Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
40
VECTRON G 1.55
VECTRON G 1.85
Bedieningshandleiding
Voor de gespecialiseerde vakman
Aangeblazen gasbrander...................... 2-17 nl
Operating instructions
For specialist installation engineers
Gas burners ......................................... 18-33 en
Contents
Burner description
en
Waiting for heat request Always disconnect the power supply
before installing or removing the
Valve leak check control unit. Do not attempt to open or
carry out repairs on the control unit.
(by gas pressure measurement in valve space)
Burner motor on
Ignition transformer on
Flame present
Functional sequence phases: 6: Test time 1 (valve space depressurised) 11: Post-ignition time
1: No voltage 7: Second phase - valve check 12: Operation
2: Power supply on, no heat request 8: Test time 2 (valve space filled) 13: Burner stop
3: Heat request, check air pressure switch 9: Preventilation 14: Standby
idle position 9: Pre-ignition, activation of unauthorised
4: Motor on, check air pressure flame monitoring
5: First phase: sealing test 10: Flame formation, safety period
01/2009 - Art. Nr. 4200 1016 3900A 21
Downloaded from www.Manualslib.com manuals search engine
Function
Allocation chart
Connection socket
Connector
no.
Terminal
Connecto
r no.
Terminal
Operating function
Safety function
Description of functions from the sensor to the burner tip. The - Gas solenoid valves close
When the system is switched on for the ionisation current must be at least 8 A. - Flame goes out
first time, after a power failure or safety - Blower motor runs on (14 sec)
shutdown, after a lack of gas or after the Safety functions - Valve leak check performed
system has been out of operation for 24 - If no flame is produced when the - Burner motor switches off
hours, a sealing test is performed on the burner is started (gas release), the - Burner is ready for operation
gas valves with the blower motor burner will be switched off at the end
running before the burner is started. of the safety period, lasting no more
After the leak check, the pre-ventilation than 3 seconds, and the gas valve will
period of 24 seconds begins. close.
- If the flame goes out during operation,
During pre-purge period the gas supply is interrupted within en
- Blower pressure is monitored. one second. A restart takes place.
- The combustion chamber is monitored Once the burner starts, operation is
for flame signals. continued. Otherwise, a safety
shutdown is triggered.
At the end of the pre-purge period - If there is a lack of air during pre-
- Ignition is switched on ventilation or operation, a safety
- main and safety valve are opened shutdown is triggered.
- burner starts - If there is a lack of gas, the burner
does not begin operation or switches
Monitoring off. A waiting time of 2 minutes
The flame is monitored by an ionisation follows. This is followed by a further
sensor. The sensor is insulated and start attempt. If there is still no gas
fitted to the gas head and is routed pressure, a further waiting time of 2
through the baffle plate into the flame minutes follows. The waiting time can
zone. The sensor must not have any only be reset by interrupting the power
electrical contact with earthed parts. The supply to the burner.
burner switches to malfunction if a short Waiting times: 3 x 2 min, then 1 hour
circuit occurs between the sensor and
the burner earth. In the event of controller shutdown
During burner operation, an ionised - Controller thermostat interrupts heat
zone is produced in the gas flame request
through which a rectified current flows
Burner assembly
Burner installation position
Gas connection, installation location
Diagram 1:
Standard setting
Diagram 2:
Burner head setting for older heating en
boilers with tendency toward CO
emissions
Fit the two plates C between baffle
plate A and natural gas shutter D.
Adjustment data
Air regulation
Burne r
Burne r
A ir fla p he a d Ga s
T yp e Burne r he a d ga s D im e n s io n A ir in ta k e
p o s itio n a ir p r e s s o s ta t
of pow e r pre s s ure Y a d ju s te r
103 B pre s s ure s e ttin g
ga s (k W ) 1 1 9 pBr (m m ) s e ttin g
0 to 1 8 pL (d a P a )
(d a P a )
(d a P a )
15 22 4 13 10 1
V G1 .4 0 25 36 7 14 20 1
35 69 10 19 25 1 en
G2 0 40 36 11 26 25 ( 1) 1
V G1 .5 5 100
G2 5 50 44 15 27 30 1
62 76 10 46 25 -
V G1 .8 5 76 104 12 45 30 -
86 126 18 55 35 -
15 34 3 5 22 1
V G1 .4 0 25 84 7 12 25 1
35 156 11 20 30 1
40 50 12 28 25 1
G3 1 V G1 .5 5 100
50 63 18 29 30 1
59 76 10 45 25 -
V G1 .8 5 70 93 13 45 30 -
85 123 18 56 35 -
(1 ): D e fa u lt s e ttin g
The adjustment data listed above are the default settings. The factory-set adjustment values are outlined in bold. These adjustment
values are normally suitable for commissioning the burner. Always check the adjustment values on a case by case basis. System-
specific corrections may be necessary.
