Ejercicio 1: Calcular las intensidades de lnea.

1 I1 1 1 1
R
2 I2 2 2 2
S
3 I3 3 3 3
T
N IN N
N
J1 J2 J3 K1 K2 K3
U = 220 V

Z2 Z2
Z1 ZZ11 Z1

N Z2

Z1 = 3 + 3j
Estrella equilibrada Z2 = 3 + 3 j
Triangulo Equilibrado
2/3

Estrella equilibrada Triangulo Equilibrado


UL = 220 V UL = 220 V
UF= 127,0171 V UF= 220 V
R= 1,732051 R= 3
X= 3 X = 1,7321
Z = 3,464102 Z = 3,4641
f = 1,047198 rad f = 0,5236 rad
f = 60 f = 30
IF = 36,66667 A IF = 63,509 A
IL = 36,66667 A IL = 110 A

J1 = 36,67 30,00 = 31,75 + 18,33 j K1 = 110,00 60,00 = 55,00 + 95,26 j

J2 = 36,67 -90,00 = 0,00 + -36,67 j K2 = 110,00 -60,00 = 55,00 + -95,26 j

J3 = 36,67 -210,00 = -31,75 + 18,33 j K3 = 110,00 -180,00 = -110,00 + 0,00 j

I1 = J1 + K 1
I1 = 142,93 52,63 = 86,75 + 113,60 j
I 2 = J2 + K 2
I2 = 142,93 -67,37 = 55,00 + -131,93 j
I 3 = J3 + K 3
I3 = 142,93 -187,37 = -141,75 + 18,33 j
Ejercicio 4: Calcular las intensidades de lnea. Ejercicio 4: Calcular las intensidades de lnea.

1 I1 1 1 1 I1 1
R R
2 I2 2 2 2 I2 2
S S
3 I3 3 3 3 I3 3
T T
UL = 380 V ZL= 1+0,5 j UL = 380 V ZL= 1+0,5 j
J1 J2 J3 K1 K2 K3 I1 I2 I3

Z1 Z1 Z2 Z2

Z1 Z2

Z1 = 6 + 0 j Z2 = 6 + 0 j Z CT = 3 + 0 j

Ejercicio 4: Calcular las intensidades de lnea. Ejercicio 4: Calcular las intensidades de lnea.

1 I1 1 1 I1 1
R R
2 I2 2 2 I2 2
S S
3 I3 3 3 I3 3
T T
UL = 380 V ZL= 1+0,5 j UL = 380 V
I1 I2 I3 I1 I2 I3

Z CE = 1 + 0 j Z Total = 2 + 0 ,5 j

Estrella equilibrada sin neutro

UL = 380 V Modulo Argumento Real Imaginario


Zc1 2,06 14,04 2,00 0,50
UF = 219,393 V Zc2 2,06 14,04 2,00 0,50
Zc3 2,06 14,04 2,00 0,50

Modulo Argumento Real Imaginario


Un'n = 0,0000 0,0000 0,0000 0,0000
Tensiones simples
Uz1= U1N' = 219,3931 90,0000 0,0000 219,3931
en la carga
Uz2= U2N' = 219,3931 -30,0000 190,0000 -109,6966
Uz3= U3N' = 219,3931 -150,0000 -190,0000 -109,6966

Modulo Argumento Real Imaginario


Intensidades de I1 = 106,5015 75,9640 25,8300 103,3217
Lnea Totales I2 = 106,5015 -44,0360 76,5643 -74,0303
I3 = 106,5015 -164,0360 -102,3942 -29,2915

Modulo Argumento Real Imaginario


Intensidades de J1 = 53,2508 75,9640 12,9150 51,6609
Lnea carga 1 J2 = 53,2508 -44,0360 38,2821 -37,0151
J3 = 53,2508 -164,0360 -51,1971 -14,6457

Modulo Argumento Real Imaginario

Intensidades de K1 = 53,2508 75,9640 12,9150 51,6609


Lnea carga 2 K1 = 53,2508 -44,0360 38,2821 -37,0151
K3 = 53,2508 -164,0360 -51,1971 -14,6457

U1'2' = U2'3' = U3'1' = 184,47 V de tension de lnea en la carga


Ejercicio 1: Calcular la lectura de los tres ampermetros:
I1
R A1
I2
S A2
I3
T A3
230 V
50 Hz
M M
3

