Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com
isenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189340687F
14 9614 Fax: +45 9614 9615 info@deif.com www.deif.com SW version: 4.50.x or later
AGC-4 installation instructions 4189340687
UK
1. General information
1.1. Warnings, legal information and safety..................................................................................................4
1.1.1. Warnings and notes ......................................................................................................................4
1.1.2. Legal information and disclaimer ..................................................................................................4
1.1.3. Safety issues ................................................................................................................................4
1.1.4. Electrostatic discharge awareness ...............................................................................................4
1.1.5. Factory settings ............................................................................................................................4
1.2. About the installation instructions...........................................................................................................5
1.2.1. General purpose ...........................................................................................................................5
1.2.2. Intended users ..............................................................................................................................5
1.2.3. Contents and overall structure ......................................................................................................5
3. Mounting
3.1. AGC-4 mounting and dimensions........................................................................................................11
3.1.1. Mounting of the unit.....................................................................................................................11
3.1.2. Unit dimensions...........................................................................................................................11
3.1.3. Panel cutout.................................................................................................................................12
3.1.4. Drilling template in mm (inches) .................................................................................................13
3.1.5. Mounting instructions...................................................................................................................13
3.1.6. Tightening torques.......................................................................................................................13
4. Hardware
4.1. Board slot positions..............................................................................................................................15
4.1.1. Unit top side overview..................................................................................................................16
4.1.2. Terminal strip overviews..............................................................................................................17
4.1.3. Input/output lists...........................................................................................................................22
4.1.4. Slot #1, power supply PCB..........................................................................................................23
4.1.5. Slot #1, power supply PCB - AGC mains unit..............................................................................24
4.1.6. Slot #2, serial communication (option H).....................................................................................25
4.1.7. Slot #2, external I/O module (option H8.2)..................................................................................26
4.1.8. Slot #2, 7 digital inputs (option M13.2)........................................................................................27
4.1.9. Slot #2, relay outputs (option M14.2)...........................................................................................27
4.1.10. Slot #3, load sharing control (option G3)...................................................................................28
4.1.11. Slot #3, 13 binary inputs and 4 relay outputs (option M12).......................................................29
4.1.12. Slot #4, relay outputs (option M14.4, standard).........................................................................30
4.1.13. Slot #4, analogue outputs for GOV/AVR or transducer (option E1)..........................................30
4.1.14. Slot #4, analogue outputs for GOV/AVR or transducer (option EF2)........................................30
4.1.15. Slot #4, combination outputs for GOV/AVR or transducer (option EF4)....................................31
4.1.16. Slot #4, PWM, relay and analogue outputs for GOV/AVR (option EF5)....................................31
4.1.17. Slot #4, PWM and analogue outputs for GOV/AVR (option EF6)..............................................32
4.1.18. Slot #4, analogue outputs for GOV/AVR or transducer (option E2)..........................................32
4.1.19. Slot #5, AC measuring...............................................................................................................33
4.1.20. Slot #5, AC measuring - AGC mains unit..................................................................................34
4.1.21. Slot #5, AC measuring - AGC BTB unit.....................................................................................35
4.1.22. Slot #6, 7 digital inputs (option M13.6)......................................................................................35
4.1.23. Slot #6, 4 relay outputs (option M14.6)......................................................................................36
4.1.24. Slot #6, 4 analogue inputs (option M15.6).................................................................................36
4.1.25. Slot #6, 4 multi-inputs (option M16.6)........................................................................................36
4.1.26. Slot #6, analogue outputs for transducer (option F1)................................................................37
4.1.27. Slot #7, engine interface card (std.)...........................................................................................38
4.1.28. Slot #7, engine interface card (std.) AGC mains/BTB...............................................................39
4.1.29. Slot #8, engine interface communication (option H5)................................................................40
4.1.30. Slot #8, Cummins engine interface communication (option H6)................................................40
4.1.31. Slot #8, 7 digital inputs (option M13.8)......................................................................................40
4.1.32. Slot #8, 4 relay outputs (option M14.8)......................................................................................41
4.1.33. Slot #8, 4 analogue inputs (option M15.8).................................................................................41
4.1.34. Slot #8, 4 multi-inputs (option M16.8)........................................................................................41
