A Slide No 1
Index
1. COFEM Presentation
3. Installation Design
4. CONVENTIONAL
Fire detection and Fire Alarm System
Conventional Systems
y features
CLVR and LONDON Modeles
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 2
Index
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 3
COFEM Presentation
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 4
1 Cofem Presentation (1/9)
1.
- COFEM,
COFEM s.a,
s a is a Spanish Fire Protection
Manufacturer with more than 40 years at the market.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 6
1 Cofem Presentation (3/9)
1.
COFEM offers:
ff
- Expertice
p technical equipment
q p
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 7
1 Cofem Presentation (4/9)
1.
1) S
Support
t Assitance,
A it
2) Training courses,
4) ON-LINE SW Configuration
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 8
1 Cofem Presentation (5/9)
1.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 9
1 Cofem Presentation (6/9)
1.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 10
1 Cofem Presentation (7/9)
1.
Cala dOr
Camper
Camper Headquarter
Headquarter Hotel
at Mallorca at Mallorca
(Shoes Factory)
Hercules Towers
at Los Barrios Cadiz
(Offices buiding)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 11
1 Cofem Presentation (8/9)
1.
Beatriz Atlantis SPA Hotel
Some COFEM references ((Cont):
) at Puerto de la Cruz - Canary Islands
Faculty of
Informatics
at Madrid
Caldea thermal-ludic
El Pozo Factory at Alama de Murcia
Hotel at Andorra la Vella
(Food Factory) Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 12
1 Cofem Presentation (9/9)
1.
Campana Refinery
In Argentina
Tvoli Theater
MRW Transports at Barcelona
at Coslada High Speed Train AVE Station at Zaragoza
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 13
Certifications and CE mark
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 14
2 Certification and CE mark
2.
2.1.- Main European Union Policies
- UE is
i establieshed
bli h d with
i h the
h purpose off allow:
ll
Erase/Delete:
- Phisical barriers,
barriers
- Tariffs or quotes
-Thecnical Standards diferences
-and Conformity Evaluation means
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 15
2 Certification and CE mark
2.
2.2.- European Union Directives
The Directives
- Low
L V lt
Voltage
- Simple Pressure Vessels
- Safety
S f t off Toys
T
- Construction Product
- Electromagnetic
El t ti Compatiblity
C tiblit
- ()
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 16
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (1/4)
1) Application field:
- Any
ypproduct which is pproduced for incorporation
p in a
permanent manner in construction works, including both
buildings and civil engineering works
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 17
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (2/4)
3) Evaluation of Conformity:
- Define the means which assure that one product fulfill the
ms
essencial requirements
Alarm System
e Detection
Manufacture Approval Body Tasks
and
System CE Marking Documents
Tasks (Certification Based on:)
Fire
Fire A
FPC
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 18
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (3/4)
4) CE Mark:
- The products which incorporate the Essential Requirements
and Evaluation of Conformity shall affix the CE mark.
MANDATORY
Voluntary
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 19
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (4/4)
5) Mandatory Standards:
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 20
2 Certification and CE mark
2.
2.5.- Construction Product REGULATION CPR
CPR Vs CPD:
1)) Name of documents are changed.
g
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 21
2 Certification and CE mark
2.
2.6.- Summary
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 23
3 Installation Design
3.
3.1.- Introduction
- EU
U has
as pub
published
s ed TS54-14
S5 ((Technical
ec ca Spec
Specification
cat o as a
an European
u opea
recommendation)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 24
3 Installation Design
3.
3.2.- Recommendation (1/14)
SUMMARY
1. Detection Zones and Alarm Zones.
2. Fault efects limitations.
3. Detectors distribution
4. Manual Call Point distribution
5
5. Fire Alarm devices distribution
6. Cables
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 25
3 Installation Design
3.
3.2.- Recommendation (2/14)
1
1. D t ti
Detection and
d Al
Alarm Z
Zones
a. Detection Zones
The division of the premises/bilding in Detection Zones should
comply with:
- Floor Area 1600 m2
- Areas with more than 5 rooms:
Remote indicator above the doors or,
Room indication at the Control Panel.
