Ring main unit

Why ?
+ Compact design
+ Automation ready
+ Safe and simple operation
+ Easy to install
+ Maintenance free
+ Climate independent
+ Cost effective

Applications
Aegis Plus has been designed and developed for optimal performance
in a range of applications, from power generation and distribution to
commercial and industrial requirements.

Power generation and distribution Industries


Secondary substations Mining
Ring main network protection Automotive
Wind farms Iron and steel
Solar power plants Paper and pulp
Co-generation facilities Cement and petroleum
Water and waste water

Commercial buildings
Shopping centres Infrastructure
Hospitals Metro stations
Schools Airports
Hotels Seaports
Office buildings Tunnels
Warehouses
Data centres

Page 2
Front cable termination ring main unit with 3 and 4 switching
functions in a single SF6 insulated stainless steel enclosure
Aegis Plus is a new generation of ring main unit
designed for secondary distribution networks
up to 24kV. This range is available in indoor and
outdoor formats to suit various application needs,
and it offers high levels of reliability, personnel
safety and maintenance free operation.

General features:
12kV, 17.5kV and 24kV with up to 630A ratings
Non-extensible range
3 and 4 functions in a single SF6 insulated stainless
steel tank
No on-site SF6 gas handling for installation
Intuitive single line mimic diagram
Vacuum interrupter for circuit breakers
Front access cable terminations with DIN 400 Type C bushings
Motorisation for remote control
Circuit breaker protection with time limit fuses or relays
IP67 hermitically sealed stainless steel switching chamber
Suitable for indoor (IP4X) and outdoor (IP54) applications
Easy integration with SCADA networks
Integrated RTU with optional automatic transfer scheme (ATS)
Aegis Plus AFLR unit (gas exhaust via chimney)
Wide range of load break switch and vacuum circuit breaker
combinations

Customer benefits: Additional safety features:


Economic full life cost Internal arc protection AF / AFL / AFLR

Maintenance free Fully interlocked mechanism with padlocks

Insensitive to external environment Anti-reflex mechanism

Proven and reliable technology Accessible Earth and Test facility at the front
of the unit
Simple and safe operation
VPIS tested to IEC 62271-206
Easy to install
VDS tested to IEC 61243-5
Suitable for mini substations
Automation ready

Page 3
Protection options
Aegis Plus can be fitted with a host of
optional accessories including advanced
circuit breaker protection devices. A range
of self-powered relays and time limit fuses
(TLF) are available to provide greater fault
protection and preservation of network assets.

Protection relay:
Woodward WIP1 relays offered as standard, other
suppliers available on request
Offers advanced protection solutions with DMT and
IDMT curves
Protects the transformer from short circuit, overload
and earth faults
Available in self powered and dual powered formats WIP1 relay

Local and remote tripping options


RS485 interface with Modbus protocol for
communication with RTU

Time limit fuse:


Alternative low cost protection solution compared
to electronic relays
Fully complies with ENA TS 41-36 (Energy Networks
Association, UK)
Protects the transformer from short circuits and
earth faults
Resetting of protection is done by changing LV fuses,
no access to HV compartment is required

Time limit fuse

Feature Relay TLF


Short circuit protection Yes Yes
Earth fault protection Yes Yes
Overload protection Yes No
Upstream and downstream discrimination protection Yes Yes
Remote tripping option Yes Yes
Transformer range Wide range Up to 2MVA

Page 4
Automation ready
Aegis Plus can be configured with the next-
generation Gemini 3 RTU. This is an all new,
highly flexible, general-purpose Remote
Terminal Unit designed to remotely
monitor and control medium/high voltage
switchgear.

