Sei sulla pagina 1di 86

Transfer Panel ATI

Instruction Manual
GENERAL SAFETY INSTRUCTIONS
a. This leaflet provides indispensable f. The maintenance operations must
instructions in termes of the safety, be carried out exclusively by autho-
the connection and the operation of rised and appropriately trained per-
the automatic transfer switch. sonnel.

b. This system must exclusively be g. This system complies with the com-
installed by specialised, qualified munity directives applicable to this
personnel. product. Thus, it bears the CE mark.

c. Before making the connections, it is


essential that the earth cable be con-
nected.

d. Keep the cabinet clean using a dry h. Compliance with IEC 60947-6-1.
cloth.
i. Information available in this instruc-
e. It is recommended that this leaflet tion manual are not contractual.
be kept in a place easily accessible
to all those who may need it.

2
INTRODUCTION________________________________________________ 4 - 6
GENERAL INTRODUCTION ____________________________________ 4
ATI TRANSFER PANEL RANGE _________________________________ 4
NEW MOTORIZED CHANGEOVER SWITCH _____________________ 4
OPTIONS AVAILABILITY _______________________________________ 5
ENVIRONMENT ______________________________________________ 6

TECHNICAL CARACTERISTICS_____________________________________ 6

ENCLOSURES INSTALLATION _________________________________ 7 - 37


FIRST OPERATIONS ______________________________________ 7 - 10
BOTTOM CABLE ENTRY ENCLOSURES ___________________ 11 - 17
TOP CABLE ENTRY ENCLOSURES _______________________ 18 - 24
OPTIONAL CONNECTIONS ______________________________ 25 - 37
GENERAL POINTS___________________________________________ 37

ENGLISH
VOLTAGE CONFIGURATIONS _________________________________ 38 - 42
VOLTAGE OPTIONS__________________________________________ 38
CABLE CONNECTIONS BETWEEN SWITCH
AND ELECTRONIC MODULE _________________________________ 38
ELECTRONIC MODULE CONNECTIONS ___________________ 39 - 42

INPUTS AND OUTPUT CONTACTS ________________________________ 43

CURRENT INPUTS (for metering) __________________________________ 43

BASIC PRODUCT USE________________________________________ 44 - 62


GENERAL INTRODUCTION ___________________________________ 44
ELECTRONIC MODULE USAGE __________________________ 44 - 45
PROGRAMMING ACCESS____________________________________ 45
PROGRAMMING EXIT________________________________________ 45
PROGRAMMING MENUS_____________________________________ 46
SETUP MENU___________________________________________ 47 - 48
VOLTAGE MENU ________________________________________ 49 - 50
FREQUENCY MENU _____________________________________ 50 - 51
TIMERS MENU__________________________________________ 51 - 52
COMMUNICATION MENU ________________________________ 52 - 54
MANUAL MODE _____________________________________________ 55
AUTOMATIC MODE __________________________________________ 56
LOSS OF MAINS AUTOMATIC SEQUENCE _____________________ 57
MAINS RETURN AUTOMATIC SEQUENCE _________________ 58 - 59
TEST MODE ACCESS________________________________________ 60
TEST MODE EXIT____________________________________________ 60
OFF LOAD TESTING _________________________________________ 61
ON LOAD TESTING __________________________________________ 62

METERING PRODUCT USE ___________________________________ 63 - 75


GENERAL INTRODUCTION ___________________________________ 63
ELECTRONIC MODULE USAGE __________________________ 63 - 64
PROGRAMMING ACCESS____________________________________ 64
PROGRAMMING EXIT________________________________________ 64
PROGRAMMING MENUS_____________________________________ 65
SETUP MENU___________________________________________ 66 - 67
VOLTAGE MENU ________________________________________ 68 - 69
FREQUENCY MENU _____________________________________ 69 - 70
TIMERS MENU__________________________________________ 70 - 71
COMMUNICATION MENU _____________________________________71
PRODUCT METERING ___________________________________ 72 - 73
MANUAL MODE _____________________________________________ 74
MAINS RETURN AUTOMATIC SEQUENCE _____________________ 74
TEST MODE ACCESS________________________________________ 75
TEST MODE EXIT____________________________________________ 75

COMMUNICATION ___________________________________________ 76 - 79
LIST OF PARAMETERS TO BE DISPLAYED_________________ 76 - 79
SAVED COMMAND __________________________________________ 79

MAINTENANCE ______________________________________________ 80 - 83

FAULT FINDING GUIDE ___________________________________________ 84

3
INTRODUCTION
GENERAL INTRODUCTION
NEW ATI enclosure integrates a new Simplify connections between the
4-pole changeover switch including mechanical switch and the electronic
electronics control to meet standard module.
IEC 60947-6-1. Thanks to the chan- With the mode switch in manual posi-
geover switch technology, it is always tion, Padlocking, as well as handle
possible to manually operate the sys- insertion operations are then directly
tem to guarantee the changeover panel accessible from the front panel.
operation in any situation. The electronic module, also accessible
The new enclosure design allows from the front panel, includes:
switch front panel access to: Sources monitoring
Avoid opening of the enclosure for Metering display (V and f as standard)
manual operation Test operations and Sequences pro-
Allow electronic module access for gramming using keypad.
programming and monitoring

ATI TRANSFER PANEL RANGE


The new ATI panel range will be available from 63 A to 1 600 A.
New ATI range models
MODEL
ATI 63 A ATI 630 A
ATI 100 A ATI 800 A
ATI 125 A ATI 1 000 A
ATI 250 A ATI 1 250 A
ATI 400 A ATI 1 600 A
Standard offer includes Bottom cable entry. Top cable entry is offered as an
option.

NEW MOTORIZED CHANGEOVER SWITCH


The new switch included in the enclosure is made of 3 different parts:
1. A mechanical switch.
2. A motorized block to operate the switch electrically.
3
3. An electronic module on the top of the motorized block, driving loss of mains
and mains return sequence.
2
1 Features and benefits: Main sensing circuit is 3 phases and
Gen sensing circuit is single phase
ATI 035 A

The new Motorisation block is inclu-


ded in a moulded case Standard product includes, phase to
It is possible to remove the motorized phase + phase to neutral voltage
block and the electronic module measurement and displays system
without being obliged to disconnect frequency (phase 1) and switch num-
the power cables ber of operations.
Manual operation directly acts on the The product including metering allows
shaft of the mechanical switch for current measurement as well as power
better reliability metering (kW, kVar, kVA and PF).
The complete enclosure meets stan-
dard IEC 60947-6-1 (ATS applications)
The enclosure is self-powered (from
Main and Gen sources). There is no
need for an external power source to
allow automatic sequence after loss
of power
All thresholds and timers can be set
using the display and the keypad, or
via modbus (optional)
The standard product integrates
voltage and frequency control for
better diagnostic

4
INTRODUCTION (continued)
OPTIONS AVAILABILITY
Option 9
Top Cable Entry
Option 8
Communication Option 7
2In / 2Out
Option 1
Metering Option
Option 5
Voltage 277 VAC

ENGLISH
Option 2
IP54 Protection Kit

Option 3
Option 6 Solid Neutral
Auxiliary contacts
ATI 036 A GB

Option 4
Lightning Protection

Factory options are delivered pre-installed in the enclosures

Option 6: Option 9:
Auxiliary contacts for switch posi- Top Cable Entry. For cables to be
tion information, padlocking and routed through the top rather than
Auto / Manual mode information are bottom. Option code is TICT.
optionally available. Option code is
TAUX.
Option 1: Option 5:
A metering module allowing stan- A switch allowing 277 Vac specific
dard features + current and power voltage option for customers requi-
metering facilities on a larger backlit ring voltage code V601 (480/277 Vac).
display. Option code is TMET. Option code is THVM.

Loose options are available, for customer mounting in the enclosures


Option 2: Option 7:
IP54 protection rating is available as 2IN / 2OUT.1 plug in module allowing
an option. A specific protection win- auxiliary contacts for Main and
dow must be installed on the front Generator available information is also
panel of the enclosure to avoid water available as an option. Option code is
infiltration in the enclosure. Option TIO2.
code is TIP5.
Option 8:
Option 3: 1 plug in communication module,
Solid neutral link is available as an JBUS / MODBUS protocole, can
option on the switch itself, when optionally be ordered allowing remote
switching of the neutral cable is not communication of the changeover
required. Option code is TLNK. system. Option code is TCOM.
Option 4:
Lightning protection is also available
as an option to avoid ATS damage in
case of a strike on the power cables.
This option is highly recommended
in stormy areas. Option code is TLPR
and TI02 is included.

5
INTRODUCTION (continued)
ENVIRONMENT
The complete enclosure meets following environmental requirements:
Ingress protection of IP41 with overall Operating temperature of 40 C to 95 % humidity non condensing at
rating of IP21 65 C with de-rating 40 C
Operating temperature of 10 C to Maximum storage is one year Maximum operating altitude without
40 C without de-rating 80 % humidity non condensing at switch de-rating is 2 000 m above
55 C sea level.

TECHNICAL CARACTERISTICS
Characteristics
Thermal Current Ith (40 C) 63 A 100 A 125 A 250 A 400 A 630 A 800A 1 000A 1250 A 1600 A
Assigned isolement voltage Ui (V) 800 800 800 800 800 1 000 1 000 1 000 1000 1000
Assigned voltage to chocks Uimp (kV) 8 8 8 8 8 12 12 12 12 12
IEC 60947-6-1 Characteristics
Assigned current Ie (A) (B categorie)
415 Vac AC31B 63 100 125 250 400 630 800 1 000 1250 1600
Operating Class
Material class PC PC PC PC PC PC PC PC PC PC
Maximum short circuit current using gG DIN fuse
Max short circuit (kA eff) 100 100 100 50 18 70 50 100 100 100
Fuse size (A) 63 100 125 250 400 630 800 1 000 1250 2 x 800
Peak current value: withstand and closing operation (kA peak) 10 14 18 23 23 45 48 75 75 75
Short circuit Operation
Rated short time withstand current (kA eff) 5 5 10 10 10 12.6 16 20 25 32
Rated short circuit making capacity (kA max) 8.5 8.5 17 17 17 25.2 27,2 40 52.5 67
Other Characteristics
Commutation duration
I-II ou II-I (s) (1) 0.75 0.75 0.75 1.3 1.3 1.3 2,6 2,6 2.8 2.8
I-o ou II-0 (s) (1) 0.45 0.45 0.45 0.85 0.85 0.85 1,6 1,6 1,7 1,7
Black time durating during commutation under Un (ms) 300 300 300 600 600 600 1 500 1 500 1700 1700
Power input
230 Vac mini / maxi (V) 184/276 184/276 184/276 184/276 184/276 184/276 184/276 184/276 210/310 210/310
277 Vac mini / maxi (V) - Option 5 221/332 221/332 221/332 221/332 221/332 221/332 221/332 221/332 240/380 240/380
Consumption during switching operation
230 Vac maxi / average (VA) 420/80 420/80 420/80 400/100 400/100 420/110 450/120 450/120 470/128 470/128
277 Vac maxi / average (VA) - Option 5 420/80 420/80 420/80 400/110 400/110 420/115 450/125 450/125 470/128 470/128
Mechanical characteristics
Number of commutation (durability) 10 000 10 000 10 000 8 000 8 000 5 000 4 000 4 000 3000 3000
Weight (complete std enclosure) kg 21 21 21 39 44 66 125 130 230 330
All these characteristics are given as information and are not contractual
(1): Between order sent and final position (under nominal conditions)