10 CV 2 CV
cos = 0,8 cos = 0,9
= 0,9 =1

Solucin:
UL = 230 V
R R
S S
T T
N N
R S
230 V 230 120 V

P = 8177,8 W CV 10 P= 1472 W CV 2
fdp= 0,8 h= 0,9 fdp = 0,9 h= 1
UL = 230 V UL = 230 V
P= 8177,8 W j = 0,644 rad P= 1472 W j = 0,451 rad
Q= 6133,3 Var j = 36,87 Q = 712,92 Var j = 25,842
S= 10222 VA IL= 25,66 A S = 1635,6 VA IL= 7,1111 A

Estrella equivalente Z = 32,344 25,84 = 29,109 + 14,1 j


UF = 132,79 V IF = 25,66 A
ZE = 5,175 36,8699 = 4,14 + 3,105 j URS = 230 120 = -115 + 199,2 j
Triangulo equivalente IRS = 7,1111 94,16 = -0,516 + 7,092 j
UF = 230 V IF = 14,81 A
ZT = 15,525 36,8699 = 12,42 + 9,315 j

I1 = 25,66 53,1301 = 15,40 + 20,53 j I1 = 7,1111 94,16 = -0,516 + 7,092 j


I2 = 25,66 -66,8699 = 10,08 + -23,60 j I2 = 7,1111 274,2 = 0,5156 + -7,092 j
I3 = 25,66 -186,87 = -25,48 + 3,07 j I3 = 0 0 = 0 + 0j

Aplicando el primer lema a cada fase obtenemos las intensidades totales:


IT1 = 31,374 61,69 = 14,88 + 27,62 j Lectura de A1: 31,4 A
IT2 = 32,467 289,05 = 10,60 + -30,69 j Lectura de A2: 32,5 A
IT3 = 25,660 173,13 = -25,48 + 3,07 j Lectura de A3: 25,7 A
.03/06/2010
Ejercicio 2: Calcular la lectura de los tres ampermetros.
Aplicando el primer lema a cada fase
I1 obtenemos las intensidades totales:
R A1 IT1 = 46,034 73,34 = 13,19 + 44,10 j

I2
S A2 IT2 = 57,753 295,76 = 25,10 + -52,01 j

I3
T IT3 = 39,101 168,33 = -38,29 + 7,91 j
A3

230 V Sistema Desequilibrado


50 Hz M M M M
3 Lectura de A 1: 46,0 A

Lectura de A 2: 57,8 A
10 CV 5 CV 3 CV 1/4 CV
Lectura de A 3: 39,1 A
cos = 0,85 cos = 0,9 cos = 0,83 cos = 0,8
= 0,84 = 0,82 = 0,85 = 0,81
UL = 230 V Carga Carga Carga
R R Monofsica RS R Monofsica ST R Monofsica TR
S S S S
T T T T
N N N N
R S S T T R
230 V U = 230 V U = 230 V U = 230 V

Pe = 8761,9048 W P= 10 CV Pe = 4487,8 W P= 5 CV Pe = 2597,6 W P= 3 CV Pe = 227,16 W P= 0,25 CV


fdp= 0,85 = 0,84 fdp= 0,9 = 0,82 fdp= 0,83 = 0,85 fdp= 0,8 = 0,81
UL= 230 V UL= 230 V UL= 230 V UL= 230 V
P= 8761,9048 W = 0,55481 rad P= 4487,8 W = 0,451 rad P= 2597,6 W = 0,592 rad P= 227,16 W = 0,644 rad
Q= 5430,1409 Var = 31,7883 Q= 2173,54 Var = 25,84 Q= 1745,6 Var = 33,9 Q= 170,37 Var = 36,87
S= 10308,123 VA IL= 25,8756 A S= 4986,45 VA IF= 21,68 A S= 3129,7 VA IF= 13,61 A S= 283,95 VA IF= 1,235 A
Carga en: Estrella Carga en: Tringulo R= 9,54788 X= 4,624 R= 14,029 X = 9,428 R= 149,04 X= 111,8
UF = 132,79056 V UF = 230 V Z= 10,6088 Z= 16,903 Z= 186,3
IF = 25,875642 A IF = 14,9393 A
R= 4,3620938 R= 13,0863 URS = 230 120 = -115 + 199,2 j UST = 230 0 = 230 + 0j UTR = 230 240 = -115 + -199,2 j
X= 2,7033829 X= 8,11015
Z= 5,131875 Z= 15,3956 IRS = 21,6802 94,158 = -1,57 + 21,62 j IST = 13,607 -33,9 = 11,29 + -7,59 j ITR = 1,2346 203,13 = -1,135 + -0,485 j

