Minimum Electrical Clearance.

APRIL 22, 2011 250 COMMENTS (HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/04/22/MINIMUM-ELECTRICAL-


CLEARANCE-2/#COMMENTS)

Minimum Electrical Clearance As Per BS:162.

INDOOR
Voltage in KV Phase to earth in mm Phase to phase in
mm
0.415 15.8 19.05
0.600 19.05 19.05
3.3 50.8 50.8
6.6 63.5 88.9
11 76.2 127.0
15 101.6 165.1
22 139.7 241.3
33 222.25 355.6

Minimum Electrical Clearance As Per BS:162.

OUTDOOR
Voltage in KV Phase to earth in mm Phase to phase in
mm
6.6 139.7 177.8
11 177.8 228.6
22 279.4 330.2
33 381 431.8
66 685.8 787.4
110 863.6 990.6
132 1066.8 1219.2
220 1778 2057.4

Minimum Working Clearance:

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 1/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles

OUTDOOR SWITCHYARD
Voltage in To ground in mm Between
KV section(mm)
11 2750 2500
33 3700 2800
66 4000 3000
132 4600 3500
220 5500 4500

Minimum Ground Clearance As Per IE-1956(Rule 77)

Voltage in KV To ground in mm
132 6.10
220 7.00
400 8.84
800 12.40

Minimum Clearance between Lines Crossing Each Other (IE-1957)

System Voltage 132KV 220KV 400KV 800KV


Low & Medium 3.05 4.58 5.49 7.94
11-66KV 3.05 4.58 5.49 7.94
132KV 3.05 4.58 5.49 7.94
220KV 4.58 4.58 5.49 7.94
400KV 5.49 5.49 5.49 7.94
800KV 7.94 7.94 7.94 7.94

Minimum Height above Railway As Per IE-1957

Voltage Broad Meter & Narrow Gauges


Above 66KV up to
14.60 Meter
132KV
Above 132KV up to 15.40 Meter
220KV
Above 220KV up to 17.90 Meter
400KV
Above 400KV up to 19.30 Meter
500KV
Above 500KV up to 23.40 Meter
800KV

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 2/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles

Various Air clearances to be provided as per IE rule 64

Voltage KV 33KV 66KV 110KV 220KV 400KV


BIL (Kvp) 170 325 550 1050 1425
P-E (cm) 30 63 115 240 350
P-P(cm) 40 75 135 210 410
P-G (Meter) 3.7 4.0 4.6 5.5 8.0
Section 2.8 3.0 3.5 4.3 6.5
Clearance(Mt)

Clearances from Buildings of HT and EHT voltage lines IE Rule 80

Vertical Distance
High voltage lines up to
3.7 Meter
33KV
Extra High Voltage 3.7 Meter + Add 0.3 meter for
every additional 33KV
Horizontal clearance between the conductor and Building
High Voltage Up to 11 KV 1.2 Meter
11KV To 33KV 2.0 Meter
Extra High Voltage 2.0 Meter + Add 0.3 meter for
every additional 33KV

Clearance above ground of the lowest conductor As per IE Rule 77

Over head Line Across Street


Low and Medium Voltage 5.8 Meter
High Voltage 6.1 Meter
Over head Line Along Street (Parallel To Street)
Low and Medium Voltage 5.5 Meter
High Voltage 5.8 Meter
Over head Line Without Across or Along Street
Low/Medium /HT line up 4.6 Meter
to 11KV If Bare Conductor
Low/Medium /HT line up 4.0 Meter
to 11KV If Insulated
Conductor
Above 11 KV Line 5.2 Meter
Above 33KV Line 5.8 Meter + Add 0.3 meter for
every additional 33KV

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 3/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles

Clearance between conductors and Trolley / Tram wires (IE Rule 78)

Low and Medium Voltage 1.2 Meter


High Voltage Line Up to 1.8 Meter
11KV
High Voltage Line Above to 2.5 Meter
11KV
Extra High Voltage Line 3.0 Meter

Clearances from Buildings of low & medium voltage lines(IE Rule 79 )

For Flat roof, Open Balcony, Verandah Roof and lean to


Roof
Line Passes Over Building Vertical 2.5 Meter
Clearance
Line Passes Adjustment of Building 1.2 Meter
Horizontal Clearance
For pitched Roof
Line Passes Over Building Vertical 2.5 Meter
Clearance
Line Passes Adjustment of Building 1.2 Meter
Horizontal Clearance
Advertisements

Top 10 Project
Software
Review a Free List of the Best
Project Management Software
Products - Start Now!
Capterra

FILED UNDER UNCATEGORIZED

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 4/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical) from Gujarat University. He has more than 14 years
experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical
Projects(Planning-Designing-coordination-Execution). He is Presently associate with one of the leading business group as a Deputy
Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical
Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for "Electrical Mirror" and "Electrical India" Magazines. He is
Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and
help technical enthusiasts to nd suitable solutions and updating themselves on various Engineering Topics.

250 Responses to Minimum Electrical Clearance.

S.CHELLAPPA says:
June 24, 2011 at 8:12 am
There seems to be an inadvertent error (probably typing error)Under the heading
Minimum Ground Clearance As Per IE-1957 (Rule 77), the heights are given in mm
Kindly correct the same

Reply
Shivaji Mande says:
May 9, 2012 at 1:26 pm
Jignesh sir,

Can you pl. explain, what should be the height of foundation of Indoor transformer (22KV, 1 MVA) from ground. Which
standard do we refer for that???

Reply
Vikas Garg says:
July 5, 2011 at 5:10 pm
i m Electrical Engineer with 2 year of experiance in grid construction and transmission. can u please suggest me some Electrical
handbooks

Reply
Ramachandra laxman says:
July 5, 2011 at 6:06 pm
Hai sir. can u please tell me what is the clearence between two phases in a 11KV indoor substation panel.

Reply
hari says:
July 20, 2011 at 12:37 pm
Hai sir.
can u please tell me what will be the clearence between phase to phases of 11 kv line & 220 line as when new 11 kv line to be
erected /passed just below at mid point tower of 220 kv line

Regards,
Hari Vallavah
Mail ID hari.v.sharma @gmail.com

Reply
Jignesh.Parmar says:
July 20, 2011 at 2:42 pm
Please refer Indian Electricity Rule abstract
h ps://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/
Minimum Clearance between Lines Crossing Each Other As Per IE-1957 Rules
System Voltage 132KV 220KV 400KV 800KV
Low & Medium 3.05 4.58 5.49 7.94
11-66KV 3.05 4.58 5.49 7.94
132KV 3.05 4.58 5.49 7.94
220KV 4.58 4.58 5.49 7.94
400KV 5.49 5.49 5.49 7.94
800KV 7.94 7.94 7.94 7.94

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 5/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
Sanjay Bhalodiya says:
May 20, 2013 at 9:16 am
Dear Mr. Jignesh,

Can you give detail of What is the minimum P-E clearance between conductor(Jumper) to IPS tube in air for voltage 420
KV as per dierent standard ?

P-E when IPS Eathed


P-P when conductor & IPS tube both charged.

Regards,
Sanjay Bhalodiya

agni says:
July 3, 2013 at 10:23 am
Sir Could you please tell me whether partition wall between HT & LT panel is required ?IF no please send me the IS codes
or any relevant documents

Gnanaprakash says:
July 19, 2013 at 3:53 pm
WHAT IS THE DISTANCE BETWEEN THE 33KV LINE POLES?ANY IE Rule?

saurabh pathak says:


June 26, 2014 at 11:55 am
what will be clearence between 11 kv parrel line

Jignesh.Parmar says:
June 27, 2014 at 6:58 pm
Already given in blog..in Safety clearance Post

edwin menezes says:


December 11, 2014 at 5:11 am
Jignesh Sir,
i have a questiuon. IS 110 KV overhead new line allowed in city corporation residential area as the house comes under it in
mangalore, karnataka ?

