COMMENT CONTROL SHEET

PROJECT: RPLC DEEP CONVERSION


DOC. No. V-SIE-EL001-COMMON-074-C
SIEMENS DOC. No.
DOCUMENT TITILE INTERFACE SIGNAL LIST WITH PSCS
REVISION C DATE 3/28/2014

Comment HYUNDAI-WISON Close-out


No. Sheet No. HYUNDAI-WISON Comment SIEMENS Reply
by Confirmation Status

PMC understand that this list will be


updated according to the clarification
between HIWIN and Siemens on the
Maintenance Network under the Change Please send us document "Order Instruction
1 1 H. Shimizu Order Instruction CP-P-GE-09962-COI-13- clarify this requirement. Rev A" in order to
CP-P-GE-09962-COI-13-003
003 Rev A. The relevant note or
description shall be provided to remind
that this update is mandatorily necessary.

The signals to PSCS described in V-SIE-


EL001-COMMON-050 Rev C Alarm
Annunciator Panel are not listed in this Noted, signals described in V-SIE-EL001-
document.
2 1 H. Shimizu COMMON-050 Rev C Alarm Annunciator
HIWIN/SIEMENS shall make clear the Panel will be included on this document.
definition of this document. It is
consolidated list of the signals to/from
PSCS from/to all the GIS related panels.
(General Comment)

The signal description shall be common


with other drawings.

For example in comparison with


3 1 H. Shimizu Noted.
Transformer Protection Panel SIE-EL001-
COMMON-048 Rev D, the following is
observed.
87L Protection <--> Main Protection TP1
Over current Protection <--> Backup
Protection TP2

Where is this Explanation ? Explanation sheet will be corrected on next


4 2 W.S. Park * Equipment Label shall be added revision.
It shall be Ethernet

PMC understand that this list will be


updated according to the clarification
between HIWIN and Siemens on the
Maintenance Network under the Change See comment n 1.
5 2 H. Shimizu Order Instruction CP-P-GE-09962-COI-13-
003 Rev A. The relevant note or
description shall be provided to remind
that this update is mandatorily necessary.

Maintenance signals(diagnostic and


troubleshooting) of GIS shall be
communicate with PSCS (Schneider PASIS
6 4 W.S. Park System). Siemens shall specify the required Noted.
signals for above requirements and
provide the relevant note or description in
the list.
(General Comment for "General Lock out
SF6 signal")
According GIS drawings, "General lockout
As per PMC review the General Lock out SF6" signal is provided, for example, V-SIE-
7 4, 7, 9 H. Shimizu SF6 signal is not provided in the current EL001-COMMON-028 Rev 0, sheet RB1 and
GIS Circuit diagram, for example, SIE- V-SIE-EL001-COMMON-029 Rev 0, sheet RB1.
EL001-COMMON-028 Rev B, which shall be
updated.

Lack of "Lock Out Relay Operated" for bus Noted, it will be included.
8 7 H. Shimizu tie.

It shall be +R03
It shall be +R04
11, 13, 14, It shall be +R05
9 16, 18, 20, W.S. Park It shall be +R09 Noted.
21 It shall be +R10
It shall be +R11
It shall be +R12