PUMP


9 HOTTF-1 MCC-1602B-PC-01
(H01-MCC-01) (H01-G-1602B)
Trench 1 3 25 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG COMPACT ELECTROSTATIC COALESCER


10 HOTTF-1 MCC-1103-PC-01
(H01-MCC-01) (H01-G-1103)
Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG OFF SPEC PUMP


11 HOTTF-1 MCC-1204-PC-01
(H01-MCC-01)
Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG NITROGEN GENERATOR


12 HOTTF-1 MCC-PC-0101
(H01-MCC-01) (PACKAGE LOAD)
Trench 1 3 240 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
13 HOTTF-1 MCC-PC-0102A
(H01-MCC-01)
BOILER LOAD-1 Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
14 HOTTF-1 MCC-PC-0102B
(H01-MCC-01)
BOILER LOAD-2 Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6
PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Volta
Size
Equipment Equipment Runs Core Type Gra
(Sq.mm)
(KV
MCC - LV SWG
15 HOTTF-1 MCC-PC-0102C
(H01-MCC-01)
BOILER LOAD-3 Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
16 HOTTF-1 MCC-PC-0103
(H01-MCC-01)
AIR COMPRESSOR UNIT-1 Trench 1 3 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
17 HOTTF-1 MCC-PC-0104
(H01-MCC-01)
TO AC UPS UNIT Trench 1 3 6 Cu/PVC/PVC 450/7

MCC - LV SWG
18 HOTTF-1 MCC-PC-0105-01
(H01-MCC-01)
TO SEPERATOR - 03 Trench 1 5 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
19 HOTTF-1 MCC-PC-0105-02
(H01-MCC-01)
TO SEPERATOR - 03 Trench 1 5 16 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
20 HOTTF-1 MCC-PC-0106
(H01-MCC-01)
EXISITNG LOW VOLTAGE SWITCHGEAR Trench 1 4 240 Cu/XLPE/PVC/GSWA/PVC 0.6

MCC - LV SWG
21 HOTTF-1 MCC-PC-0107
(H01-MCC-01)
OPERATOR CABIN Trench 1 3 16 Cu/PVC/PVC 0.6

MCC - LV SWG
22 HOTTF-1 MCC-PC-0108
(H01-MCC-01)
PORTABLE CABIN OFFICE Trench 1 3 16 Cu/PVC/PVC 0.6

FROM EXISITING SWITCHGEAR

23 HOTTF-1 MCC-PC-0108 EXISITING SWITCHGEAR TO EXISITING LIGHT AND SMALL POWER DB Trench 1 4 16 Cu/XLPE/PVC/GSWA/PVC 0.6

TO EXISITING LIGHT AND SMALL


24 HOTTF-1 JB-LPDB-PC-01
POWER DB
LIGHTING JUNCTION BOX-1 Trench 1 4 16 Cu/XLPE/PVC/GSWA/PVC 0.6

25 HOTTF-1 LIGHTING JUNCTION BOX-1 TO ALL LIGHT FITTING _ 1 3 2.5 Cu/PVC/PVC 450/7

26 HOTTF-1 MCC-PC-0109 EXISITING SWITCHGEAR ANTISCALANT Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

27 HOTTF-1 MCC-PC-0110 EXISITING SWITCHGEAR H2S SCAVENGER Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6


PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Volta
Size
Equipment Equipment Runs Core Type Gra
(Sq.mm)
(KV

28 HOTTF-1 MCC-PC-0111 EXISITING SWITCHGEAR DE MULSIFER Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

29 HOTTF-1 MCC-PC-0112 EXISITING SWITCHGEAR DIESEL INJECTION Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

30 HOTTF-1 MCC-PC-0113 EXISITING SWITCHGEAR ANTI FOAM Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

31 HOTTF-1 MCC-PC-0114 EXISITING SWITCHGEAR O2 SCAVENGER Trench 1 3 6 Cu/XLPE/PVC/GSWA/PVC 0.6

32 HOTTF-1 MCC-PC-0115-01 EXISITING SWITCHGEAR TO SEPERATOR 01 & 02 Trench 1 5 16 Cu/XLPE/PVC/GSWA/PVC 0.6

33 HOTTF-1 MCC-PC-0115-02 EXISITING SWITCHGEAR TO SEPERATOR 01 & 02 Trench 1 5 16 Cu/XLPE/PVC/GSWA/PVC 0.6

CONTROL CABLE
MCC - LV SWG CRUDE TRANSFER PUMP -1
34 HOTTF-1 MCC-1102A-CC-LCS-01
(H01-MCC-01) (H01 - G - 1102A) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -1


35 HOTTF-1 MCC-1102A-CC-ES-01
(H01-MCC-01) (H01 - G - 1102A) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -1


36 HOTTF-1 MCC-1102B-CC-LCS-01
(H01-MCC-01) (H01 - G - 1102B) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -1


37 HOTTF-1 MCC-1102B-CC-ES-01
(H01-MCC-01) (H01 - G - 1102B) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -1


38 HOTTF-1 MCC-1102C-CC-LCS-01
(H01-MCC-01) (H01 - G - 1102C) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -1


39 HOTTF-1 MCC-1102C-CC-ES-01
(H01-MCC-01) (H01 - G - 1102C) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -2


40 HOTTF-1 MCC- 1106A-CC-LCS-01
(H01-MCC-01) (H01-G-1106A) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -2


41 HOTTF-1 MCC-1106A-CC-ES-01
(H01-MCC-01) (H01-G-1106A) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7
PROJECT TITLE:

HEAVY OIL LONG TERM TESTING FACILITY (HOT


DOCUMENT TITLE:

ELECTRICAL CABLE SCHEDULE

From Description To Description Cable Details

Sr.No. Unit Cable Numbering Routed Via


Volta
Size
Equipment Equipment Runs Core Type Gra
(Sq.mm)
(KV
MCC - LV SWG CRUDE TRANSFER PUMP -2
42 HOTTF-1 MCC- 1106B-CC-LCS-01
(H01-MCC-01) (H01-G-1106B) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG CRUDE TRANSFER PUMP -2


43 HOTTF-1 MCC- 1106B-CC-ES-01
(H01-MCC-01) (H01-G-1106B) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG WASH WATER PUMP


44 HOTTF-1 MCC-1602A-CC-LCS-01
(H01-MCC-01) (H01-G-1602A) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG WASH WATER PUMP


45 HOTTF-1 MCC-1602A-CC-ES-01
(H01-MCC-01) (H01-G-1602A) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG WASH WATER PUMP


46 HOTTF-1 MCC-1602B-CC-LCS-01
(H01-MCC-01) (H01-G-1602B) - LCS
Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG WASH WATER PUMP


47 HOTTF-1 MCC-1602B-CC-ES-01
(H01-MCC-01) (H01-G-1602B) - EMERGENCY STOP
Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG
48 HOTTF-1 MCC-1204-CC-LCS-01
(H01-MCC-01)
OFF SPEC PUMP-LCS Trench 1 5 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7

MCC - LV SWG
49 HOTTF-1 MCC-1204-CC-ES-01
(H01-MCC-01)
OFF SPEC PUMP-EMERGENCY STOP Trench 1 3 2.5 CU/XLPE/PVC/GSWA/PVC-FR 450/7