Temperature Derating
Nominal Rating Cable Size De rate IEC 947-3
(40 C Max) 50 C 60 C 65 C 40 C 415 V 60 C 415 V
(A) (mm2) (A) (A) (A) AC 22 AC 23 AC 22 AC 23
63 16 63 50 45 AC23A 63A AC23A 45A
100 35 100 80 63 AC23A 100A AC23A 63A
125 50 125 100 80 AC23A 125A AC23A 80A
250 120 250 220 200 AC23A 250A AC23A 200A
400 240 360 300 250 AC22A 400A AC23A 250A AC23A 250A
630 2 x 185 550 500 400 AC22A 630A AC23A 500A AC23A 400A
800 2 x 240 720 640 540 AC22A 800A AC23A 800A AC23A 540A
1 000 4 x 150 880 800 680 AC22A 1000A AC23A 1000A AC23A 680A
1 250 4 x 240 1 150 1 000 820 AC22A 1 250A AC22A 1 000A
1 600 5 x 240 1 300 1 100 930 AC22A 1 600A AC22A 1 100A

Single phase configuration


Table available for single phase configurations using a 4 poles switch and connecting 2 poles in parrallel
Max ambiant Temperature = 40 C

Nominal Rating 3 phase configuration Nominal Rating 1phase configuration


(A) (2 poles in //) (A)
(1)
63 100 Short circuit level required for 160A
100 160 (1) not acceptable for 100A version
125 200 (2) Short circuit level required for 630A
250 400 not acceptable for 400A version
400 630 (2) (3)Short circuit level required for 800A

630 800 (3) not acceptable for 630A version


(4)Short circuit level required for 1 600A
800 1 250
1 000 1 600 (4) not acceptable for 1 000A version
(5)
1250 1 800 Short circuit level required for 2 500A
1 600 2 500 (5) not acceptable for 1 600A version

Metering accuracy
Voltage and frequency: 1 % on power input range.
6
ENCLOSURES INSTALLATION
FIRST OPERATIONS
The system is delivered in position 0 in
manual mode, start generator contact
closed.

Shroud

Remove the shroud to allow terminals


access.

ENGLISH
400A / 630A
ATI 037 A

Remove the plastic protection of the


plexiglas cover.

7
ENCLOSURES INSTALLATION (continued)
Handle with chain

Fix the handle + chain on the enclo-


sure itself.

x1

ATI 038 A

8
ENCLOSURES INSTALLATION (continued)
Wall mounting brackets

Use the mounting brackets delivered


in a bag inside the enclosure to fix the
enclosure on a wall.

x4
x4

ENGLISH
M6

x4

x4
ATI 039 A

9
ENCLOSURES INSTALLATION (continued)
Voltage sensing kit

Cut the voltage sensing kit clips to


allow cables connections using
screws/nuts/contact washers delive-
red in a bag inside the enclosure.

3
ATI 040 A

10
ENCLOSURES INSTALLATION (continued)
BOTTOM CABLE ENTRY ENCLOSURES
63 A / 100 A / 125 A ratings

Power Cables Connection


Power Cables Connection A-A
A

1 2 3 N

ENGLISH
Load

Generator Main

A Earth cable 25 mm2 (Max)

Torque : M8 13 Nm (Max)
Phase and neutral M10 26 Nm (Max)
cable 50 mm2 (Max)

400
276
128

90
70
273 238 122

248 448

39
15
558
600

39
17
7.5
9

7
ATI 041 A GB

12.5 441
455

11
ENCLOSURES INSTALLATION (continued)
250 A rating

Power Cables Connection

A Power Cables Connection


A-A

1 2 3 N

Load

Generator Main

A Earth cable 120 mm2


or 2 x 50 mm2 (Max) Torque : M8 13 Nm (Max)
Phase and neutral cable
M10 26 Nm (Max)
150 mm2 or 2 x 70 mm2 (Max)

600
495

185
245

60
348 435 82.5
323 648

39
15
39
17
7.5
9
900

858

7
ATI 042 A GB

12.5 641
655

12
ENCLOSURES INSTALLATION (continued)
400 A rating

Power Cables Connection


A Power Cables Connection

1 2 3 N

ENGLISH
Main

Load

Generator

Earth cable 120 mm2


A or 2 x 70 mm2 (Max) Torque : M10 26 Nm (Max)
Phase and neutral cable M12 45 Nm (Max)
240 mm2 or 2 x 120 mm2 (Max)

600

495

185
245

60
348 435 82.5
323 648

39
15
39
17
7.5
9
900

858

7
ATI 043 A GB

12.5 641
655

13
ENCLOSURES INSTALLATION (continued)
630 A rating

Power Cables Connection

A
A-A

1 2 3 N

Main

Load

Generator

Phase and neutral cable


2 x 240 mm2 (Max)
A Earth cable
240 mm2 (Max) Torque : M10 26 Nm (Max)
M12 45 Nm (Max)

600
14

288
320

328
46
30

495
455 72.5
423 545 30
398
900

200
ATI 044 A

605

14
ENCLOSURES INSTALLATION (continued)
800 A / 1 000 A ratings

Power Cables Connection


A A-A

ENGLISH
Load
Earth cable: Main
-800A:2x120mm2 or 1x300mm2 (Max)
-1000A:2x240mm2 or 1x300mm2 (Max)
Generator

A Phase and neutral cable Torque: M10 26Nm (Max)


800A:3x240mm2 or 2x300mm2 (Max) M12 45Nm (Max)
1000A:4x240mm2 or 2x300mm2 (Max)

28
720

30
14

480
520

623
600 536
1175
1375

200

775
ATYS 127 A GB

536
50 120
50
80
14

480

50
80

15
ENCLOSURES INSTALLATION (continued)
1 250 A rating

Power Cables Connection


A
A-A

Load

Earth cable
2 x 240 mm2
or 1 x 300 mm2 (Max)

Main

Generator

A Phase and neutral cable Torque: M12 45Nm (Max)


2 x 300 mm2 or 4 x 240 mm2 (Max)

100
555

100

100

800
798
1000
775
1800

1600
1800

200

100

58
100

81
ATYS 131 B GB

555

803
79

58
100

100 100

800

16
ENCLOSURES INSTALLATION (continued)
1 600 A rating

Power Cables Connection


A A-A

ENGLISH
Earth cable
2 x 300 mm2
or 3 x 240 mm2 (Max)

Load

Main

Generator

A Phase and neutral cable Torque: M12 45Nm (Max)

100
6 x 240 mm2 or 4 x 300 mm2 (Max)
555

100

100

800
798
1000
775
1800

1600
1800

200

100

58
100

81
ATYS 132 B GB

555

803
79

58
100

100 100

800

17
ENCLOSURES INSTALLATION (continued)
TOP CABLE ENTRY ENCLOSURES
63 A / 1 00 A / 125 A ratings -
Top cable entry
Power Cables Connection

A
A-A
Earth cable 25 mm2 (Max)

Generator
Main

Load

1 2 3 N

A Phase and neutral cable 50 mm2 (Max)


Torque : M8 13 Nm (Max)
M10 23 Nm (Max)

273
448 248

39
15
39
17
558

7.5
9

600

441 12.5
455

238 122
70
128

90

276
400
ATI 045 A GB

18
ENCLOSURES INSTALLATION (continued)
250 A ratings - Top cable entry
Power Cables Connection

A-A
A Earth cable 120 mm2
or 2 x 50 mm2 (Max)

ENGLISH
Main

Generator
Load

1 2 3N

A Phase and neutral cable Torque : M8 13 Nm (Max)


150 mm2 or 2 x 70 mm2 (Max)
M10 26 Nm (Max)

348
648 323

39
15
39
17
7.5
9

900
858

641 12.5
655

435 82.5
60
245

185

495
600
ATI 046 A GB

19
ENCLOSURES INSTALLATION (continued)
400 A ratings - Top cable entry
Power Cables Connection

A A-A
Earth cable 120 mm2
or 2 x 70 mm2 (Max)

Load Main

Generator

1 2 3 N

Phase and neutral cable Torque : M10 26 Nm (Max)


A 240 mm2 or 2 x 120 mm2 (Max) M12 45 Nm (Max)
348
648 323

39
15
39
17
7.5
9

900
858

641 12.5
655

435 82.5
60
245

185

495
600
ATI 047 A GB

20
ENCLOSURES INSTALLATION (continued)
630 A ratings - Top cable entry
Power Cables Connection

A A-A
2
Earth cable 240 mm (Max)

ENGLISH
Load
Main

Generator

1 2 3 N

Phase and neutral cable Torque : M10 26 Nm (Max)


2x240 mm2 (Max) M12 45 Nm (Max)
423
A 398

1150
200

600

540 30
455 72.5
495
50

46
288

328
280

13

600
ATI 048 A

21
ENCLOSURES INSTALLATION (continued)
800 A/1000 A ratings Top cable entry

Power Cables Connection

A A-A

Generator

Main

Load

Earth cable:
-800A:2x120mm2 or 1x300mm2 (Max)
-1000A:2x240mm2 or 1x300mm2 (Max)

A
Phase and neutral cable:
800A:3x240mm2 or 2x300mm2 (Max)
1000A:4x240mm22 or 2x300mm2 (Max) Torque: M10 26Nm (Max)
28 M12 45Nm (Max)
14 720
30
480
520

623
600
536
13

1 3
1175
1375

12
200

775
536
50
120
50
80
14
ATI 048 C GB

480

50
80

22
ENCLOSURES INSTALLATION (continued)
1250 A rating Top cable entry

Power Cables Connection


Phase and neutral cable
A 2 x 300 mm2 or 4 x 240 mm2 (Max)

A-A

A Generator

Main

ENGLISH
Load

Earth cable
2 x 240 mm2
or 1 x 300 mm2 (Max)

100
Torque : M12 45Nm (Maxi)
555

100

100

800
798
1000
775
1800

1600
1800

200

100

58
100

81
ATYS 133 B GB

555

803
79

58
100

100 100

800

23
ENCLOSURES INSTALLATION (continued)
1600 A rating Top cable entry

Power Cables Connection

Phase and neutral cable


6 x 240 mm2 or 4 x 300 mm2 (Max)
A

A-A

Load

Main

Earth cable
2 x 300 mm2 Generator
or 3 x 240 mm2 (Max)

A
100

Torque M12 45Nm (Maxi)


555

100

100

800
798
1000
775
1800

1600
1800

200

100

58
100

81
ATYS 134 B GB

555

803
79

58
100

100 100

800

24
ENCLOSURES INSTALLATION (continued)
OPTIONAL CONNECTIONS

Option 1
Verify there is no voltage
on the terminals before Metering Option
Available from third release 2004. This
mounting the options. option is factory fitted and includes a
specific metering display + metering
CTs to allow current + power metering.

