Front cable termination ring main unit with 3 and 4 switching
functions in a single SF6 insulated stainless steel enclosure
Aegis Plus is a new generation of ring main unit
designed for secondary distribution networks
up to 24kV. This range is available in indoor and
outdoor formats to suit various application needs,
and it offers high levels of reliability, personnel
safety and maintenance free operation.
General features:
12kV, 17.5kV and 24kV with up to 630A ratings
Non-extensible range
3 and 4 functions in a single SF6 insulated stainless
steel tank
No on-site SF6 gas handling for installation
Intuitive single line mimic diagram
Vacuum interrupter for circuit breakers
Front access cable terminations with DIN 400 Type C bushings
Motorisation for remote control
Circuit breaker protection with time limit fuses or relays
IP67 hermitically sealed stainless steel switching chamber
Suitable for indoor (IP4X) and outdoor (IP54) applications
Easy integration with SCADA networks
Integrated RTU with optional automatic transfer scheme (ATS)
Aegis Plus AFLR unit (gas exhaust via chimney)
Wide range of load break switch and vacuum circuit breaker
combinations
Proven and reliable technology Accessible Earth and Test facility at the front
of the unit
Simple and safe operation
VPIS tested to IEC 62271-206
Easy to install
VDS tested to IEC 61243-5
Suitable for mini substations
Automation ready
Page 3
Protection options
Aegis Plus can be fitted with a host of
optional accessories including advanced
circuit breaker protection devices. A range
of self-powered relays and time limit fuses
(TLF) are available to provide greater fault
protection and preservation of network assets.
Protection relay:
Woodward WIP1 relays offered as standard, other
suppliers available on request
Offers advanced protection solutions with DMT and
IDMT curves
Protects the transformer from short circuit, overload
and earth faults
Available in self powered and dual powered formats WIP1 relay
Page 4
Automation ready
Aegis Plus can be configured with the next-
generation Gemini 3 RTU. This is an all new,
highly flexible, general-purpose Remote
Terminal Unit designed to remotely
monitor and control medium/high voltage
switchgear.
Page 5
Technical data
Rated Voltage kV 12 17.5 24
General
Rated frequency Hz 50 50 / 60 50
Rated lightning impulse withstand voltage
Directly earthed kV 75 95 125
Across disconnector kV 85 110 145
Rated power frequency withstand voltage
Directly earthed kV 28 38 50
Across disconnector kV 32 45 60
Protection
Indoor IP IP4X
Outdoor (Non-extensible) IP IP54
Tank with HV parts IP IP67
Mechanical impact protection IK IK7 (indoor) IK10 (outdoor)
Internal arc protection
AFL kA 1 sec 20
AFLR kA 1 sec 20
SF6 gas
Annual leakage rate < 0.1%
Filled pressure (at 20C) Bar (G) 0.4
Minimum operating pressure Bar (G) 0.1
Installation conditions
Ambient air temperature (without derating) C -25 to +40
Relative humidity (max) - over period of 24hrs (IEC 62271-1, sub-clause 2.1) 95%
BusBars
Rated normal current A 630
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Load Break Switch : L function
Rated normal current A 630
Rated active load breaking current A 630
Rated cable charging breaking current A 10 10 16
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Mechanical endurance class
Load break switch M2 (5,000)
Earth switch M0 (1,000)
Electrical endurance class short circuit making
Load break switch E3 (5 times)
Earth switch E2 (5 times)
Operating mechanism
Local: Close - Open Hand Lever
Remote: Close - Open Motor
Circuit Breaker : V function (Non-auto reclose)
Rated normal current A 630
Rated active load breaking current A 630
Rated short circuit breaking current kA 21 21 21
Rated short circuit making current kA 52.5 52.5 / 54.6 52.5
Rated cable charging breaking current A 25 31.5 31.5
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Mechanical endurance class short circuit making
Circuit breaker M1 (2,000)
Earth switch M0 (1,000)
Electrical endurance class (making)
Circuit breaker E2 (2 times)
Earth switch E2 (5 times)
Operating mechanism
Operating sequence for mechanism O-3min-CO-3min-C0
Local: Close - Open Hand lever - Pushbutton
Remote: Close - Open Motor - Coil
Page 6
Technical data
Rated Voltage kV 12 17.5 24
Circuit Breaker : C function (Auto reclose)
Rated normal current A 630
Rated active load breaking current A 630
Rated short circuit breaking current kA 21 21 21
Rated short circuit making current kA 52.5 52.5 / 54.6 52.5
Rated cable charging breaking current A 25 31.5 31.5
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Mechanical endurance class
Circuit breaker M2 (10,000)
Earth switch M0 (1,000)
Electrical endurance class (making)
Circuit breaker E2 (4 times)
Earth switch E2 (5 times)
Operating mechanism
Operating sequence for mechanism O- 0.3s-CO-15s-CO
Local: Spring charging / Close - Open Handle / Pushbuttons
Remote: Spring charging / Close - Open Motor / Coil
Circuit Breaker : T function
Rated normal current A 250
Rated active load breaking current A 250
Rated short circuit breaking current kA 21 21 21
Rated short circuit making current kA 52.5 52.5 / 54.6 52.5
Rated cable charging breaking current A 25 31.5 31.5
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 3.15 3.15 3.15
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 7.9 7.9 7.9
Mechanical endurance class
Circuit breaker M1 (2,000)
Earth switch M0 (1,000)
Electrical endurance class (making)
Circuit breaker E2 (2 times)
Earth switch E2 (5 times)
Operating mechanism
Operating sequence for mechanism O-3min-CO-3min-CO
Local: Close - Open Hand lever - Pushbutton
Remote: Close - Open Motor - Coil
Standards
Aegis Plus complies with the latest international standards:
Page 7
Dimensions
1050mm 1391mm 685mm
H H
Lucy Middle East FZE Lucy Electric South Africa (Pty) Ltd Lucy Electric (Beijing) Co. Ltd
PO Box 17335, Jebel Ali, Dubai, Unit 2, Cranberry Industrial Park, Cranberry Street,
United Arab Emirates Laser Park, Honeydew, 2170, South Africa Room 1122, Tower A Gateway Square,
Tel: +97 148 129 999 Tel: +27 11 025 7490 Chaoyang, Beijing, China
Fax: +97 148 129 900 Fax: +27 11 794 3277 : 100027
Email: salesme@lucyelectric.com Email: salesza@lucyelectric.com : +86 (0)10 59231176
: +86 (0)10 5923 1177
Lucy Electric (Thailand) Ltd Postal Address: : salescn@lucyelectric.com
388 Exchange Tower, 37th Floor, P.O. Box 1078, Honeydew, 2040
Unit 3702, Sukhumvit Road,
Klongtoey, Bangkok, 10110
Tel: +66 (0) 2 663 4290
Fax: +66 (0) 2 663 4293
Email: salesth@lucyelectric.com
AGPBR004EN