Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Installation and
Maintenance Instructions
PUB002-004-00
Date of issue 08/13
I
This manual covers IQT range actuators: THE ROTORK IQT RANGE THE FIRST 1/4 TURN VALVE ACTUATOR
THAT YOU CAN COMMISSION AND INTERROGATE WITHOUT
* IQT - Operation of isolating/regulating 1/4 turn valves.
REMOVING ELECTRICAL COVERS.
* IQTM - Operation of modulating 1/4 turn valves.
* IQTF - Operation of part-turn and slow speed multi-turn valves. Using the supplied infra-red Setting Tool to access the actuator set up
* IQTFS - Battery failsafe. procedures, point and shoot setting of torque levels, position limits and
all other control and indication functions can be made safely, quickly and
It provides instruction on: conveniently, even in hazardous locations. The IQT allows commissioning
and adjustment to be carried out with the main power supply to the
* Manual and electrical (local and remote) operation. actuator switched on or off.
* Preparation and installation of the actuator onto the Standard diagnostics access information about the control system, valve
valve. and actuator status in the form of display icons and help screens.
* Commissioning and adjustment of the Instantaneous valve torque and position can be monitored on the actuator
Primary Settings for correct valve operation. with a single key press of the Setting Tool.
* Commissioning and adjustment of the Secondary The on board Datalogger captures operational and valve torque data
enabling informed maintenance choices to be made. IQ Insight software
Settings to suit site-specific control and indication
for PC allows the Datalogger to be interrogated, as well as the complete
requirements. actuator set up to be configured and recorded.
* Maintenance Troubleshooting. The actuator containing the Setting Tool will be identified with a yellow
* Sales and Service. label on the terminal cover.
Visit our web site at www.rotork.com for more information on the IQT and
other Rotork actuator ranges.
Refer to Publication E185E for repair, overhaul and
spare part instructions.
III
Display window
Conduit entries
Battery sealing plug
Metal (8mm Allen key required)
Plastic (10mm Allen key required)
as appropriate.
Control Cover
Hand / Auto
lever
IQelecCvr IQelecCvr
Stop Bolts
1
CONTENTS
Page Page Page
1 Health and Safety 2 6 Cable Connections 10 10 IQT Battery Failsafe Instructions 62
6.1 Earth/Ground Connections 10 10.1 Introduction 62
2 Storage 3
6.2 Removing Terminal Cover 10 10.2 Specification 63
3 Operating your IQT Actuator 3 6.3 Cable Entry 10 10.1 Commissioning instructions 64
3.1 Operating by Hand 3 6.4 Connecting to Terminals 10 11 Maintenance, Monitoring
3.2 Operating Electrically 3 6.5 Replacing Terminal Cover 10 and Troubleshooting 67
3.3 Display Local Indication 4
7 Commissioning 11 11 Torque-reference profile 69
3.4 Display Status Indication Travel 5
7.1 The Setting Procedure 11 11.1 Setting Tool Pro Download & Upload 70
3.5 Display Status Indication Control 5
7.2 The Rotork Setting Tools 12 11.2 Help Screens 73
3.6 Display Alarm Indication 5
7.3 Entering the Actuator 15 11.3 IQT Infrared Diagnostic & Configuration 78
4 Preparing Drive Bush 7 Setting Procedure 11.4 Environmental 79
4.1 Bases F05 to F07 7 7.4 Setting Mode Password 15 12 Weights and Measures 80
and FA05 to FA07 7.5 New Password 15 Binary, Hexadecimal and Decimal
4.2 Bases F10 to F14 7 7.6 Checking Mode 15 Conversion Table 81
and FA10 to FA14
7.7 Crossroad 16
4.3 Machining the Drive Bush 7
7.8 The Actuator Display 16 13 IQT Approvals 82
4.4 Fitting the Drive Bush 7 Setting/Checking Mode Approved Fuses 83
Maximum Flamepath Gaps 83
5 Mounting the Actuator 8 7.9 Returning to Valve Position Display 16
5.1 IQT Actuators 8 8 Commissioning Appendix A 84
5.2 IQTM Actuators 8 Basic Settings 17
5.3 IQTF Actuators 8 Basic Settings Contents 18
5.4 Lifting the Actuator 8 9 Commissioning
5.5 Securing Actuator to Valve 8 Configuration Settings 27
5.6 Stop Bolts 9 Configuration Settings Contents 29
Default Options 60
2
1 Health and Safety
This manual is produced to enable a given in the applicable edition of the No inspection or repair should be
competent user to install, operate, IEE Wiring Regulations should be undertaken unless it conforms to the WARNING: Enclosure Materials
adjust and inspect Rotork IQT applied. Also the user should be fully specific hazardous area certification IQT actuators are manufactured from
range valve actuators. Only persons aware of his duties under the Health requirements. Under no circumstances aluminium alloy with stainless steel.