- Zones with more than 1 fire compartment :
Zone limits should be the fire compartment, and
Zone Area 400 m2
- Zone should be limited to one floor, unless:
Stairwell,
St i ll lightwell,
li ht ll liftwell,
lift ll etc,
t but
b t inside
i id one fire
fi compartment.
t t
Building total Area 300 m2
b
b. Alarm Zones
According to Fire alarm response strategy.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 26
3 Installation Design
3.
3.2.- Recommendation (3/14)
2
2. Fault efect limitations
a. A single cable fault can afect only to one function by zone:
- Automatic detection,
- Manual Call points,
- Fire Alarm devices,
- Input/Output devices,
- Auxiliary devices,
- AND NOT more than 32 detectors or 10 Manual call points,
- Neither losing all Fire alarm devides in the building (At least one
device should work )
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 27
3 Installation Design
3.
3.2.- Recommendation (4/14)
One own output per zone for automatic detection and Manual call points
2 Fire Alarm device per each Zone and
1) 1) There
Zone <should
1600 mbe
Conventional 2) 2) Neither
AND it shouldZones losing
NOTwith
be lost
moteall
moreFirethan
than alarm
32 devides
1 Fire in or
detectors the10building
Compartement manual call points,
Area:
Zones Area should be Fire compartment, and Zone Area 400 m2
Example Up to 10 Up to 32
FC1 FC3
Zone 1
10 m
FC2
10 m
Zone2
20 m 20 m
Up to 10
Up to 32
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 28
3 Installation Design
3.
3.2.- Recommendation (5/14)
2
2. F l efect
Fault f limitations
li i i (Cont)
(C )
b. Two faults per circuit should not loss detector, manual call points and
alarm devices in:
- Area > 10 000 m2 .
- Area > 5 Fire compartments
compartments.
Fire compartments
Loop
p1
Loop 2
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 29
3 Installation Design
3.
3.2.- Recommendation (6/14)
- 32 elements between isolators
Addressable - Only one functionality between isolators
Example - At least 1 alarm device per Zone
- Area < 10000 m2 neither 5 Fire compartments FC: Fire Compartment
FC1 FC3
10 m
FC2
Zone 1 Zone 2
1m
20 m 20 m
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 30
3 Installation Design
3.
3.2.- Recommendation (7/14)
Smoke
3
3. D t t
Detectors distribution
di t ib ti
Detector
Premises Area (m2) Detector Type Premises Ceiling Slope 20 Ceiling Slope 20
Height (m) SV (m2) Dmx. (m) SV (m2) Dmx. (m)
SL 80 UNE-EN 54-7 12 80 6,3
, 80 6,3
,
SL 80 UNE-EN 54-7 6 60 5,5 90 6,7
6 h 12 80 6,3 110 7,4
SL 30 UNE-EN 54-5, Clase A1 7,5 30 3,9 30 3,9
UNE-EN 54-5, Clase A2, 6 30 3,9 30 3,9
B, C, D, E, F, G
SL 30 UNE-EN 54-5, Clase A1 7,5 20 3,2 40 4,5
UNE-EN 54-5, Clase A2, 6 20 3,2 40 4,5
B, C, D, E, F, G
Heat Detector
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 31
3 Installation Design
3.
3.2.- Recommendation (8/14)
4
4. M
Manual
lCCall
ll P
Points
i t
Minimum sound level should be 65 dB(A) at any point (75 dB(A) if the objetive
is to wake up sleeping people) or 5 additional db(A) over the ambient noise.
Maximum sound level should be 120 dB(A).
If sound
d level
l l exceed
d 60 dB(A) because
b off noise
i ambiente,
bi t Fire
Fi alarm
l signal
i l
should be sound and light.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 32
3 Installation Design
3.
3.2.- Recommendation (9/14)
5
5. Fi Alarm
Fire Al device
d i (Cont)
(C t)
It should
h ld bbe a minimum
i i off 2 sounders
d in
i the
th building,
b ildi and
d att least
l t 1 per Fire
Fi
Compartment and Detection zone.
Sound Level Distance
(dB-(A)) (m)
It should not be more than 1 door between a
120 1
sounder and anyplace where it should be heard.