On the burner:
Set the burner head and air flap
according to the table.
On the valve:
Remove the protective cap on the
pressure regulator (104/C).
Turn screw C:
- clockwise: more power
- anti-clockwise: less power
(Caution! No stop! The full adjustment
range is 10 turns. One turn =
60 daPa).
Set pressure pBr via screw C.
Measure gas pressure at point 119
and 119pBr.
Electrical connection
1 2
Warning: if the grey connector on the
gas pressostat is not fitted correctly
(image 2), the burner will go into
malfunction mode and the fault
"Awaiting gas pressure" will be
displayed.
Setting the gas pressostat Turn the dial clockwise until the gas
To set the shut-off pressure: Remove pressostat shuts down the burner.
the cover of the gas pressostat. Turn it clockwise again to set the gas
Connect a device for measuring gas pressostat 10 % above the
pressure pa. predetermined shutdown value.
Start the burner. The gas pressostat adjustment value
Reduce the gas pressure upstream of must be higher than the blower pressure
the train by closing the manual shut- but lower than the gas pressure
off valve until either: downstream of the gas valve.
- Gas pressure pa downstream of the Check the switch-off point:
train reduces to 70 % Open the manual shut-off valve
- Flame stability noticeably Burner start
decreases Close the manual shut-off valve
- The CO value increases The gas shortage program should start
- The flame signal worsens without the burner control unit triggering
considerably a safety shutdown.
Maintenance
Burner and boiler servicing must only Checking the exhaust gas
be carried out by a trained heating temperature
specialist. The system operator is Check the flue gas temperature at
advised to take out a service contract regular intervals.
to guarantee regular servicing. Clean the boiler if the flue gas
temperature is more than 30 K above
Please observe the following points: the value measured at the time of
Disconnect the electrical supply and commissioning.
close the gas shut-off valve before To simplify the check, use a flue gas
carrying out any maintenance or temperature indicator.
cleaning work.
en
Troubleshooting
Burner does not start after Drop in supply voltage or power failure. Check the cause of the fall in voltage or
thermostat shutdown. the power failure.
No malfunction indicated on the Control unit malfunction. Replace the control unit.
automatic combustion control unit.
Burner starts briefly when switched Control unit was deliberately shut down. Unlock the unit.
on, switches off and the red LED
lights up.
Burner does not start. Air pressure switch: not in rest position
Incorrect adjustment Readjust the pressure switch.
contact is welded Replace the pressure switch.
Burner does not start. Insufficient gas pressure Check gas lines.
Clean the filter.
Normal gas pressure Gas pressostat wrongly set or defective Check the gas pressostat or replace the
compact gas unit.
Burner blower starts up. Burner Air pressure switch: the contact does not close Check the pressure transmitter (foreign
does not start. bodies) and wiring.
Burner blower starts up. Burner Flaring during pre-ventilation or pre-ignition. Check the valve. Check flame
does not start. monitoring.
The burner starts, the ignition No flame at the end of the safety period.
switches on, then failure
Gas throughput set incorrectly. Adjust the gas throughput.
Faulty flame monitoring circuit Check the condition and position of the
ionisation sensor in relation to earth.
Check the condition and connections of
the ionisation circuit (cable(s) and
measurement bridges).
Valves jamming.
The burner switches off during Air pressure switch: contact opens during start- Adjust or replace the pressure switch.
operation. up or during operation.
Check the ionisation sensor circuit.
Flame failure during operation. Check or replace the automatic
combustion control unit.
as well as the
number of the
completed service
contract (accessible
A4 Display via the fault menu)
BP1 push-button 1
Request: fault code To change the telephone number
BP2 push-button 2 Call up the fault menu by pressing BP1,
Request: values then keep pressing the button to scroll
through BP1 until the desired pictogram
is displayed.
Press BP2 to enter a change in the
pictogram: the first figure flashes.
Select the value (from 0 to 9) by
repeatedly pressing BP1.
Confirm by pressing BP2.
Repeat the operation until you reach the
last figure.
Hotline
ELCO Austria GmbH
Aredstr.16-18 0810-400010
2544 Leobersdorf
ELCO Belgium nv/sa
Z.1 Researchpark 60 02-4631902
1731 Zellik
ELCOTHERM AG
Sarganserstrasse 100 0848 808 808
7324 Vilters
ELCO GmbH
Dreieichstr.10 0180-3526180
64546 Mrfelden-Walldorf