competent by virtue of their training and Safety Act 1974. should any modification or alteration be The user must ensure that the operating
or experience should install, maintain carried out on the actuator as this could environment and any materials
For the USA: NFPA70, National Electrical
and repair Rotork actuators. Work invalidate the actuators hazardous surrounding the actuator cannot lead
Code is applicable.
undertaken must be carried out in area approval certification. Access to to a reduction in the safe use of, or the
accordance with the instructions in The mechanical installation should be live electrical conductors is forbidden protection afforded by, the actuator.
this and any other relevant manuals. carried out as outlined in this manual in the hazardous area unless this is Where appropriate the user must
The user and those persons working and also in accordance with relevant done under a special permit to work, ensure the actuator is suitably protected
on this equipment should be familiar standards such as British Standard otherwise all power should be isolated against its operating environment.
with their responsibilities under any Codes of Practice. If the actuator has and the actuator moved to a non-
statutory provisions relating to the nameplates indicating that it is suitable hazardous area for repair or attention. WARNING: Operating by Hand
Health and Safety of their workplace. for installation in hazardous areas then
Due consideration of additional the actuator may be installed in Zone With respect to handwheel operation of
hazards should be taken when using 1, Zone 21, Zone 2 and Zone 22 (or Div Rotork electric actuators, see warning
the IQT range of actuators with other 1 or Div 2, class I or Class II) classified on p3.
equipment. Should further information hazardous area locations only. It should
and guidance relating to the safe use not be installed in hazardous area This actuator must only be
of the Rotork IQT range of actuators be locations with an ignition temperature located in areas where the risk of
required, it will be provided on request. less than 135C, unless suitability for impact to the viewing window
lower ignition temperatures has been is low.
The electrical installation, maintenance
indicated on the actuator nameplate.
and use of these actuators should be Actuator may start and
It should only be installed in hazardous WARNING: Thermostat Bypass
carried out in accordance with the operate when remote control is
area locations compatible with the gas
National Legislation and Statutory If the actuator is configured to bypass selected, depending on remote
groups stated on the nameplate.
Provisions relating to the safe use of the motor thermostat then the hazardous control signal status and actuator
this equipment, applicable to the site of The electrical installation, maintenance area certification will be invalidated. configuration.
installation. and the use of the actuator should be Additional electrical hazards may occur
carried out in accordance with the code when using this configuration. The
For the UK: Electricity at Work
of practice relevant for that particular user should ensure that any necessary
`Regulations 1989 and the guidance
Hazardous Area certification. additional safety measures are considered.
3
2 Storage 3 Operating your
IQT Actuator
If your actuator cannot be installed 3.1 Operating by Hand To engage handwheel drive, turn When the selector is locked in the Local
immediately store it in a dry place until the Hand/Auto lever clockwise whilst or Remote positions the Stop facility is still
you are ready to connect incoming turning the handwheel, see Fig 3. The available. The selector can also be locked
cables. WARNING lever can now be released upon which in the Stop position to prevent electrical
With respect to handwheel it will return to its original position. The operation by Local or Remote control.
If the actuator has to be installed but
handwheel will remain engaged until
cannot be cabled it is recommended operation of Rotork electric
the actuator is operated electrically
that the plastic transit cable entry plugs actuators, under no circumstances when it will automatically disengage
are replaced with metal plugs which are should any additional lever and return to motor drive. If required
sealed with PTFE tape. device such as a wheel-key the Hand/Auto lever can be locked in
The Rotork double-sealed construction or wrench be applied to the either position using a padlock with a
will preserve internal electrical handwheel in order to develop 6.5mm hasp.
components perfectly if left more force when closing or
undisturbed. opening the valve as this may 3.2 Operating Electrically
cause damage to the valve and/or Check that power supply voltage agrees
It is not necessary to remove any with that stamped on the actuator
electrical compartment covers in order actuator or may cause the valve
to become stuck in the seated/ nameplate. Switch on power supply. It
to commission the IQT actuator. is not necessary to check phase rotation.
backseated position.
Rotork cannot accept responsibility for Fig. 3.1
deterioration caused on-site once the Do not operate the actuator
covers are removed. Local Control
electrically without first checking, With the red selector positioned at
Every Rotork actuator has been fully using the infra-red Setting Tool, Local (anti-clockwise) the adjacent black
tested before leaving the factory to that at least the Primary Settings knob can be turned to select Open or
give years of trouble free operation, have been made (refer to Section Close. To Stop, turn red knob clockwise.
providing it is correctly commissioned, 8 page 17).
installed and sealed.
Selecting Local/Stop/Remote Remote Control
Operation Rotate the red selector to the Remote
The red selector enables either Local or position (clockwise), this gives remote
Remote control, lockable in each position control only for Open and Close but
using a padlock with a 6.5mm hasp. local Stop can still be used by turning
Fig. 3 the red knob anti-clockwise.
4
3.3 DisplayLocal Indication description text in the lower display. Open Closed
The two tri-colour LED's will be Red, The two tri-colour LED's will be Green,
6. Battery Alarm Icon - This icon will be
the open symbol and "Open Limit" will closed symbol and "Closed Limit" will
displayed when a battery is detected as
be displayed be displayed.
low or flat. "Battery low" or "flat" will
also be displayed in the lower display.