ENGLISH
Metering :
- (Sensing) CTS
- Specific Metering Display
ATI 049 A GB

Option 2
IP54 protection kit
x1

x4
1 M5

x1

x4

x1

4 25
25
7

3
2
92
354

4
ATI 050 A GB

25
ENCLOSURES INSTALLATION (continued)
Option 3

Solid neutral kit


63A / 100A rating

x2 M8

x1
x2

x2
x1

x1
x2 M8x20

1
ATI 051 A

Torque : M8 > 13 Nm (Max)

26
ENCLOSURES INSTALLATION (continued)
Option 3

Solid neutral kit


125A / 250A rating

x3

x1 x1

ENGLISH
x1

x2
x3 M8/M10 x 20

3
ATI 052 A

Torque : M8 > 13 Nm (Max)


M10 > 26 Nm (Max)

27
ENCLOSURES INSTALLATION (continued)

x1 x4 M10 / M12

x1

x2
400A : x4 M10 x 30
x1 630A : x4 M12 x 35
1 x1

x2

3
ATI 053 A

Torque: M10 > 26 Nm (max)


M12 > 45 Nm (max)

28
ENCLOSURES INSTALLATION (continued)
Option 3

Solid neutral kit


800A rating

x1 x1 M10: x2
M12: x4
M10: x2
M12: x4

ENGLISH
x1 M10: x2
M12: x4
x1
M10x40: x2
M12x35: x1
M12x40: x2
M12x45: x1

A
see detail

detail A
1/2

M12x45 (x2)
M12x35 (x1)

M10x40 (x2)
M12x40 (x2)

Torque: M10 > 26 Nm (max)


M12 > 45 Nm (max)

29
ENCLOSURES INSTALLATION (continued)
Option 3

Solid neutral kit


1 000A rating

x1 M10: x8
M12: x4
x1
M10: x8
M12: x4
x1
M10: x8
M12: x4
x1 M10x35: x4
M10x45: x4
M12x40: x2
M12x50: x2

A
see detail

detail A
1/2 M10x45 (x4)

M10x35 (x4)

M12x50 (x2)

M12x40 (x2)
ATYS
ATI 053 A A
130

Torque: M10 > 26 Nm (max)


M12 > 45 Nm (max)

30
ENCLOSURES INSTALLATION (continued)
Option 3

Solid neutral kit


1 250A rating

x2 M12: x18

x1
M12: x18
x1

ENGLISH
M12: x18

M12X45: x18
A
see detail

detail A

A
ATYS 135 B

A SECTION A-A

31
ENCLOSURES INSTALLATION (continued)
Option 3

Solid neutral kit


1 600A rating

x4 M12: x18

x1
M12: x18
x1
M12: x18

A M12X45: x18
see detail

detail A

A
ATYS 136 B

A
SECTION A-A

32
ENCLOSURES INSTALLATION (continued)
Option 4
Lightning protection

A 3 minutes power off


action is required before
startup to allow option
recognition.
x1 M6
Bottom Connection Top Connection

ENGLISH
x1 x2

M8
x2

x1
125A 125A
250A 250A

A
B

A
5

1/2

ATI
Electronic module
C
4
B
1 2
3 N
CONTACT Q2 3P

CONTACT Q2 1P
CONTACTS
SURGYS

FUSE

FUSE
ATI 054 A GB

5
2IN/2OUT
Option

A specific menu in the metering


architecture allows monitoring of the
protection. Cf variable LIP in the mo-
nitoring menu.
LIP variable = 1 as soon as the pro-
tection operates (fuse blow or lightning
protection operation).
This information is verified every
5 seconds.
Error led also blinks to inform of LIP
operation.
It might then either be required to
change a fuse or the lightning module.

33
ENCLOSURES INSTALLATION (continued)
Option 4 (continued)
Lightning protection equipment Connection diagram

L3 L3
L2 L2
L1 L1
N N

2
4mm

RMS 50
Q2 50A

102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac G Voltage Sensing
4mm2

203

103
204

104
205

105
L/N L/N L/N L/N

206

106
SURGYS

7
D40 D40 D40 D40

8
Opt.2 Opt.1

9 10
11 12

6mm2
ATI 055 A GB

ATI Electronic Module


0.75mm2
+
-

11 11 11 11

14 14 14 14
CONTACT Q2 3P

CONTACT Q2 1P
CONTACTS
SURGYS

FUSE

FUSE
C
+

2IN/2OUT
14
13

Option

34
ENCLOSURES INSTALLATION (continued)
Option 5
277 Vac option
Switch is available in 277 Vac version.

Option 6
Auxiliary contacts for 0,1,2 position,
padlock and Auto / Manual Mode.
Available from factory.

ENGLISH
f g h i j

20 21 22 23 24 25 26 27
1 2 3 N
ATI 056 A GB

1 2 0 A/M Padlocking

Identification Terminals Type Feature Rating


f 20-21 Output Position 1 Auxiliary contact

Resistive load: 10 A Inductive load: 3 A


Contact closed when

Max Vac: 250 - Max operations: 5 x 107


switch is in position 1
g 20-22 Output Position 2 Auxiliary contact
Contact closed when
switch is in position 2
h 20-23 Output Position 0 Auxiliary
contact Contact closed
when switch is in position 0
i 24-25 Output Auto / Manu information
Contact closed when
Automatic mode is active
j 26-27 Output Padlocking information
Contact closed when
the switch is padlocked

Contact f, g and h are closed when the


switch is in position 1, 2 or 0.
Contact i is closed when the switch is
in Automatic mode.
Contact j is closed when the switch is
padlocked.

35
ENCLOSURES INSTALLATION (continued)
Option 7
2 IN / 2 OUT option
Main available / Gen available output
contacts.
The contact closes as soon as the
source is available.

A 3 minutes power off x1

action is required before


startup to allow option
recognition.

1/2

OUT
9 / 10 : Main Available output contact
a b
9 10 11 12
11/12 : Gen Available output contact
ATI 057 A GB

Identification Terminals Type Feature Rating


a 9-10 Output Main available information
Max operations 105 - Galvanic insulation
230 Vac - 5 A - 1 150 VA

2,5 kV (1 min 50 Hz)

b 11-12 Output Gen available information

36
ENCLOSURES INSTALLATION (continued)
Option 8
Communication module
Read paragraph communication for
A 3 minutes power off instructions.
Installation of this module allows RS485
action is required before connection. Protocoles avaible are
startup to allow option JBUS / MODBUS.
recognition.
x1

ENGLISH
1/2

2
ATI 058 A GB

RS485 2 or 3 wires half duplex


Protocol JBUS / MODBUS protocol / RTU mode
Speed 2400, 4800, 9600, 14 400, 19 200, 28 800, 38 400 Bauds
Galvanic insulation 4 kV (1 min 50 Hz)

GENERAL POINTS

Recommendations: For standard configurations, an RS


You should use a shielded twisted pair 485 link is used to connect up to 31
(LIYCY type). In a disturbed environ- ATI with a PC or a PLC over a distance
ment or large network (in terms of of 1 500 metres, using JBUS / MOD-
length) we recommend the use of BUS protocol.
2 shielded pairs (type LIYCY-CY). In
this case, one pair is used for the
+ and the , and another pair, where
the 2 wires are short-circuited, for the 1500 M

0 V.
A repeater (1 channel) or an arrestor
(4 channels) should be used if you
intend to exceed the distance R = 120
N 1 N 2 N n
(1 500 m) and / or maximum number R = 120
DIRIS 109 B

(31) of ATI. Please contact us for Programmable


controllers
more information.
Other systems
NB:
A 120 ohm resistance (found on the
additional module) must be fixed at
both ends of the link. 1500 M 1500 M

Other solutions are available (modem,


optical fibre, etc.). Please contact us.
0+- -+0
R = 120 N 1 repetor N n
RS485 R = 120
Programmable
DIRIS 110 B

controllers

Other systems

37
VOLTAGE CONFIGURATIONS
VOLTAGE OPTIONS
To meet all voltages required by the market, 2 ATI versions have been developed:

Standard 230Vac +/- 20%


50 Hz 3 phase 4 wires - 3P4L 60 Hz 3 phase 4 wires 3P4L
Star connections Star connections
FG Wilson Voltage FG Wilson Voltage
option code option code
V502 415 / 240V V603 440 / 254V (2)
V503 400 / 230V V605 380 / 220V
V504 380 / 220V V608 220 / 127V
V507 220 / 127V V610 208 / 120V (3)
V510 200 / 115V (1) V611 240 / 139V
(1): +20%/-12%
(2): +13%/-20%
(3): +20%/-15%

50 Hz 3 phase 3 (4) wires - 3P3(4)L 60 Hz 3 phase 3 (4) wires 3P3(4)L


Delta connections Delta connections
V506 230 / 115V V606 240 / 120V
V508 220 / 110V V607 230 / 115V
V609 220 / 110V

50 Hz single phase 3 wire 1P3L 60 Hz single phase 3 wire 1P3L


V522 240 / 120V V622 240 / 120V
V524 230 / 115V V624 230 / 115V
V526 220 / 110V V626 220 / 110V

50 Hz single phase 2 wire 1P2L 60 Hz single phase 2 wire 1P2L


V521 240V V621 240V
V523 230V V623 230V
V525 220V V625 220V

Optional 277 Vac ( + / -20 % for rating below 630 A, + 20 / -15 % for rating
800 A and above)
50 Hz 3 phase 4 wires - 3P4L 60 Hz 3 phase 4 wires 3P4L
Star connections Star connections
FG Wilson Voltage FG Wilson Voltage
option code option code
V601 480 / 277V

CABLE CONNECTIONS BETWEEN SWITCH


AND ELECTRONIC MODULE

A voltage sensing kit is used to provide


sensing and power connections from
the switch terminals to the electronic
module terminals.
The ATI enclosures are delivered as In standard ATI (bottom
standard for 3 phases 4 wires applica- entry) generator cable is
tions, 400 /230 Vac nominal voltage.
In some 3 phase 4 wires, all 3 phases 3 red and main cable is black.
wires, or single phase 2 or 3 wires In top entry ATI main cable
applications, sensing connections keep is red and generator cable
the same, but power connections must
be modified according to guidelines is black.
included before connection diagrams.