Sanat says:
February 2, 2016 at 10:17 am
Can you please conrm me the minimum clearance required for crossing national highway with 400 KV overhead
transmission line.

Awaiting your reply.

om prakash says:
December 12, 2011 at 5:00 am
Clearence between 11Kv & 220Kv when crossing is 4.58 Mtr

Reply
S A PATEL says:
August 27, 2011 at 3:26 am
Empty Drum to be removed from transformer area.

is it comes the Indian electricity rule -64 ?

Safety inspector has given the command to remove the empty oil drums from transformer yard.

is it ok as per ie rule 64 ???

Reply
Jignesh.Parmar says:
September 8, 2011 at 4:20 pm
IE-64
(iv) State in case of transformers or switches or static condensers involving the use of more than 2,275 litres of oil in one
chamber, if suitable oil soak pits are provided.
(v) Where 9,000 litres or more of oil is used in any one oil tank, has provision been made for draining away or removal of oil

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 6/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
which may leak or escape from such tank(s)?
9000 liters of oil in any one oil tank, receptacle or chamber is involved,provision shall be made for the draining away or
removal of any oil which may leak
or escape from the tanks receptacles or chambers containing the same, special precautions shall be taken to prevent the spread
of any re resulting from the
ignition of the oil from any cause and adequate provision shall be made for extinguishing any re which may occur. Spare oil
shall not be stored in an such
sub-station or switch station.

There is no any indication for Empty Barrel. If The Authorized person said to remove barrel as a safety view than it is
understood.Please follow one Golden Rule Do not argue the Person who have authority so follow Instruction of authorized
person to sort out issue.

Reply
Pradeep Kumar Yadav says:
September 14, 2011 at 9:57 am
Hi sir,

I am working in BHEL as a electrical engineer . Can you please tell me what is the minimum clearance required between 33 KV
underground power cable and GAIL gas pipeline. kindly reply me soon with some evident documents .

Ma er Urgent

Pradeep Kumar yadav

Reply
Jignesh.Parmar says:
September 14, 2011 at 4:50 pm
As Per QUATAR GENERAL ELECTRICITY CORPORATION

2.3 Telephone, Water, Sewerage & Gas Services


The service facilities for telephone, water, sewerage, gas, etc. shall not be permi ed to be laid within the cable reservations.
The following minimum clearances shall be
observed for respective service lines at crossing points. Such crossings may not be permi ed if the cables rating / integrity
will be aected in any way by the services to
cross the cable reserve.
Service/Utility Vertical clearance (Minimum)
Water & TSE Mains (to crossbelow EHV cable level) 500 mm
Water distribution lines 200 mm above cable protective tile Sewerage Mains (to cross below EHV cable level)=
1000 mm
Drainage= 500 mm below the cable or
200 mm above the cable protective tile
Gas pipes= 600 mm
Telephone lines =200 mm above the cable protective tile
LV / 11kV cables 150 150 mm above the cable protective tile

Reply
Pradeep Kumar Yadav says:
September 15, 2011 at 8:51 am
sir,
In my case the GAIL Gas line is approximately 1000mm below the ground and I am planning to keep power cable 500mm
inside PVC conduit below the Gas pipeline, I am unable to execute it due to lack of supporting document, can you please
suggest me any source for this.

Pradeep Kumar Yadav

Jignesh.Parmar says:
September 17, 2011 at 10:52 am
As per IS 1255
Clearances The desired minimum clearances are as follows:
Power cable to power cable Clearance not necessary;
however, larger the
clearance, be er would be
current carrying capacity

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 7/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Power cable to control cables : 0.2 m
Power cable to communication cable : 0.3 m
Power cable to gas/water main : 0.3 m

As per The Iranian Petroleum Standards (IPS)-160


FOR 400/230 volt.
Minimum vertical distance between power cables and gas pipelines in intersections.
TABLE 3
VOLTAGE MINIMUM DISTANCE METERS
380/220 volt 0.5
20 kilo volt 1
63 kilo volt 1.5

Henri Botha says:


June 5, 2012 at 1:48 am
Water pipeline to be 500mm from an 11kv MV cable?
Is this assumption correct?
Can you please advise?

Regards
Henri Botha
Electrical Superintendant
Ulan West Mines Australia

amin ur rashid khan mayo says:


September 16, 2011 at 1:45 pm
my learned sir,
i am not an electrical engineer but as an internal auditor i have to deal with them,here in pakistan.
we installed static meters on connection above 5kw,especially CNG connection escaping by paying penalty against LPF,how ever
the kvarh showing,consumer using ground earth system. notices issued to consumer for improving pf but in vain, do i proceed
further if u agree. thank you

Reply
antony says:
October 19, 2011 at 7:22 am
I have a 500kva generator supply a 53km 33kV line with over 8 transformers along dierents points of the load centres. th line is
built soundly but has a problem of tripping the generator everytime. i have been told its a problem of capacitance build up. can
you kindly explain what could be the problem with this line

antony

Reply
antony says:
October 19, 2011 at 7:24 am
can 150kVa transformer supply a 23km 33kv line? if yes after how long should the conductors be transposed

Reply
om prakash dashora , Assistant Manager , MPRRDA. Dhar says:
December 4, 2011 at 12:30 pm
How maney minimum vertical clearance should be adopted for highway construction under power line 400 kv.

Reply
Jignesh.Parmar says:
December 4, 2011 at 1:17 pm
Please refer Electrical Notes of This Blog..

Reply
Viswanath T says:
January 17, 2016 at 7:23 am
Kindly give the BS-162 equivalent IS Standard code for busbar clearance on indoor panel.

babsabM. Yunus Shaikh says:


December 7, 2011 at 6:16 am
can a portion(300mtr span) of 400kV HT overhead line be replaced with underground cable on the outskirts of mumbai. What
would be the cost and time for completion of 300mtr span. Please coment

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 8/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
sanjay says:
January 20, 2012 at 11:42 am
How to decide the busbar size & how to decide the electrical clearences between phase to phase ,phase to earth?

Reply
sanjay says:
January 20, 2012 at 11:43 am
What is the exact dierence between precision & accuracy?

Reply
prashant agrawal says:
January 22, 2012 at 4:48 am
i am a petrol pump owner wants to know about the minimum distance from over head high tension line (11-33kva) from a petrol
pump licence area.

Reply
Nazeer says:
July 25, 2012 at 6:23 am
Hi sir iam working in 33.2 mv substation. Here in daily 5 to 6 a day voltage uctuavatio (under voltage, over voltage) i want
to know what is the resens behind that fault.

Reply
gajendiran says:
February 8, 2012 at 3:48 am
i need clarication, minimum distance from Transformer HT side to fencing

Reply
vikas says:
February 8, 2012 at 3:11 pm
sir
my name is vikas working as surveyor in aptransco.
sir i can do towerspo ing manually .can i have any indian software for the tower spo ing .please refer

Reply
gajendiran says:
February 13, 2012 at 11:56 am
sir,

im gajendiran working as Electrical engineer in L&T.

minimum clearance between 22KV HT cable & LT ,LV cable in UG system

Reply
Jignesh.Parmar says:
February 16, 2012 at 5:05 pm
Please refer Abstract of CPWD and IS code of this Blog

Reply
Ejaz Ahamed says:
February 15, 2012 at 6:20 am
Hi sir,
Could you please tell me the minimum space required around an indoor substation(33/415v) so as to a ain re safety
requirements?

Reply
Naveen says:
February 25, 2012 at 2:25 am
pls refer any book for substation design. I want Know details of SAS also.

Reply
Nikita says:
February 26, 2012 at 6:02 pm

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 9/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Hi,
I am interested to buy an apartment near electrical transmission line (it looks like very very high power line).
Builder has maintained distance from centre line of powerline to building at 75 meters..
Is there any health hazard involved in living near high tension line?

