Sei sulla pagina 1di 3

Note: Change the Logo on master page D. Change the coloured backgrounds on the assigned master pages.

This line will not print.

Retrofit guide.
From CFCs to HCFCs to HFCs refrigeration.

CFC HCFC HFC


R12 R401A, R409A R437A
High
temperature R22 R422D, R424A, R434A
(~ >0C)
Oil change R134a*, R427A*

R426A, R437A

R12 Oil change R134a*


Medium
R401B, R409B R437A
temperature
(0C 25C) R500 R417A, R422A, R422D, R424A, R434A
Refrigeration

R134a*, R404A*, R407A*, R407C*, R407F*,


R22 Oil change
R507A*, R427A*

Low R22 R422D


Temperature
R402A, R402B, R408A R422A**, R428A**
(25C
50C) R502 Oil change R404A*, R407A*, R507A*

R13 R508B*, R410A*, R23*


Very low
temperature R503 R508B*, R410A*, R23*
(< 50C)
R13B1 R410A*, MO89

*polyol ester oil (POE) must be used


**R422Aand R428A are retrofit gases for R502 and will require systems to be suitable for R502 pressures and an expansion device suitable for R404A
The information is provided for guidance only. We make no warranties, expressed or implied, and assume no liability in connection with any use of this information. For further support please contact your local Linde supplier.

Linde AG
Gases Division, Seitnerstrasse 70, 82049 Pullach, Germany, Phone +49.89.7446-2399, Fax +49.89.7446-2071, refrigerants@linde-gas.com, www.linde-gas.com/refrigerants
Retrofit guide.
From CFCs to HCFCs to HFCs air conditioning.

CFC HCFC HFC


R12 Oil change R134a*, R427A*

Residential & R426A, R437A


light domestic R22 R417A, R422D, R424A
Stationary air conditioning

Oil change R407C*, R427A*

R11 R123 Consult supplier

Centrifugal R12 R423A


chillers R114 R124 Consult supplier

R236fa*

R22 R422D, R424A, R434A, R438A


DX chillers
Oil change R404A*, R407A*, R407C*, R407F*,R427A*
conditioning
Mobile air

Mobile air
R12 R437A
conditioning

*polyol ester oil (POE) must be used


The information is provided for guidance only. We make no warranties, expressed or implied, and assume no liability in connection with any use of this information. For further support please contact your local Linde supplier.

Linde AG
Gases Division, Seitnerstrasse 70, 82049 Pullach, Germany, Phone +49.89.7446-2399, Fax +49.89.7446-2071, refrigerants@linde-gas.com, www.linde-gas.com/refrigerants
Retrofit guide.
From HCFCs to HFCs.

No oil change R422D, R424A, R434A


High temperature (~ >0C)
Oil change R134a*, R427A*

No oil change R417A, R422A, R422D, R424A, R434A


Medium temperature (0C 25C)
Oil change R134a*, R404A*, R407A*, R407C*, R407F*, R507A*, R427A*
Refrigeration
No oil change R422A**, R422D, R428A**
Low temperature (25C 50C)
Oil change R404A*, R407A*, R507A*

Very low temperature (< 50C) No oil change R508B*, R410A*, R23*, MO89

No oil change R417A, R422D, R424A


Residential & light domestic
Oil change R407C*, R427A*

Stationary air conditioning Centrifugal chillers No oil change Consult Supplier

No oil change R422D, R424A, R434A, R438A


DX chillers
Oil change R404A*, R407A*, R407C*, R407F*, R427A*

*polyol ester oil (POE) must be used


**R422Aand R428A are retrofit gases for R502 and will require systems to be suitable for R502 pressures and an expansion device suitable for R404A
The information is provided for guidance only. We make no warranties, expressed or implied, and assume no liability in connection with any use of this information. For further support please contact your local Linde supplier.

Linde AG
Gases Division, Seitnerstrasse 70, 82049 Pullach, Germany, Phone +49.89.7446-2399, Fax +49.89.7446-2071, refrigerants@linde-gas.com, www.linde-gas.com/refrigerants

Potrebbero piacerti anche