7. IR Icon - This icon flashes during infra
red communication activity.
8. Percentage Open Icon - This icon will
be displayed when a percentage Open Open Limit Closed Limit
value is in the upper display.
The liquid crystal display screen has 2 Fig. 3.3 Fig. 3.5
modes of position indication:
Fig. 3.2 The Actuator Display With the main power supply switched
1. Valve position power on Mid Travel off, the display screen is powered by
The display consists of: 2. Valve position power off The two tri-colour LED's will be Amber, a battery and continues to display
percentage open value will be shown actuator position. However, the battery
1. Position Display - This is the main On power up the actuators liquid and "Stopped" will be displayed when
7-segment position display with icons. does not support screen back-lighting,
crystal display screen is back-lit with an there is no actuator movement. position indicator lamps or dot matrix
2. Text Display - This is a 2 line, 16 amber light and one of the indicator display.
characters dot matrix display which lamps will be on, dependent on
allows text to be used to compliment position. The display screen will show LED Indicators
the position display and icons. percentage open or an end of travel
symbol. (See Figs 3.3, 3.4 and 3.5)
3. Infra Red LED's. WARNING: Mid Travel LED
As standard, red lamp signifies valve colour may be affected by viewing
4. 1 x Bi colour LED, 1 x Amber colour open, amber intermediate, and green Stopped angle and lighting level.
LED for position indication. lamp signifies valve closed. Open and
The Close LED colour can be changed
5. Alarm Icon - This will be displayed closed colour functions can be reversed
to red if required. The Mid Travel amber
for Valve, Control, and Actuator alarms. on request.
LED can be switched off if required.
Alarm indication is supported by fault Fig. 3.4
Refer to Section 9.16, page 58.
5
3.4 Display Status Indication Timer Active Interrupter Timer option Remote Control Remote control 3.6 Display Alarm Indication
Travel enabled only. Interrupter Timer has selected red selector. The IQT display provides alarm indication
The IQT display provides real time stopped the actuator mid travel for a in the form of text and alarm icons.
Local Close Local close signal applied
status indication. The top line of the period equal to the set Timer Off
black selector.
text display is reserved for travel status time. Refer to 9.13 page 55. There are 2 alarm icons:
indication. Fig 3.6 shows the travel Local Open Local open signal applied
status example Closed Limit . black selector.
3.5 Display Status Indication Remote Close Remote close (hardwired General Alarm:
Control or analogue) signal applied.
The bottom line of the text display is
Remote Open Remote open (hardwired Battery Alarm:
reserved for control status indication
or analogue) signal applied.
and is displayed for approximately 2
Closed Limit seconds after the control mode or Remote ESD Remote hardwired
signal is applied. Fig 3.7 shows the emergency shut down signal applied.
control status example Remote Control . General Alarm
Remote Bus Open Remote Bus * open
signal applied. The general alarm icon will be
Fig. 3.6 supported with text in the bottom line
Available travel status conditions displayed: Remote Bus Close Remote Bus* signal indicating the particular alarm, or if
applied. more than one is present, each alarm
Closed Limit Actuator has reached the will be displayed in sequence.
Remote Bus ESD Remote Bus*
set closed limit position. Closed Limit emergency shut down signal applied. Fig 3.8 shows the status example
Open Limit Actuator has reached the Remote Control * Bus Control option fitted may be TORQUE TRIP CL .
set open limit position.
Pakscan, Profibus, Modbus,
Moving Open Actuator is traveling in Fig. 3.7 DeviceNet or Foundation Fieldbus.
the open direction. Refer to actuator wiring diagram.
Available control status conditions displayed:
Moving Closed Actuator is traveling in
the closed direction. Local Control Local control selected -
red selector. Stopped
Stopped Actuator has stopped in a
Local Stop Local stop selected red
TORQUE TRIP CL
mid travel position, indicated in the
top display (%open). selector.
Fig. 3.8
6
Available alarm conditions displayed: Actuator Alarms TORQ SENSOR FAIL Detected failure When a low or flat battery
in the torque sensing system alarm is displayed the battery
Valve Alarms THERMOSTAT TRIP Motor control contact Rotork.
thermostat has tripped due to should be replaced immediately. It
TORQUE TRIP CL tripped off on torque is essential that the correct battery
extended motor operation. EEPROM MISSING Contact Rotork
while moving in the close direction. type is fitted to maintain actuator
Operation is inhibited until the
TORQUE TRIP OP tripped off on torque thermostat resets automatically certification. Refer to page 67.
while moving in the open direction. when the motor control cools. Battery Alarm After replacing a battery the
Check actuator duty cycle against alarm icon will continue to be
MOTOR STALLED no movement process requirements (running time,
detected after a signal to move. displayed until the next check and
torque, ambient temperature). may take up to 1 hour. Cycling the
Control Alarms PHASE LOST (3-phase models only). power will force a battery check
The phase supply the actuator and clear the alarm.