38
VOLTAGE CONFIGURATIONS (continued)
ELECTRONIC MODULE CONNECTIONS
The Voltage sensing kit provides power
and sensing to the electronic module
Verify voltage between from the generator and the main side.
101 / 102 & 201 / 202
= 220 / 240 Vac20 %
Main sensing is 3 phases sensing: Gen sensing is single phase sensing:
103: Neutral 203: Phase 1
104: Phase 3 205: Phase 3
105: Phase 2

ENGLISH
106: Phase 1

3 Phases 4 Wires connections-3P4L


A. No wiring change required from standard delivery
Configurations:
V502 415 / 240 Vac 50 Hz
V503 400 / 230 Vac 50 Hz
V504 380 / 220 Vac 50 Hz
V603 440 / 254 Vac 60 Hz
V605 380 / 220 Vac 60 Hz
V601 480 / 277 Vac 60 Hz - Special Voltage Option 5 = 277 Vac

LOAD

1
2
3
N

Genset controller

A A
102 101
201 202

Power 230 Vac

Voltage Sensing OO Power 230 Vac

B B
203

103

1-2 7-8
Voltage Sensing
204

104

3-4 5-6
205

105

5-6 3-4

1-2
206

106

7-8

a
7

b
8

c
9 10

d
Opt. 2 Opt. 1
11 12

e
ATI 059 A GB

f g h i j
20 21 22 23 24 25 26 27

39
VOLTAGE CONFIGURATIONS (continued)
3 Phases 4 Wires connections-3P4L
B. Wiring change required from standard Configurations:
delivery: A & B power wires from ter- V507 220 / 127 Vac 50 Hz
minals 206 & 103 must be connected V510 200 / 115 Vac 50 Hz
to terminals 205 & 104 to provide V608 220 / 127 Vac 60 Hz
220/230 Vac or 240 Vac to the power V610 208 / 120 Vac 60 Hz
inputs 101/102 and 201/202. V611 240 / 139 Vac 60 Hz

LOAD

1
2
3
N

Genset controller

A A

102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac

B B
203

103

1-2 7-8
Voltage Sensing
204

104

3-4 5-6
205

105

5-6 3-4

1-2
206

106

7-8
ATI 060 A GB

a
b

3 Phases 3 (4) Wires connections-3P3(4)L

Wiring change required from stan- Configurations:


dard delivery: A & B power wires from V506 230 / 115 Vac 50 Hz
terminals 206 & 103 must be con- V508 220 / 110 Vac 50 Hz
nected to terminals 205 & 104 to pro- V606 240 / 120 Vac 60 Hz
vide 220 / 230 Vac or 240 Vac to the V607 230 / 115 Vac 60 Hz
power inputs 101/102 and 201/202. V609 220 / 110 Vac 60 Hz

LOAD

1
2
3
M

Genset controller

A A
102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac

B B
203

103

1-2 7-8
Voltage Sensing
204

104

3-4 5-6
205

105

5-6 3-4

1-2
206

106

7-8
ATI 061 A GB

a
b

40
VOLTAGE CONFIGURATIONS (continued)
1 Phase 3 Wires connections-1P3L
Wiring change required from stan- Configurations:
dard delivery: A & B power wires V522 240 / 120 Vac 50 Hz
from terminals 206 & 103 must be V524 230 / 115 Vac 50 Hz
connected to terminals 205 & 104 V526 220 / 110 Vac 50 Hz
to provide 220 / 230 Vac or 240 Vac V622 240 / 120 Vac 60 Hz
to the power inputs 101 / 102 and V624 230 / 115 Vac 60 Hz
201 / 202. V626 220 / 110 Vac 60 Hz
LOAD

ENGLISH
1
2
3

Genset controller

A A

102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac

B B
203

1-2 103 7-8


Voltage Sensing
204

104

3-4 5-6
205

105

5-6 3-4

1-2
206

106

7-8
ATI 062 A GB

a
7

b
8

1 Phase 2 Wires connections-1P2L

Wiring change required from stan- V521 240 Vac 50 Hz


dard delivery: A & B power wires from V523 230 Vac 50 Hz
terminals 206 & 103 must be con- V525 220 Vac 50 Hz
nected to terminals 205 & 104 to pro- V621 240 Vac 60 Hz
vide 220 / 230 Vac or 240 Vac to the V623 230 Vac 60 Hz
power inputs 101/102 and 201/202. V625 220 Vac 60 Hz
LOAD

Genset controller

A A
102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac

B B
203

103

1-2 7-8
Voltage Sensing
204

104

3-4 5-6
205

105

5-6 3-4

1-2
206

106

7-8
ATI 063 A GB

a
7

b
8

41
VOLTAGE CONFIGURATIONS (continued)
1PAP
Split phase network / single phase This configuration must be used on
generator. applications using single phase gen-
erators to supply 2 phases networks
feeding single phase loads.

LOAD

1 1
1 2
N
N N

Genset controller

A A

102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac

B B
203

1-2 103 7-8


Voltage Sensing

N.C.
204

104

3-4 5-6
205

105

5-6 3-4

1-2
206

106

7-8
ATI 064 A GB

a
7

b
8

Three phase network / single phase This configuration must be used on


generator. applications using single phase ge-
nerators to supply 3 phases networks
feeding single phase loads.
Wiring change required. Change 5-6
and 7-8 on 205 & 206.

LOAD

1 1
1 2
1 3
N N

Genset controller

A A
102 101
201 202

Voltage Sensing OO Power 230 Vac


Power 230 Vac

B B
203

103

1-2 7-8
Voltage Sensing
204

104

3-4 5-6
205

105

7-8 3-4

1-2
206

106

5-6
ATI 065 A GB

a
7

b
8

42
INPUTS AND OUTPUT CONTACTS

ensing

Voltage
206

106
7-8

7
b

8
Opt. 2 Opt. 1
c

9 10
d

11 12
e
ATI 066 A GB

to lightning protection

ENGLISH
option

Identification Terminals Type Feature Rating


a 7 Inputs Common terminal

- Max number of operations 108


- Max inverse voltage 30 Vdc
- Max direct voltage 30 Vdc
- Min direct voltage 10 Vdc

- Galvanic insulation 3 kV
b 7-8 Input AT Timer inhibit input

- Min pulse duration 1 s


Dry contact to close between terminals
7-8 to inhibit AT timer

(1 min 50 Hz)
c 7-9 Input Remote test on load input
Dry contact to close between terminals 7-9 to start
remotely a test on load (only
available in automatic mode)
d 10 ( + ) Power supply Power supply dedicated
to lightning option
7 (-) 5 Vdc < V7-10 < 16 Vdc without load
9 Vdc < V7-10 < 10 Vdc for 1 to 2 inputs
e 11-12 Output Start Gen signal
30 V DC 1 A

CURRENT INPUTS (for METERING)

Short circuit plug If the load is supplied, before discon-


delivered with the spare part
LOAD necting the main connector, it is
R1 R2 S1 S2 T1 T2
necessary to short-circuit the secondary
T2
T1
of the current transformer (short-circuit
S2 plug to be mounted).
S1
R2
R1

1 1
2 2
3 3
N N
Puissance 230 V AC -

Mesure de tension OO Puissance 230 V AC

102 101
201 202

R1 R2 S1 S2 T1 T2
203

103
204

104
- Mesure de tension

R1 R2 S1 S2 T1 T2
205

105
ATI 090 A

I1 I2 I3
206

106
7
8
9

43
BASIC PRODUCT USE
GENERAL INTRODUCTION
Verify power applied on the The product provides sources availabil- The product requires at least one type
ity monitoring, Automatic / Manual of network configuration and a network
electronic module power inputs Retransfer, Manual / Automatic or Test nominal voltage configuration to be input
terminals 101-102 or 201-202 operation monitoring, voltage and fre- via the keypad by the user.
before powering up the unit. quency metering, and good operation or Other default values can be kept or mo-
error information. dified according to hereafter program-
ming guidelines.

ELECTRONIC MODULE USAGE

Front Panel Introduction

The electronic module is directly Following diagram introduces prod-


mounted on the motorized block. uct front panel.
It integrates the following features: Led indication is only active once
ATI 067 A

- Voltage and frequency metering the product is powered (power led


- Automatic transfer controls activated).

LCD Keypad Error Led


7 digits to display information 1 red led to indicate a fault
14 pointers to inform about displayed information unit or source: - Led is on = switch error
- : Mains information - Com: communication active Action from software not confirmed by an auxiliary
- : Generator information - V: Volt contact. Reset after power off
- L1, L2, L3 : Information - Hz: Hertz - Led blinks in case of lightning protection operation
regarding Phase 1,2 or 3 - %: percentage No reset required (blinking disappears once input is low)
- : Timer active - sec: second
- PROG: Programming active - min: minute
- n: number of commutations

Modes annunciation and Tests


1 Top yellow led for Manual Mode position linked
to the key position
1 green led for Automatic Mode position linked
to the key position
2 Bottom yellows leds for Test On and
Off Load position Linked to the test pushbutton press
Symbols are represented to make comprehension easier

Source availability
2 green Leds to indicate if
Gen and Mains sources are available
(voltage and frequency measurement)
- Led is on = source available Power Led
- Led is off = source missing 1 green led
- Blinks slowly as soon
as the product is powered
and software runs correctly
Switch state - Always on = Power OK and
2 green Leds to indicate if software error
the switch is opened or closed - Always off = Power off or
- Led is on = switch is closed software error if another
- Led is off = switch is opened led is on and LCD is OK
1 Yellow led to indicate if both
switches are in 0 position
- Led is on = both switches opened
- Led is off = Gen or Mains
switch closed

Retransfer Inhibit
1 yellow Led, linked to
retransfer inhibit pushbutton
Push button - Led is on = retransfer
inhibit feature is active
: Home push button during programming - Led is off = retransfer
inhibit inactive
: Lamps test button - Led is blinking = retransfer
is blocked, waiting for a push
on the retransfer inhibit
pushbutton to allow retransfer

Switch Position Indications


0, 1 or 2 position display
Keyswitch
Insert key to allow switch
operational mode modification
Turn right to access automatic mode
Turn left to access manual mode

Manual Operation
Insert handle to manually Padlock
operate the switch. Pull the yellow handle to allow padlock insertion
Manual operation only possible Padlocking possible in position 0,1 or 2
ATI 068 A

in Manual mode (keyswitch), but only in Manual mode (keyswitch position),


when not padlocked handle out of housing.

44
BASIC PRODUCT USE (continued)
Software version
Software version is displayed on the
unit after reset (powering up action after

ATI 068 A GB
3 minutes power off to discharge the

{
{
unit). Version Number

Product Programming
Before first product use,
access programming mode Product Programming is possible in It is not accessible when a test or an
Automatic Mode in position 1 when the automatic sequence is activated.

ENGLISH
and verify product Mains Source is available, or in Manual
programming parameters. mode.

PROGRAMMING ACCESS
Programming mode is accessible by
pressing and holding the validation push-
button for 5 seconds and then entering
the code 1000:

Press for 5 seconds

Press once to display 1

Validate
ATI 070 A

Access to programming Menus

PROGRAMMING EXIT
To exit the Programming and come
back to visualisation mode, hold the
validation pushbutton for 5 seconds.
Parameters saved permanently
once exit.

45
BASIC PRODUCT USE (continued)
PROGRAMMING MENUS
Architecture and navigation
The programming mode integrates 5 Menus

Setup: Network parameters


Volt: Voltage detection levels
Default values are Fr: Frequency detection levels
tim: Automatic timer settings
loaded as standard. Comm: Communication parameters (Optional), communication module
must be plugged.
Setup parameters must always be verified/modified in accordance to the
application.

Optional
ATI 071 A

The first menu to access is the Setup menu


ATI 072 A

46
BASIC PRODUCT USE (continued)
SETUP MENU
Parameter Display
The setup menu integrates 5 parame-
ters described in the table hereunder.
The table explains parameters definition,
settings possibilities, and default values.

ENGLISH
Press Down push button to access parameter required.

Press Up push button to come back to previous value, or press

or Home push button to come back to .

Definition Setting range Default value


Un: Phase-Phase From 200 to 480 V 400 V AC
nominal voltage.

nt: Network configuration. 1P2L, 1P3L, 3P4L 3P4L


Type of metering 3P3L, 1PAP
(1P or 3P phases).
Number of active wires
(2L, 3L or 4L)
definition.

Fn: Nominal frequency. 50 or 60 Hz 50 Hz

trI: Retransfer inhibit feature: Yes or No No


press on RTI button required to
allow retransfer from gen to
main.