4.1.35. Slot #8, external I/O module (option H8.8)................................................................................42
5. Wirings
5.1. AC connections....................................................................................................................................43
5.1.1. Neutral line (N).............................................................................................................................43
5.1.2. Current transformer grounding....................................................................................................43
5.1.3. Fuses...........................................................................................................................................43
5.1.4. Breaker wiring..............................................................................................................................43
5.1.5. 3-phase........................................................................................................................................44
5.1.6. Single phase................................................................................................................................45
5.1.7. 2-phase L1L2 (split phase)..........................................................................................................46
5.1.8. 2-phase L1L3 (split phase)..........................................................................................................47
5.1.9. Island mode and power management (option G4/G5/G8)...........................................................48
5.1.10. Power management (option G5), AGC mains...........................................................................49
5.1.11. Power management (option G5), AGC BTB..............................................................................50
5.2. DC connections....................................................................................................................................51
5.2.1. Load sharing lines (option G3).....................................................................................................51
5.2.2. Digital inputs................................................................................................................................51
5.2.3. Analogue inputs (option M15.X)..................................................................................................52
5.2.4. Multi-inputs (option M16.X)..........................................................................................................53
5.2.5. External setpoints (option G3/M12) ............................................................................................54
5.2.6. Multi-inputs (102, 105, 108).........................................................................................................54
5.2.7. RPM input....................................................................................................................................56
5.2.8. Stop coil.......................................................................................................................................57
5.2.9. Transistor outputs (open collector outputs).................................................................................57
5.3. Communication....................................................................................................................................58
5.3.1. CANbus (option G4/G5/G8).........................................................................................................58
5.3.2. Modbus (option H2).....................................................................................................................59
5.3.3. Profibus DP (option H3)...............................................................................................................61
5.3.4. CANbus engine communication (option H5)................................................................................62
5.3.5. Cummins GCS (option H6)..........................................................................................................63
5.3.6. CANbus engine communication (option H7)................................................................................64
5.3.7. External I/O module (option H8)..................................................................................................65
5.3.8. Display cable (option J)...............................................................................................................65
6. Technical information
6.1. Technical information, AGC-4..............................................................................................................66
6.1.1. Technical specifications ..............................................................................................................66
1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
The general purpose of this document is to give the user important information to be used in the installation of
the unit.
Please make sure to read this document before starting to work with the Multi-line 2 unit and
the gen-set to be controlled. Failure to do this could result in human injury or damage to the
equipment.
The concept of the AGC is to offer a cost-effective solution to genset builders, who need a flexible generator
protection and control unit for medium to large genset applications. Being part of the Multi-line product family,
the standard functions can be supplemented with a variety of optional functions.
It contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the LCD
display.
2.1.3 Options
The Multi-line 2 product range consists of different basic versions, which can be supplemented with the flexi-
ble options needed to provide the optimum solution. The options cover e.g. various protections for generator,
busbar and mains, voltage/VAr/PF control, various outputs, power management, serial communication, addi-
tional operator display etc.
2.2.5 Display
Prepared for remote mounting
Push-buttons for start and stop
Push-buttons for breaker operations
Status texts
2.2.6 M-Logic
Simple logic configuration tool
Selectable input events
Selectable output commands
Load
Controller
Controller
Load
Controller
TRANSDUCER
P/4-20 mA
Load
Controller
TRANSDUCER
P/4-20 mA
Load
Controller
TRANSDUCER
P/4-20 mA
Load
Controller
Controller Controller
G G
For information about the power management application, please refer to "Description of Op-
tion G4, G5 and G8".
3. Mounting
3.1 AGC-4 mounting and dimensions
3.1.1 Mounting of the unit
The unit is designed for mounting inside the panel. The display can be installed on the panel door and con-
nected to the main unit with a display cable.
115 (4.528)
165 (6.486)
144 (5.669)
15 (0.59)
115 (4.528)
215(8.465)
230 (9.055)
115 (4.528)
Display or AOP
174.0
= =
26.0 26.0
15.0
41.0
=
61.0
50.5
230.0 (9.055)
215.5 (8.484)
114.9 (4.524)
14.3 (0.563)
6.6 (0.260)
112.6 (4.433)
119.1 (4.689)
Controller unit: 1.5 Nm for the six M4 screws (countersunk screws are not to be used)
Plug connections (terminals): 0.5 Nm, 4.4 lb-in
220.0 (8.661)
0.2 Nm
115.0 (4.528)
Display
9P Female
Sub 0
connector
0.7 Nm
Screw M3
Bossard BN5687 Max. 10 mm
or similar Min. 6 mm
20.0 (0.787)
4. Hardware
4.1 Board slot positions
The unit housing is divided into board slot positions. This means that the unit consists of a number of printed
circuit boards (PCB) mounted in numbered slots. The green terminal blocks are then mounted in the PCBs.
