: Possible mounting
Protection system suited to the environment
The LSA 50.2 is IP 23.
Standard winding protection for clean environments with relative humidity 95 %, including indoor marine environments.
Options : - Filters on air inlet : derating 5%.
- Filters on air inlet and air outlet (IP 44) : derating 10%.
- Winding protections for harsh environments and relative humidity greater than 95%.
- Space heaters.
- Thermal protection for winding.
General characteristics
Insulation class H Excitation system AREP or PMG
Winding pitch 2/3 AVR type R 450
Number of wires 6 - (option 12) Voltage regulation (*) 0.5 %
Protection IP 23 Short-circuit current 300% (3 IN) : 10s
Altitude 1000 m Totale Harmonic distortion THD (**) in no-load ....: < 3.5 % according to IEC
Overspeed 2250 min-1 Totale Harmonic distortion THD (**) on linear load: < 3.5 % according to IEC
Air flow 1.8m3/s, 50 Hz - 2.2m3/s, 60 Hz Waveform: NEMA = TIF (**) < 50
(*) Regulator input voltage, steady state, within the below total harmonic distortion (THD) limits.
(**) Total harmonic distortion between phases, no-load or on-load (non-distorting).
94 P. F.: 0.8
94 93.7
P. F.: 0.8
93.7
93.2 93
93
0 200 400 600 800 1000 1200 1400 kVA 0 200 400 600 800 1000 1200 1400 1600kVA
Reactances (%). Time constants (ms) - Class H / 400 V - 6 wires version (12 wires optional)
M6 (6f) L7 (6f) L8 (6f) VL10 (6f) M6 (12f) L8 (12f)
Kcc Short-circuit ratio 0.31 0.34 0.31 0.33 0.36 0.37
Xd Direct-axis synchro. reactance unsaturated 392 364 378 362 345 329
Xq Quadrature-axis synchro. reactance unsaturated 235 218 227 217 207 197
Tdo No-load transient time constant 3634 3750 3910 4058 3634 4247
Xd Direct-axis transient reactance saturated 19.4 17.4 17.4 16.0 17.0 13.9
Td Short-circuit transient time constant 180 180 180 180 180 180
Xd Direct-axis subtransient reactance saturated 16.5 14.8 14.8 13.6 14.5 11.8
Td Subtransient time constant 18 18 18 18 18 18
Xq Quadrature-axis subtransient reactance saturated 17.3 15.5 15.4 14.2 15.2 13.4
Xo Zero sequence reactance unsaturated 3.6 3.6 3.3 3.1 3.60 3.30
X2 Negative sequence reactance saturated 16.9 15.2 15.1 13.9 14.89 12.67
Ta Armature time constant 27 27 27 27 27.0 27.0
Other class H/400 V data
io (A) No-load excitation current 0.9 1.0 0.9 0.9 0.82 0.80
ic (A) On-load excitation current 4.1 4.0 3.9 3.7 3.21 3.01
uc (V) On-load excitation voltage 44 44 42 41 40.3 37.9
ms Response time (U = 20% transient) 500 500 500 500 500 500
kVA Start (U = 20% cont. or 50% trans.) 2895 3181 3701 4248 2300 3325
% Transient U (on-load 4/4) - P.F.: 0.8 LAG 13.5 12.4 12.4 11.7 12.3 10.5
W No-load losses 13960 15260 15420 16520 14025 15310
W Heat dissipation 51240 53260 57110 59020 43515 47696
L7 - (6 w)
L8 - (6 w)
15
L8 - (12 w)
VL10 - (6 w)
Voltage drop
10
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 kVA
kVA at P.F. 0.8
20 % M6 - (12 w) L7 - (6 w) L8 - (6 w) L8 - (12 w)
VL10 - (6 w)
15
Voltage rise
10
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 kVA
kVA at P.F. 0.8
25
20
Voltage drop
15
12%
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 kVA
1430 Locked rotor kVA
1) For a1starting
) For a PF
P.F.with a than
other other
0.6,than
the 0.6, multiply
starting kVA the
must kVA
be by K = Sinby
multiplied /K0.8
= Sine P.F. / 0.8
Calculation example
Example for a different
of calculation for aP.F.