114 2
108 4
G
General
l acoustic
ti approuches:
h
102 8
Each time it is doubled the distance, you lose 6 dBs,
30 dBs are lost for every Fire door, 96 16
20 dBs are lost for every standard door
door. 90 32
84 64
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 33
3 Installation Design
3.
3.2.- Recommendation (10/14)
Minimum of 2 sounders in the building, and at least
1 per Fire Compartment and Detection zone.
Conventional
Example Up to 10 Up to 32
FC1 FC3
Zone 1
10 m
FC2
10 m
Zone2
20 m 20 m
Up to 10
Up to 32
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 34
3 Installation Design
3.
3.2.- Recommendation (11/14)
Minimum of 2 sounders in the building, and at least
1 per Fire Compartment and Detection zone.
Addressable
Example
FC: Fire Compartment
FC1 FC3
10 m
FC2
Zone 1 Zone 2
1m
20 m 20 m
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 35
3 Installation Design
3.
3.2.- Recommendation (12/14)
6
6. C bl
Cables
In Loops:
Cable should be fire protected when faults
could affect more than 1 detection zone => If cable installation is routed for
different ways, it is acceptable using standard cables.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 36
3 Installation Design
3.
3.2.- Recommendation (13/14)
Operation of the Fire Alarm Devices
Conventional
Example Up to 10 Up to 32
FC1 FC3
Zone 1
10 m
FC2
10 m
Zone2
20 m 20 m
Up to 10
Up to 32
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 37
3 Installation Design
3.
3.2.- Recommendation (14/14)
If cable installation is routed for different ways, it is acceptable using standard cables.
Those cables that needs to work for more than 1 minute after detection of a fire: Sounders and its feed
Addresable
Example
p FC: Fire Compartment
FC1 FC3
10 m
FC2
Zone 1 Zone 2
1m
20 m 20 m
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 38
CONVENTIONAL
Fire Detection and Fire Alarm Systems
CLVR and
LONDON
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 39
4 Conventional System
4.
4.1.- Conventional System features (1/2)
C
Conventional
ti l features
f t
- Detector/Manual Call Point proccesses the Alarm Status
- Detector/Manual Call Point communicates with Control panel establishing voltage levels
i the
in th communication
i ti line.
li
Zone1 .
Zone 2
Control Panel doesnt know detector or Manual call point it is in Alarm status.
Need of divide area in detection ZONES.
ZONES
System limited to 32 elements by Zone.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 40
4 Conventional System
4.
4.1.- Conventional System features (2/2)
COFEM Offers
Off 2 kind
ki d off Conventional
C ti l Control
C t l Panels
P l
COFEM
Conventional Control Panels
2 to 12 Zones
2 to 128 Zones/Relays
Conventional Extinguishing
E ti i hi
CLVRxxZ CLVR02EXT
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 41
4 Conventional System
4.
4.2.- CLVR: Models
- 5 models available:
Conventional
Control Panels
CLVR02Z
CLVR04Z
CLVR08Z
CLVR12Z Extinguishing
Control Panel
CLVR02EXT
Z: Zone
Model EXT EXTinguishing
EXT: EXTi i hi
Zones N
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 42
4 Conventional System
4.
4.3.- CLVR: Technical Features (1/4)
Up to 32 elements (with detectors and manual call
points) per zone.
Space
S f 2 batteries
for b tt i off 7 Ah.
Ah
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 44
4 Conventional System
4.
4.3.- CLVR: Technical Features (3/4)
Possibility of ON
ON-LINE
LINE Software in a PC using the MODBUS
functionallity
Systems
Integration
EN 54 Contact ID on Demand.
Demand
EN 12094
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 45
4 Conventional System
4.
4.3.- CLVR: Technical Features (4/4)
3 Operation Modes at Extinguihing :
1) Standard Mode: Advance Warning Extinguishing
Output (R1) is activated by Zone 1 or Zone 2 in Alarm
Status.
2) Consecutive Mode: R1 output is activated intermittently
(1 s with Zone 1 or Zone 2 in Alarm status, 0.5 s with
both Zone 1 and 2 in Alarm Status and continuosly when
the delay of the Extinguishing Output (R2) has finished)
finished).