Crs: Reset number of commutation Yes or No No


counter (from Main to Gen).
Displays no once reset.
ATI 073 A

47
BASIC PRODUCT USE (continued)
Parameter modification

Display the required parameter for settings are described in the previous
modification. table.
Apply the same procedure described Example:
hereunder for network voltage modifica- We want to modify network voltage
tion, to all other parameters. Possible from 400 V to 230 V.

Press to access the first digit (blinking)

Press twice to display 2 (blinking)

Press to access the second digit (blinking)

Press 3 times to display 3 (blinking)

Press to validate the value


ATI 074 A

To return to Setup menu press home pushbutton or press down to continue.

Press to return to Setup menu Press to reach next parameter


ATI 076 A
ATI 075 A

48
BASIC PRODUCT USE (continued)
VOLTAGE MENU

To reach voltage menu from Setup menu press once .

Parameter Display
The voltage menu integrates 8 parame- Generator sensing single phase.
ters described in the table hereunder. Over and under voltage detection lev-
The table explains parameters defini- els + hysteresis are defined as per-
tion, settings possibilities, and default centage of nominal voltage.
values. Hysteresis levels allow under and over

ENGLISH
Over and Under voltage conditions are voltage conditions reset (voltage needs
verified on Mains and Generator side to to pass hysteresis level to reset).
allow operation as per the flow chart.
Mains sensing is 3 phase and

Press Down push button to access parameter required.


Note:
These values only need to be
changed if a value is required other Press Up push button to come back to previous value
than the default.
or Home push button to come back to .

Definition Setting range Default value

oU: Main Over voltage detection 102 - 120 % 115 %

oUh: Main Over voltage hysteresis 101 - 119 % 110 %


detection

uU: Main Under voltage detection 80 - 98 % 85 %

uUh: Main Under voltage hysteresis 81 - 99 % 95 %


detection

oU: Generator over voltage detection 102 - 120 % 115 %

oUh: Generator over voltage 101 - 119 % 110 %


hysteresis detection

uU: Generator under voltage 80 - 98 % 85 %


detection

uUh: Generator under voltage 81 - 99 % 95 %


hysteresis detection
ATI 077 A

49
BASIC PRODUCT USE (continued)
Parameter modification

Display the required parameter for dification. Possible settings are described
modification. in the previous table.
Apply the same procedure as described
in Setup Menu for network voltage mo-

FREQUENCY MENU

To reach frequency menu from voltage menu press once .

Parameter Display

The frequency menu integrates 8 parameters described in the table hereunder.


The table explains parameters definition, Over and under frequency detection levels
settings possibilities, and default values. + hysterisis are defined as percentage of
Over and Under frequency conditions are nominal frequency.
verified on Mains and Generator side to Hysteresis levels allow under and over
allow operation following operational flow frequency conditions reset (frequency
chart. needs to pass hysteresis level to reset).

Press Down push button to access parameter required.

Press Up push button to come back to previous value

or Home push button to come back to .

Definition Setting range Default value

oF: Main over frequency detection 101 - 120 % 105 %

oFh: Main over frequency hysteresis 100.5 - 119.5 % 103 %

uF: Main under frequency 80 - 99 % 95 %

uFh: Main Under frequency hystere- 80.5 - 99.5 % 97 %


sis

oF: Generetor over frequency 101 - 120 % 105 %

oFh: Generator over frequency 100.5 - 119.5 % 103 %


hysteresis

uF: Generator under frequency 80.5 - 99.5 % 95 %

uFh: Generator under frequency 80 - 99 % 97 %


hysteresis
ATI 078 A

50
BASIC PRODUCT USE (continued)
Parameter modification

Display the required parameter for modification. Possible settings are


modification. described in the previous table.
Apply the same procedure as described
in the Setup Menu for network voltage

TIMERS MENU
To reach timer menu from frequency menu press once .

ENGLISH
Parameter Display

The timers menu integrates 5 para- The table explains parameters definition,
meters described in the table settings possibilities, and default values.
below. Timers operation is described in opera-
tional flow chart page.

Press Down push button to access parameter required.

Press Up push button to come back to previous value

or Home push button to come back to .

Definition Setting range Default value


2Mt: loss of mains validation timer. 0 to 60 sec. 5 sec.
Once mains has disappeared,
2Mt is started. If Mains comes
back before 2Mt ends,
the commutation cycle is not
started. (Delay on Gen start.)

At: Generator voltage and frequency 0 to 60 sec. 5 sec.


stabilisation timer. Generator
needs to be stable during AT
to allow transfer from Mains.

1Mt: Mains Return validation timer. 0 to 30 min. 2 min.


Once main is back 1Mt is
started. If Mains disappears
before 1Mt ends, the load is
not switched back to the Mains.

rot: Run on time timer. Once the 0 to 10 min. 4 min.


load is switched back from the
Generator to the Mains, ROT is
started and the Generator
will stop once ROT is finished
(allows generator cool down).

dbt: Dead Band timer. This timer is 0 to 20 sec. 5 sec.


counted down before transferring
the load from the Mains source
to the Generator or vice versa.
It allows the load residual voltage
to decrease under a non critical
ATI 079 A

value before transfer (Necessary


in case of rotating loads).

51
BASIC PRODUCT USE (continued)
Parameter modification

Display the required parameter for modification. Possible settings are


modification. described in the previous table.
Apply the same procedure as described
in the Setup Menu for network voltage

COMMUNICATION MENU (OPTIONAL)


This menu is only
To reach timer menu from frequency menu press once .
accessible when the option
has been purchased and is
Parameter Display
present in the optional slots.
Once plugged into the elec- The COMM menu integrates 4 Communication operation is described in
tronic module, a 3 minutes parameters described in the table paragraph 5.
hereunder.
power off action is required
The table explains parameters definition,
for option identification by settings possibilities, and default values.
software.

Press Down push button to access parameter required.

Press Up push button to come back to previous value

or Home push button to come back to .

Definition Setting range Default value

Slave Jbus / Modbus adress 001 to 247 005

Communication Speed 2 400,4 800,9 600,


(baud) 14 400,19 200,
28 800, 38 400 9600

Stop Bit 0,1,2 1

Parity No, Eve (Even), No


Odd
ATI 080 A

52
BASIC PRODUCT USE (continued)
Product metering

General comments
Metering is active as soon as the unit is After commutation cycle, the display
powered. comes back to Mains voltage L1N (first
Commutation cycles have priority over variable of the mode).
Visualisation mode and display timers Visualisation mode architecture is as
count down as soon as they are active. described hereunder.
Any value available in this mode can
be kept on the screen once displayed.

ENGLISH
excepted during commutation cycle;
comes back to timer count down after
5 s.

General comments

To access requested value press , , or .

If lightning protection
option is fitted, LIP menu is
available. cf option 4.

Optional
ATI 081 A

53
BASIC PRODUCT USE (continued)
Values definition

All these values are not Main Voltage L1-N


accessible on all networks :

3P4L Main Voltage L2-N


Main U1, U2, U3
U12, U23, U31
Gen U31
Main Voltage L3-N
1P3L
Main U12, U23, U31
Gen U31
Main Voltage L1-L2
1P2L
Main U31
Gen U31
Main Voltage L2-L3
3P3L
Main U12, U23, U31
Gen U31
Main Voltage L3-L1
1PAP
Main U1, U2, U3
Gen U31
Main frequency

Reminder:
Mains sensing is 3 phases.
Generator sensing is single phase. Generator Voltage L3-L1

Generator Frequency

Loss of Mains validation Timer

Delay on transfer Timer

Mains return validation timer

Run on timer (Generator cool down period)

Dead Band timer

Main -> Gen commutation Counter

LIP = option
Lightning protection operation (0 or 1)

54
BASIC PRODUCT USE (continued)
MANUAL MODE
To access Manual Mode turn the front
keyswitch to manual position.
Do not force the product
Manual operation
Take the handle, attached to the chain, from Position 1 turn clockwise to
on the right side of the enclosure, to reach position 0
manually operate the switch. from position 0 turn clockwise to
Verify the switch position on the front reach position 2

ENGLISH
position label before any manual from position 2 turn anti clockwise
operation. to reach position 0
from position 0 turn anti clockwise
to reach position 1

Padlocking
Do not leave the manual Padlock is only possible in manual
handle in automatic mode. position.
handle must be out of its housing to
padlock
padlock is possible in position 0, 1, 2.
Manually pull the padlock handle to
allow padlock insertion in the hole.

Manual mode operation


Once in manual mode it is possible:
To access programming and
visualisation menus
To padlock the switch
To operate the switch with the handle
To start the Gen using test off load
pushbutton.

MANUAL MODE

Handle Start Generator


Programming Visualisation Padlocking
Operation (Test off Load)

55
BASIC PRODUCT USE (continued)
AUTOMATIC MODE
Turn the keyswitch from Manual to The unit integrates a power capacitor
Automatic position. source to provide enough power during
The automatic mode must be activated black out (loss of mains) to wait for gen-
as soon as automatic starting of the erator starting. (It does not have power to
generator and source switching is drive the switch to zero position). Further
required after loss of mains condition. external protection will be required if
phasing is a concern.

Possible actions
Once in automatic mode it is possible:
To access programming and visuali-
sation menus
To start off load or on load testing
To start a loss of Mains sequence
To start a Mains return sequence

AUTO MODE

Off load On load Loss of Mains Mains Return


Programming Visualisation
testing testing sequence sequence

Manual-automatic mode/power return condition

As soon as the unit is switched from The same table is considered after a
Manual to Automatic mode, the auto- complete power off action (Power
matic cycle is started. Cap must be completely discharged
Mains and Generator voltage & = 3 minutes).
Read timers definition for 1MT or 2MT frequency are verified to define the
understanding. new stable position of the switch.

New stable switch position:

Original switch position Status of supply New position


Mains Available, genset available or unavailable Mains
Mains Mains unavailable for 2MT time period, Genset. If genset unavailable start
genset available or unavailable genset first and wait for AT timer
period before transfer
Genset Genset on load, mains unavailable Genset
Genset Genset on load, mains available Mains
for 1MT time period
Zero Mains available, genset unavailable Genset to count down 1MT before
transfer to Mains
Zero Mains available, genset available Mains
Zero Mains unavailable, genset available Genset
Zero Mains unavailable, genset unavailable No action (because no supply).
When supply becomes available
change to mains or genset

The switch immediately transfers as soon as the keyswitch is turned from


Manual to Automatic mode or as soon as Power comes back.

56
BASIC PRODUCT USE (continued)
LOSS OF MAINS AUTOMATIC SEQUENCE Specific features

This Sequence is started as soon as Remote AT timer Inhibit


the switch is in automatic mode and in It is possible to bypass the At timer
position 1. using the ATI input (closing the contact)
Position 1: when At timer setting is at its maximum
Mains is available value = 60s.
Switch is in position 1 (Mains) Active when At = At Max = 60 s
Generator is on or off (cf programming mode).
When input ATI (terminals 7-8) is high,
At is bypassed.

ENGLISH
Sequence description

Automatic mode

Loss of
mains?
No
Loss of main?

Power Cap Activation


Yes until Genset availability

2MT = 0
Count down 2MT Genset
start up

Main comes back Start Genset


before 2MT ends?

Reset 2MT

Yes
Generator
available?

No No

Yes
Stop gen Mains avaible ?

Yes
ATI = AT
max ?