Some of these board slots are standard and some are intended for options. The board slot positions are ar-
ranged as illustrated below.
Only hardware options, which will affect the hardware of the unit, are represented in the table.
The software options will be seen through the PC utility software. The software options that are
not represented in the above table can be found in the data sheet.
1 2
3 4
37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
CAN A
CAN B Ethernet Service port Display
Ethernet
9
Power
Self check ok
Alarm inhibit
73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97
5 6
7 8
1 The numbers in the drawing above refer to the slot numbers indicated in the table below.
:
No. Slot
1 #1, terminal 1-28, power supply (standard)
2 #2, terminal 29-36, communication and I/O extensions
3 #3, terminal 37-64, in-/outputs/load sharing
4 #4, terminal 65-72, governor, AVR, in-/outputs (standard)
5 #5, terminal 73-89, AC measuring (standard)
6 #6, terminal 90-97, in-/outputs
7 #7, terminal 98-125, engine I/F (standard)
8 #8, terminal 126-133, engine communication, in-/outputs.
9 LED I/F
The hardware shown in slot #3 is option M12 and G3. For a detailed description of these op-
tions, please refer to the option manuals.
Mains unit
The hardware shown in slot #3 is option M12 and G3. For a detailed description of these op-
tions, please refer to the option manuals.
BTB unit
The hardware shown in slot #3 is option M12 and G3. For a detailed description of these op-
tions, please refer to the option manuals.
7 NC
8 NO Relay 08 Open mains breaker/configurable
9 Com. 250V AC/8 A
10 NC
11 NO Relay 11 Close mains breaker (synchronising)/configurable
12 Com. 250V AC/8 A
13 NC
14 NO Relay Open generator breaker
15 Com. 250V AC/8 A
16 NC
17 NO Relay Close generator breaker (synchronising)
18 Com. 250V AC/8 A
19 NC
20 Open collector 1 Transistor output/Relay 20 Pulse output 1, kWh counter/configurable
21 Open collector 2 Transistor output/Relay 21 Pulse output 2, kVArh counter/configurable
22 Com. Common Common terminal for terminals 20 and 21
23 Digital input 23 Optocoupler Configurable
24 Digital input 24 Optocoupler Mains breaker open/configurable
25 Digital input 25 Optocoupler Mains breaker closed/configurable
26 Digital input 26 Optocoupler Generator breaker open
27 Digital input 27 Optocoupler Generator breaker closed
28 Com. Common Common for terminals 23 to 27
7 NC
8 NO Relay 08 Open mains breaker/configurable
9 Com. 250V AC/8 A
10 NC
11 NO Relay 11 Close mains breaker (synchronising)/configurable
12 Com. 250V AC/8 A
13 NC
14 NO Relay 14 Open tie breaker/configurable
15 Com. 250V AC/8 A
16 NC
17 NO Relay 17 Close tie breaker (synchronising)/configurable
18 Com. 250V AC/8 A
19 NC
20 Open collector 1 Transistor output/Relay 20 Pulse output 1, kWh counter/configurable
21 Open collector 2 Transistor output/Relay 21 Pulse output 2, kVArh counter/configurable
22 Com. Common Common terminal for terminals 20 and 21
23 Digital input 23 Optocoupler Configurable
24 Digital input 24 Optocoupler Mains breaker open/configurable
25 Digital input 25 Optocoupler Mains breaker closed/configurable
26 Digital input 26 Optocoupler Tie breaker open/configurable
27 Digital input 27 Optocoupler Tie breaker closed/configurable
28 Com. Common Common for terminals 23 to 27
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the
cable impedance. The terminals 29/33 and 31/35 are internally connected.
Never connect the GND terminal 30 to earth. Only connect it to a third wire in the communica-
tion cable!
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the
cable impedance. The terminals 29/33 and 31/35 are internally connected.
Never connect the GND terminal 30 to earth. Only connect it to a third wire in the communica-
tion cable!
Never connect the GND terminal 30 to earth. Only connect it to a third wire in the communica-
tion cable!
Terminals 29 and 32 are internally connected. Terminals 31 and 34 are internally connected.
