Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The following example is included to illustrate a structured approach to the recording of results.
Attention is drawn to the following characteristics:
the specification of test equipment;
the requirement to record calibration and corrective actions (step 1) [consistent with
principle 4.2.1 (e)];
the specification of acceptable tolerances (heading panel and step 10);
instructions detailing the action to be taken on discovery of a fault (step 11);
the recording of the test result in the form of a code number allowing future analysis,
reporting and review [consistent with principle 4.5.1 (b)].
60
TRIP & ALARM TESTING
LOOP : (CLASS A)
TEST METHOD
TITLE :
ACTION OF TRIP :
TEST EQUIPMENT :
LOOP NO :
DATE :
1. Ensure that there is a valid PERMIT to WORK for this test. Inform the
Panelman that testing is about to be carried out.
3. One man to remain in the Control Room, the other to carry out the outside
work.
4. Isolate the impulse lines. SLOWLY open the LP vent needle valve to allow
the pressure to fall SLOWLY, the high [process] alarm will be initiated but
continue to allow the pressure to fall until the Extra high [process] trip
annunciator is initiated.
RESULTS
0 PASS 0 RETESTED OK
1 OPERATED EARLY 1 BLOCKAGE 1 INITIATOR 1 NO SPARES
2 OPERATED LATE 2 CALIBRATION ERROR 2 LOGIC 2 NO TIME/LAB
3 DID NOT OPERATE 3 BREAKAGE 3 SOLENOID VALVE 3 NOT KNOWN
4 FOUND DEFEATED 4 S/D MECHANISM 4 NEEDS S/D
5 WET/STUCK 5 DESIGN
9 NOT DONE 9 OTHER 9 OTHER 9 OTHER
INSTRUMENT : ..............................................................
8. When conditions are stable, reset the trip using the Reset button.
9. Ask an authorised person to reset all conditions [1], [2], [3], [4], [5]. Check
that the associated data alarms have returned to normal.
10. Check and record the zero reading of the transmitter at process pressure. If it
is in error by more than 2.5% of full scale, then the test has FAILED.
11. If any part of the system failed to operate correctly or if the reading did not
correspond with the required trip or alarm setting within the prescribed limits
then the test has failed. Check each item of the loop. Repair where necessary
and re-test If extensive repairs have to be carried out, inform the Process
Supervisor.
12. Check that the [process] indication and annunciator(s) have returned to
normal. Ensure that valve(s) [1], [2], [3], [4], [5] have returned to normal.
62
APPENDIX 3.3: EXAMPLE OF PROOF TEST DOCUMENT
CONTROL
The following example is included to illustrate some of the principles of effective document
control.
Attention is drawn to the following characteristics:
reference to company, plant and unit;
unique document reference number [consistent with principle 4.3.1 (b)];
reference to the specific SIS;
revision history [consistent with principle 4.3.1 (b)];
specific reference to risk assessment [consistent with principle 4.7.1 (a)];
multiple approvals [consistent with principle 4.6.1 (c)];
definitions of the meanings of the different approvals [consistent with principle 4.6.1
(b)];
reference to a controlling procedure for the management of controlled documents
[consistent with principle 4.3.1 (b)].
63
Company Plant Unit
Procedure Number:
Document Issue A B C D E
Date
Risk Assessment No.
Document Administrator
(Technology)
Procedure has been risk assessed
and will be filed as master copy
64