PFother
with athan 0.6: than
other Starter motor
0.6: motorkVA calculated
starting at 0.4 P.F. =at1250
kVA calculated kVA
PF 0.4 = 1250 kVA
0.4=0.4
Sin P.F. Sin = 0.9165
0.9165 K = 1.145
K = 1.145 corrected =
kVA corrected kVA = 1430
1430 kVA kVA
VoltageVoltage drop for VL10 =to12
dip corresponding %. = 12%.
VL10
2 ) For aother
2) For voltages voltage U 400V
than other (Y),
than230V
400 V(D)(Y), 230Hz,
at 50 V (then
) atkVA
50 must
Hz, multiply the kVA
be multiplied byby
(400/U) 2 2 or (230/U)
(400/U)or (230/U)2. 2.
LSA 50.2 L7 - (version: 6 wires) P. F.: 1 LSA 50.2 VL10 - (version: 6 wires) 96.7 P. F.: 1
96.5
97%
96.4 96.4 96.7
96% P. F.: 0.8
96.7
95.2 96 P. F.: 0.8
95.8 95 96.1
95.4
95 95.5
95.8 95.6
95.5
95
94
93.2
94
93 93.8
92.7 93.4
93
200 400 600 800 1000 1200 1400 1600 1800 2000 kVA 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 kVA
93 94
93.5
92.2 93.1
92 93
0 200 91.8 400 600 800 1000 1200 1400 kVA 200 400 600 800 1000 1200 1400 1600 1800 2000kVA
Reactances (%). Time constants (ms) - Class H / 480 V - 6 wires version (12 wires optional)
M6 (6f) L7 (6f) L8 (6f) VL10 (6f) S4(12f) M6(12f) L8(12f)
Kcc Short-circuit ratio 0.29 0.33 0.30 0.32 0.30 0.31 0.32
Xd Direct-axis synchro. reactance unsaturated 407 377 394 368 394 398 380
Xq Quadrature-axis synchro. reactance unsaturated 244 226 236 220 236 239 228
Tdo No-load transient time constant 3634 3750 3910 4058 3411 3634 4247
Xd Direct-axis transient reactance saturated 20.2 18.1 18.1 16.3 20.8 19.7 16.1
Td Short-circuit transient time constant 180 180 180 180 180 180 180
Xd Direct-axis subtransient reactance saturated 17.1 15.4 15.4 13.8 17.7 16.7 13.7
Td Subtransient time constant 18 18 18 18 18 18 18
Xq Quadrature-axis subtransient reactance saturated 18.0 16.1 16.1 14.4 18.6 17.6 13.4
Xo Zero sequence reactance unsaturated 3.7 3.7 3.5 3.1 3.90 3.70 3.50
X2 Negative sequence reactance saturated 17.6 15.8 15.8 14.2 18.19 17.21 14.62
Ta Armature time constant 27 27 27 27 27.0 27.0 27.0
Other class H/480 V data
io (A) No-load excitation current 0.9 0.9 0.9 0.9 0.78 0.82 0.79
ic (A) On-load excitation current 4.2 4.1 4.0 3.7 3.48 3.60 3.37
uc (V) On-load excitation voltage 46 45 44 41 43.9 45.3 42.4
ms Response time (U = 20% transient) 500 500 500 500 500 500 500
kVA Start (U = 20% cont. or 50% trans.) 3553 3927 4593 5281 2148.5 2766.5 3993.9
% Transient U (on-load 4/4) - P.F.: 0.8 LAG 13.9 12.8 12.8 11.8 14.3 13.7 11.7
W No-load losses 22000 23820 24080 25640 20431 22067 23904
W Heat dissipation 64830 67290 72430 72720 55785 63639 69741
L8 - (6 w)
L8 - (12 w)
15
VL10 - (6 w)
Voltage drop
10
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 kVA
kVA at P.F. 0.8
15
Voltage rise
10
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 kVA
kVA at P.F. 0.8
25
Voltage drop
20
15
13%
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 kVA
1786 Locked rotor kVA
1) For a1starting
) For a PF
P.F.with a than
other other
0.6,than
the 0.6, multiply
starting kVA the
mustkVA
be by K = Sinby
multiplied /K0.8
= Sine P.F. / 0.8
Calculation example
Example for a different
of calculation for aP.F.