3) Simultaneous Mode: R1 output is activated when Zone
1 and 2 are both in Alarm Status.
A30XT PUCAR
- Conventional Heat detector. - Conventional Manual Call Point.
- Absolute temperature (64C). - Resettable.
- Protec cover.
- Red led Alarm.
A30XV
- Conventional Rate of Rise Heat
detector. PIAL
- Temperature rate of rise and
absolute temperature (64
(64C)
C). - Remote action indicator.
- Allows installation on switchgear
boxes.
A30XH - High reliability through 2 red leds.
- Optical
p Smoke detector.
- It includes heat sensor (64C).
HIGH/LOW Bases
A30XHS
- High: Allows 20 mm electrical tube.
tube
- Optical Smoke detector.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 47
4 Convencional System
4.
4.5.- CLVR: Wiring Diagrama (1/2)
- General connection
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 48
4 Convencional System
4.
4.5.- CLVR: Wiring Diagram (2/2)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 49
4 Conventional System
4.
4.6.- LONDON: Technical features
- It allows up to 10 Repeaters.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 50
4 Sistema Convencional
4.
4.7.- LONDON: Wiring Diagram
Module / Zones Card
Module / Relay Card
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 51
ANALOGUE and ADDRESSABLE
Fire detection and Fire Alarm System
LYON model
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 52
5 Addressable Lyon System
5.
5.1.- Addressable System features (1/2)
Add
Addressable
bl System
S t f t
features
- Each detector sends the measured value to Control panel in digital format.
- Control panel establish th quescient or Alarm status.
Detector is only a sensor.
Control panel knows all elements System is allowed with more than 32
elements if instaled in loop
p format ((according
g with standard))
Digital communication greatly increases the functionality of the system.
COFEM offers
ff 3 kind
ki d off C
Control
t l Panels
P l (Full
(F ll compatible
tibl between
b t th )
them)
Device Elements
Zafir:
Up to 2 loops Lyon:
Up to 199 devices per loop Up to 20 loops
Up to 199 devices per loop
C-Lyon:
Up to 2 loops
Up to 99 devices per loop
Loops Number
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 54
5. Addressable Lyon System
5.2.- Lyon control panel Technical Features
- Base
B control
t l panell configurable
fi bl up to
t 8 loops
l (199 elements
l t by
b loop).
l )
- Expandible up to 20 loops, using an additional box.
- Capacity for up to 99 zones.
- File that stores up to 4095 events with date and time.
- Outputs:
1) Monitored delayable general sounder (between 0 and 10 min),
2) non monitored alarm (Voltage free relay)
3) Fault, Monitored and delayable.
- Evacuation button.
- Backlit LCD display of 4 lines and 40 characters.
- Incorporates 7 languages by default.
- Configurable and manageable through PC-EASYcoNET software.
- Allows connection of up to 15 repeaters.
- Allows connection of up to 15 network control panels.
- MODBUS interface.
- EN 54-2 and EN 54-4 certified.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 55
5. Addressable Lyon System
5.3.- Aditional technical features
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 56
5. Addressable Lyon System
5.4.- Sensors / Manual Call Point / PIAL / Bases (1/2)
A30XTA PUCAY
- Addressable Heat sensor. - Addressable Manual call point with
-Temperature rate of rise and isolator.
absolute temperature (64C). - Resettable
- Protective cover
A30XHA - Red led flash/fix
- Addressable Optical Smoke sensor.
- It includes heat sensor (64C) PIAL
- Remote action indicator.
- Allows installation on switchgear
boxes.
A30XHAS - High reliability through 2 red leds.
- Addressable Optical Smoke sensor.
sensor
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 57
5. Addressable Lyon System
5.4.- Detectores / Pulsador / PIAL / Zcalo (2/2)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 58
5. Addressable Lyon System
5.5.- Modules / SIRAY / FAE /Repeater
KMAY MYOA
- Addressable Master module with isolator. - Addressable Relay and Technical
- Allows connection of conventional detectors and signal module with isolator.
manual call point (20 heat/ratre of rise or - R1 Relay monitored.