The GEMINI 3 has a modular design such General features:


that it can be configured from a very Fault detection (Earth and Phase)
simple monitoring device through to a
LED status indicators
sophisticated multi switch control unit.
It can be set up with a high input count Real time clock (SCADA synchronised)
of analogue and digital signals as well as Dual isolated Ethernet and RS232 ports
secure switchgear
Supervisory selection and indication
control outputs.
USB and HMI ports
There are several modules currently Event memory 6500 events in non-volatile memory
available in the Gemini 3 RTU: Optional flash SD memory card (factory fitted)
Master Control Module (MCM) Contains the Maintenance free
main processor and supervises all modules. The
MCM handles the protocol communications.
Integrated design
Switch Control Module (SCM) Provides the
inputs and outputs to perform secure controls. The Gemini 3 RTU is an optional feature in Aegis Plus,
This allows one switch to be controlled but additional integrated neatly in the upper section of the unit
modules can be added to increase the number of (factory fitted). This eliminates the need for an additional
controlled switches. exterior control box and associated cabling on site.

Power Supply Module (PSM) Works with the Switch


Control Module to provide secure switching operations.
The PSM generates regulated power to all other modules
and external communication equipment. The PSM also
provides the intelligent battery charging function for the
RTU to maintain a secure supply.

Input Output Module (IOM) General purpose


module that covers digital and analogue inputs and
relay outputs.

Fault Passage Module (FPM) Dual fault passage


indicator module which detects and alarms for
Overcurrent and Earth Faults.

Human Machine Interface (HMI) Allows local


control and monitoring without the need for a
computer. An LCD screen displays site information
and can be customised by the user.

Page 5
Technical data
Rated Voltage kV 12 17.5 24
General
Rated frequency Hz 50 50 / 60 50
Rated lightning impulse withstand voltage
Directly earthed kV 75 95 125
Across disconnector kV 85 110 145
Rated power frequency withstand voltage
Directly earthed kV 28 38 50
Across disconnector kV 32 45 60
Protection
Indoor IP IP4X
Outdoor (Non-extensible) IP IP54
Tank with HV parts IP IP67
Mechanical impact protection IK IK7 (indoor) IK10 (outdoor)
Internal arc protection
AFL kA 1 sec 20
AFLR kA 1 sec 20
SF6 gas
Annual leakage rate < 0.1%
Filled pressure (at 20C) Bar (G) 0.4
Minimum operating pressure Bar (G) 0.1
Installation conditions
Ambient air temperature (without derating) C -25 to +40
Relative humidity (max) - over period of 24hrs (IEC 62271-1, sub-clause 2.1) 95%
BusBars
Rated normal current A 630
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Load Break Switch : L function
Rated normal current A 630
Rated active load breaking current A 630
Rated cable charging breaking current A 10 10 16
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Mechanical endurance class
Load break switch M2 (5,000)
Earth switch M0 (1,000)
Electrical endurance class short circuit making
Load break switch E3 (5 times)
Earth switch E2 (5 times)
Operating mechanism
Local: Close - Open Hand Lever
Remote: Close - Open Motor
Circuit Breaker : V function (Non-auto reclose)
Rated normal current A 630
Rated active load breaking current A 630
Rated short circuit breaking current kA 21 21 21
Rated short circuit making current kA 52.5 52.5 / 54.6 52.5
Rated cable charging breaking current A 25 31.5 31.5
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Mechanical endurance class short circuit making
Circuit breaker M1 (2,000)
Earth switch M0 (1,000)
Electrical endurance class (making)
Circuit breaker E2 (2 times)
Earth switch E2 (5 times)
Operating mechanism
Operating sequence for mechanism O-3min-CO-3min-C0
Local: Close - Open Hand lever - Pushbutton
Remote: Close - Open Motor - Coil