ESD ACTIVE ESD signal applied. When connected to terminal 3 is lost.
present the ESD signal overrides all Operation is inhibited. Open Limit
local and remote control signals.
Once the ESD action is carried out 24V LOST The 24 volt customer BATTERY LOW PWR LOSS INHIBIT
operation is inhibited while the ESD supply (terminals 4 & 5) has tripped. If, on power up, the actuator detects
signal is maintained. Refer to 9.3 Check remote control wiring. Supply Fig. 3.7 a discharged battery and actuator
ESD Action page 32. is protected with a resettable fuse. power loss inhibit feature [OS] is
The actuator checks the battery level enabled (refer to page 57), both
INTERLOCK ACTIVE Open and/or close LOCAL CONTROL FAIL Check operation
at approximately 1 hour intervals. The battery and general alarm icons will
interlocks are configured on and are of control selectors (black and red).
battery alarm icon is displayed when be displayed and the bottom line will
active. Refer to 9.3 Interlock page 34. CONFIG ERROR There may be an error the actuator detects its battery as being indicate alternately PWR LOSS INHIBIT and
Operation in the direction of an in the configuration (set up) of the low and the display will indicate BATTERY BATTERY FLAT . Electrical operation will be
active interlock(s) is inhibited. actuator. Check and reset basic LOW . inhibited. The battery must be replaced
Note that when conditional control is setting and check configuration and the limits must be reset. Refer to
configured, an active interlock will settings. If the battery is flat or missing the
display will indicate BATTERY FLAT . Section 11, page 67 and Section 8,
not inhibit local control operation. page 17.
POS SENSOR FAIL Detected failure in
the position sensing system contact
Rotork.
7
4 Preparing Drive Bush
Fig. 4.3
8
5 Mounting the Actuator
Secure actuator to valve with four The IQT stop bolts are located below Stop Bolt sizes.
fixing bolts. Check that the cast groove the terminal compartment. Stop bolt IQT 125 to 500: M12 bolt requiring
in actuator base is not obstructed see adjustment allows +/ 5 variation of 19mm AF spanner.
Fig 5.1. Its purpose is to protect the travel at each end position. Screwing
actuator in the event of a product leak bolts in reduces movement, out IQT1000 & 2000: M20 bolt requiring
from the valve stem/gland packing. increases movement. For clockwise 30mm AF spanner.
Check base fixing bolts are tight. closing valves the right hand bolt is the
closed stop as shown with spanner in Adjustment for non seating
valves types
5.6 Stop Bolts fig 5.2. The left is the open stop. Stop
For closed and open stop position
It is recommended that stop bolt bolts are factory set to give a nominal
adjustment:
adjustment be carried out by the 90 travel.
valvemaker/supplier before the valve Undo stop bolt lock-nut. Move actuator
is fitted into pipework. Once installed, and valve to the required stopping
the valve maker/supplier should position (it may be necessary to
be consulted before stop bolt re- unscrew stop bolt to allow more travel).
adjustment is carried out. Stop bolts Screw stop bolt in until a stop is felt.
can be wired to prevent tampering. Tighten stop bolt lock nut.
After setting or adjustment of stop
bolts the actuator limits must be reset, Adjustment for seating valves
refer to Limits LC, LO page 24. types
For closed and open stop position
adjustment:
Undo stop bolt lock-nut. Move
actuator and valve to the required
seating position of the valve (it may be
Fig. 5.2 necessary to unscrew stop bolt to allow
more travel). Screw stop bolt in until
a stop is felt and then back off by 3
turns. Tighten stop bolt lock-nut.
7. Key Close actuator When a button is depressed the Setting Tool transmits the relevant instruction
to the actuator by infra-red pulses and must therefore be directly in front of the
8. Infra-red Transmitter Window actuator indicator window and at a distance no greater than 0.75m.
13
* Pressing these two arrow keys together returns the actuator display to the
position indication mode
14
7 Commissioning continued
Download / Upload Function Duracell, Coppertop, type MN1500 When a button is depressed the Function Setting
Duracell, Procell, type MN1500 Setting Tool Pro transmits the relevant Code Code
This new feature has been introduced
with the new Rotork Setting Tool GP, Super Alkaline, type GP15A instruction to the actuator by infra-red
Pro. It allows the user to download pulses and must therefore be directly in
Other types of AA size batteries,
datalogger files and download/upload front of the actuator indicator window
including Duracell, Ultra, type
configuration files. The new tool is MN1500, must not be fitted. For
and at a distance no greater than Close Action
weatherproof and intrinsically safe battery replacement see Section 7.
0.75m.
Function Close on Torque Setting
and so it can be used safely in all Option
environments. For more information Refit cover ensuring red indicator LED
refer to Section 11.1, page 70. faces the transmitter window in the Display Set-Up Mode
back cover. The Setting Tool and Setting Tool Pro Function Setting
The enclosure of the actuator Setting arrow keys are used to access and Code Value
Setting Tool Pro Battery Tool Pro is manufactured from the navigate through the actuator set-up
Replacement materials: procedure using the actuator display.