15 smoke/manual call points). - IN2 Closed contact as ALARM.
MDA1Y KABY
- Addressable 1 relay module with isolator.
- Loop isolator.
- 2 relays of simultaneous action from
- Inside High base..
Control p
panel.
- Maximum 70 per loop.
loop
- R1 Relay monitored.
- R2 Relay is NO/NC not monitorized. SIRAY
- Addressable sounder with isolator.
MDA2Y - Equivalence
E i l off 10 elements.
l t
- Addressable 2 relays module with isolator. - Programmed from Control panel.
- Relays programmed independently from - Maximum 6 or 10 per loop.
control panel. FAE 03 / 05
- Inside a chest.
MSTAY - FAE03: 3 A / FAE05: 5 A
- Addressable Thechnical signal module Repeater
with isolator.
isolator
- Up to 15.
- 2 NO/NC input signals monitored..
- Direct actions on the Control panel
- IN1 Closed contact as ALARM
(Alarm resets, faults, and general).
- IN2 Closed contact as FAULT. Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 59
5. Addressable Lyon System
5.6.- Wiring diagram (1/2)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 60
5. Addressable Lyon System
5.6.- Wiring diagram (2/2) Manual Call Points
Zone
Control Equivalence
Loop Element Logical
Reference Description Panel with loop
limit equivalence Relays
Limit Isolator
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 62
5. Addressable Lyon
y System
y
5.8.- Configuration (1/7)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 63
5. Addressable Lyon
y System
y
5.8.- Configuration (2/7)
Elements list
2. Configure Zones list and Element list that active relays (optional).
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 65
5. Addressable Lyon
y System
y
5.8.- Configuration (4/7)
2- Identification of N
2 N element insde the 2- Identifyy p
programming
g g number and p
place
loop of installation
3- Insert N element in binary codeinside 3- Physical installation
the device
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 67
5. Addressable Lyon
y System
y
5.8.- Configuration (6/7)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 68
5. Addressable Lyon
y System
y
5.8.- Configuration (7/7)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 69
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (1/4)
Characteristics
- ON-LINE management in Windows environment
(monitoring test mode,
(monitoring, mode situation maps,
maps null or rearm zones,
zones etc)
- Licence by Installation
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 70
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (2/4)
NOTE
Fiber Optic Line 1 Line 2
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 71
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (3/4)
b Null/Rearm elements/zones
b.
c. Test (General/Zones)
d. Sensitivity
f. General Rearm
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 72
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (4/4)
2) Events (Alarm,
(Alarm Fault,
Fault etc)
Information Window
3) Graphical Presentation
Allows up-load drawing in
.BMP, JPG, WMF or GIF format
- 1 or 2 loops
l (99 elements
l t per loop).
l )
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 75
5. Addressable Lyon System
5.10.- Derived Control panels (3/3)
D i
Devices li
limit
it per C
Control
t lP Panell
Control Element Logical
Loop Loop Control Control
Panel Loop limit equivalence Relays
Reference Description limit limit Panel limit Panel limit
limit
LYON Control panel ZAFIR Control panel C-LYON Control panel
Addressable optical-heat
A30XHA 199 --- 199 398 99 198 1 --- ---
sensor
Addressable optical
A30XHAS 199 --- 199 398 99 198 1 --- ---
sensor
A30XTA Addressable heat sensor 199 --- 199 398 99 198 1 --- ---
Addressable optical-heat-
A30XHTCO 199 --- 199 398 99 198 1 --- ---
monxide Multisensor
Add
Addressable
bl Manual
M l Call
C ll
PUCAY 70 --- 70 140 70 140 1 --- 1
Point
Conventional Zone master
KMAY 39 --- 39 78 19 38 5 --- 1
detection module
MDA2Y 2 Relays module 16 99 16 32 16 32 5 2 1
MDA1Y 1 Relay module 32 199 32 64 19 38 5 1 1
R l and
Relay dT
Technical
h i l
MYOA 32 199 32 64 19 38 5 1 1
signal module
MSTAY Technical signal module 70 --- 70 140 49 98 2 --- 1
KABY Loop isolator module 70 --- 70 140 70 140 --- --- 1
SIRAY/
Addressable sounder 10 99 10 20 6 12 10 1 1
SIRAYL
Control panel limits:
LYON Control Panel ZAFIR Control panel Central C-LYON
a) 199 elements, 32 logic relays and 70 isolators a) 199 elements, 32 logic relays and 70 isolators per a) 99 elements, 32 logic relays and 70 isolators per
per loop. loop. loop.