Reply
Ar M S Devarmani says:
February 27, 2012 at 5:22 am
Please tell me what will be clear horizontal and vertical distance between 110kv line and building, as i am comming up with
resdiantial building beside 110kv line in karnataka. as per KEB SR

Reply
mega says:
February 27, 2012 at 11:26 am
why we have maintain phase to phase clearance? if we didt maintain the clearancewhat will happen?

Meganathan.A

Reply
Jignesh.Parmar says:
February 27, 2012 at 4:29 pm
R u Electrical engineer !!!

Reply
karthick says:
February 28, 2012 at 5:48 pm
y upper & lower lips have some gap for eating

ph to ph clearance to aviod short circuit of phase to phase

Reply
Marcos says:
June 25, 2012 at 12:17 am
For obvious reasons.
But there are indicated minimun values.
The real minimun I believe should be checked against line reactance and other parameters, as there may be for example loses
due to these factors.
(btw: i am not electrical, i am civil. Sorry for my comments, may be unaccurate or wrong)

Reply
manoj arora says:
March 23, 2012 at 3:56 pm
Hi Friends , Need ur advice ..

What should be the minimum vertical clearance between 11 KV HT ABC(3*35+75 sq mm) and 415 LT ABC(2*16+25 sq mm) . Both
the cables are crossing at one point ( Used for overhead distribution system)

Thanx in advance

Waiting for response


Manoj Arora

Reply
Jignesh.Parmar says:
March 23, 2012 at 5:52 pm
As Per IE Rules:
Low/Medium Crossing to 11KV to 66KV= 3.05 Meter

Reply
manoj arora says:
March 24, 2012 at 3:00 am
But i think it is for bare conductor , i need to know about cable (Both are cable)

manoj arora says:


March 25, 2012 at 7:47 am
waiting for advice
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 10/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
Jignesh.Parmar says:
March 25, 2012 at 10:36 am
Power cable to power cable Clearance not necessary;
however, larger the clearance current carrying capacity would be be er

Reply
manoj arora says:
March 26, 2012 at 8:13 am
didnt get you sir .

just wanted to know about this particular case:

11 KV HT ABC used for 10KVA Distribution Transformer , Further 415 V LT ABC for laying LT Lines

Reply
muthukumaran says:
March 27, 2012 at 4:16 am
Hi could you share What does the IEC mentions about the clearanace between phase to ground and phase to phase ,For the
variuos voltage levels?

Reply
sudarshan says:
March 28, 2012 at 2:10 am
We are going to installing in 11kv/420 transformer opencast mine in one shed.what is safe distance for installing control panels
and starters? what are safety we have to follow /

Reply
Abhishek Sarkar says:
March 28, 2012 at 6:26 pm
what is the minimum ground clearance required for a low tension aerial bunched cable line?

Reply
Hemant Sali says:
April 4, 2012 at 6:41 am
Dear Jignesh please correct the reference of Indian Electricity Rules as IE Rules 1956 instead of 57. Besides Central Electricity
Authority Regulations Measures relating to Safety and Electric Supply 2010 have replaced IE Rules. Refer Govt of India
Notication dated 24 September 2010.

Reply
Jignesh.Parmar says:
April 4, 2012 at 3:43 pm
Thanks for highlighting Typing ERROR.

Reply
Hemant Sali says:
April 8, 2012 at 9:44 am
I had also mentioned IE Rules have been replaced with the regulations as, safety measures for Generation Transmission
Distribution and Use of Electrical Power have so far been regulated by Indian Electricity Rules 1956 and as amended time
to time. These Rules were made as per the Section 37 of Indian Electricity Act 1910 by Central Electricity Board. After
enactment of Electricity Act 2003, the Indian Electricity Act 1910 stood repealed as per Section 185 of EA 2003. However
the savings from the same section clause (2) (c) states that:
the Indian Electricity Rules, 1956 made under section 37 of the Indian Electricity Act, 1910 (9 of 1910) as it stood before
repeal shall continue to be in force till the regulation under section 53 of this Act are made
As per the powers conferred to Central Electricity Authority (CEA), by section 177 clause (2) (b) read with section 53 of
Electricity Act 2003, stating to provide suitable measures relating to safety and electric supplynotied Regulations were
published on website of CEA. Its date of publish in Gaze e of India is 24th September 2010.

Jignesh.Parmar says:
April 8, 2012 at 11:12 am
Dear Completely Agree with You. But Still Lots of Engineer confused between IE Act and IE Rule and its revision (Further
Grid Code,supply code,GERC for gujarat).I have also faced a problem in one Interview in Power distribution company. I
could not succeed to explain interviewer about IE Rule and IE Act. Interviewer himself was confused between IE Rules
and IE act.By the way thanks for explained it deeply.

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 11/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Hemant Sali says:
April 8, 2012 at 9:14 am
for clearance between underground electrical cable and other utility service like gas, water, sewage pipe lines is there any
reference in IEC or IEEE

Reply
ram says:
April 14, 2012 at 12:26 pm
please send me notes regarding testing,commisioning,operation & maintenance of electrical equipments for132 kv s/s

Reply
Santosh Behera says:
April 20, 2012 at 6:20 am
Dear Jignesh
Could you please tell me the minimum clearance of 400 KV line from building, so that the electronics equipements like
communication panels, SCADA panels etc. will not be eected from electomagnetic induction.

Thanking you

Santosh Behera

Reply
Jignesh.Parmar says:
April 22, 2012 at 1:31 pm
As per IE Rules & CPWD Noms:
Horizontal Clearance of HT Line from Building is 2 Meter for 33KV and Add 0.3 Meter for Next each 33KV So for 440KV
It is 5.9 Meter.

Reply
Tahid Alli says:
May 3, 2012 at 2:48 pm
hi ,
sir i am satyam want to know about all ie rules in internet .plz help me.i am not belongs to elect. engg.

Reply
Senthil says:
June 19, 2012 at 4:44 pm
Hi Mr. Jignesh Parmer,

I intend to purchase an apartment near a 40 feet HT line (voltage unknown, probably 33kV), which is located 7 meters away from
the building. Is it safe to buy the house? What are the ill eects of having HT line near residential house? Could you please
advise?

Thank you In advance

Reply
akhilesh sharma says:
June 21, 2012 at 5:46 pm
sir, what sould be the min. distance between new petrol pump and 11kv line in national highway

Reply
Julian Rudzki says:
June 27, 2012 at 8:34 am
what is the minimum clearance between 100 mm water pipe and 11kv cable
Julian

Reply
ram chandra says:
July 5, 2012 at 7:46 am
sir.
Two lines ( one 400 Kv and other 200 KV) are parallel to each other, is any criteria for Maritain minimum distance between two
Parallel line.

Reply
Jignesh.Parmar says:
July 12, 2012 at 4:04 pm
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 12/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Please Refer Abstract of IE rules and CPWD of this Blog.

Reply
CHANDRASHEKHAR M says:
July 6, 2012 at 4:04 pm
HI ,

Sir, MY QUERY REGARDING 22KV LINE , LINE START FROM RECEIVING STATION AFTER 22 KV GANTRY A TAKE OFF
STRUCTURE IS ERECTED.

can we have a 22 KV , 300 amp drop out out door fuse for 3 phase 20 kv line , fault level is 16 KA.

i am working on project 20 kv line d/c where i have to install 300 amp out door drop out fuse on Take o structure.

Reply
CHANDRASHEKHAR M says:
July 6, 2012 at 4:12 pm
SIR,
FOR 22 KV FEEDING D/C OVER HEAD LINE WHAT SHOULD BE THE CLEARANCE FROM GROUND , PHASE TO PHASE
AND PHASE TO EARTH

Reply
mahesh.b says:
July 13, 2012 at 8:36 am
SIR PLEASE LET ME KNOW THE GROUND CLEARENS OF 66KV LANE PASSING ABOVE THE STREET AND THE
CONSTRUCTION DISTANCE (GROUND CLEAREANS ETC)

Reply
Jignesh.Parmar says:
July 13, 2012 at 2:11 pm
It is already given On BlogJust Read Abstract of IE Rule and CPWD.