ZE = 5,131875 31,78833 = 4,36209 + 2,7034 j ZRS = 10,6088 25,842 = 9,548 + 4,624 j ZST = 16,903 33,9 = 14,03 + 9,428 j ZTR = 186,3 36,8699 = 149 + 111,8 j

S = 10308,123 31,78833 = 8761,9 + 5430,1 j SRS = 4986,45 25,842 = 4488 + 2174 j SST = 3129,7 33,9 = 2598 + 1746 j STR = 283,95 36,8699 = 227,2 + 170,4 j

I1 = 25,876 58,21 = 13,63 + 21,99 j I1 = 21,6802 94,158 = -1,57 + 21,62 j I1 = 0 0 = 0,00 + 0,00 j I1 = 1,2346 383,13 = 1,135 + 0,485 j
I2 = 25,876 -61,79 = 12,23 + -22,80 j I2 = 21,6802 274,16 = 1,572 + -21,6 j I2 = 13,607 -33,9 = 11,29 + -7,59 j I2 = 0 0 = 0+ 0j
I3 = 25,876 -181,79 = -25,86 + 0,81 j I3 = 0 0 = 0+ 0j I3 = 13,607 146,1 = -11,29 + 7,59 j I3 = 1,2346 203,13 = -1,135 + -0,485 j
.03/06/2010
Ejercicio 2.1.: Calcular la lectura de los tres ampermetros.
Aplicando el primer lema a cada fase
I1 obtenemos las intensidades totales:
R A1
IT1 = 36,511 61,74 = 17,29 + 32,16 j
I2
S A2
IT2 = 28,481 297,20 = 13,02 + -25,33 j
I3
T A3
IN IT3 = 16,109 177,82 = -16,10 + 0,61 j
N

ITN = 16,04 207,63 = -14,21 + -7,44 j

400 V
50 Hz M M M M Sistema Desequilibrado
3
Lectura de A1: 36,5 A

10 CV 5 CV 3 CV 1/4 CV Lectura de A2: 28,5 A


cos = 0,85 cos = 0,9 cos = 0,83 cos = 0,8
= 0,84 = 0,82 = 0,85 = 0,81 Lectura de A3: 16,1 A

UL = 400 V Carga Carga Carga


R R Monofsica RN R Monofsica SN R Monofsica TN
S S S S
T T T T
N N N N
R N S N T N
400 V U = 230 V U = 230 V U = 230 V

Pe = 8761,9048 W P= 10 CV Pe = 4487,8 W P= 5 CV Pe = 2597,6 W P= 3 CV Pe = 227,16 W P= 0,25 CV


fdp= 0,85 = 0,84 fdp= 0,9 = 0,82 fdp= 0,83 = 0,85 fdp= 0,8 = 0,81
UL= 400 V UL= 230 V UL= 230 V UL= 230 V
P= 8761,9048 W = 0,55481 rad P= 4487,8 W = 0,451 rad P= 2597,6 W = 0,5917 rad P= 227,16 W = 0,644 rad
Q = 5430,1409 Var = 31,7883 Q= 2173,54 Var = 25,84 Q= 1745,6 Var = 33,901 Q= 170,37 Var = 36,87
S= 10308,123 VA IL= 14,8785 A S= 4986,45 VA IF= 21,68 A S= 3129,7 VA IF= 13,607 A S= 283,95 VA IF= 1,235 A
Carga en: Estrella Carga en: Tringulo R= 9,54788 X= 4,624 R= 14,029 X= 9,4277 R= 149,04 X= 111,8
UF = 230,94011 V UF = 400 V Z= 10,6088 Z= 16,903 Z= 186,3
IF = 14,878494 A IF = 8,5901 A
R= 13,193478 R= 39,5804 URN = 230 90 = 1E-14 + 230 j USN = 230 -30 = 199,19 + -115 j UTN = 230 -150 = -199,2 + -115 j
X= 8,1765835 X= 24,5298
Z= 15,521739 Z= 46,5652 IRN = 21,6802 64,158 = 9,45 + 19,51 j ISN = 13,607 -63,9 = 5,9861 + -12,2 j ITN = 1,2346 -186,87 = -1,226 + 0,148 j