b) 20 loops with 199 logic relays b) 2 loops with 199 logic relays b) 2 loops with 199 logic relays
per control panel. per control panel. per control panel.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 76
CO Detection system for parking
COsensor Model
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 77
6 CO Detection System COsensor
6. COsensor
6.1.- Design recommendations
1) Certification
It is certified according with the UNE 23.300
23 300 standard and agreed with CE Directives
(CE mark).
2) Installation recomendation
Parking cars mechanically ventilated with site for more than 5 cars or 100 m2
Ventilation activation with 100 ppm CO concentration (50 ppm if there are workers)
CO detector coverture: 200 m2
Installation high: Between 1,5 and 2 m from floor.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 78
6 CO Detection
6. D t ti S t
System CO
COsensor
6.2.- CCO-1 Control Panel (1/2)
1) Models available:
CCO110: 1 Zone and up to 10 detectors
CCO115: 1 Zone and up to 15 detectors
CCO115 DVB: 1 Zone, Up to 15 detectors, Doble Ventilation and Batteries.
2) F
Funcionamiento
i i t (CCO110/115)
Alarm Alarm
[CO]
Delay Stop
Alarm
Al
Parameter Value Margin
level
Postventilation
Delay Alarm Ventilacin Level: 50 ppm Programable (30 150 ppm)
Time
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 79
6 CO Detection System COsensor
6. COsensor
6.2.- CCO-1 Control Panel (2/2)
Alarma
3) Operation CCO115 DVB Level
Ventilation 2
Parameter Value Margin Level
Ventilation level 1: 50 pp
ppm Fix Ventilation 1
Ventilation Delay 1: 4 min Programable (1 9 min) Level
Postventilation Dalay 1: 4 min Fix
DRY CONTACT
4) Installation
LIMIT 2A
C NA
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 80
6 CO Detection
6. D t ti S t
System CO
COsensor
6.3.- CCO1-4 Control Panel(1/2)
1) Models available:
CCO122 / CCO222 / CCO322 / CCO422: X Zones and up to 22 detectors
All model acept DBV opcion (Doble Ventilation and Batteries)
2) Operation (CCO1-4)
Each Zone is configured independently.
Alarm Alarm
[CO]
Delay Stop
Alarm
Al
level
Postventilation Parameter Value Margin
Delay Alarm Ventilacin Level: 50 ppm Programable (20 150 ppm)
Ventilation Ventiltion Actived Ventilacin Delay:
y 4 min Programable
g ( 9 min))
(1
Delay Stop
Postventilation Delay: 4 min Fix
Ventilation Ventilation
Actived Actived
Time
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 81
6 CO Detection System COsensor
6. COsensor
6.3.- CCO1-4 Control Panel (2/2)
Alarma
3) Operation CCO1-4
CCO1 4 Level
Ventilation 2
Level
Parmetro Valor Margen
Ventilation 1
Ventilation level 1: 50 ppm Programable (20 150 ppm)
Level
Ventilation Delay 1: 4 min Programable (1 9 min)
Fuse
4) Installation
Detectors in serial or parallel with polarity
Ventilation Output:
p Dryy contact 2 A.
Detectors (up to 22 per Zone) Detectors (up to 22 per Zone)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 82
6 CO Detection System COsensor
6.
6.4.- CO Detector
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 83
6 CO Detection System COsensor
6. COsensor
6.5.- NO2 Detector
DNO2 Detector
DNO2 Detector
Internal Algorithm to indicate NO2 ppm in CO ppm equivalent:
+ 2 ppm of NO2 are equivalent to 50 ppm of CO
+ 14 pp
ppm of NO2 are equivalent
q to 300 pp
ppm of CO
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 85