PFother
with athan 0.6: than
other Starter motor
0.6: motorkVA calculated
starting at 0.4 P.F. =at1560
kVA calculated kVA
PF 0.4 = 1560 kVA
0.4=0.4
Sin P.F. Sin = 0.9165
0.9165 K = 1.145
K = 1.145 corrected =
kVA corrected kVA = 1786
1786 kVA kVA
VoltageVoltage drop for VL10 =to13
dip corresponding %. = 13%.
VL10
2 ) For aother
2) For voltages voltage U 480V
than other (Y),
than277V
480 V(D),
(Y), 277 (YY)
240V V ( at
), 240 V (YY
60 Hz, then- kVA
12 wires
mustonly) at 60 Hzby (480/U)2 or (277/U)2 or (240/U)2.
be multiplied
multiply the kVA by (480/U) 2 or (277/U) 2 or (240/U) 2 .
Electric Power Generation 7
Low Voltage Alternators - 4 pole
LSA 50.2 - 6 wires (12 wires optional) - 1250 to 1640 kVA - 50 Hz / 1250 to 2000 kVA - 60 Hz
100000
1000
time (ms)
100000
Symmetrical
LSA 50.2 M6
Asymmetrical
10000
Current (A)
1000
time (ms)
100000
1000
1000
time (ms)
100000
Symmetrical
LSA 50.2 VL10
Asymmetrical
10000
Current (A)
1000
time (ms)
8
Cable
output
753
Access to
A.V.R.
1203
N - 0.127
- 0.050
BX - 0.100
368
P
0
786
284
450 - 2
+1
M12
PMG option
25
Access to
rectifiers 100
8 Air outlet 1 hole M24 Air inlet 600 50
50
210 470 240 700
7 800 1 hole 35 214 36 S DIA, XBG eq. sp. hole on M PCD
160
100
140
170
145
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flange S.A.E. 18 Flange S.A.E. 21
Type Xr Lr M J Xr Lr M J
LSA 50.2 S4 564 1320.5 833 18.17 549 1320.5 831 18.62
LSA 50.2 M6 608 1420.5 934 20.6 593 1420.5 932 21.09
LSA 50.2 L7 643 1520.5 1005 22.23 627 1520.5 1003 22.68
LSA 50.2 L8 667 1520.5 1082 24.6 652 1520.5 1081 25.05
LSA 50.2 VL 10 714 1620.5 1192 27.27 698 1620.5 1191 27.72
NOTE : Dimensions are for information only and may be subject to modifications. Contractuel 2D drawings can be downloaded from the Leroy-
Somer site, 3D drawing files are available upon request.
Cable
210 output
753
Access to
A.V.R.
120 m6
787.4 - 0.127
1203
18 109
0
2x2 hole 35
880
368
2x2 hole M24
32
786
450 - 1
0
M12
PMG option
25
Access to
rectifiers 100
Air outlet Air inlet 600 50
50
285 685 700
7 425 405 60 214 36
210
188.5
120
130
160
100
145
140
170
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Type Xr Lr M J
LSA 50.2 S4 590 1509 761 16.58
LSA 50.2 M6 632 1609 862 19.05
LSA 50.2 L7 667 1709 932 20.63
LSA 50.2 L8 690 1709 1010 23
LSA 50.2 VL10 736 1809 1120 25.67
NOTE : Dimensions are for information only and may be subject to modifications. Contractuel 2D drawings can be downloaded from the Leroy-
Somer site, 3D drawing files are available upon request.