ZE = 15,521739 31,78833 = 13,1935 + 8,1766 j ZRN = 10,6088 25,842 = 9,548 + 4,624 j ZSN = 16,903 33,9 = 14,029 + 9,428 j ZTN = 186,3 36,8699 = 149 + 111,8 j

S = 10308,123 31,78833 = 8761,9 + 5430,1 j SRN = 4986,45 25,842 = 4488 + 2174 j SSN = 3129,7 33,9 = 2597,6 + 1746 j STN = 283,95 36,8699 = 227,2 + 170,4 j

I1 = 14,878 58,21 = 7,84 + 12,65 j I1 = 21,6802 64,158 = 9,45 + 19,51 j I1 = 0 0 = 0,00 + 0,00 j I1 = 0 0 = 0+ 0j
I2 = 14,878 -61,79 = 7,03 + -13,11 j I2 = 0 0 = 0+ 0j I2 = 13,607 -63,9 = 5,99 + -12,22 j I2 = 0 0 = 0+ 0j
I3 = 14,878 -181,79 = -14,87 + 0,46 j I3 = 0 0 = 0+ 0j I3 = 0 0 = 0+ 0,00 j I3 = 1,2346 -186,87 = -1,226 + 0,148 j
IN = 21,6802 244,16 = -9,45 + -19,51 j IN = 13,607 116,1 = -5,986 + 12,22 j IN = 1,2346 -6,8699 = 1,226 + -0,148 j
Ejercicio 3: La red de elctrica de naves agroindustriales se alimentan de un sistema
trifsico de tensiones equilibradas. Si se supone que las cargas en cada nave estn
equilibradas y de valores dados en el siguiente esquema, Calcular:

I1
R
I2
S
I3
T

400 V
50 Hz
Nave 1 Nave 2

P1=50 KW P1=30 KW
cos = 0,8 cos = 0,7
Inductivo Inductivo
1.- Intensidad de lnea general
2.- Factor de potencia general.
3.- Estrella equivalente a la nave 1.
4.- Tringulo equivalente al nave 2.
5.- Si se desea corregir el factor de potencia conjuntamente, Nave 1 + Nave 2, hasta 0,9
determinar la potencia reactiva total necesaria de la batera de condensadores.

Solucin:

U (V) P (W) Q (Var) S (VA) cos f f(rad) I (A) ZE f() RE XE


Local 1 400,000 50000,000 37500,000 62500,000 0,800 0,644 90,211 2,560 36,870 2,048 1,536
Loca 2 400,000 30000,000 30606,122 42857,143 0,700 0,795 61,859 3,733 45,573 2,613 2,666
Total L1L2 400,000 80000,000 68106,122 105063,999 0,761 0,705 151,647 1,523 40,409 1,160 0,987

Intensidad de lnea general: IL = 151,647 A Est. equiv. al local 1: Z1 = 2,560 36,870

F.d.p. del conjunto de los dos locales = 0,761 Tringulo equiv. al local 2: Z2 = 11,200 45,573

Correccin del f.d.p. hasta: 0,9

U (V) P (W) Q (Var) S (VA) cos f f(rad) I (A) ZE f() RE XE


Total L1L2 400,000 80000,000 68106,122 105063,999 0,761 0,705 151,647 1,523 40,409 1,160 0,987
Condensador 400,000 0,000 -29360,353 29360,353 0,000 -1,571 42,378 5,450 -90,000 0,000 -5,450
Total L1L2 400,000 80000,000 38745,768 88888,889 0,900 0,451 128,300 1,800 25,842 1,620 0,785

Qf = 38745,7684 VAr
Qi = 68106,122 VAr f(Hz) = 50 CT (mF) = 0,1947 mF
Qc =Qf-Qi = -29360,353 VAr Xc() = -5,450 j CE (mF) = 0,58411 mF

