Flat Plate Design

Long Span 18.17 ft


Short Span 14.33 ft
Span Length (Ln): 17.34 ft

(L2): 14.33 ft

Minimum Thickness : 4.83 in. 6.36 in.


(BNBC)

or ,

Minimum thickness (tmin) = 7.79 in.

Hence
Thikness (choose)= 7.0 in

Load Calculation:

Self Weight = 0.09 ksf


Floor Finish = 0.02 ksf
Partitioon Wall = 0.05 ksf
Live Load = 0.04 ksf
w= 0.198 ksf

For Interior Panel:


Moment Calculation :
M0 = 87.889115
For Interior Panel :

Total negative Moment : 57.12792 Kip-ft

Total positive Moment : 30.76119 Kip-ft

Short Direction:

Moment (Kip-ft) depth (d) Steel (As), in2


Strip
(-) ve Moment (+) ve Moment in. As(-) ve
Column strip 42.85 18.46 6.00 4.00

Middle Strip 14.28 12.30 6.00 1.33

For Column Strip:


As(-) ve in2 Dia of bar as No.of Bar Spacing Unit
4.00 10mm 0.11 36.37 3.00 in. c/c
12mm 0.2 20.01 4.30 in. c/c
16mm 0.31 12.91 8.06 in. c/c

As(+) ve in2 Dia of bar as No.of Bar Spacing Unit


1.72 10mm 0.11 15.67 6.96 in. c/c
12mm 0.2 8.62 12.65 in. c/c
16mm 0.31 5.56 19.61 in. c/c

For Middle Strip:


As(-) ve( in2) Dia of bar as No.of Bar Spacing Unit
1.33 10mm 0.11 12.12 8.99 in. c/c
12mm 0.2 6.67 16.35 in. c/c
16mm 0.31 4.30 25.34 in. c/c

As(+) ve (in2) Dia of bar as No.of Bar Spacing Unit


1.15 10mm 0.11 10.45 10.44 in. c/c
12mm 0.2 5.75 18.98 in. c/c
16mm 0.31 3.71 29.41 in. c/c

For Exterior Panel:


Moment Calculation :
M0= 87.889115
for Interior Panel :

Interior negative Moment : 61.52238 Kip-ft

Total positive Moment : 45.70234 Kip-ft

Exterior negative Moment : 22.85117 Kip-ft


Short Direction:

Moment (Kip-ft) depth (d) Steel (As), in


Strip
(-) ve Moment (+) ve Moment in. As(-) ve
Int. Column strip 46.14 27.42 6.00 4.31

Middle Strip 15.38 18.28 6.00 1.44

EXt. Column strip 22.85 27.42 6.00 2.13

For interior Column Strip:


As(-) ve in2 Dia of bar as No.of Bar Spacing Unit
4.31 10mm 0.11 39.17 2.78 in. c/c
12mm 0.2 21.54 5.06 in. c/c
16mm 0.31 13.90 7.84 in. c/c

As(+) ve in2 Dia of bar as No.of Bar Spacing Unit


2.56 10mm 0.11 23.28 4.68 in. c/c
12mm 0.2 12.80 8.51 in. c/c
16mm 0.31 8.26 13.20 in. c/c

For Middle Strip:


As(-) ve( in2) Dia of bar as No.of Bar Spacing Unit
1.44 10mm 0.11 13.06 8.35 in. c/c
12mm 0.2 7.18 15.18 in. c/c
16mm 0.31 4.63 23.53 in. c/c

As(+) ve (in2) Dia of bar as No.of Bar Spacing Unit


1.71 10mm 0.11 15.52 7.02 in. c/c
12mm 0.2 8.54 12.77 in. c/c
16mm 0.31 5.51 19.80 in. c/c

For Exterior Column Strip:


As(-) ve in2 Dia of bar as No.of Bar Spacing Unit
2.13 10mm 0.11 19.40 2.81 in. c/c
12mm 0.2 10.67 5.11 in. c/c
16mm 0.31 6.88 7.92 in. c/c
As(+) ve in2 Dia of bar as No.of Bar Spacing Unit
2.56 10mm 0.11 23.28 4.68 in. c/c
12mm 0.2 12.80 8.51 in. c/c
16mm 0.31 8.26 13.20 in. c/c
Properties :

f'c= 2.5 ksi n= 10.18


fy= 60 ksi r= 21.33
fc= 1.125 ksi k= 0.32
fs= 24 ksi j= 0.89
R= 0.16

Kip-ft

Steel (As), in2


As(+) ve
1.72

1.15

Kip-ft
Steel (As), in2
As(+) ve
2.56

1.71

2.56
Flat Plate Design
Long Span 18.17 ft
Short Span 14.33 ft
Span Length (Ln): 13.5 ft

(L2): 18.17 ft

Minimum Thickness : 3.76 in. 4.95 in.