Reply
Subhendu Mohanta says:
July 20, 2012 at 11:57 am
Dear Sir,
Kindly let us inform that, what is the minimum clearance to be maintained between wall & the transformer body. ( Note:
Transformer Rating : 33 KV, 15 MVA)

Reply
Shailesh tripathi says:
July 21, 2012 at 6:10 am
Hai sir please tell what is the minimum clearence between 11 kv HT line & 415 v LT line at the crossing.

Reply
Jignesh.Parmar says:
July 21, 2012 at 2:41 pm
Refer Abstract of IE Rules and CPWD of this Blog..

Reply
Lalan says:
July 28, 2012 at 1:13 am
Sir, can u please tell me is there any EMF (Electro Magnetic Field) norms in India to be followed for erecting 33 KV overhead line,
coz im following all norms as per IE 1956, but still Civil Court have injunction-ed my n stopped my line work

Reply
joshthangiah says:
July 29, 2012 at 7:15 am
sir, What is the minimum distance clearance from the Diesel tank to EB Sub station For giving NOC to install 15000 litres
Diesel tank in a private company which is very next to EB sub station ..can we allow..if there is an electical burst or disaster in
the EB sub station will it aect the diesel tanks of the pvt company

Reply
SYUKRI says:
August 12, 2012 at 1:45 pm
HI Sir
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 13/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Need to know the status overhead laying if HV and LV lay in the same pole, that is still under safety hazard or there is a dispute
act installation,,,,need comment,,,,thanks

Reply
Jignesh.Parmar says:
August 12, 2012 at 2:09 pm
Depend upon Your Country Nome,Rules&Regulation ..Normally not in Practice but if Required to do for min Clearance Refer
Electrical Safety Clearance Part-3 of this Blog.

Reply
Kapil says:
August 17, 2012 at 9:33 am
Sir,
Could you please tell us the minimum distance (horizantal) required between an underground storage tank storing class A
product (petrol) at a petrol pump and an HT (LT line also).
I have so much, but not able to nd any such rule.

Reply
Rsy Buxton says:
September 5, 2012 at 2:53 pm
Please let me know in feet the distance that power lines can be above ground level, sidewalks, streets, etc. My email is
pud56@aol.com. Thanks in advance.

Reply
Jignesh.Parmar says:
September 5, 2012 at 3:05 pm
Ground clearance,Street Clearance,Side walks for Power line for various voltage and Code is already given in the post of
Electrical Safety Clearance from 1 to 4 of this blog.
If you need distance in Feet just convert meter in to feet1Meter=3.28Feet.

Reply
lordakash1989 says:
September 6, 2012 at 8:49 am
I want to know the distance b/w two conductor of 400 kv transmission line.

Reply
Ravi says:
September 7, 2012 at 6:18 pm
Sir i wish to get clear details of the EHT 220kv OH line, Minimum Ground & Vertical Clearance,
the TLM ocials are confusing & its making some Unwanted delay & convince ,some times it makes us feel they are taking us
for ride & they are harassing.So please request you to kindly give me the proper details. Hoping for a positive response soon
Regards- Ravi

Reply
Jignesh.Parmar says:
September 8, 2012 at 2:53 pm
Ravi,
It is already given in the post of Safety Clearance 1to4 by various Code and Standard

Reply
Manish Shende says:
September 11, 2012 at 4:52 pm
Hello Jignesh,

What is the re Safety system required for 132 KV, 220 KV and 400 KV Sation.

and what re safety standard followed in India.

Thanks and regards


Manish Shende

Reply
Imam Jaer says:
September 25, 2012 at 12:48 pm

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 14/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Dear Mr Jignesh Can you tell me Minimum clearance required
between HSD 16000ltrs to Under ground HT cable of 33kv.

Reply
Jignesh.Parmar says:
September 25, 2012 at 2:51 pm
Please refer Post of Electrical Safety Clearance Part-1 to Part-6

Reply
sunil says:
November 6, 2012 at 5:42 am
i found voltage between R-phase to neutral was 300V , between Y-phase to neutral was 315V and between B-phase to neutral was
50V, and between earth to neutral was 175V. Neatral was not disconnted. what was reason of high voltage between neutral to
earth.

Reply
Jignesh.Parmar says:
November 6, 2012 at 4:58 pm
You will not get any diculty in three phase load but get serious voltage various ion between Phase and Neutral in single
Phase Load.
There are lots of Possibility of ge ing Voltage between Earth & Neutral.
(1) Neural Broken.
(2) Dry Neural Earthing Pit.
(3) Loose Earthing Pit Connection to Transformer Neural.
(4) In distribution There may be interchange between Earthing and Neutral.
(5) In Distribution eld somebody locally Earthed Neutral (Except TC Neutral Earthing) (Multiple Neutral Earthing).

For more reference read Neutral Floating Post of this Blog..

Reply
anil says:
November 22, 2012 at 9:23 am
hi jignesh
nice to see you running such a useful blog. a 66Kva line passes thru my commercial plot with two poles inside the boundary. i
propose to build a shed . can u please suggest me the distance as to how far from the pole end can i start my shed walls and also
how far can the slope of shed shud be from the wires???
thanx

Reply
saroj says:
December 10, 2012 at 12:27 pm
what is the vertical electrical clearance to petrol pump

Reply
Nachiketa says:
December 11, 2012 at 12:02 pm
Hi Jignesh

The minimum clearance laid down in the CEA regulations, 2010 does apply on industrial Units also? if no then what are the
limits and where do i nd this?
Thanks in advance

Reply
Kiran says:
December 28, 2012 at 12:00 pm
Hi . Can any one explain the basis from which electrical clearances are derived i guess they have been derived from
dielectric strengths of air.can any one elaborate this pls???

Reply
Jignesh.Parmar says:
December 28, 2012 at 1:56 pm
Yes denitely It depends on dielectric strength of Air..

Reply
Abhijit says:

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 15/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
January 8, 2013 at 8:16 pm
Sir,
For high voltage testing of SF6 GCB the clearances of 150kV/meter is sucent or not??? Please mention both clearances i.e.
vertical & horizontal.

Reply
Tushar Patel says:
January 10, 2013 at 6:45 pm
Dear Sir,

Recently ive bought a duplex in baroda and after i bought it, i get to know that my duplex is near to this Hyper Tension wire
line. after discussion with the builder i found that he has left 12.30ft space between the house and the H. T. Line.

I would like to know


whether it would be sucient distance between house and H. T. Line?
would there be any precaution i should take?
the house is ground+1 oor, can we build 2nd oor if we want to in future?
can there be any health issues if we leave close by H. T. Line with the distance of 12.30ft?

I do hope that you would be kind enough to enlighten me with your knowledge and experience.

Thanks
Tushar

Reply
ram says:
January 14, 2013 at 8:28 am
Dear sir
I am planing to purchase 1 plot near HT lines. Distance between ht line & plot is 15m . Kindly suggest me is there any problem to
helth if i built home at that place

Reply
sam says:
March 6, 2013 at 9:06 am
hello sir,
I am doing a project in simulation. I want to know the distance between the lowest conductor of transmission line (carrying
345kV) and the ground.

Reply
Ankur says:
April 11, 2013 at 5:34 am
Hi,

Could you please provide minimum electrical clearance required between phases of 11 kV Air break switch. A copy of
supporting document would be appreciated.

Reply
U am Du a says:
April 30, 2013 at 4:20 am
Can you please tell me what should be the gap between LV panel to back side wall and side clearance with anothe LV pannel.
and please tell me the same thing with HV pannel
Here LV means 415 V and HV means 6.6KV

Reply
Jignesh.Parmar says:
April 30, 2013 at 2:12 pm
Please refer old post of this Blog..Safety Clearance Part 1 to 5

Reply
gajen says:
May 1, 2013 at 12:34 am
for LV panel 300MM OR 1000MM (ACB PANEL OR APFC)

HV 1200 MM

Reply
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 16/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
O.P.Bansal says:
April 30, 2013 at 12:54 pm
Pl. intimate me horizontal clerence for 400 kV and 220 kV transmission lines

Reply
Jignesh.Parmar says:
April 30, 2013 at 2:12 pm
Please refer old post of this Blog..Safety Clearance Part 1 to 5

Reply
O.P.Bansal says:
May 1, 2013 at 8:59 am
Can a 400 kV transmission line run in parallel to 220 kV transmisin line with a disatnce of 5.94 mtr. between their condcutor.