Battery status can be checked by looking Each actuator function with it's current
Polycarbonate, ABS blend setting is represented on screen by
at the Infra-red transmitter window
while depressing any Setting Tool Pro
Polycarbonate a combination of code and text. The Open Torque
button except the download button. A
Silicon Rubber Setting Tool change keys (+ and ) Function 40% Setting
flashing red indicator should be seen. If the actuator Setting Tool Pro is likely allow the user to view the available Value
to come into contact with aggressive setting options.
Battery replacement must be substances (e.g. solvents that may
carried out in a safe area. To replace The examples of displayed functions
affect polymetric materials), then it is Close Action , [C2] and Open Torque , [tO]
the battery remove the six cap head the responsibility of the user to take
screws in the back of the Setting are shown to the right. Note that a
suitable precautions (e.g. regular checks setting option or value is highlighted.
Tool Pro. Remove the back cover to as part of the routine inspections or
expose the battery. establishing that the materials are This instruction manual uses both code
In order to maintain hazardous resistant to the specific chemical) and text for description.
area certification the actuator that prevent it from being adversely
Setting Tool Pro shall only be affected, thus ensuring that the type of
fitted with the following AA size, protection is not too compromised.
alkaline-manganese, approved No form of repair must be attempted
battery types: on the actuator Setting Tool Pro.
15
7.3 Entering the Actuator 7.4 Setting Mode Password 7.5 New Password [PC] 7.6 Checking Mode
Setting Procedure To enable setting and adjustment of the To configure a new password, the The actuator function settings can be
With the actuator securely mounted actuator functions the correct password actuator must be in setting mode with checked without entering the correct
on the valve, the mains supply on and must be entered. The factory set (default) the password display setting mode password. The settings can only be
Local control or Stop selected. password is [ld]. If the actuator has enabled showing, viewed and not altered. The setting bars
previously been set with a site password will not be seen.
PRESS THE m KEY. this must be entered.
PRESS THE k KEY.
The actuator upper display will remain The display will change to [PC]. Using the
Use the + or - keys to scroll through the + or - key scroll through the available
the same and the lower display will available passwords 00FF (hexadecimal).
change to Torque value. This will be passwords until the desired password is
With the correct password displayed press
represented by Torque = XX% and a displayed. Enter Password
the enter key.
bar graph. (For instantaneous torque PRESS THE KEY. ID Hex
& position monitoring, refer to Section PRESS THE KEY.
11, page 68.) Two setting bars will appear and will Password Display, Checking Mode
remain visible on every function display
Once the procedure has been completed
screen. In addition, "Password Correct"
PRESS THE m KEY. in the required mode
will be displayed for 3 seconds.
Change Password
The actuator display will change and IE Hex
PRESS THE m KEY.
the password protection display will be The procedure branch [Cr] (crossroad)
seen. Password Changed to [IE] display can now be seen (refer to Section
7.7 page 16).
NOTE: The new password becomes
Enter Password
effective the next time setting mode is
Password Correct
entered.
Enter Password Default Password,
ID Hex Setting Mode Enabled
7.7 Crossroad [Cr] 7.8 The Actuator Display In setting mode the Setting Tool + 7.9 Returning to
Setting/Checking Mode or - keys will cause the setting to be Valve Position Display
Actuator functions as laid out in the changed. In checking mode the settings There are five ways of returning to valve
Basic and Configuration commissioning cannot be altered. position display:
stages, can be individually displayed by
In setting mode, once displayed, a new 1. Approximately 5 minutes after the
Basic Setup using the Setting Tool arrow keys.
Config Setup
setting can be entered into the actuator last Setting Tool operation the
The m arrow key will always display memory by pressing the key. display will automatically return to
the FIRST function on the next level The setting will flash off and back on, position display.
To access the Basic Settings press DOWN within the procedure. confirming its selection, and "Stored "
the arrow m key (refer to Section 8 will be displayed for 2 seconds in the 2. Press the m and k arrow keys
Commissioning Basic Settings page 17). The k arrow key will always display text display. together.
the NEXT function on the SAME level
To access the Configuration Settings and will wrap around the functions on 3. Press the m arrow key until the
TOP LEFT display returns to position.
press the arrow k key (refer to the same level. PORTION
Section 9 Commissioning Configuration Function e.g. 4. Select Remote control using the
Settings page 27). The actuator display indicator lamps will
continue to indicate valve position but tC = Torque Close red Local/Stop/Remote selector.
will also flash during IR communication. 5. If you have the new Setting Tool
TOP RIGHT Pro then you can use the iarrow
Actuator functions are displayed in PORTION
code form in the top left portion of the key to return to position display.
Close Torque Function Setting
liquid crystal display screen. e.g. Value = 40%
40%
The setting for the displayed function is
shown in the top right hand portion of LOWER DISPLAY
the screen. Depending on the actuator Function: Close Torque
function displayed, its setting may be Setting Value: 40%
an option or a value.
