Troubleshooting
4-1 Wired remote controller
- If an error occurs, ( ) icon will be displayed on the wired remote controller.
- Press the Test button to see the error code.
Product operation in
error condition
Error mode Contents Measure Error type
Outdoor unit/
Compressor/Indoor unit
Indoor unit communication Check the communication cable of indoor unit. Check Communication
Operation Off
error the DC output voltage at the communication terminal error
Indoor temperature sensor Check indoor unit room temperature sensor. Check Indoor sensor
Operation Off
(open/short error) indoor unit PCB connector CN41 (White) error
Indoor unit Eva In sensor Check indoor unit pipe sensor. Check indoor PCB Indoor sensor
Operation Off
(Open/Short) connector CN41(White) error
Indoor floating switch Check indoor unit float sensor. Check indoor PCB Self diagnostic
Operation Off
secondary detection connector CN5 (black) error
26 Samsung Electronics
Outdoor unit
Capacities not matched Check the option code of the indoor unit Operation Off protection
control error
Samsung Electronics 27
COM1/COM2 cross installation Check that wired remote controller is connected to the Wired remote
Normal operation
error COM2 terminal of the indoor unit controller error
28 Samsung Electronics
Error
Meaning Troubleshooting
code
Indoor unit ($POUSPM kit) orders emergency stop.
E177 Emergency stop
Check the indoor unit ($POUSPM kit).
Control kit quantity must be matched with outdoor unit
E201 Control Kit quantity is mismatched.
1 by 1. Check the $POUSPM kit quantity. It must be 1EA.
Detection of outdoor freezing when compressor Outdoor unit (Condenser) froze.
E403
stops. Check condenser.
Protection of outdoor overload when compressor Compressor is overloaded. Please check same as E461
E404
stops. and check compressor when it starts.
Discharge temperature of a compressor in an
E416 Discharge temperature is overheated.
outdoor unit is overheated.
Heating operation is not available since the
E440
outdoor air temperature is over 35C.
Check the outdoor temperature.
Cooling operation is not available since the
E441
outdoor air temperature is lower than -15C.
Compressor is overloaded. Please check same as E461
E465 Compressor over load error
and check compressor when it starts.
E468 Current sensor error Exchange INVERTER PBA.
EEPROM date is wrong. Exchange EEPROM or MAIN PBA.
E471 Outdoor EEPROM error
(This error don't occur in EMF 150-AM)
IPM(IGBT Module) or PFCM temperature sensor
E474 Exchange INVERTER PBA.
error
Check reactor located in control plate.
E484 PFC overload error
If reactor is normal, exchange INVERTER PBA.
Samsung Electronics 53