Reply
Dharmesh says:
May 15, 2013 at 5:58 am
HI Jignesh,
Can u please tell me the Dos & Donts for developing the Land by a Developer after laying underground 66KV Cable?

Reply
Dharmesh says:
May 21, 2013 at 12:09 pm
Dear Jignesh, please answer the above question . Id be very thankful to u..

Reply
Chirag Gandhi says:
May 31, 2013 at 7:10 am
Dear Jigneshbhai,

How r u? Your knowledge is very useful to us so many many thanks to u.


And want to ask what is the power line crossing clearances for 1200 kV line to another power lines and give the refrence le so I
can so to other and in IE rules it is given? If yes than plz. provide it to me.

Thanks a Lot.
Chirag Gandhi

Reply
rameshan says:
July 25, 2013 at 8:22 pm
subsequent to Indian Electricity Act 2003, the basis of Electrical safety also changed wrt said act in place of IE Rule 1956 or rules
prior to 2003. Please detail the clauses/acts wrt to Indian Electricity act 2003.

Reply
Guruda says:
July 26, 2013 at 7:54 am
Respected Sir,

Please clarify whether Emergency Door /Window can be placed near Transformer yard.

Regards,
Guru

Reply
pankaj says:
July 26, 2013 at 2:46 pm
ht clearnce

Reply
Fernando says:
August 1, 2013 at 7:03 am
Sir, Pl Clarify if we can build a road across (North to South) of high tension line in our land? There are 2 HT lines running from
East to West one 110000volts and the 2nd one is 230000 volts in our site. What is the ground clerence required.

Reply
Shatrughan Yadav says:
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 17/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
August 3, 2013 at 11:25 am
What is the minimum allowable residual AC and DC voltage for operation /maintenance of electrical circuit??
It is the voltage that persists in the phase after disconnection of the equipment!!!

Reply
Sub Division ocer M S E D C L says:
August 21, 2013 at 4:45 pm
Plz give an idea of state highway crossing 11 kv and Lt line
vertical and horizontal clearance from ground .
and whom should shift HT/LT lines along the roads

Reply
ravipvr05 says:
August 22, 2013 at 2:23 pm
For 33 kV
1. What should be the distance between two poles (Rail pole)
2.What is the calculation for conductor sag between two poles
There are any standard specications for these??

Reply
anoop says:
September 21, 2013 at 6:26 am
CAN U PLEASE GUIDE ME ON GROUND CLEARANCE OF 33KV , 66KV , 132, 220 AND ABOVE LINES AS PER IE
IS THERE ANY CHANGES IN RULE 77, IE 1956 IN ELECTRICITY ACT 2003?????

ANAND

Reply
SUSHIL says:
September 24, 2013 at 2:33 pm
Hello Sir,

Can you please tell me,


Allowable distance between Electrical & other network [may be water,fuel line] in Underground MEP services.

please share NEC/BS/else standard details.

Thanks in advance
Sushil
Qatar

Reply
Jignesh.Parmar says:
September 24, 2013 at 3:08 pm
Already given in the Blog with reference Standard..

Reply
Rahul says:
July 28, 2016 at 5:37 am
Sir Could you please tell me whether partition wall between HT & LT panel is required ?IF no please send me the IS codes
or any relevant documents

anoop says:
October 7, 2013 at 6:23 am
Mr. Jignesh parmar their is a amendment in the indian electricity act 2003 in 2005, u have not mentioned dat here, the standars
for safety i.e, the ground clearance is changed!!!
please have a check on this and then reply

Reply
Rudrendra says:
October 16, 2013 at 6:56 am
what should be the minimum clearance required between to two parallel 33KV lines

Reply
Jignesh.Parmar says:
October 16, 2013 at 6:13 pm
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 18/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Already given in the blog..

Reply
Rudrendra says:
October 16, 2013 at 7:00 am
How to reduce the earth to neutral voltage (other than earth pit)?

Reply
baljeet singh says:
October 22, 2013 at 10:24 am
I have one ac high voltage test set , I want to know what is the minimum distance to be leave from the false sealing to phase point
, Phase point is at the height 1.5 mtr from the ground level .we will give the voltage between phase to earth with the sample up to
100 kv
,

Reply
shamsul bahari saad says:
October 23, 2013 at 4:59 am
Dear Mr Jignesh. I came to know that the BS 162 was replaced by BS 7354. Any changes on the minimum electrical clearance for
indoor & outdoor? Can you share the BS 7354?

Reply
k.shanmugaraja says:
October 25, 2013 at 6:53 am
sir what is the distance between lpg storage godwon and 110kv line

Reply
Jignesh.Parmar says:
October 26, 2013 at 6:09 pm
Already given in the Blog..

Reply
Yatindra says:
December 1, 2013 at 12:40 pm
Thanks

Reply
asad says:
December 23, 2013 at 2:26 pm
can u tell me shall our company lay the pipeline below 110 kv line?or how much we hv to maintained ?

Reply
Latif Ahmad Parray says:
January 25, 2014 at 7:43 am
Please guide me with , the minimum horizontal clearance between the conductor & the building incase of 220KV & 132KV
transmission lines. Also do we have to keep some additional clearance for conductor swing due to wind etc.

Reply
siddu says:
January 26, 2014 at 5:49 pm
hello sir,
In my case, 400KV line has been erected by PGCIL without prior notice and no compensation given to us. Is this possible or any
electricity act is there to erect without giving compensation. It is huge loss to us because 1.5 hectares land is laid with 400KV line.
Please suggest what i can do? can i get compensation? no trees.
from siddu

Reply
nitin mishra says:
February 15, 2014 at 11:41 am
Please suggest that on transmission line 132KV for crossing of railway line which type tower is required and what should be
ground clearence for that

Reply
Soumen says:
March 6, 2014 at 8:01 am

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 19/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
When a pvc cable(6 sq mm, 2core) for lv consumer is passes by two adjacent building what is the horizontal and vertical
clearance should be maintained?

Reply
Mohit Thali says:
March 7, 2014 at 4:59 pm
11kV tranmission wire is going to pass by my house will it have any eect and what is the minimum distance between the wire
and house wall

Reply
Bhawgati Prasad Jangir says:
March 8, 2014 at 11:23 am
Hi Mr. Jignesh, is there any separation criteria between 33kV & 220kV underground burried cable recommended by code ??

Reply
SIVA says:
April 11, 2014 at 5:27 am
Dear sir,

i need indoor clearances PHASE TO PHASE AND PHASE TO EARTH FOR 11KV,22KV,33KV as per IEC STANDARD.

Reply
angelito cortez says:
June 19, 2014 at 7:19 pm
thank you so much.GOD bless you,please may i know the minimum and maximum distance between two tower overhead lines
33 kV.or standard distance tower to tower ?conductor size 366.2 Sq.mm

Reply
RAMACHANDRAN S says:
June 23, 2014 at 6:58 am
Dear Sir,

Is the above given busbar clearance between phases is same for CU & AL or what.?

Reply
Salil Swarendra says:
July 21, 2014 at 4:21 am
minimum clearance to be maintained between 33kv line crossing 11KV line

Reply
santosh says:
July 21, 2014 at 11:04 am
Dear Sir,

One of our project we have erected 22kv switchgear for substation and we have used armoured cable that is bo om entry for the
switch gear we have removed the outer sheath of the armoured cable for a 0.5meter and connected to the switchgear bus bar.the
problem is there is cable tray carrying armoured cables which is used for control purpose to the plc panel which is in bo om
trench the distance between the cable tray and 22kv cable is 200mm.
my questions is since The 22kv cable running near by cable tray it will eect the control cable signals in the cable tray.

if yes what should be the distance between the cable tray and 22kv cable as per IEC std
and also send me calculation for this.