Text relating to the function and setting Typical Actuator Function Display
values will be displayed in the lower Setting Mode Enabled
display.
17
8 Commissioning
Basic Settings
ELECTRICAL OPERATION MUST Power Off Setting
NOT TAKE PLACE UNTIL THE BASIC IQT allows settings to be viewed and
SETTINGS HAVE BEEN MADE AND set without main power. To enable this
CHECKED. function, engage handwheel drive and
rotate until the output drive moves
The actuators Basic Settings affect
(refer to page 3). The Setting Tool can
the correct operation of the valve by
now be used. As long as a Setting
the actuator. If the actuator has been
Tool key press takes place within the
supplied with the valve, the valve
30 seconds timeout period, Power
maker or supplier may have already
Off Setting will remain enabled. If no
made these settings.
infra-red Setting Tool communication
This instruction assumes setting mode takes place the display will return to
has been entered (refer to section 7.4 indicating position. The actuator must
page 15). then be operated by handwheel to
re-enable Power Off Setting.
Viewing the Basic Settings
With the actuator mounted on the Settings and operation must
valve, the power supply on and Local be verified by electric operation
or Stop control selected, point the
Setting Tool at the actuator indicator and function test of the actuator
window from a distance of no more to ensure correct operation.
than 0.75m. By pressing the m key
and, when appropriate, the k key,
it is possible to move through the
procedure, displaying the various
functions and their settings as shown
in Fig. 8.1 (refer to page 18).The
right-hand side of Fig.8.1 explains the
function of each LCD display.
18
Function Description
50 Position Display REFER TO SECTION 7, COMMISSIONING
(This may be an open or closed symbol or a % open value.)
m m
50
Torque Torque and Position Display
m m
P? k PC k Ir k tP Password k Password Change k IrDA k Torque Reference Profile
m m
Cr k Configuration Crossroad k Configuration Settings, refer to page 32.
The actuator can be configured to be Using the + or - key, display the Having ensured that the display
clockwise or anti-clockwise to close. character conforming to correct closing corresponds to the established
Manually operate actuator and valve direction. closing direction
to establish correct closing direction.
Conversion Handwheel direction labels
PRESS THE KEY.
are available. The displayed option will flash (stored),
indicating that it has been set.
50 PRESS THE k KEY.
Close Direction
m Clockwise
50 [C] in the Setting Field Indicating
Torque
Clockwise to Close
m
P? k PC k Ir k tP
m
cr
m Close Direction
Anticlockwise
c1 k c2 k c3
[A] in the Setting Field Indicating
m Anti-clockwise to Close
tC k tO
m
LC k LO
m
50
20
C2 Close Action
IQT actuators are designed to stop at 50 Using the + or - key, display the NOTE: When set to close on torque,
the end of travel by torque limitation required option. the actuator will apply the level of
against the actuator stop bolts. Stop m torque as set for [tC] in seating the
bolts should therefore be set to the 50 valve (refer to [tC] page 22).
precise stopping position required, refer Torque
to section 5.6. m
IQTF actuators can be configured to P? k PC k Ir k tP Close Action
close on torque or limit. Refer to valve
m Close on Torque
manufacturers instructions.
cr [Ct] in the Setting Field Indicating
Refer to valve manufacturer Close on Torque - default setting.
for recommended setting.
m
c1 k c2 k c3
m
tC k tO
Close Action
m Close on Limit
LC k LO [CL] in the Setting Field Indicating
m Close on Limit.
50
IQT actuators are designed to stop at 50 Using the + or - key display the NOTE: When set to open on torque,
the end of travel by torque limitation required option. the actuator will apply the level of
against the actuator stop bolts. Stop m torque as set for [tO] in back seating
bolts should therefore be set to the 50 the valve (refer to [tO] page 23).
precise stopping position required, refer Torque
to section 5.6. m
IQTF actuators can be configured to P? k PC k Ir k tP Open Action
close on torque or limit. Refer to valve
m Open on Torque
manufacturers instructions.
cr [Ot] in the Setting Field Indicates
Refer to valve manufacturer Open on Torque - defualt setting.
for recommended setting. In the
m
absence of valvemaker instructions c1 k c2 k c3
set Open Limit.
m
tC k tO
Open Action
m Open on Limit
LC k LO [OL] in the Setting Field Indicates
m Open on Limit.
50
The value of torque available in the Using the + and - keys, the display
close direction can be configured. recommended value. In the absence of
a recommended torque value, try a low
Refer to valve manufacturer
setting and increase until satisfactory
for recommended value. Close Torque
valve operation is achieved.
40%
The closing torque value can be varied
between 40% and Rated (100%), in If the actuator fails to 40% of Rated Torque
1% increments. complete a closed valve operation
due to the set torque being
reached (Torque Trip CL Alarm, page 5)
50 this may indicate a valve and/or
m process problem or change. It is the
responsibility of the user to ensure Close Torque
50 the valve and process conditions are 99%
Torque
The value of torque available in the The opening torque value can be NOTE: Rated torque is quoted on the
open direction can be configured. varied between 40% and Rated, in 1% actuator nameplate. Boost torque is at
increments. In addition Boost can least 140% of Rated torque.