El valor de la capacidad de la batera en estrella ser: 0,584 mF

El valor de la capacidad de la batera en tringulo ser: 0,195 mF


UL = 400 V Solucin ejercicio 3
R R
S S
T T
N N

400 V 400 V

P= 50000 W P= 30000 W
fdp= 0,8 fdp= 0,7
UL= 400 V UL= 400 V
P= 50000 W = 0,6435 rad P= 30000 W = 0,7954 rad
Q= 37500 Var = 36,87 Q= 30606,122 Var = 45,573
S= 62500 VA IL= 90,211 A S= 42857,143 VA IL= 61,859 A

Carga en: Estrella Carga en: Tringulo Carga en: Estrella Carga en: Tringulo
UF = 230,94011 V UF = 400 V UF = 230,94011 V UF = 400 V
IF = 90,21098 A IF = 52,083 A IF = 61,858957 A IF = 35,714 A
R= 2,048 R= 6,144 R= 2,6133333 R= 7,84
X= 1,536 X= 4,608 X= 2,6661333 X= 7,9984
Z= 2,56 Z= 7,68 Z= 3,7333333 Z= 11,2

I1 = 90,211 53,13 = 54,13 + 72,17 j I1 = 61,859 44,43 = 44,18 + 43,30 j

I2 = 90,211 -66,87 = 35,44 + -82,96 j I2 = 61,859 -75,57 = 15,41 + -59,91 j


I3 = 90,211 -186,87 = -89,56 + 10,79 j I3 = 61,859 -195,57 = -59,59 + 16,61 j

ZE = 2,560 36,87 = 2,048 + 1,536 j ZE = 3,733 45,57 = 2,6133 + 2,66613 j

ZT = 7,680 36,87 = 6,144 + 4,608 j ZT = 11,200 45,57 = 7,84 + 7,9984 j

S = 62500,000 36,87 = 50000 + 37500 j S= 42857,143 45,57 = 30000 + 30606,1 j

Total: Carga 1 + Carga 2


IT1 = 151,647 49,59 = 98,30 + 115,47 j ZE = 1,523 40,41 = 1,1596 + 0,98718 j
IT2 = 151,647 289,59 = 50,85 + -142,87 j ZT = 4,569 40,41 = 3,4788 + 2,96155 j

IT3 = 151,647 169,59 = -149,15 + 27,40 j S= 105063,999 40,41 = 80000 + 68106,1 j

Si colocasemos vatmetros para medir la potencia total, la lectura de estos seran:

PT= 80000,00 W W1 1
Aron P = W1 + W2
W2 2
W1= 400 x 151,65 cos( 10,41 )= 59.660,5
W2= 400 x 151,65 cos( -289,59 )= 20.339,5
3
P = 80.000,0 W

Tres vatimetros: P = W1 + W2 + W3 1
W

W1= 230,94011 x 151,65 cos( 40,41 )= 26.666,7 W RECEPTOR


W2= 230,94011 x 151,65 cos( -319,59 )= 26.666,7 2
W3= 230,94011 x 151,65 cos( -319,59 )= 26.666,7
W
P = 80.000,0 W 3 TRIFASICO

P=W1 + W2 + W3

W. Reactivo : Q = 1,73 W W1 1

W3= 400 x 151,65 cos( 49,59 ) =


39.321,1 2
Q= 1,732 x 39321 = 68.106,1 Var
3
Ejercicio 4: Un generador trifsico a 50 Hz cede una potencia de 452,083 kW. La
carga pasiva consume 400 KW con f.d.p. 0,8 inductivo. (ver esquema)
Generador Lnea Carga

I1 ZL 1' Z
1

2 I2 ZL 2' Z

3 I3 ZL 3' Z

Z L = 0,1+0,1j N'
Pg=452,083 KW Pc=400 KW
f = 50 Hz cos = 0,8
Determinar:
1.- La intensidad, tensin e impedancia por fase de la carga.
2.- Tensin de lnea en el generador.
3.- La batera de condensadores que se conectara en paralelo con la carga para
que el factor de potencia (carga + batera) sea de 1.
4.- Si se supone que la tensin en bornes de la carga se mantiene constante una
vez instalada la batera de condensadores, calcular la nueva intensidad de lnea.
5.- Tensin de lnea en el generador en el caso supuesto del apartado 4.