4.1.11 Slot #3, 13 binary inputs and 4 relay outputs (option M12)
4.1.13 Slot #4, analogue outputs for GOV/AVR or transducer (option E1)
4.1.14 Slot #4, analogue outputs for GOV/AVR or transducer (option EF2)
4.1.15 Slot #4, combination outputs for GOV/AVR or transducer (option EF4)
4.1.16 Slot #4, PWM, relay and analogue outputs for GOV/AVR (option EF5)
4.1.17 Slot #4, PWM and analogue outputs for GOV/AVR (option EF6)
Connect PWM - to the engine battery negative and PWM + to the engine control system S-SPD
(speed) input (called RATED SPEED on the ADEM controller and PRIMARY THROTTLE on the
PEEC controller).
4.1.18 Slot #4, analogue outputs for GOV/AVR or transducer (option E2)
The I/O list below is for the AGC mains unit (G5).
100 MPU input 0.5-70V AC/ Magnetic pick-up with wire break
101 MPU GND 10-10,000 Hz
107 C
108 A Multi-input 3
109 B
110 C
111 Com. Common Common for terminals 112-117
112 Digital input 112 Optocoupler Configurable
113 Digital input 113 Optocoupler Configurable
114 Digital input 114 Optocoupler Configurable
115 Digital input 115 Optocoupler Configurable
116 Digital input 116 Optocoupler Configurable
117 Digital input 117 Optocoupler Configurable
118 Digital input 118 Optocoupler Emergency stop and common for 119 and 120
119 NO Relay Run coil
24V DC/5 A
120 NO Relay Start prepare
24V DC/5 A
121 Com. Relay Crank (starter)
122 NO 250V AC/5 A
A3 CAN-L
B1 CAN-H CANbus interface B
B2 GND (option G4 or G5, G8)
B3 CAN-L
107 C
108 A Multi-input 3
109 B
110 C
111 Com. Common Common for terminals 112-117
112 Digital input 112 Optocoupler Configurable
113 Digital input 113 Optocoupler Configurable
114 Digital input 114 Optocoupler Configurable
115 Digital input 115 Optocoupler Configurable
116 Digital input 116 Optocoupler Configurable
117 Digital input 117 Optocoupler Configurable
118 Digital input 118 Optocoupler Emergency stop and common for 119 and 120
119 NO Relay Not used
24V DC/5 A
120 NO Relay Not used
24V DC/5 A
121 Com. Relay Not used
122 NO 250V AC/5 A
A3 CAN-L
B1 CAN-H CANbus interface B
B2 GND (option G4 or G5)
B3 CAN-L
Terminals 133 and 130 are internally connected. Terminals 131 and 128 are internally connec-
ted.
5. Wirings
5.1 AC connections
The Multi-line 2 unit can be wired up in 1-phase, 2-phase or 3-phase configuration.
Contact the switchboard manufacturer for accurate information about required wiring for the
specific application.
5.1.3 Fuses
If the cables are protected with fuses, then use 2 A, slow blow.
5.1.5 3-phase
AMF, fixed power, peak shaving, load takeover, mains power export.
5.2 DC connections
5.2.1 Load sharing lines (option G3)
37 38 39 37 38 39 37 38 39
PS COMMON QS PS COMMON QS PS COMMON QS
0...5 0...5 0...5 0...5 0...5 0...5
V DC V DC V DC V DC V DC V DC
Switch
23
23
Multi-line 2
Multi-line 2 Switch
28 (COM.)
28 (COM.)
Emergency stop:
12/24V DC
118
Multi-line 2
99 (COM.) 0V DC
Multi-line 2
4-20 mA
transducer 91
+12/24V DC + +
Analogue input 91
0V DC - -
90 (Common)
Measurement
Passive transducer
Multi-line 2
4-20 mA
transducer 91
+12/24V DC + -
Analogue input 91
Measurement
0V DC 90 (Common)
V DC sensor
Multi-line 2
91
0-10V DC
Analogue input 91
sensor
90 (Common)
R = 450
Multi-line 2
4-20 mA
transducer 91
+12/24V DC + +
Analogue input 91
0V DC - -
90 (Common)
Measurement
Passive transducer
Multi-line 2
4-20 mA
transducer 91
+12/24V DC + -
Analogue input 91
Measurement
0V DC 90 (Common)
V DC sensor
Multi-line 2
91
0-10V DC
Analogue input 91
sensor
90 (Common)
R = 450
0-5V DC
Battery Multi-line 2
0-5V DC 91
Multi-input
0V DC 90
Pt100
Pt100 Multi-line 2
90
Multi-input
91
2000 Ohm
W Multi-line 2
potentiometer
10V DC
40 or 42
0V DC 41 (Common)
2000 Ohm
W Multi-line 2
potentiometer
10V DC
40 or 42
-10V DC 41 (Common)
0V DC
Active transducer
Multi-line 2
4-20 mA
transducer A
+12/24V DC +
+ Out B Multi-input
0V DC -
Measurement In - Out C
Passive transducer
Multi-line 2
4-20 mA
transducer A
+12/24V DC + - B Multi-input
0 V DC C
If the passive sensor has its own battery supply, the voltage must not exceed 30V DC.