Refer to valve manufacturer
be configured when no open torque
for recommended value.
protection is required. PRESS THE KEY. Open Torque
100%
The displayed value will flash (stored),
BOOST SHOULD NOT BE indicating that it has been set. Rated
50 SELECTED WHEN THE ACTUATOR
HAS BEEN CONFIGURED TO OPEN
m ON TORQUE (refer to [C3] page 21)
50 UNLESS BACK SEATING AT RATED Should the set level of torque be
developed in opening, the actuator will Open Torque
Torque
TORQUE IS ACCEPTABLE.
m torque trip and stop. Boost
Using the + and - keys, display the
P? k PC k Ir k tP
recommended torque value.
PRESS THE m KEY. Boost
m
In the absence of a recommended
cr torque value, try a low setting and In checking mode, on pressing the m
m increase until satisfactory valve key after reviewing open torque setting,
operation is achieved. Open Torque the display will revert to valve position.
c1 k c2 k c3
40%
m If the actuator fails to
complete a open valve operation 40%
tC k tO
due to the set torque being
m reached (Torque Trip OP Alarm, page 5)
this may indicate a valve and/or
LC k LO
process problem or change. It is the
m responsibility of the user to ensure
the valve and process conditions are Open Torque
50
within specified operational limits 99%
before increasing the Set Open 99%
torque value.
24
LC Set Limit Closed LO Set Limit Open
NOTE: It is possible to set the Open With [LC] displayed 50 With [LO] displayed
Limit Position [LO] first.
m
50
50 Torque
m
m Set Close Limit Set Open Limit
Move to Close P? k PC k Ir k tP Move to Open
50
m
Torque
50 Positional Display IQT operating time can be adjusted between 25% and 100% of the maximum
m time (50% and 100% for IQT2000). IQT are factory set at the maximum speed.
To access speed setting [AA] screen, bus system [OP] has to be set to [On],
using the + and - key.
IQT Speed
IrDA
m comms
P? k PC k Ir k tP After this setting, proceed to screen [AA]. 100%
m Contact Function To meet full duty cycle performance, IQTM actuators are despatched with the With [AA] displayed
cr k Contact S1 r1 minimum speed set.
m Use the + and - key to select the
m required actuator operating time. The
Contact S2 r2
Primary m settings are displayed in percentage of
Functions
Contact S3 r3 maximum rated speed.
m PRESS THE KEY.
Contact S4 r4 The displayed value will flash, indicating
m
ESD Action that it has been set.
Control Mode
Configuration A1 All speed settings are adjustable in
m percentage increments. Any value of %
Extra Indication Remote
Contacts CPT Control Source outside of the range stated will not be
Option Selection OE k OI k Od accepted into the actuator memory.
m
FL
m NOTE: Mains power has to be on
PA
for speed setting to be carried out.
m
IQT Speed IQT Type
Setting Setting
AA k Ab
26
Return to
Positional Display
50 If the procedure has been followed as
described, the positional display will
m indicate that the actuator is in the open
50 position.
Torque
Fig. 9
50
Positional Display 28
m
Torque
2-Wire Remote
Priority: Stay
Actuators are delivered with the The actuator can be set to carry out a Where a high level of safety integrity The default setting for Torque Switch
interlock facility disabled [OF] Disabled . partial stroke test using a signal applied is required, Conditional Control can Bypass is [OF] Off , the torque switches
Refer to the actuator wiring diagram to the open interlock input to initiate be configured. In this mode two are not bypassed during the unseating
or PUB002-002 for interlock control a partial stroke test. Refer to wiring discreet signals are required for remote movement.
circuits. diagram. operation. Remote control will be
To bypass the torque switches during
conditional on both a control signal
To enable remote external interlocks The default for partial stroke/interlocks the unseating movement press the +
(open or close) and the appropriate
press the + or - key. is [OF] Disabled . or - key.
interlock signal being applied
The display will change to [On] Enabled . To enable partial stroke testing press simultaneously. Failure of either or a The display will change to [On].
the + or - key. spurious signal will not cause operation.
PRESS THE KEY. PRESS THE KEY.
The display will change to [PS] Partial Interlocks [A8] must be set [On]
The displayed option will flash (stored) Enabled . Interlock signals are not The displayed option will flash (stored)
Stroke .
indicating that it has been set. required for local operation. indicating that it has been set.
PRESS THE KEY.
The default setting for conditional The torque switches will be bypassed
The displayed option will flash (stored) control is [OF] Disabled . To enable from closed limit to 5% open when
indicating that it has been set. conditional control press the + or - key. opening and from open limit to 95%
The display will change to [On] Enabled . when closing. Bypassing the torque
Interlocks switches makes torque in excess of
Disabled PRESS THE KEY. rated and up to actuator stall available
for unseating a sticky valve. Outside
The displayed option will flash (stored)
these positions the torque setting will
Interlocks
indicating that it has been set.
revert to the values set for [tC] Close
Note: If interlocking is required in only Partial Stroke Torque , see page 22 and [tO] Open
one direction, it will be necessary to
Torque , page 23.
connect a link between the actuator
terminals associated with the other To access partial stroke test settings
direction. Refer to wiring diagram. PRESS THE m KEY.