Looking forward for your response

Reply
B L Prakash says:
July 27, 2014 at 4:39 pm
very useful

Reply
U am Du a says:
August 5, 2014 at 11:11 am
Can any body tell what should be the minimum distance maintained from 415 V MCC to side walls and what should be the in
between distance to be maintained in between two MCC (415V) panel as per IS

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 20/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
Surender Chaudhari says:
August 7, 2014 at 9:27 am
Sir,
What should be the min distance between 220kv transmission line & wind turbine.

Reply
krishnan says:
August 9, 2014 at 7:01 am
Hi Sir ,

The information shared is very much useful . I am planning to buy a at in chennai near perumbakkam and a HT line of 11 KV is
passing 15 meters near the building . I was worried a bit but I am condent to proceed with the plan after reading your article .
Thanks a lot .

Regards
Krishnan

Reply
yogesh says:
August 20, 2014 at 2:57 pm
hello sir,
a 1200 kv electricity transmission line is about to pass above my lawn.the line will be below the terrece of my house at par as the
inclination of the line form the lower post to the upper post is around 45-50 degree as it is a slope..my questions to you are,
1)what should be the minimum distance between the wire and the house.???
2:what should be the minimum height of the wire from my lawn..??
3:what are the health risks ???
thank you and regards
yogesh sapkota
sikkim,INDIA

Reply
harish says:
September 16, 2014 at 4:35 am
Can anyone give me any standard /reference for horizontal/parellel clearance of 400kv line from national highway. 4km line is
proposed parallel. For tha purpose i want to know this clearance standard.

Reply
harish says:
September 16, 2014 at 3:25 pm
Kindly tell me any standard reference for the horizontal/parallel clearance required for the 400kv proposed transmission line
from national highway.presently suggested rout by surveyor is 20m away from the national highway and it is running Parallel to
NH upto 4 KM distance.
Can i get any standard which gives clearance details.

Reply
hemant says:
September 25, 2014 at 1:19 pm
Dear,
I am planning to buy at , which is located somewhat roughly about 500 meters away from 66kV power substation , is it safe . As
I am not aware of such things but confused on reading few details on web that it may cause cancer.(emf).
kindly share your knowledge and give your expert view.
Thanks

Reply
Rotchill Pineda Cejar says:
September 30, 2014 at 9:09 am
good day sir,

thank you for sharing with us i would like to know the vertical clearance of 13,2kv line constructed under 69kv line. thank you
and best regards.

Rotchill P.Cejar
Philippines

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 21/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
Jees says:
October 7, 2014 at 7:17 am
Sir can I build a one story home under 400 kv line is there any violation what all documents are needed to get the permission and
is there any health hazards bulding home under 400kv power line

Reply
Murugan.S says:
October 9, 2014 at 5:10 am
Sir , a diesel pipe line ca cross the cable tray or not. if yes what should be the clearance. if not reason for that. please reply me sir.

Reply
Aditya VIbhute says:
October 11, 2014 at 5:49 am
Sir, What should be the clearance between DTC & Water body?

Reply
markellis312 says:
October 21, 2014 at 6:03 am
I am Rekesh and i am an engineer in electrical i done my engineering from Gujarat university i have 5 year experience in DTC &
water body. I wanna join your organization.

Reply
Lymperis George says:
November 6, 2014 at 2:12 pm
Hello Sir , I wonder if it is theoretically possible to have 11kv line and 33kv line on the same poles? I understand that minimum
separations between 11kv and 33 kv needs to be 355mm, therefore it seems possible . Do you know of any precedents ?

Reply
satyanarayana says:
November 15, 2014 at 4:39 pm
Hello Sir,

I am Satya, my house is under the 2 lines of high voltage wires, and frequently i am noticing earthing problem for my equipment
can you pls. suggest can i use earth pits for my residence and the wire is 15 feet above from my ceiling
or pls. suggest how to keep my electronic safe

Reply
askar says:
November 19, 2014 at 4:46 am
what is minimum clearance required form communication cable to MV/KV power cable?

Reply
Pingback: oering free bingo

A.K.Malek.GETCO, S.E.(TR),Palanpur. says:


November 30, 2014 at 3:54 pm
What is minimum clearance as per rule between 66 KV UG power cable and CNG gas pipeline
to be laid under ground beneath power cable.

Reply
Jignesh.Parmar says:
November 30, 2014 at 4:54 pm
Sir,
As per Qatar General Electricity and Water Corporation standard
for 63KV Distance between Cable and Gas Pipe line Horizontal 3 Meter and Vertical 1.5 Meter.

Reply
chandrasekhar says:
December 12, 2014 at 4:47 am
If a transmission line ( 11 Kv/33 KV etc) running parallel to 2X25 Kv traction line for a distance of 1 Km-3 Km
what will the induction eects and what should be minimum horizontal distance to be maintained between traction and
transmission lines rnning parallel please post calculations with some examples

Reply

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 22/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
sk says:
December 16, 2014 at 5:40 am
What should be dieance between 11kv line and tree according to indianelectricity rules

Reply
guru says:
December 22, 2014 at 9:45 am
Hi..
can you please tell me the safe distance from 66KVA for building the house in bangalore.
also is it OK to keep a GAS cylinder near 66KVA power line.
please suggest.

Reply
SK says:
December 24, 2014 at 8:11 am
Minimum vertical ground clearance of 66 KV and above lines over National Highways as per IE Rules/CEA Rules.

Reply
satsh reddy says:
January 7, 2015 at 6:20 am
Dear Sir, in HT & LT transmission lines crossings general LT line was bo om & HT line was upper. what happens if its vice
versa( HT bo om & LT uppeer)

Reply
Md.Monjurul Alom says:
January 28, 2015 at 4:01 am
Dear sir, Building rooftop to 33KV Electrical line distance (Horizontal & Vertical Clearance)

Reply
Mohammed Hussain says:
February 11, 2015 at 6:08 am
Dear sir can i have BS:162 document

Reply
eswar says:
March 8, 2015 at 4:50 am
pls tell me distance between 800KVDC over head power line and voice communication(.3 khz to 4khz) under ground cable

Reply
says:
March 16, 2015 at 5:22 am
we are using the channel of 2390mm for 33kv subtransmission line using open conductor. Does it may cause any problem due to
inductioon or not???

Reply
Azad Rasheed says:
March 26, 2015 at 8:40 am
whats the minimum clearance between 132 kv outdoor step up transformer with human???

Reply
L M AGGARWAL says:
April 2, 2015 at 2:19 pm
What should be the height of 4 pole DP structure with an 33kv 3-phase isolator on top and operable using a gangue rod with its
handle at bo om , bushings , insulators and for termination of each incoming and outgoing 2 nos 33kv cables. Also , pl clarify if
there is a minimum requirement of 11m or 13m height of pole structure under certain conditions ?

Reply
vishwas says:
April 9, 2015 at 5:31 am
jignesh sir,
i want to know if mpeb not follow the rule of minimum clearance from residential house for shifting 33 kva ht line so what action
we can take.please suggest me .

Reply
SHAHZAD says:

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 23/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
April 23, 2015 at 8:27 am
Dear Sir,what will be the minimum clearance of 380 kv cables from severage PIPE
line above ground.KINDLY GIVE THE REFERENCE ALSO.

Reply
Amit says:
April 27, 2015 at 5:49 am
I m in Oman,as per one tender scope we have to construct chain link fencing in switch yard,where we have Power transformers
installed,can you tell me min how much safety horizontal clearance should be maintained from the fence is the system level is
132 kv & 220 Kv.Plz help

Reply
AJIT KUMAR DASH says:
May 8, 2015 at 12:22 pm
my home is 300mtr distance from service electric.i have an ac and it is not take load when on.i have 5 kv stablizer also,how can i
use ac pl tell me.