Reset AT No

No
ATI = 1 ?

Gen fails
Count down AT Yes

AT = 0

Yes No
DBT 0 ?

Transfer 1 >0

Count down DBT

DBT = 0

Transfer 0 >2 Transfer 1 >2

Transfer 1 >2
Go to mains
return automatic
ATI 083 A

sequence

57
BASIC PRODUCT USE (continued)
MAINS RETURN AUTOMATIC SEQUENCE
This sequence is started as soon as the
unit is in automatic mode and in posi-
tion 2.
Position 2:
Mains is not available
Switch is in position 2 (Generator)
Generator is off

Specific features
Retransfer Inhibit Feature Once retransfer from the Generator
Once the Mains is back, it might be to the Mains is ready, RTI feature
preferable not to immediately transfer blocks the retransfer and the RTI led
the load from the generator to the is blinking.
mains. A manual press on the RTI push but-
If Retransfer inhibit feature has been ton is necessary to start retransfer.
enabled in the programming mode,
the RTI led is on (default value).
ATI 084 A GB

RTI Led
RTI pushbutton

58
BASIC PRODUCT USE (continued)
Sequence description

Main not available


Generator running &
Switch in position 2

ENGLISH
Mains
return
No
Mains
return?
Yes

Manual re-transfer No Loss of


Yes
Mains ?

1MT = 0
Count down 1MT

Mains lost again


before 1MT RTI Yes
times out? activated?

Reset 1MT

No Yes No
RTI PB
pressed ?

DBT 0?
Yes
No

Transfer 2 >0

Count Down DBT

DBT = 0

Transfer 0 >1 Transfer 2 >1

To loss of Reset ROT Count Down


mains sequence
ROT
Loss of mains
Transfer 2 >1
ROT = 0
ATI 085 A GB

Stop generator
position 1
Back to mains control

59
BASIC PRODUCT USE (continued)
Test Mode

TEST MODE ACCES


Press and hold the test pushbutton for
5 seconds to allow test modes access.
Enter code = 4000

Press during 5 sec

Press 4 times to display 4

Validate
ATI 086 A

TEST MODE EXIT


Press and hold the test pushbutton for
5 seconds to exit test mode and come
back to visualisation mode after test TEST
achievement.

60
BASIC PRODUCT USE (continued)
OFF LOAD TESTING
This test is possible in automatic in
position 1 when the mains is avai-
lable or in manual mode. It can be
considered as a Generator manual
start in manual mode.

Description
This mode allows generator testing This test is possible in automatic or
without load transfer from the Mains manual mode

ENGLISH
to the Generator. This test is not possible when an
The generator is started and stopped automatic sequence is running.
normally

Sequence
Press Test pushbutton to make test off
load Led blink and press validation
pushbutton to start.

Press Test Push button

TEST
Press Test Push button
5 seconds to exit

TEST

No
Test off Load
Led blinks ?

Yes

Validate

Start Gen

No
Gen ?

Yes
Validate

No
Stop G ?
ATI 087 A GB

Validate

61
BASIC PRODUCT USE (continued)
ON LOAD TESTING
Keypad activation
This test is only possible in automa-
tic mode in position 1 and Mains
available.

Description :
This test simulates a loss of mains
condition. Loss of Mains sequence is
started and Mains return sequence
automatically activated as soon as
generator is available.
All timers are run following their set-
ting.
The retransfer inhibit feature is
always activated during test on load
(from keypad).
Press Test pushbutton to make test
on load Led blinking and press vali-
dation pushbutton to start the cycle,
Following Loss of Mains + Mains
return sequences.
Remote activation via remote test
on load input
It is possible to remotely start the test
on load closing contacts 7 and 9 on
the electronic module.
The cycle is started as soon as the
input is closed.
The retransfer from generator to mains
is blocked, and only allowed once the
input is de activated.

62
METERING PRODUCT USE
GENERAL INTRODUCTION
Verify power applied on the The product provides sources availability The product requires at least one type of
monitoring, Automatic/Manual Retransfer, network configuration and a network nominal
electronic module power inputs Manual / Automatic or Test operation voltage configuration to be input via the
terminals 101-102 or 201-202 monitoring, voltage and frequency metering, keypad by the user.
before powering up the unit. and good operation or error information. The Other default values can be kept or modified
product provides sources error information. according to hereafter programming guide-
Furthermore, the metering module allows lines.
current and power metering on a large back-
lited display.

ENGLISH
ELECTRONIC MODULE USAGE
Front Panel Introduction
The electronic module is directly mounted Following diagram introduces product
on the motorized block. front panel.
ATI 067 A

It integrates the following features: Led indication is only active once the
- Voltage and frequency metering product is powered (power led
- Automatic transfer controls activated).
LCD Keypad Error Led
Larger LCD to display information. 1 red led to indicate a fault
- Led is on = switch error
Action from software not confirmed by an auxiliary
contact. Reset after power off
- Led blinks in case of lightning protection operation
Modes annunciation and Tests
No reset required (blinking disappears once input is low)
1 Top yellow led for Manual Mode position linked
to the key position
1 green led for Automatic Mode position linked
to the key position
2 Bottom yellows leds for Test On and
Off Load position Linked to the test pushbutton press
Symbols are represented to make comprehension easier

Source availability
2 green Leds to indicate if
Gen and Mains sources are available
(voltage and frequency measurement)
- Led is on = source available
- Led is off = source missing

Power Led
1 green led
- Blinks slowly as soon
Switch state as the product is powered
2 green Leds to indicate if and software runs correctly
the switch is opened or closed - Always on = Power OK and
- Led is on = switch is closed software error
- Led is off = switch is opened - Always off = Power off or
1 Yellow led to indicate if both software error if another
switches are in 0 position led is on and LCD is OK
- Led is on = both switches opened
- Led is off = Gen or Mains
switch closed

Retransfer Inhibit
1 yellow Led, linked to
retransfer inhibit pushbutton
Push button - Led is on = retransfer
inhibit feature is active
: Home push button during programming - Led is off = retransfer
inhibit inactive
: Lamps test button - Led is blinking = retransfer
is blocked, waiting for a push
on the retransfer inhibit
pushbutton to allow retransfer

Switch Position Indications


0, 1 or 2 position display
Keyswitch
Insert key to allow switch
operational mode modification
Turn right to access automatic mode
Turn left to access manual mode

Manual Operation
Insert handle to manually Padlock
operate the switch. Pull the yellow handle to allow padlock insertion
Manual operation only possible Padlocking possible in position 0,1 or 2
ATI 068 B

in Manual mode (keyswitch), but only in Manual mode (keyswitch position),


when not padlocked handle out of housing.

63
METERING PRODUCT USE (continued)
Software version

ATI 069 B
Software version is displayed on the
unit after reset (powering up action after
3 minutes power off to discharge the

{
{
Version Number
unit).

Product Programming
Before first product use,
access programming mode Product Programming is possible in It is not accessible when a test or an
Automatic Mode in position 1 when the automatic sequence is activated.
and verify product Mains Source is available, or in Manual
programming parameters. mode.

PROGRAMMING ACCESS
Programming mode is accessible by
pressing and holding the validation push-
button for 5 seconds and then entering
the code 1000:

Press for 5 seconds

Press once to display 1

Validate
ATI 070 B

Access to programming Menus

PROGRAMMING EXIT
To exit the Programming and come
back to visualisation mode, hold the
validation pushbutton for 5 seconds.
Parameters saved permanently
once exit.

64
METERING PRODUCT USE (continued)
PROGRAMMING MENUS
Architecture and navigation
The programming mode integrates 5 Menus

Setup : Network parameters


Voltage levels : Voltage detection levels
Default values are Fr eq. levels: Frequency detection levels
loaded as standard. tim ers: Automatic timer settings
Communication : Communication parameters (Optional), communication

ENGLISH
module must be plugged.

Setup parameters must always be verified/modified in accordance to the


application.

Option
ATI 071 B

The first menu to access is the Setup menu


ATI 072 B

65
METERING PRODUCT USE (continued)
SETUP MENU
Parameter Display
The setup menu integrates 6 parame-
ters described in the table hereunder.
The table explains parameters definition,
settings possibilities, and default values.

Press Down push button to access parameter required.

Press Up push button to come back to previous value, or press

or Home push button to come back to

Definition Setting range Default value


NOM.VOLT : Phase-Phase From 200 to 480 V 400 V AC
nominal voltage.

NETWORK : Network configuration. 1P2L, 1P3L, 3P4L 3P4L


Type of metering (1P or 3P 3P3L, 1PAP
phases).
Number of active wires (2L,
3L or 4L)
definition.

NOM.FREQ : Nominal frequency. 50 or 60 Hz 50 Hz

CT : winding ratio of current transformers 50 / 5 to 1600 / 5 500 / 5


50/5 to 1600/5

TRANS IHI : Retransfer inhibit feature: Yes or No No


press on RTI button
required to allow retransfer
from gen to main.

CNT RST : Reset number of commuta- Yes or No No


tion counter (from Main to
Gen).
ATI 073 C

Displays no once reset.

66
METERING PRODUCT USE (continued)
Parameter modification

Display the required parameter for settings are described in the previous
modification. table.
Apply the same procedure described Example:
hereunder for network voltage modifica- We want to modify network voltage
tion, to all other parameters. Possible from 400 V to 230 V.

ENGLISH
Press to access the first digit (blinking)

Press twice to display 2 (blinking)

Press to access the second digit (blinking)

Press 3 times to display 3 (blinking)

Press to validate the value


ATI 074 B

To return to Setup menu press home pushbutton or press down to continue.

Press to return to Setup menu Press to reach next parameter


ATI 076 B
ATI 075 B

67
METERING PRODUCT USE (continued)
VOLTAGE MENU

To reach voltage menu from Setup menu press once .

Parameter Display
The voltage menu integrates 8 parame- Generator sensing single phase.
ters described in the table hereunder. Over and under voltage detection lev-
The table explains parameters defini- els + hysteresis are defined as per-
tion, settings possibilities, and default centage of nominal voltage.
values. Hysteresis levels allow under and over
Over and Under voltage conditions are voltage conditions reset (voltage needs
verified on Mains and Generator side to to pass hysteresis level to reset).
allow operation as per the flow chart.
Mains sensing is 3 phase and
Note:
These values only need to be Press Down push button to access parameter required.
changed if a value is required other
than the default.
Press Up push button to come back to previous value

or Home push button to come back to

Definition Setting range Default value

OV U : Main Over voltage detection 102 - 120 % 115 %

OV U HYS : Main Over voltage hysteresis 101 - 119 % 110 %


detection

UND.U : Main Under voltage detection 80 - 98 % 85 %

UND.U HYS : Main Under voltage hys- 81 - 99 % 95 %


teresis detection

OV U : Generator over voltage detection 102 - 120 % 115 %

OV U HYS : Generator over voltage 101 - 119 % 110 %


hysteresis detection

UND.U : Generator under voltage 80 - 98 % 85 %


detection

UND.U HYS : Generator under voltage 81 - 99 % 95 %


hysteresis detection
ATI 077 B

68
METERING PRODUCT USE (continued)
Parameter modification

Display the required parameter for dification. Possible settings are described
modification. in the previous table.
Apply the same procedure as described
in Setup Menu for network voltage mo-

FREQUENCY MENU

To reach frequency menu from voltage menu press once .