Solucin:
U (V) P (W) Q (Var) S (VA) cos f f(rad) I (A) ZE f() RE XE
Carga 692,823 400.000,00 300.000,00 500.000,000 0,800 0,644 416,665 0,960 36,870 0,768 0,576
Lnea 52.083,000 52.083,00 73.656,485 0,707 0,785 416,665 0,141 45,000 0,1 0,1
Total L+C 793,990 452.083,00 352.083,00 573.010,888 0,789 0,662 416,665 1,100 37,912 0,868 0,676
Intensidad de lnea general: IL = 416,665 A Est. equiv. a la carga: Zc = 0,960 36,870

Tensin de fase en la carga = 400,0 V Estrella Lnea+Carga: Ze = 1,100 37,912

Tensin de Lnea en el generador = 794,0 V Perdida de potencia en la Lnea: 52,083 KW

Potencia aparente necesaria en el generador: 573,0 KVA

Correccin del f.d.p. hasta: 1


U (V) P (W) Q (Var) S (VA) cos f f(rad) I (A) ZE f() RE XE
Carga 692,823 400.000,000 300.000,000 500.000,000 0,800 0,644 416,665 0,960 36,870 0,768 0,576
Condensador 692,823 0,000 300.000,000 300.000,000 0,000 1,571 249,999 1,600 90,000 0,000 1,600
T.Cond+Carga 692,823 400.000,000 0,000 400.000,000 1,000 0,000 333,332 1,200 0,000 1,200 0,000

U (V) P (W) Q (Var) S (VA) cos f f(rad) I (A) ZE f() RE XE


T.Cond+Carga 692,823 400.000,00 0,00 400.000,000 1,000 0,000 333,332 1,200 0,000 1,200 0,000
Lnea 33.333,120 33.333,120 47.140,150 0,707 0,785 333,332 0,141 45,000 0,1 0,1
Total L+C 752,775 433.333,12 33.333,12 434.613,265 0,997 0,077 333,332 1,304 4,399 1,300 0,100

Nueva Intensidad de lnea = 333,33 A Perdida de potencia en la Lnea: 33,333 KW

U de Lnea en el generador = 752,77 V


P. aparente necesaria en el generador: 434,6 KVA

.03/06/2010
Problema:
Una industria absorbe 415 kVA ( con f.d.p.= 0,875 en retraso) de una red trifsica de 240
V en un momento determinado. Si suponemos la industria equilibrada en cargas, calcular:

a) La impedancia por fase de la planta.

b) El ngulo de desfase entre la tensin y la intensidad de fase.

c) El diagrama vectorial completo.

Solucin:
a) Suponemos la planta elctricamente equivalente a una conexin en estrella de tres
impedancias idnticas Z1 = Z 2 = Z3 = Z .

1 1'

I1
240 -120
U'1 Z 1 1
415 KVA
0,875
240 120 IN N'
Z2 2 Z3 3

2 3'
U'2 U'3
240 0 I2 2'

3 I3

La tensin por fase es: UF = 240 / 3 = 138,564 V.

A partir de la formula de la potencia aparente de una carga trifasica equilibrada, podemos


despejar la intensidade de lnea, IL = S/( 3 UL), y en el caso de la estrella IF = IL , por lo que la
corriente por fase es: IF = IL = S / ( 3 UL) = 415000 / (1,732 H 240) = 1140,954 A.

La impedancia por fase es: Z = UF / IF = 138,564 / 1140,954 = 0,1214 .

b) El ngulo de desfase entre las tensines simples (138,564 V) y las correspondientes


intensidades de lnea (1141 A) viene dado por: cos n = 0,875 B> n = 28,9551 .

La corriente en cada fase retrasa 291 respecto a su tensin.

La impedancia compleja por fase vale: Z = 0,12 29

1 3/06/2010
c) El diagrama vectorial completo es el de la figura siguiente. En la prctica se
representara una fase solamente.

Las intensidades de lnea son: I1 = 114190 29 = 1141 61

I 2 = 1141 30 29 = 1141 59

I3 = 1141 150 29 = 1141 179

U 3 = U 12
I 1 =1141 61
U1

30
= 29

I 3 =1141 -179 U 1 = U 23

U3 U2

I 2 =1141 -59
U 2 = U 31

Diagrama de tensiones e intensidades.