Digital inputs
Multi-line 2
A
R B Multi-input
The resistor is only mounted if wire fail supervision is required. The value of the resistor
should be 270 +/-10%.
Pt100/Pt1000
2-wire 3-wire
Pt100/1000 Multi-line 2 Pt100/1000 Multi-line 2
0
A A
I
B Multi-input B Multi-input
P
C C
VDO
1-wire 2-wire
RMI Multi-line 2 RMI Multi-line 2
A A
B Multi-input B Multi-input
C C
0-40V DC
Battery Multi-line 2
0-40V DC A
B Multi-input
0V DC C
MPU Multi-line 2
Output 100
101
NPN sensor
NPN Multi-line 2
+12/24V DC R
+V DC
C
Output 100
C
0V DC 101
0V DC
PNP sensor
PNP Multi-line 2
+V DC +12/24V DC
C
Output 100
R C
0V DC 101
0V DC
Charger, W output
Charger Multi-line 2
C
W 100
101
+12/24V DC
Multi-line 2
123
124
A1
Stop coil
A2
0V DC
A1
0,5 F External
Relay
100 V counter
A2
Multi-line 2 Multi-line 2
0 VDC 0 VDC
Connection to PLC:
+12/24 VDC
PLC
4,7 k
Input (positive)
20 kWh
Multi-line 2
22 (Com. For 20/21)
0 VDC
5.3 Communication
5.3.1 CANbus (option G4/G5/G8)
Examples with three AGC units connected, e.g. one AGC mains and two generator AGC units.
120 120
120 120
Connect shield to earth at one end only. Shield ends must be insulated with tape or insulation
tubing.
DATA (GND)
DATA - (B)
DATA + (A)
DATA (GND)
DATA - (B)
DATA + (A)
DATA (GND)
DATA - (B)
29 30 31 29 30 31 29 30 31
DATA - (B)
DATA (GND)
DATA + (A)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
DATA (GND)
DATA - (B)
DATA + (A)
DATA (GND)
DATA - (B)
DATA + (A)
DATA (GND)
DATA - (B)
29 30 31 29 30 31 29 30 31
DATA - (B)
DATA (GND)
DATA + (A)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
This solution is only feasible if the COM line is insulated. Check PLC/other device before con-
necting.
Normally, the Modbus does not need bias resistors (end terminators). These are only needed
in case of very long lines and/or many nodes (>32) on the Modbus network. If bias resistors
are needed, the calculation should be based on the following data:
Cable: Belden 3105A or equivalent. 22 AWG (0.6 mm2) twisted pair, shielded, <40 m/m, min.
95% shield coverage.
COM
DATA - (A)
DATA + (B)
COM
DATA - (A)
DATA + (B)
COM
DATA - (A)
29 30 31 29 30 31 29 30 31
DATA - (A)
COM
DATA + (B)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Multi-line 2
CAN-H
CAN-GND
CAN-L
120
120
CAN-L
CAN-GND
CAN-H
ECM
engine control module
Multi-line 2
CAN-H
CAN-GND
CAN-L
120
120
CAN-L
CAN-GND
CAN-H
ECM
engine control module
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
The terminating resistor at the engine side might not be needed, please refer to the engine
manufacturers literature.
DATA (GND)
DATA + A
DATA - B
DATA (GND)
DATA + A
131 132 133 18 20 31
R R
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Normally, the communication does not need bias resistors (end terminators). These are only
needed in case of very long lines between the two modules. If bias resistors are needed, the
calculation should be based on the following data:
Cable: Belden 3105A or equivalent. 22 AWG (0.6 mm2) twisted pair, shielded, <40 m/m, min.
95% shield coverage.
Multi-line 2
CAN-H
CAN-GND
CAN-L
A1 A2 A3
120
120
CAN-L
CAN-GND
CAN-H
ECM
engine control module
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
The terminating resistor at the engine side might not be needed, please refer to the engine
manufacturers literature.