ENGLISH
Parameter Display

The frequency menu integrates 8 parameters described in the table hereunder.


The table explains parameters definition, Over and under frequency detection levels
settings possibilities, and default values. + hysterisis are defined as percentage of
Over and Under frequency conditions are nominal frequency.
verified on Mains and Generator side to Hysteresis levels allow under and over
allow operation following operational flow frequency conditions reset (frequency
chart. needs to pass hysteresis level to reset).

Press Down push button to access parameter required.

Press Up push button to come back to previous value

or Home push button to come back to


.

Definition Setting range Default value

OV F: Main over frequency detection 101 - 120 % 105 %

OV F HYS : Main over frequency 100.5 - 119.5 % 103 %


hysteresis

UND.F: Main under frequency 80 - 99 % 95 %

UND.F HYS: Main Under frequency 80.5 - 99.5 % 97 %


hysteresis

OV F : Generetor over frequency 101 - 120 % 105 %

OV F HYS : Generator over frequency 100.5 - 119.5 % 103 %


hysteresis

UND.F: Generator under frequency 80.5 - 99.5 % 95 %

UND.F HYS: Generator under frequency 80 - 99 % 97 %


hysteresis
ATI 078 B

69
METERING PRODUCT USE (continued)
Parameter modification

Display the required parameter for modification. Possible settings are


modification. described in the previous table.
Apply the same procedure as described
in the Setup Menu for network voltage

TIMERS MENU
To reach timer menu from frequency menu press once .

Parameter Display

The timers menu integrates 5 para- The table explains parameters definition,
meters described in the table settings possibilities, and default values.
below. Timers operation is described in opera-
tional flow chart page.

Press Down push button to access parameter required.

Press Up push button to come back to previous value

or Home push button to come back to


.

Definition Setting range Default value


2Mt: loss of mains validation timer. 0 to 60 sec. 5 sec.
Once mains has disappeared,
2Mt is started. If Mains comes
back before 2Mt ends,
the commutation cycle is not
started. (Delay on Gen start.)

At: Generator voltage and frequency 0 to 60 sec. 5 sec.


stabilisation timer. Generator
needs to be stable during AT
to allow transfer from Mains.

1Mt: Mains Return validation timer. 0 to 30 min. 2 min.


Once main is back 1Mt is
started. If Mains disappears
before 1Mt ends, the load is
not switched back to the Mains.

dbt: Dead Band timer. This timer is 0 to 20 sec. 5 sec.


counted down before transferring
the load from the Mains source
to the Generator or vice versa.
It allows the load residual voltage
to decrease under a non critical
value before transfer (Necessary
in case of rotating loads).

rot: Run on time timer. Once the 0 to 10 min. 4 min.


load is switched back from the
Generator to the Mains, ROT is
started and the Generator
ATI 079 B

will stop once ROT is finished


(allows generator cool down).

70
METERING PRODUCT USE (continued)
Parameter modification

Display the required parameter for modification. Possible settings are


modification. described in the previous table.
Apply the same procedure as described
in the Setup Menu for network voltage

COMMUNICATION MENU (OPTIONAL)


This menu is only
To reach timer menu from frequency menu press once .
accessible when the option
has been purchased and is

ENGLISH
Parameter Display
present in the optional slots.
Once plugged into the elec- The COMM menu integrates 4 Communication operation is described in
tronic module, a 3 minutes parameters described in the table paragraph 5.
hereunder.
power off action is required
The table explains parameters definition,
for option identification by settings possibilities, and default values.
software.

Press Down push button to access parameter required.

Press Up push button to come back to previous value

or Home push button to come back to


.

Definition Setting range Default value

Slave Jbus / Modbus adress 001 to 247 005

Communication Speed 2 400,4 800,9 600,


(baud) 14 400,19 200,
28 800, 38 400 9600

Stop Bit 0,1,2 1

Parity No, Eve (Even), No


Odd
ATI 080 B

71
METERING PRODUCT USE (continued)
PRODUCT METERING

General comments
Metering is active as soon as the unit is After commutation cycle, the display
powered. comes back to Mains voltage L1N (first
Commutation cycles have priority over variable of the mode).
Visualisation mode and display timers Visualisation mode architecture is as
count down as soon as they are active. described hereunder.
Any value available in this mode can
be kept on the screen once displayed.
excepted during commutation cycle;
comes back to timer count down after
5 s.

If lightning protection
General comments
option is fitted, L.PROTECT
menu is available. cf option 4.
To access requested value press , , or .

Option
ATI 081 B

72
METERING PRODUCT USE (continued)
Values definition

All these values are not Main Voltage L1-N, L2-N, L3-N
accessible on all networks :
Main Voltage L1-L2, L2-L3, L3-L1
3P4L
Main U1, U2, U3
U12, U23, U31 Main frequency
Gen U1, U2, U3, U12, U23, U31

ENGLISH
1P3L
Main U12, U23, U31 Generator Voltage L1-N, L2-N, L3-N
Gen U12, U23, U31

1P2L Generator Voltage L1-L2, L2-L3, L3-L1


Main U31
Gen U31

3P3L Generator Frequency


Main U12, U23, U31
Gen U12, U23, U31
Current I1, I2, I3
1PAP
Main U1, U2, U3
Gen U1, U2, U3
Current in the neutral

Mains and Generator sensing are


3 phases. Loss of Mains validation Timer

Delay on transfer Timer

Mains return validation timer

Dead Band timer

Run on timer (Generator cool down period)

Main -> Gen commutation Counter

Power factor (over all)

Total active power on 4 quadrants (+/-)

Total reactive power on 4 quadrants (+/-)

Total apparent power


LIGHTNING
PROTECTION
= option Lightning protection operation (0 or 1)

73
METERING PRODUCT USE (continued)
MANUAL MODE
The functionality is similar to the basic
product (see the manual mode of the
basic product paragraph).

MAINS RETURN AUTOMATIC SEQUENCE


This sequence is started as soon as the
unit is in automatic mode and in posi-
tion 2.
Position 2:
Mains is not available
Switch is in position 2 (Generator)
Generator is off

Specific features
Retransfer Inhibit Feature Once retransfer from the Generator
Once the Mains is back, it might be to the Mains is ready, RTI feature
preferable not to immediately transfer blocks the retransfer and the RTI led
the load from the generator to the is blinking.
mains. A manual press on the RTI push but-
If Retransfer inhibit feature has been ton is necessary to start retransfer.
enabled in the programming mode,
the RTI led is on (default value).
ATI 084 B GB

RTI Led
RTI pushbutton

The sequence is similar to the basic


product.

74
METERING PRODUCT USE (continued)
Test Mode

TEST MODE ACCES


Press and hold the test pushbutton for
5 seconds to allow test modes access.
Enter code = 4000

ENGLISH
Press during 5 sec

Press 4 times to display 4

Validate
ATI 086 B

TEST MODE EXIT


Press and hold the test pushbutton for
5 seconds to exit test mode and come
back to visualisation mode after test TEST
achievement.

Test on load and test off load facilities


are similar to the basic product.

75
COMMUNICATION
The JBUS/MODBUS used by the ATI The mode of communication is the
involves a dialogue using a master- RTU (Remote Terminal Unit) using
slave hierarchical structure. There are hexadecimal characters of at least 8
two possible dialogues: bits.
the master communicates with a
slave (ATI) and waits for its reply
the master communicates with all the
slaves (ATI) without waiting for their
reply.

The standard communications frame


consists of :

Slave address Function code Address Data CRC 16

NB: According to the JBUS / MODBUS To correctly use information, the


When selecting slave address 0, a protocol, transmission time must be following functions are important:
message is sent to all the instruments less than 3 silences, i.e. the emission 3 : to read n words (maximum 128).
present on the network (only for func- time of 3 characters so that the mes- 6 : to write one word.
tions 6 and 16). sage is processed by the ATI. 8 : to diagnose exchanges between
the master and the slave via
meters 1, 3, 4, 5 and 6.
Comment: 16 : to write n words (maximum 128).
The maximum reply time is 250 ms.
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Table of values on 2 words


Decimal Hexa Number
Address Address of words Variable Units
768 300 2 I1 A/100
770 302 2 I2 A/100
772 304 2 I3 A/100
774 306 2 In A/100
776 308 2 U12Main V/100
778 30A 2 U23Main V/100
780 30C 2 U31Main V/100
782 30E 2 V1Main V/100
784 310 2 V2Main V/100
786 312 2 V3Main V/100
788 314 2 Freq.Main Hz/100
790 316 2 Active power (total) kW/100
792 318 2 Reactive power (total) kVar/100
794 31A 2 Apparent power (total) kVA/100
796 31C 2 Power factor 0,001
880 370 2 U12 Gen V/100
882 372 2 U23 Gen V/100
884 374 2 U31Gen V/100
886 376 2 V1Gen V/100
888 378 2 V2Gen V/100
890 37A 2 V3Gen V/100
892 37C 2 FreqGen Hz/100
894 37E 1 1MT V/100
895 37F 1 2MT V/100
896 380 1 AT s
897 381 1 DBT s
898 382 1 ROT s

Example:
To read U31 gen = 228,89, the
following message should be sent:
76
COMMUNICATION (continued)
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) (continued)

High-order Low-order High-order Low-order


Slave Function CRC 16
address address word n word n
05 03 03 74 00 02 85D1

ATI reply:

Number Value Value


Slave Function CRC 16
of bytes high-order low-order

ENGLISH
Hex 05 03 04 59 69 458D
Dec 89 105

Decimal value = 89 x 256 + 105


= 22 889 (/100)

Table of values on 1 word


Decimal Hexa Number
Address Address of words Variable Units
1792 700 1 U12 Main V/100
1793 701 1 U23 Main V/100
1794 702 1 U31 Main V/100
1795 703 1 V1 Main V/100
1796 704 1 V2 Main V/100
1797 705 1 V3 Main V/100
1798 706 1 Freq. Main Hz/100
1799 707 1 U12 Gen V/100
1800 708 1 U23. Gen V/100
1801 709 1 U31 Gen V/100
1802 70A 1 V1. Gen V/100
1803 70B 1 V2. Gen V/100
1804 70C 1 V3. Gen V/100
1805 70D 1 Freq. Gen Hz/100
1806 70E 1 1MT Timer s
1807 70F 1 2MT Timer s
1808 710 1 AT Timer s
1809 711 1 DBT Timer s
1810 712 1 ROT Timer s
1813 715 1 I1 A/100
1814 716 1 I2 A/100
1815 717 1 I3 A/100
1816 718 1 In A/100
1817 719 1 Active power (total) kW
1818 71A 1 Reactive power (total) kVar
1819 71B 1 Apparent power (total) kVA
1820 71C 1 Power factor 0,001

77
COMMUNICATION (continued)
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) (continued)
Table of values of the programming zone
Decimal Hexa Number Standard
Address Address of words Variable Units Product
Type of network - x
0 = 3P4L - 1 = 1P3L
2 = 1P2L - 3 = 3P3L
512 200 1 4 = 1PAP
513 201 1 CT primary A x
518 206 1 VNominal V x
519 207 1 FNominal - 50 or 60 Hz x
0 = No, 1 = Yes
521 209 1 Transfer Inhibit Feature x
522 20A 1 VOver % (0-100) x
523 20B 1 VHystOver % (0-100) x
524 20C 1 VUnder % (0-100) x
525 20D 1 VHystUnder % (0-100) x
526 20E 1 VGenOver % (0-100) x
527 20F 1 VHystGenOver % (0-100) x
528 210 1 VGenUnder % (0-100) x
529 211 1 VHystGenUnder % (0-100) x
530 212 1 FOver % (0-100) x
531 213 1 FHystOver % (0-100) x
532 214 1 FUnder % (0-100) x
533 215 1 FHystUnder % (0-100) x
534 216 1 FGenOver % (0-100) x
535 217 1 FHystGenOver % (0-100) x
536 218 1 FGenUnder % (0-100) x
537 219 1 FHystGenUnder % (0-100) x
538 21A 1 1MT Timer min x
539 21B 1 2 MT Timer s x
540 21C 1 AT Timer s x
541 21D 1 DBT Timer s x
542 21E 1 ROT Timer min x

Example:
Configuration of 233 V nominal
voltage for ATI n 5.