Reply
paranthaman says:
May 11, 2015 at 3:25 pm
sir, i have agriculture land 0.5 acre in tamil nadu, erode dist.
110kv cable crossing exactly middle on the land.
i want to make poultry farm in this land.
what is the rules for this.please help me.
thank you.

Reply
manish chovatia says:
May 21, 2015 at 3:20 am
How many distance between transformer and diesel generator as per ie rules

Reply
Raju says:
May 27, 2015 at 8:31 am
clearance to be maintained for 110kV Lines to Air port

Reply
rahul patidar says:
June 19, 2015 at 8:53 am
i like ur prole jignesh sir
and i want a qns to u relates my project..
can i

Reply
rahul patidar says:
June 19, 2015 at 8:58 am
how should measure the emf from 35kv line, which are going from in front my college building, indore

can mobile apps(EMF sensor, EMF detector) give a accurate value,if we do the analysis of my college campus.

Reply
siva says:
July 13, 2015 at 10:26 am
Dear sir,
what is the distance required between 11 kv cable and LT cable in a same trench ? Any partition wall is required between HT and
LT cables ?

Regards
M Siva

Reply
Lgalang says:
August 4, 2015 at 3:53 am
Hi sir,

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 24/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
What is the minimum clearance of between the underground electrical lines and water lines with related specic code or
standard.

Thanks

Reply
Manoj Mondal says:
August 10, 2015 at 9:35 am
what should be the minimum distance between ht panel & transformer??

Reply
sonjoy says:
August 27, 2015 at 1:41 pm
for a 400 kv line what would be the spacing between the phase conductor

Reply
naveen kumar dwivedi says:
September 6, 2015 at 6:59 am
what should be minimum clearence above HFL in navigable river.

Reply
Channabasavaraju.M.D says:
September 18, 2015 at 8:37 am
As per the IE Rule 1956 or K E B act 2010 what is the minimum safety distance should maintain for installation of H S D U/G
storage tank I.e either transformer or HT line

Reply
Ramesh says:
October 18, 2015 at 8:27 am
Dear sir please tell me pole/tower heights for dierent voltage levels i.e. starts from 11kV to 400 kV.

Reply
Pradeep Chauhan says:
October 31, 2015 at 10:35 am
Dear Sir,

Please can you tell me what should be the ground clearance between HV side and ground

Reply
Udayaprakash says:
November 6, 2015 at 6:53 am
i am studying electrical and electronics engineering,i want real time detail about transmision and distribution.

Reply
bharath says:
November 9, 2015 at 7:13 am
Dear Sir
please tell me what is the gap between 11kv 630kva transformer and 11kv single ht breaker panel and is there required any re
wall between those two equipments. any documents to be refer

Reply
bharath says:
November 9, 2015 at 7:17 am
Dear sir i have a doubt what should i maintain gap between 11kv 630kva transformer and 11kv ht breaker panel and is there any
requirement of re wall between them please suggest any standard document to be followed

Reply
Mohammad Azam Khan says:
November 18, 2015 at 5:01 am
I think IE-1956 has been revised/updated. What is the clearance for 33 kV as per revised rules.

Reply
sivasubramanian says:
November 18, 2015 at 2:10 pm
Hi sir we are planing to lay a 33 KV transmission line which IS stand i can refer and,
what is the distance i have keep with existing 11 kv line as per stranded.
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 25/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
JayMachave says:
December 2, 2015 at 4:57 pm
Hi Sir
Plz tell me the minimum clearance for petrol pump from 400kv Substation and 440/220 kv line.
And which book should be refer for this.
kindly reply to jay.machave@gmail.com

Reply
Akhilesh Verma says:
December 22, 2015 at 12:52 pm
Hi Jignesh
Can you provide me the IS/IEC Ref & details for phase to phase clearance for 415V V System.

Reply
rupesh sharma says:
December 28, 2015 at 5:51 am
sir can you please reply on rupeshharitash@gmail.com for my following query
what is the minimum distance requirement for two 66kv/11kv transformers in dence residential
area.will be highly thankful for your responce

Reply
thana says:
December 28, 2015 at 8:08 am
why indoor and outdoor phase to phase and earth clearnce is dierent.pl explain ..

Reply
Mr Kanot perme says:
January 4, 2016 at 3:01 am
Hi I am Mr perme from Arunachal, there is a 132kV overhead line as well tower erected and passing near my house.So you plse
suggest me the required clearance of 132KV tower and over head line from my house?

Reply
Sanjay Gwande says:
January 23, 2016 at 7:28 am
Dear sir we have to install 11kv/0.440 v [2500kva] transformer and our LT load is more than 2800 amps so we have no any adea
regarding distance between transformer and LT panel to save power losses so sir plz guide to us how much distance required
between transformer and LT panel.

Reply
Ankur says:
February 4, 2016 at 2:36 pm
what is ground clearaance in100kv & 1200kv?
Please reply

Reply
jeevan says:
March 11, 2016 at 8:30 am
Hi what is the mininmum distance from ground to cable tray in a working area.

Reply
Tapan Desai says:
April 15, 2016 at 6:53 am
Hello Sir,
Please say Distance between P-E & P-P in SF6 Medium

Reply
Nitin Mallan says:
April 22, 2016 at 1:28 pm
hiii. I am an electrical enginnering student. I wanted to know if there is a 220 KVA Line, what is the working height and
conduction limit from ground.

Reply
sudhir says:
May 3, 2016 at 11:49 am

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 26/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Can we keep 800kv electrical generator control panel outside , the temp more than 50 degree cel

Reply
Nouman Akram says:
May 4, 2016 at 9:01 am
Dear Sir,
What is safe surrounding clearness distance for 11 KV power cables ( 500 mm2 )?

Reply
G S Sharma, Electrical Engineer (Construction of lines and GSS) says:
May 14, 2016 at 7:21 am
Dear Sir, please tell about the mid span clearances of dierent voltages ranging from 11 kv to 800 kv with dierent roads
categories like metalled road, highways, NH, Mega highway express way etc

Reply
Krishnan says:
May 19, 2016 at 11:38 pm
I bought a at, and a 220KV EHT goes through it. The distance of cables from the towers are around 8-9 metres, is this safe to
habitat?

Also, our society is interested in moving this EHT line. How do we go about doing it?

Reply
Rudrendra says:
June 14, 2016 at 6:43 am
Can any body share the standard heights of P,R,S la ice type towers used in 132 KV Transmission line

Reply
Rudrendra says:
June 14, 2016 at 6:45 am
What is standard voltage and frequency variations for dierent voltage levels

Reply
Rudrendra says:
June 14, 2016 at 7:02 am
What is basic consideration while selecting the insulation voltage level of power cables.

I mean in 415 V LT cables there are three standards available in the market like 500 V,690V & 1.1 KV. How to select which one is
suitable for our requirement.

Reply
Sumit Parihar says:
June 17, 2016 at 4:50 am
Sir i want to get knowledge about sub station installation on HT cable
1). If I have incomming side 33 kv VCB of 3500 KVA and i want to distribute its outgoing supply ( 33 kv) with the help of ABC
cable to 4 nos of 1000 KVA transformers.
2) Can it be done with the help of bus-bar of 33kv level, if so what should be the separation between R-Y-B bus bars & Four
connecting cables of same phase on R phase bus-bar

Reply
Manjunath Ukkali says:
June 28, 2016 at 8:56 am
dear sir,

what vertical clearance required HT line to trasformer yard

Reply
Manjunath Ukkali says:
June 28, 2016 at 9:08 am
Dear sir,
Can we install trasnformer yard below the HT LINES need your guidelines.

thank you
Manjunath

Reply
https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 27/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
lutendo says:
July 9, 2016 at 7:53 am
can you please dene high voltage clearance

Reply
Birendra Kumar Singh says:
July 12, 2016 at 7:25 am
What are the standards for clearance between communication cables, ABC cables and cables and ground for 230/400 & 11kv and
33 kv lines? Also between cables and line conductors.