1 1'

I 1 = 1141 90 - 29

139 90 U'1 Z1 1
415/3 KVA
0,875
N'
N

Esquema monofsico equivalente

2 3/06/2010
Ejercicio: Determinar las lecturas de los vatmetros W1 y W2 cuando la impedancia de cada una
de las cargas conectadas en tringulo a la red trifsica de la figura sean:

a) Z12 = Z 23 = Z31 = Z = 1 + j 3 b) Z12 = Z 23 = Z31 = Z = 3 + j

Comprobar los resultados. Nota: UL = 400 V.

W1
R I1

W2
S I2

T I3

400 V I 2T I 3T I 1T
50 Hz
2
Z12

Z23

1 3
Z31

RECEPTOR TRIFASICO

Solucin:

a) Si Z = 1 + j 3 en forma cartesiana, en forma polar ser : tg = /3 , = 60o , Z = 2


y por tanto Z = 2 60 .

U12 400 120


Las intensidades de fase en la carga sern: I12 = = = 200 60
Z12 2 60

U 23 400 0
I 23 = = = 200 60
Z23 2 60

U 31 400 120
I31 = = = 200 180
Z31 2 60

y por tanto, los fasores de las intensidades de las corrientes de lnea sern:

I1 = I12 I31 = 200 60 200 180 = 200 3 30

I 2 = I 23 I12 = 200 60 200 60 = 200 3 90

I3 = I31 I 23 = 200 180 200 60 = 200 3 210

Las lecturas de los vatmetros W1 y W2 resultarn, en consecuencia:

3 3/06/2010
W1 = U13 I1 cos ( U13 , I1 ) = 400 200 3 cos (30 ) = 120000 W

W2 = U 23 I 2 cos ( U 23 , I 2 ) = 400 200 3 cos (90 ) = 0 W

Con lo que: PT = W1 + W2 = 120.000 W Como comprobacin se tendr:

PT = 3 PF = 3 (I12)2 R12 = 3 2002 1 = 120000 W

o bien: PT = 3 UL IL cos = 3 400 200 0,5 = 120000 W

b) En este supuesto: Z = 3 + j en forma cartesiana, en forma polar ser : tg = 1//3 , =


30o , Z = 3 + 1 =2 y por tanto Z = 2 30 .

Las intensidades de fase y linea sern: IF = UL/Z = 400/2 = 200 A e IL = 3 IF = 200 3 A

y los fasores de las intensidades de las corrientes de lnea tendran por expresin:

I1 = 200 3 90 30 = 200 3 60

I 2 = 200 3 30 30 = 200 3 60

I1 = 200 3 150 30 = 200 3 180

Las lecturas de los vatmetros W1 y W2 sern en estas nuevas condiciones:

W1 = U13 I1 cos ( U13 , I1 ) = 400 200 3 cos (0 ) = 80000 3 W

W2 = U 23 I 2 cos ( U 23 , I 2 ) = 400 200 3 cos (60 ) = 40000 3 W

Con lo que: PT = W1 + W2 = 80000 3 +40000 3 = 120000 3 W

Como comprobacin: PT = 3 PF = 3 (IF)2 R = 3 2002 3 = 120000 3 W

o bien: PT = 3 UL IL cos = 3 400 200 3 3 /2 = 120000 3 W

Para el supuesto (a) se comprueba asimismo que:

W1 - W 2 120000 - 0
tg ( ) = 3 = 3 = 3.
W1 + W 2 120000 + 0

Para el supuesto (b):

W1 - W 2 80000 3 - 40000 3 40000 3 1


tg ( ) = 3 = 3 = 3 =
W1 + W 2 80000 3 + 40000 3 120000 3 3

4 3/06/2010
Ejercicio 2: 3/6/2010

W1 W1
R I1 R I1

W2 W2
S I2 S I2

T I3 T I3

400 V I 2T I 3T I 1T 400 V I 2T I 3T I 1T
50 Hz 50 Hz
2 2
Z 12 Z12

Z 23 Z23

1 3 1 3
Z 31 Z31

R ECEPTO R TRIFASICO RECEPTOR TRIFASICO


2,0000 60,000 2,0000 30,000

Solucin:

UL = 400 V UL = 400 V
R R
S S
T T
N N

400 V 400 V

P= 120000 W P= 120000 W
fdp= 0,5 fdp= 0,8660254
UL= 400 V UL= 400 V
P= 120000 W = 1,047198 rad P= 120000 W = 0,523599 rad
Q = 207846,097 Var = 60 Q = 69282,0323 Var = 30
S= 240000 VA IL= 346,4102 A S = 138564,065 VA IL= 200 A
Carga en: Estrella Carga en: Tringulo Carga en: Estrella Carga en: Tringulo
UF = 230,940108 V UF = 400 V UF = 230,940108 V UF = 400 V
IF = 346,410162 A IF = 200 A IF = 200 A IF = 115,4701 A
R = 0,33333333 R= 1 R= 1 R= 3
X = 0,57735027 X= 1,732051 X = 0,57735027 X= 1,732051
Z= 0,66666667 Z= 2 Z= 1,15470054 Z= 3,464102

I1 = 346,4102 30,000 = 300,00 + 173,21 j I1 = 200,0000 60,000 = 100,00 + 173,21 j

I2 = 346,4102 -90,000 = 0,00 + -346,41 j I2 = 200,0000 -60,000 = 100,00 + -173,21 j


I3 = 346,4102 -210,000 = -300,00 + 173,21 j I3 = 200,0000 -180,000 = -200,00 + 0,00 j

ZE = 0,6667 60,000 = 0,333333 + 0,577350269 j ZE = 1,1547 30,000 = 1 + 0,577350269 j

ZT = 2,0000 60,000 = 1 + 1,732050808 j ZT = 3,4641 30,000 = 3 + 1,732050808 j

S = 240000,0000 60,000 = 120000 + 207846,0969 j S = 138564,0646 30,000 = 120000 + 69282,0323 j

W1 = 400,00 x 346,41 x 0,87 x = 120000,00 W W1 = 400,00 x 200,00 x 1,00 x = 80000,00 W


W2 = 400,00 x 346,41 x 0,00 x = 0,00 W W2 = 400,00 x 200,00 x 0,50 x = 40000,00 W

W1 + W2 = 120000,00 W W1 + W2 = 120000,00 W
Ejercicio : Calcular la lectura de los dos watmetros. 3/6/2010
W 1 IR
1 = R

W 2 IS
2 = S

IT
3 = T

U L= 2 2 0 V I 12 I 13

M o to r M o to r
M1 M2
10 CV 10 CV
cos = 3/2 cos = 3/2
= 0 ,9 = 0 ,9
Solucin:

Carga Carga
R Monofsica RS R Monofsica RT
S S
T T
N N
R S R T
U = 220 V U = 220 V

Pe = 8177,778 W P= 10 CV Pe = 8177,778 W P= 10 CV
fdp= 0,866025 = 0,9 fdp= 0,866025 = 0,9
UL= 220 V UL= 220 V
P= 8177,778 W = 0,523599 rad P= 8177,778 W = 0,5236 rad
Q= 4721,442 Var = 30 Q= 4721,442 Var = 30
S= 9442,884 VA Z= 5,126 S= 9442,884 VA Z= 5,126
IF= 42,9222 A R= 4,439 IF= 42,9222 A R= 4,439
X = 2,562776 X= 2,56278

URS = 220,00 120 = -110,00 + 190,53 j URT = 220,00 60 = 110,00 + 190,53 j

IRS = 42,92 90 = 0,00 + 42,92 j IRT = 42,92 30 = 37,17 + 21,46 j

ZRS = 5,13 30 = 4,44 + 2,56 j ZRT = 5,13 30 = 4,44 + 2,56 j

SRS = 9442,88 30 = 8177,78 + 4721,44 j SRT = 9442,88 30 = 8177,78 + 4721,44 j

I1 = 42,92 90 = 0,00 + 42,92 j I1 = 42,92 30 = 37,17 + 21,46 j


I2 = 42,92 270 = 0,00 + -42,92 j I2 = 0,00 0 = 0,00 + 0,00 j
I3 = 0,00 0 = 0,00 + 0,00 j I3 = 42,92 210 = -37,17 + -21,46 j

Aplicando el primer lema a cada fase


obtenemos las intensidades totales:

IT1 = 74,34343 60,00 = 37,17 + 64,38 j W1 = 220 x 74 x 0,5 = 8177,78 W

IT2 = 42,9222 ##### = 0,00 + -42,92 j W2 = 220 x 43 x -0 = 0,00 W

IT3 = 42,9222 ##### = -37,17 + -21,46 j W1 + W2 = 8177,78 W

Sistema Desequilibrado P1+P2 = 16355,56 W