Page 6
Technical data
Rated Voltage kV 12 17.5 24
Circuit Breaker : C function (Auto reclose)
Rated normal current A 630
Rated active load breaking current A 630
Rated short circuit breaking current kA 21 21 21
Rated short circuit making current kA 52.5 52.5 / 54.6 52.5
Rated cable charging breaking current A 25 31.5 31.5
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Mechanical endurance class
Circuit breaker M2 (10,000)
Earth switch M0 (1,000)
Electrical endurance class (making)
Circuit breaker E2 (4 times)
Earth switch E2 (5 times)
Operating mechanism
Operating sequence for mechanism O- 0.3s-CO-15s-CO
Local: Spring charging / Close - Open Handle / Pushbuttons
Remote: Spring charging / Close - Open Motor / Coil
Circuit Breaker : T function
Rated normal current A 250
Rated active load breaking current A 250
Rated short circuit breaking current kA 21 21 21
Rated short circuit making current kA 52.5 52.5 / 54.6 52.5
Rated cable charging breaking current A 25 31.5 31.5
Main electrical circuit
Rated short time withstand current kA 21 21 21
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 52.5 52.5 / 54.6 52.5
Earthing circuit
Rated short time withstand current kA 3.15 3.15 3.15
Rated duration of short circuit s 3 3 3
Rated peak withstand current kA 7.9 7.9 7.9
Mechanical endurance class
Circuit breaker M1 (2,000)
Earth switch M0 (1,000)
Electrical endurance class (making)
Circuit breaker E2 (2 times)
Earth switch E2 (5 times)
Operating mechanism
Operating sequence for mechanism O-3min-CO-3min-CO
Local: Close - Open Hand lever - Pushbutton
Remote: Close - Open Motor - Coil

Standards
Aegis Plus complies with the latest international standards:

IEC 62271 - 100 Alternating current circuit breakers


IEC 62271 102 Alternating current disconnectors and earthing switches
IEC 62271 103 Switches for rated voltages between 1kV and 52kV
IEC 62271 105 Alternating current switch fuse combinations
IEC 62271 200 AC metal enclosed switchgear and control gear
IEC 62271 206 VPIS systems for rated voltages between 1kV and 52kV
IEC 62271 1 HV switchgear and control gear: Common specifications
IEC 61243 5 Voltage detecting systems (VDS)
IEC 60255 Measuring relays and protection equipment

Page 7
Dimensions
1050mm 1391mm 685mm

H H

3-function unit 4-function unit 3 and 4-


function unit

H = Overall unit height (mm)


Cable termination tail height (mm) Relay/TLF fitted G3 RTU fitted
450 1280 1430
600 1430 1580
750 1580 1730

Lucy Electric worldwide offices


Lucy Switchgear Ltd Lucy Switchgear Arabia Co. Ltd Lucy Asia Pacific Sdn Bhd
Howland Road, Thame, Oxfordshire, Novotel Business Centre, L13A-03-03A, PJX-HM Shah Tower,
OX9 3UJ, United Kingdom P.O. Box 35340, Dammam 31488, No16A Jalan Persiaran Barat,
Tel: +44 1844 267 267 General Saudi Arabia 46050 Petaling Jaya, Selangor, Malaysia
Tel: +44 1844 267 222 Sales Tel: +966 3 8147 910 Tel: +603 74910700
Fax: +44 1844 267 223 Fax: +966 3 8147 914 Fax: +603 79316923
Email: salesuk@lucyelectric.com Email: salessa@lucyelectric.com Email: salesmy@lucyelectric.com

Lucy Middle East FZE Lucy Electric South Africa (Pty) Ltd Lucy Electric (Beijing) Co. Ltd
PO Box 17335, Jebel Ali, Dubai, Unit 2, Cranberry Industrial Park, Cranberry Street,
United Arab Emirates Laser Park, Honeydew, 2170, South Africa Room 1122, Tower A Gateway Square,
Tel: +97 148 129 999 Tel: +27 11 025 7490 Chaoyang, Beijing, China
Fax: +97 148 129 900 Fax: +27 11 794 3277 : 100027
Email: salesme@lucyelectric.com Email: salesza@lucyelectric.com : +86 (0)10 59231176
: +86 (0)10 5923 1177
Lucy Electric (Thailand) Ltd Postal Address: : salescn@lucyelectric.com
388 Exchange Tower, 37th Floor, P.O. Box 1078, Honeydew, 2040
Unit 3702, Sukhumvit Road,
Klongtoey, Bangkok, 10110
Tel: +66 (0) 2 663 4290
Fax: +66 (0) 2 663 4293
Email: salesth@lucyelectric.com

AGPBR004EN

Potrebbero piacerti anche