Reply
vivek says:
July 13, 2016 at 3:17 am
,
220

minimum clearance from house/ building.

Reply
Rajnish Pandey says:
March 14, 2017 at 11:49 am
IE 79 & 80

Reply
Rahul says:
July 28, 2016 at 5:38 am
Sir Could you please tell me whether partition wall between HT & LT panel is required ?IF no please send me the IS codes or any
relevant documents

Reply
Karma Dorji says:
August 16, 2016 at 11:01 am
How much is the minimum distances between 132 Kv electric line and the mobile tower nearby ????

Reply
Naresh Kumar r says:
August 20, 2016 at 12:58 am
In 220 kv line oil leakage observed from Current transformer. What may be the reason for leakage and how to rell the oil

Reply
PRATIK ANAND says:
September 24, 2016 at 7:50 am
sir ,what is the distance between train roof and electrical cable.

Reply
Ramesh Veerschowdappa says:
September 30, 2016 at 1:03 am
Sir,below 220KV line to what extent we can grown plant what about compensation given to farmers to cross cultivating land

Reply
Santhosh says:
October 24, 2016 at 9:13 am
Can you help me regarding busbar phase to phase clearance for AC panel for solar project (12 In, 1 Out), which is placed outdoor
(We have given IP65 cubical enclosure for outdoor) and also please let me know in which IEC edition busbar clearance is
mentioned with table, or in any British standard or in Indian standard edition, any of these. one of my client is asking for proof
mentioned in electrical standard book.
Now as per our LT panel of 415 Volts, Input busbar phase to phase clearance given is 50mm, Output busbar phase to phase
clearance given is 27mm. Input Busbar used is 20/6mm for 100Amps MCCB, output busbar is 2 runs 60/10mm for 1000 Amps 4-
pole ACB

Reply

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 28/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
EE says:
October 26, 2016 at 11:51 am
what should be the safe distance between a petorl bunk and EHT line

Reply
Haresh says:
November 28, 2016 at 9:30 am
Dear Sir,
Your blog is very informative. I am Not an electrical engineer.
My Question- In India, in bigger cities In typical apartment building or society (say having 150 Houses) the builder has made
a substation with Step down transformer. So the supply Voltage to HV side of transformer would be 11 or 22 or 33 KV.
In the same place there are single houses and bungalows. The distribution company of the state is providing a 230 Volt supply
for them.
My Question Why cannot those 150 houses be provided a 230 Volt supply each directly by the Maharashtra State Electricity
Board?
My question is when a 230 Volt line is already in place, then why bigger society is required to make their own substation.
After Installation and commissioning, whom does Substation belong to Electricity board or Society/Builder?

Reply
sreehari says:
December 2, 2016 at 10:36 am
Mimimum distance maintain HT panel feeder to transformer incomer

Reply
nirmal soni says:
December 27, 2016 at 7:03 am
What clearance required for UG power cable and UG water pipe line

Reply
kartheek says:
January 4, 2017 at 10:41 am
Dear sir,

Am designing the LT panel

LT GRADE 440 V AC, R,Y,B,N AND E 4000 A, I (SC)50 KA. and temperature rise for 4 hours.

Kindly suggest us the clearance for phase to phase ,phase to neutral and neutral to earth .

Bus bar selected Aluminium 125 x 10 mm

Karthik.M.S.

Reply
kartheek says:
January 6, 2017 at 6:54 am
Dear sir,
kindly let me know any handbook for
1. Electrical panel building
2. IS / IEC STANDARDS

Reply
Raj chouhan says:
January 8, 2017 at 4:15 pm
Mujko 440 kv tower par kam lagna h mere saath 3-4 log h

Reply
Mayank Mistry says:
January 24, 2017 at 7:26 am
Dear Mr. Parmar ,

What should be clearance between a lighting pole ( 12 mtrs ) with 6 nos LED 250W ood lights and HT overhead lines ( 35KV )
passing over a sports eld . Are there any refernce and statutory guideline books / standards for the same. Where to refer ?

Mayank

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 29/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
Reply
Narayanaswamy.T.M says:
February 1, 2017 at 6:35 am
Dear Mr.Jignesh Parmar, Pls let us know the Low Voltage Panel around clearance for the installation.

Reply
NDIKUMANA Jean-Claude says:
March 9, 2017 at 6:20 pm
Dear Sir, Jignesh,
Thank you for your kindly such as Technical grand brother in Engineering for all response you shared with us. My question is
what poles plumps used for in MV lines of 11kV?

Reply
Rajnish Pandey says:
March 14, 2017 at 11:47 am
Dear Mr.Jignesh,Could you please explain a case study- My building is having a horizontal distance less than 1.2 metre from a
concret electric pole which is not having any iron angle and the the low voltage wire has been wined through the white insulator
which is directly on the pole.
As a remedy can i put an Iron angle projected towards the street and shift the low voltage wire in order to increase the horizontal
clearance from my building.

Reply
Tapas Maity says:
March 23, 2017 at 6:04 am
Kindly give the IS Standard code for busbar clearance on indoor panel for 415 volt system

Reply
Irfan says:
March 28, 2017 at 3:34 am
Please tell me what is the min allowable distance between 33 KV parallel feeders

Reply
rudra says:
July 16, 2017 at 8:53 am
2.5Mtrs

Reply
Dalisux says:
March 29, 2017 at 1:47 pm
What is your minimum clearance between shield wire and phases in a 33kV line?

Reply
Kalachand Sikdar says:
April 17, 2017 at 5:16 am
Sir, 400kv Busduct is running from the top of the control room and just below SCS system is available where engineers have to
work frequently. Is it safe to work under this environment?

Reply
Borad Harshad says:
April 26, 2017 at 4:59 am
Express highway Clearance ?

Reply
Borad Harshad says:
April 26, 2017 at 5:02 am
See how much land level is from the express highway ?

Reply
kuldip raj suri says:
May 10, 2017 at 11:11 am
what should be clearance in 220 kv line phases when source is same and on same cross arm

Reply
rudra says:
July 16, 2017 at 8:49 am

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 30/31
11/9/2017 Minimum Electrical Clearance. | Electrical Notes & Articles
4.5Mtrs

Reply
Parag Sharma says:
May 11, 2017 at 6:47 am
I assumed HT line is very near to my at which is at 4th oor can you pls give me idea on minimum safety criteria on distance
from balcony to HT line etc.

Reply
rudra says:
July 16, 2017 at 8:51 am
Horizontal 2Mtrs for 33KV level +0.3mtrs for every 33KV
Vertical 3.7Mtrs for 33KV level +0.3mtrs for every 33KV

Reply
Vasantakumar says:
May 12, 2017 at 9:38 am
Dear sir
This is Vasantakumar, I am working in one of PVT.ltd Company I am having PT(33kv) Breakdown Continous 6 Times 3Years So
can You guaid me How to Stop it

Reply
Momin says:
May 30, 2017 at 2:11 pm
Sir,,how can vertical distance from teensheet ouse.

Reply
prabu kumar says:
June 21, 2017 at 1:38 am
sir for 33kv line need pole to pole distance

Reply
Jagdish N says:
July 7, 2017 at 5:47 am
Minimum Electrical Clearance As Per BS:162. for 33kV enclosed , Minimum Phase to Earth is 222mm, but as per up gradation BS
these dimension are same or change.

Reply
Jagdish N says:
July 7, 2017 at 5:53 am
Hi Jignesh

Can you provide me the IS/IEC Ref compare to BS 162 & details for phase to phase clearance for 33kV enclosed System

Reply
karthik says:
October 14, 2017 at 4:02 pm
sir, what is the clearance of 66KV and 33KV line crossing area

Reply

https://electricalnotes.wordpress.com/2011/04/22/minimum-electrical-clearance-2/ 31/31

Potrebbero piacerti anche