THIS SPECIFICATION SECTION RELATES TO STRUCTURAL ELEMENTS AND SHALL BE EDITED ONLY BY
THE STRUCTURAL ENGINEER OF RECORD FOR THE SPECIFIC PROJECT.
PART 1 - GENERAL
1.01 DESCRIPTION:
A. Provide hydrophilic rubber gasket and paste waterstops as indicated and specified.
1.03 REFERENCES:
(NTS: Select the appropriate references to be included in the project. Add or edit
references as appropriate. Delete those references that are not applicable.)
A. American Society for Testing and Materials (ASTM) Publications:
C. Equivalent British/European codes and standards may be used; however, the equivalency
shall be demonstrated and submitted by the Contractor and approved by the CM/CS.
1.04 SUBMITTALS:
1. Manufacturer's printed data and literature for all specified materials and locations
where materials are to be used.
(NTS: Use the following paragraph on projects where joints are used in structures to
contain potable water.)
B. ANSI/NSF 61 certification that joint materials proposed for use in structures to contain
potable water are non-toxic and have no adverse effect on the quality or appearance of
potable water.
B. Reject and replace waterstops which have become wet or exhibit swelling prior to
concrete placement.
F. Waterstops shall be positioned to provide a minimum of 3" [75 mm] concrete cover.
B. Transport, handle and deliver materials to the job site in the manufacturer's sealed bags,
unopened containers or banded pallets.
C. Store materials off the ground on a platform or skids and protect with covers from snow,
rain and ground splatter.
D. Store hydrophilic waterstops under cover in a dry cool location, out of direct sunlight.
Waterstops shall be maintained in a dry condition until concrete placement.
PART 2 - PRODUCTS
B. Waterstops shall be of solid construction and 3/8" x 3/4" [10 mm x 20 mm] minimum in
cross section.
E. Provide hydrophilic gasket waterstops which meet the criteria in Table 03256-1.
TABLE 03256-1
Property Test Method Limit
Ultimate Elongation ASTM D 638 70% minimum
Tensile Strength ASTM D 638 25 psi [170 kPa] minimum
Ozone Resistance ASTM D 1149 No Failure
Volatile Loss ASTM D 1203 0.50% maximum
Hardness, Shore A ASTM D 2240 20 to 60
4. or equal.
A. Provide hydrophilic rubber paste waterstops of urethane paste, thixotropic vinyl monomer
or similar materials.
D. Provide hydrophilic paste waterstops which meet or exceed the criteria in Table 03256-2.
TABLE 03256-2
Property Test Method Limit
Ultimate Elongation ASTM D 638 50% minimum
Tensile Strength ASTM D 638 25 psi [170 kPa] minimum
Ozone Resistance ASTM D 1149 No Failure
Volatile Loss ASTM D 1203 0.50% maximum
Hardness, Shore A ASTM D 2240 20 to 60
PART 3 - EXECUTION
3.01 INSTALLATION:
A. Provide hydrophilic rubber gasket and paste waterstops where specifically indicated.
D. Clean joint surface of dirt, dust, debris and laitence immediately before applying waterstop
and remove standing water.
E. Protect waterstops from moisture until concrete is placed. Waterstops which exhibit
swelling prior to concrete placement shall be removed and replaced at the contractor's
expense.
B. Seal joints in hydrophilic gasket waterstops with a hydrophilic rubber paste compound as
recommended by the manufacturer.
C. Do not bend hydrophilic gasket waterstop. Cut square and butt joints at corners.
E. Attach hydrophilic gasket waterstop to concrete surface by one of the following methods:
F. Provide one fastener one inch from the top and a second fastener four inches from the top
of vertical hydrophilic gasket waterstops regardless of which fastening method is used.
H. Do not wrap hydrophilic gasket waterstops around pipes less than the minimum diameter
recommended in the manufacturer's printed instructions.
A. Clean dirt and debris from area to receive hydrophilic paste waterstop.
C. Apply hydrophilic paste waterstop such that there is no break in the bead.
D. Place hydrophilic paste waterstop bead continuously around pipe near the center of the
wall where used for sealing pipe penetrations. Allow hydrophilic paste waterstop to cure
for 24 hours before placing concrete.
END OF SECTION