(BNBC)

or ,

Minimum thickness (tmin) = 7.79 in.

Hence
Thikness (choose)= 7.0 in

Load Calculation:

Self Weight = 0.09 ksf


Floor Finish = 0.02 ksf
Partitioon Wall = 0.05 ksf
Live Load = 0.04 ksf
w= 0.198 ksf

For Interior Panel:


Moment Calculation :
M0 = 110.00527
For Interior Panel :

Total negative Moment : 71.50343 Kip-ft

Total positive Moment : 38.50184 Kip-ft

Long Direction:

Moment (Kip-ft) depth (d) Steel (As), in2


Strip
(-) ve Moment (+) ve Moment in. As(-) ve
Column strip 53.63 23.10 5.50 5.46

Middle Strip 17.88 15.40 5.50 1.82

For Column Strip:


As(-) ve in2 Dia of bar as No.of Bar Spacing Unit
5.46 10mm 0.11 49.67 1.73 in. c/c
12mm 0.2 27.32 3.15 in. c/c
16mm 0.31 17.62 4.88 in. c/c

As(+) ve in2 Dia of bar as No.of Bar Spacing Unit


2.35 10mm 0.11 21.39 4.02 in. c/c
12mm 0.2 11.77 7.31 in. c/c
16mm 0.31 7.59 11.33 in. c/c

For Middle Strip:


As(-) ve( in2) Dia of bar as No.of Bar Spacing Unit
1.82 10mm 0.11 16.56 5.19 in. c/c
12mm 0.2 9.11 9.44 in. c/c
16mm 0.31 5.87 14.64 in. c/c

As(+) ve (in2) Dia of bar as No.of Bar Spacing Unit


1.57 10mm 0.11 14.26 6.03 in. c/c
12mm 0.2 7.84 10.96 in. c/c
16mm 0.31 5.06 16.99 in. c/c

For Exterior Panel:


Moment Calculation :
M0= 110.01
for Interior Panel :

Interior negative Moment : 77.00369 Kip-ft

Total positive Moment : 57.20274 Kip-ft

Exterior negative Moment : 28.60137 Kip-ft


Long Direction:

Moment (Kip-ft) depth (d) Steel (As), in


Strip
(-) ve Moment (+) ve Moment in. As(-) ve
Int. Column strip 57.75 34.32 5.50 5.88

Middle Strip 19.25 22.88 5.50 1.96

EXt. Column strip 28.60 34.32 5.50 2.91

For interior Column Strip:


As(-) ve in2 Dia of bar as No.of Bar Spacing Unit
5.88 10mm 0.11 53.49 1.61 in. c/c
12mm 0.2 29.42 2.92 in. c/c
16mm 0.31 18.98 4.53 in. c/c

As(+) ve in2 Dia of bar as No.of Bar Spacing Unit


3.50 10mm 0.11 31.79 2.70 in. c/c
12mm 0.2 17.48 4.92 in. c/c
16mm 0.31 11.28 7.62 in. c/c

For Middle Strip:


As(-) ve( in2) Dia of bar as No.of Bar Spacing Unit
1.96 10mm 0.11 17.83 4.82 in. c/c
12mm 0.2 9.81 8.77 in. c/c
16mm 0.31 6.33 13.59 in. c/c

As(+) ve (in2) Dia of bar as No.of Bar Spacing Unit


2.33 10mm 0.11 21.19 4.06 in. c/c
12mm 0.2 11.66 7.38 in. c/c
16mm 0.31 7.52 11.43 in. c/c

For Exterior Column Strip:


As(-) ve in2 Dia of bar as No.of Bar Spacing Unit
2.91 10mm 0.11 26.49 1.62 in. c/c
12mm 0.2 14.57 2.95 in. c/c
16mm 0.31 9.40 4.57 in. c/c
As(+) ve in2 Dia of bar as No.of Bar Spacing Unit
3.50 10mm 0.11 31.79 2.70 in. c/c
12mm 0.2 17.48 4.92 in. c/c
16mm 0.31 11.28 7.62 in. c/c
Properties :

f'c= 2.5 ksi n= 10.18


fy= 60 ksi r= 21.33
fc= 1.125 ksi k= 0.32
fs= 24 ksi j= 0.89
R= 0.16

Kip-ft

Steel (As), in2


As(+) ve
2.35

1.57

Kip-ft
Steel (As), in2
As(+) ve
3.50

2.33

3.50