Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Page 1 of 1
CONTENTS
1.0 SCOPE 4
7.0 CONCLUSION 17
8.0 ANNEXURES 18
8.1 Equipment data sheet for produced water tank. (JO-WP-MP1062-DS-2018)
8.2 Loading for wind and seismic forces for tank 20T-003A
1.0 SCOPE
The purpose of this calculation note is to design foundation for Tank No.
20T-003A Produced Water Tank.
2.2 Specifications
1. JO-WP-MP1062-SP-6001 Specification for concrete works
2 KOC-C-006 KOC / JO Standard for concrete work, material and construction.
3 KOC-C-026 KOC / JO Standard for storage tank foundation.
4 Geotechnical Investigation at SC 20, 40,41 and 42
(Service order No. SC/290/SO-249)
2.3 Basic Data
Location of Tank - SC-20
Reference Grade Elevation - 100.00
Concrete
Concrete Design Strength, f'c - 30.00 MPa
Unit weight gc - 24.00 kN/m3
Reinforcement
Yield Strength, fy - 410.0 MPa
Concrete cover to reinforcement - 75.00 mm
Soil
Unit weight gs - 18.00 kN/m3
Friction coefficient Fc - 0.40 (Coefficient between foundation and soil)
Passive earth coefficient for
lateral resistance - Not considered
Design ground water Level :
a) Wind load combinations - At Grade level
b) Other than Wind load combinations - 3.0 m from ground level (Soil Report)
Max.Net allowable soil Bearing capacity - 200.0 KPa
Allowable increase in Soil bearing capacity, (Assumed Bearing capacity for ring beam foundation)
a) For wind conditions - 25 %
hb)b For earthquake conditions - 25 %
c) For test conditions - 0 %
Factor of safety
a) Factor of safety against overturning - 2
b) Factor of safety against sliding - 2
Seismic loads are as per UBC. Hence seismic loads are divided by 1.4 to get unfactored loads.
D= 15030
12749
H=
tb= 12
15030
tf
(With water level at grade 104.200 applied for applicable wind load combinations when checking overturning)
Shape of foundation = Circular Ring Beam
Unit weight of ground water gw = 10.00 kN/m3 0
BL to ring beam base, BLb = Ab x hf x gw = 0.00 kN
BL to footing base, BLf = (Af - Ab) x hf x gw = 0.00 kN
BL to tank base excluding footing, BLt = 0.00 kN
6.1 Bearing pressure Check under ring beam foundation (For Serviciability Combinations)
=
Gross SBC in test condition (LC:2) - Net SBC + gs x hf 218 kN/m2
Gross SBC in wind condition (LC:4 &LC:5) - Net SBC x 1.25 + gs x hf = 268 kN/m2
Gross SBC in earthquake condition(LC:6) - Net SBC x 1.25 + gs x hf = 268 kN/m2
Gross SBC in operating and other - Net SBC + gs x hf = 218 kN/m2
conditions (LC:1 & 3)
where,
gs is unit weight of soil
hf is depth of bottom of foundation from grade
a) For Overturning
c) For Sliding
Calculation for torsional moment and check for torsion is performed as per ACI code as the checks
are more elaborate and also performed as per BS 8110
6.3.3 Calculation of Torsional Moment
Torsion due to eccentricity of Horizontal Forces (soil and surcharge components):
(Projection of ring footing base is neglected for torsional rigidity calculation)
C.G. of soil hoop force Fsoil from base = ysoil = (hb+tf)/3 = 0.67 m
C.G. of surcharge hoop force Fsur from base = ysur = (hb+tf)/2 = 1.00 m
C.G. = y = (Fsoil(hb+tf)/3+Fsuroper(hb+tf)/2)/(Fsoil+Fsuroper) = 0.96 m
Eccentricity of force = eh = ((hb+tf) / 2) - y = 0.04 m
Torsion = Th = (1.4 Fsuroper + 1.4 Fsoil) x eh = 7.16 kNm/m of ring footing
Torsion due to eccentricty of Vertical Forces (Fluid load, Shell edge load & Anchor Bolt components):
Shell edge load on ring beam (Vs) = 22.366 kN/m of ring footing
Eccentricity of shell edge on ring beam=evs=(bb/2-(ID-Dib)/2) = 0.000 m
Uniform fluid load on inside hz. projection of ring beam(V b) = 47.425 kN/m of ring footing
Width of Uniform fluid load on ring beam = wb=(ID-Dib)/2 = 0.350 m
Eccentricity of fluid load on inside ring beam=e vb=(bb/2-wb/2) = 0.175 m
Uniform fluid load on inside hz. projection of footing(Vf) = 0.000 kN/m of ring footing
Width of Uniform fluid load on ring footing = w f=(Dib-Dif)/2 = 0.000 m
Eccentricity of fluid load on inside ring footing=evf=(bf/2-wf/2) = 0.350 m
Torsion = Tv = 1.4 (Vb x evb + Vf x evf) = = 11.619 kNm/m of ring footing
Total torsional force (Tv+Th) = = 18.783 kNm/m of ring footing
As the ring beam is fully supported on ground the Torsion moment for per m is considered in calculation
ACl.11.6.3.8
ph = 4736 mm2
fyv = fyt = 410 N/mm2
Al = 130 mm2
Total area of steel required = 6430
Provided steel = 8373
Provided longitudinal steel is 20
### dia bars at spacing of 150 mm c/c
D
Cover
PJC
T.O.C
L LD LDR
W
45
T/2
LD/3 LD/3
section
Anchor Bolt
Reinforcement
LD/3+W/2
(LD/3+W/2) AREA
(EFFECTIVE AREA)
plan
Fig.
1
Pedestal reinforcement
Asreq = CHECK CHECK
Rebar Pitch
(tun)/(FFy) (ar) Rebar Asreq < rebar pitch
Rebar dia(mm) Spacing As Provided (Irp)
(mm2) area(mm2) Asprov & diameter
7.0 CONCLUSION
The size and design of the foundation is safe for all loading combinations considered.
8.0 Appendix-1
8.2 Loading for wind and seismic forces for tank 20T-003A