High-order Low-order High-order Low-order


Slave Function N word N octet CRC 16
address address word n word n
Hex 05 10 02 06 00 01 02 00 E9 76B8
Dec 16 233

ATI reply:

High-order Low-order
Slave Function N word CRC 16
address address
05 10 02 06 00 01 E1F4
89 105

78
COMMUNICATION (continued)
SAVED COMMAND (RESET)

The following command should be


done to save programming parame-
ters changes for ATI number 5.

NB: High-order Low-order


ATI will not reply Slave Function Values CRC 16
address address
to this command.

ENGLISH
05 06 06 00 0000 88C6

Diagnostic zone
Decimal Hexa Number Variable
Address Address of words
257 101 1 Product Identification Standard version 1239
Metering version 1241
258 102 1 Slot Ident Option 1 available option
0 communication option
Option of slot 1
0xFF no option
0x20 Main/Gen
259 103 1 Slot Ident Option 2 available option
0 communication option
Option of slot 2
0xFF no option
0x20 Main/Gen
260 104 2 Reserved
262 106 1 Version soft version of product
263 107 2 Serial number serial number
265 109 17 Reserved
278 116 1 Motor Mode 3 stable states
Bit3 Bit2 Bit1 Bit0
1 0 1 0 Auto
1 0 0 1 Padlock
0 1 1 0 Manu
282 11A 1 Switch State 3 stable states
Bit2 Bit1 Bit0
0 0 1 Position 1
0 1 0 Position 0
1 0 0 Position 2
283 11B 2 Reserved
285 11D 1 CounterMainGen Counter number of transfer
286 11E 1 Gen relay state 2 stable states
Bit1 Bit0
1 0 relay stopped
0 1 relay started

79
MAINTENANCE
N H

G1

G2

I
J

E K

C
A
B

63/100/125A 250/400A 630A

Front cover
A BB TT
H = 576 H = 876 H = 876 H = 576
H

L = 396 L = 596 L = 596 L = 396

L
Ref : 610-832 (BB)
Ref : 610-831( BB / TT) Ref : 610-833 (TT) Ref : 610-832 Ref : 610-834

Enclosure BB TT
B P

H = 600 H = 900 H = 900 H = 1400


H

L = 400 L = 600 L = 600 L = 600

P = 230 P = 305 P = 380 P = 380


L
Ref : 610-825 (BB) Ref : 610-826 (BB)
Ref : 610-828 (TT) Ref : 610-829 (TT) Ref : 610-827 Ref : 610-830

Cable gland Plate


C
Pp Lp = 276 Lp = 495 Lp = 495
Lp

Pp = 128 Pp = 245 Pp = 328

Ref : 590-950 Ref : 590-951 Ref : 590-953


Wall Mounting
D Brackets

Ref : 530-956

Manual changeover
E H = 135 H = 160 H = 260

L = 231 L = 292 L = 359

P = 148 P = 148 P = 225


H

L Ref : 604-670 (63A)


P
ATI 088 A GB

Ref : 604-671 (100A) Ref : 604-673 (250A)


Ref : 604-672 (125A) Ref : 604-674 (400A) Ref : 604-675 (630A)

80
MAINTENANCE (continued)
63/100/125A 250/400A 630A
Ref : 603-412 Ref : 603-413 (250A) Ref : 603-415
Bridging Bar Kit
F Ref : 603-414 (400A)

ATI Electronic 230V G1 : Ref : 650-881 G1 : Ref : 650-881 G1 : Ref : 650-881


G1 Module Version (basic product) (basic product) (basic product)
Ref : 650-883 Ref : 650-883 Ref : 650-883
l (metering product) (metering product) (metering product)
P
G2 : Ref : 601-700 (63A) G2 : Ref : 601-703 (250A) G2 : Ref : 601-705
Ref : 601-701 (100A) Ref : 601-704 (400A)

ENGLISH
Ref : 601-702 (125A)
H

277V G1 : Ref : 650-882 G1 : Ref : 650-882 G1 : Ref : 650-882


G2 Version (basic product) (basic product) (basic product)
Motorized Ref : 650-884 Ref : 650-884 Ref : 650-884
L
Module (metering product) (metering product) (metering product)
G2 : Ref : 601-736 (63A) G2 : Ref : 601-739 (250A) G2 : Ref : 601-741
Ref : 601-737 (100A) Ref : 601-740 (400A)
Ref : 601-738 (125A)
H = 180 P = 250
L = 200 l = 145
Load Bar Kit Ref : 330-168 Ref : 330-169
H
x1
x3

I Ref : 656-931
ATI Connectors Kit /
ATI Voltage Sensing Kit

Ref : 656-933 (250A)


Ref : 656-932 Ref : 656-934 (400A) Ref : 656-935

J Terminal Shroud
Pc
Hc = 300 Hc = 460 Hc = 640

Lc = 177 Lc = 277 Lc = 307


Hc

Pc = 176 Pc = 247 Pc = 315


Rc

Rc = 47 Rc = 57 Rc = 57

Lc
Ref : 603-408 (BB) Ref : 603-409 (BB) Ref : 603-411 (BB)
Ref : 603-417 (TT) Ref : 603-418 (TT) Ref : 603-419 (TT)

K Handle with Chain

Ref : 604-668 Ref : 604-669

Manual/auto Key x2
L
Ref : 531-273

Leg Kit 630A


M x4
Ref : 509-310
Ref : 530-195 Ref : 530-196
Weather proof strip
N (for IP 41)
Ref : 641-384 (63A) Ref : 641-387 (250A) Ref : 641-389 (630A)
Current transformer
O 641-385 (100A) 641-388 (400A)
641-386 (125A)

81
MAINTENANCE (continued)
N H

G1

G2

I
J

E K

C
A
B

800/1000A 1250 / 1600A

Front cover
A
H = 1150 H = 1580
H

L = 990
L = 771

Ref : 610-846 (BB / TT) Ref : 610-847( BB / TT)

Enclosure
B P

H = 1175 H = 1600
H

L = 775 L = 1000
P = 596
P = 775
L
Ref : 610-844 (BB / TT) Ref : 610-845 ( BB / TT)

Cable gland Plate Top Plate Bottom Plate


C
Pp Lp = 536 Lp = 1000 Lp = 916
Lp
Pp = 717
Pp = 480 Pp = 800

Ref : 590-957 Ref : 590-958 Ref : 590-961


Wall Mounting
D Brackets

Manual changeover
E 800A 1000A
H = 321 H = 330 H = 1000

L = 466 L = 466 L = 716


H

L P = 327 P = 327 P = 392


P
Ref : 604-683 (800A) Ref : 604-685 (1250A)
Ref : 604-684 (1000A) Ref : 604-686 (1600A)

82
MAINTENANCE (continued)
800/1000A 1250 / 1600A
Ref : 603-432 (800A)
Bridging Bar Kit
F Ref : 603-433 (1000A)

ATI Electronic 230V G1 : Ref : 650-881 G1 : Ref : 650-881


G1 Module Version (basic product) (basic product)
Ref : 650-883 Ref : 650-883
l (metering product) (metering product)
P
G2 : Ref : 601-732 (800A) G2 : Ref : 601-734 (1250A)

ENGLISH
Ref : 601-733 (1000A) Ref : 601-735 (1600A)

H
277V G1 : Ref : 650-882 G1 : Ref : 650-882
G2 Version (basic product) (basic product)
Motorized Ref : 650-884 Ref : 650-884
L
(metering product) (metering product)
Module
G2 : Ref : 601-742 (800A) G2 : Ref : 601-744 (1250A)
Ref : 601-743 (1000A) Ref : 601-745 (1600A)

H = 270 P = 250 H = 270 P = 250


L = 260 l = 145 L = 260 l = 145
Load Bar Kit Ref : 330-170 Ref : 330-171 (1250A)
H Ref : 330-172 (1600A)

x1
x3

I Ref : 656-931

ATI Connectors Kit /


ATI Voltage Sensing Kit

Ref : 656-943 Ref : 656-944

J Terminal Shroud 160


5
Pc 165 29 510 338
360
308

940
345
Hc

Rc
200

Lc

Ref : 603-430 (TT / BB) Ref : 603-431 (TT / BB)

K Handle with Chain

Ref : 604-682

Manual/auto Key x2
L
Ref : 531-273

Leg Kit 630A


M x4 x2

Ref : 509-310 Ref : 509-314


Ref : 530-197
Weather proof strip
N (for IP 41)
Ref : 641-390 (800A) Ref : 641-392 (1250A)
Current transformer
O 641-391 (1000A) 641-393 (1600A)

83
FAULT FINDING GUIDE
STATUS ACTION
Unit is inoperative Check that there is a 230V 20 %* AC supply on the
mains or gen power supply terminals (101,102 for mains
& 201, 202 for gen).
* or 277V 20 %

Mains LED is never Check Lamp Test.


available when it is Make sure correct nominal voltage, network
configuration & frequency has been set.
Check under / over, voltage / frequency, parameters.

Switch does not transfer Check key switch is in Auto mode (AUT).
when mains fail Check two wire start signal to gens autostart control
panel.

Gen starts but Gen Check Lamp Test.


available LED is still off Make sure genset has the same nominal voltage, network
configuration & frequency as the mains.
Check under / over voltage / frequency parameters.

Mains restores but switch Check that mains restoration timer is not too long.
does not retransfer Check key switch is in Auto mode (AUT).
Check mains voltage is within restoration limits.
Verify if manual retransfer has been disabled.

Switch retransfers ok when


mains restores, but gen Check that the ROT timer is not at a long setting.
keeps on running Check the start signal contact on the module.

Switch will not transfer Check key switch is in manual position.


with the handle Check that the switch has not been padlocked.
Check the required rotation of the switch.
Check that sufficient torque has been applied to the
handle.

Key Switch will not go Check that handle has been removed from the
into Auto mode shaft.
Check that the switch has not been padlocked.
Check that the correct key is used.

Test on load or off load


cant be started Verify password entered is 4 000.

The Unit is faulty Verify if the Lightning protection did not operate.
Replace the fuses or the lightning protection module if
damaged.
Power off the unit by removing power on power terminals
101, 102 & 201, 202 during three minutes and power up
again.

84
85
ENGLISH
277-639 ATI Panel - Phase 3

Potrebbero piacerti anche