Multi-line 2
Option H 8.8
Option H 8.2
120
120
CANopen
CAN-H
133
29
CAN-L
131
31
BECKHOFF
ON
1 2 3 4 5 6 7 8
DIP CANopen
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
6. Technical information
6.1 Technical information, AGC-4
6.1.1 Technical specifications
Positive, negative and zero sequence alarms: class 1 within 5% voltage unbalance
Class 1.0 for negative sequence current
Fast overcurrent: 3% of 350%*In
Analogue outputs: class 1.0 according to total range
Option EF4/EF5: class 4.0 according to total range
To IEC/EN60688
Operating tem- -2570C (-13...158F)
perature -25...60C (-13...140F) if Modbus TCP/IP (option N) is available in the controller.
(UL/cUL Listed: max. surrounding air temperature: 55C/131F)
Storage tem- -4070C (-40...158F)
perature
Climate 97% RH to IEC 60068-2-30
Operating alti- 0-4000 m above sea level
tude Derating 2001-4000 m above sea level:
Max. 480V AC phase-phase 3W4 measuring voltage
Max. 690V AC phase-phase 3W3 measuring voltage
Measuring volt- 100-690V AC +/-20%
age (UL/cUL Listed: 600V AC phase-phase)
Consumption: max. 0.25 VA/phase
Measuring cur- -/1 or -/5 A AC
rent (UL/cUL Listed: from CTs 1-5 A)
Consumption: max. 0.3 VA/phase
Current over- 4 x In continuously
load 20 x In, 10 sec. (max. 75 A)
80 x In, 1 sec. (max. 300 A)
Measuring fre- 30...70 Hz
quency
Aux. supply Terminals 1 and 2: 12/24V DC (8...36 V continuously, 6 V 1 sec.). Max. 11 W consump-
tion
Battery voltage measurement accuracy: 0.8 V within 8 to 32V DC, 0.5 V within 8 to
32V DC @ 20 C
Terminals 98 and 99: 12/24V DC (8...36 V continuously, 6 V 1 sec.). Max. 5 W con-
sumption
The aux. supply inputs are to be protected by a 2 A slow blow fuse. (UL/cUL Listed:
AWG 24)
Response Busbar:
times Over-/undervoltage: <50 ms
(delay set to Over-/underfrequency: <50 ms
min.) Voltage unbalance: <250 ms
Generator:
Reverse power: <250 ms
Overcurrent: <250 ms
Fast overcurrent: <40 ms
Directional overcurrent: <150 ms
Over-/undervoltage: <250 ms
Over-/underfrequency: <350 ms
Overload: <250 ms
Current unbalance: <250 ms
Voltage unbalance: <250 ms
Reactive power import: <250 ms
Reactive power export: <250 ms
Voltage-dependent I>: <250 ms
Negative sequence I: <500 ms
Negative sequence U: <500 ms
Zero sequence I: <500 ms
Zero sequence U: <500 ms
Overspeed: <500 ms
Digital inputs: <250 ms
Emergency stop: <200 ms
Multi-inputs: 800 ms
Wire failure: <600 ms
Mains:
df/dt (ROCOF): <130 ms (4 periods)
Vector jump: <40 ms
Positive sequence: <60 ms
Time-dependent undervoltage, Ut<: <50 ms
Undervoltage and reactive power low, UQ<: <250 ms
Mounting DIN-rail mount or base mount with six M4 screws
Tightening tor- 1.5 Nm for the six M4 screws (countersunk screws are not to be used)
que
Safety To EN 61010-1, installation category (overvoltage category) III, 600 V, pollution degree
2
To UL 508 and CSA 22.2 no. 14-05, overvoltage category III, 600 V, pollution degree 2
EMC/CE To EN 61000-6-2, EN 61000-6-4, IEC 60255-26.
Vibration 313.2 Hz: 2 mmpp. 13.2100 Hz: 0.7 g. To IEC 60068-2-6 & IACS UR E10
1060 Hz: 0.15mmpp. 60150 Hz: 1 g. To IEC 60255-21-1 Response (class 2)
10150 Hz: 2 g. To IEC 60255-21-1 Endurance (class 2)
Shock (base 10 g, 11 ms, half sine. To IEC 60255-21-2 Response (class 2)
mount) 30 g, 11 ms, half sine. To IEC 60255-21-2 Endurance (class 2)
50 g, 11 ms, half sine. To IEC 60068-2-27
AOP-2:
Maximum ambient temperature: 60C
Wiring: use 60/75C copper conductors only
Mounting: for use on a flat surface of type 3 (IP54) enclosure. Main disconnect must be
provided by installer
Installation: to be installed in accordance with the NEC (US) or the CEC (Canada)