Sei sulla pagina 1di 1

is sensed by thermistor RT, which is part of the bridge R3

circuit consisting of R4, R5, R6, R7, D2 and RT. The detec- 47 C2
tor for the bridge is transistor 02. R7 is set so the bridge O.l/LF
is in balance at the desired temperature. As the temper-
ature increases, RT decreases, 02 turns on and provides Q12N5569
gate drive to SCR 03. 03 turns on and shunts the gate
Sl
signal away from the TRIAC 04.04 shuts off and removes
power to the load. Now, as the temperature drops, RT
increases and 02 turns off, SCR 03 turns off, and full- 115 V RELAY WITH PICK Rl
wave power is applied to the load. Normally, the circuit 115VAC UP AND DROPOUT TIMES 1.5 k


would continue to cycle randomly, providing groups of 60 Hz OF 10-20 ms lOW
full power to the heater load. However, modulation is
applied to proportion the load power in response to small DllN4004 R2
changes in RT. The modulation is achieved by super- 10
imposing a sawtooth voltage on one arm of the bridge lOW
Cl +
through R3. The period of the sawtooth is set to equal
12 cycles of the line frequency. From one to all 12 cycles 20/LF
can be applied to the load, thus allowing the load power 250 V
to modulate in 8% steps from 0% to 100% duty cycle. The
sawtooth voltage is generated by the unijunction tran-
sistor relaxation oscillator consisting of R2, R3, R4, C2 Figure 6.107. TRIAC Prevents Relay Contact Arcing
and 01. The sawtooth wave modulates the bridge voltage
so that over a portion ofthe twelve-cycle group the bridge
voltage will be above the null point, and over the other
portion it will be below the null point. This action divides current through Rl. The maximum time that could elapse
each twelve-cycle group into an on portion and an off before the TRIAC turns on is 8-1/3 ms for the 60 Hz supply.
portion, the proportioning depending upon the amount This is adequate to ensure that the TRIAC will be on
RT has varied from the nominal value. This circuit pro- before the relay contact closes. During the positive half
vides excellent control of a resistance heater as it will cycle, capacitor Cl is charged through Dl and R2. This
tend to stabilize and apply the correct amount of power stores energy in the capacitor so that it can be used to
on a continuous basis at a steady-state duty cycle keep the TRIAC on after switch Sl has been opened. The
depending on the load requirements. The temperature is time constant of Rl plus R2 and C1 is set so that sufficient
therefore controlled over a very narrow range and no gate current is present at the time of relay drop-out after
EMI is generated. the opening of Sl, to assure that the TRIAC will still be
on. For the relay used, this time is 15 ms. The TRIAC
TRIAC RELAY-CONTACT PROTECTION therefore limits the maximum voltage, across the relay
A common problem in contact switching high current contacts upon dropout to the TRIAC's voltage drop of
is arcing which causes erosion of the contacts. A solution about 1 volt. The TRIAC will conduct until its gate current
to this problem is illustrated in Figure 6.107. This circuit falls below the threshold level, after which it will turn off
can be used to prevent relay contact arcing for loads up when the anode current goes to zero. The TRIAC will
to 50 amperes. conduct for several cycles after the relay contacts open.
There is some delay between the time a relay coil is This circuit not only reduces contact bounce and arcing
energized and the time the contacts close. There is also but also reduces the physical size of the relay. Since the
a delay between the time the coil is de-energized and the relay is not required to interrupt the load current, its rat-
time the contacts open. For the relay used in this circuit ing can be based on two factors: the first is the rms rating
both times are about 15 ms. The TRIAC across the relay of the current-carrying metal, and the second is the con-
contacts will turn on as soon as sufficient gate current is tact area. This means that many well-designed 5 ampere
present to fire it. This occurs after switch Sl is closed but relays can be used in a 50 ampere load circuit. Because
before the relay contacts close. When the contacts close, the size of the relay has been reduced, so will the noise
the load current passes through them, rather than on closing. Another advantage of this circuit is that the
through the TRIAC, even though the TRIAC is receiving life of the relay will be increased since it will not be sub-
gate current. If S1 should be closed during the negative jected to contact burning, welding, etc.
half cycle of the ac line, the TRIAC will not turn on imme- The RC circuit shown across the contact and TRIAC (R3
diately but will wait until the voltage begins to go posi- and C2) is to reduce dvldt if any other switching element
tive, at which time diode Dl conducts providing gate is used in the line.

MOTOROLA THYRISTOR DEVICE DATA


1-6-57

Potrebbero piacerti anche