Conditional
Refer to Appendix A, page 84 for Control: Disabled
instructions on partial stroke settings. Torque Switch
Bypass: Off
35
AA
9.4 Option Extra OE Display Extra Contact
Indication Contacts Set-up Screens
Extra indication contacts S5 [r5], S6 The action of turning on the Extra
[r6], S7 [r7] and S8 [r8] are available as Contact Option makes an additional
an option. series of set-up screens available
Check actuator circuit diagram for
inclusion.
When the Extra Contact Option is
included the set-up procedure and
Extra Contacts Extra Contacts
available contact functions for S5 S8
Menu: On Menu: Off
are identical to S1S4 (refer to Section
9.2 page 30).
Press the + or - key to select the Extra
Unless specified with order the default
Contact Option set-up screens [On].
setting for the extra indication contacts
will be as follows: PRESS THE KEY.
S5 [r5] Close limit The displayed option will flash (stored)
indicating that it has been set.
S6 [r6] Open limit
PRESS THE m KEY TO ACCESS S5
S7 [r7] Torque trip mid
TO S8 SET-UP DISPLAYS.
S8 [r8] Remote selected
The procedure for setting S5 to
NOTE: If the Extra Contact Option is S8 is the same as that for S1 to S4
not included in the actuator build, any (refer to Section 9.2 page 30).
settings made for S5S8 will have no
effect on the indication output of the
actuator.
36
AA
9.5 Option CPT [OI]
4-20mA Indicator
Setting instructions for actuators NOTE: If the actuator has options
including a CPT providing 4-20mA Folomatic and CPT, redefining the
analogue position feedback. CPT, will require the Folomatic to be
recommissioned (refer to Section 9.6
The CPT is an optional extra. It may be Folomatic [OI] page 37).
internally or externally powered.
Check wiring diagram for inclusion and
connection details.
Analog Feedback
CL=4ma OP=20mA
Deadband
1.2%
PRESS THE KEY. PRESS THE KEY.
Analog Signal
Range: 0-20V The displayed value will flash (stored) The displayed value will flash (stored)
indicating that it has been set. indicating that it has been set. PRESS THE KEY.
0-20V Range Selected
Press the k key to display: Press the k key to display: The displayed value will flash (stored)
[FH] High Set Point Position . [Fd] Deadband . indicating that it has been set.
PRESS THE KEY.
The displayed option will flash (stored) Press the k key to display:
indicating that it has been set. [Ft] Motion Inhibit Time .
Failsafe Action
Go to Low SP
PRESS THE KEY.
The displayed option will flash (stored) Manual / Auto
Motion Inhibit
indicating that it has been set. Disabled
Time: 05 seconds
NOTE: Failsafe action ON will be PRESS THE KEY.
effective only for systems using an The displayed option will flash (stored) PRESS THE KEY.
offset or live zero signal range, for indicating that it has been set.
PRESS THE KEY. example 420mA. The displayed option will flash (stored)
Commissioning of the Folomatic is indicating that it has been set.
The displayed value will flash (stored) [FF] will only be displayed if [FA] has now complete. Remote control may be
indicating that it has been set. been set to [On]. selected. Using the wiring diagram supplied with
the actuator, follow the instructions
Press the k key to display: Press the k key to display: on how to connect the Manual / Auto
[FA] Loss of Signal . [FF] Failsafe Action . selection switch.
Commissioning of the Folomatic is
now complete. Remote control may be
selected.
40
AA
9.7 Remote Control Source Od Remote Control Source
The available forms of remote control The setting of Remote Control Source To change the remote source press the
are listed below: will be determined by the option that + or - key until the required setting is
has been fitted, if any. displayed.
1 - Standard hardwired control
2 - Analogue control-Option Folomatic [rE] Hard-Wired Only : Pushbutton/relay PRESS THE KEY.
3 - Network control including: contact control.
The displayed option will flash (stored)
Option Pakscan
[oP] Network : Pakscan, Profibus, indicating that it has been set.
Option Modbus Modbus, Foundation Fieldbus or
Option Profibus DeviceNet control.
Option Foundation Fieldbus
Option DeviceNet [bo] Folomatic : Analogue Proportional
control.
The setting for Remote Control Source
[OF] Remote Disabled : Remote control Control Type
will depend on the type of remote
Hard-wired Only
control required and the option disabled.
specified and fitted. Check actuator Standard Hardwired
circuit diagram for remote control form. Remote Control
41
AA
9.8 Bus System PA Pakscan Node Pb Pakscan
Option Pakscan Address Baud Rate
Setting instructions for actuators The actuator Pakscan Field Control Unit The actuator Pakscan Field Control Unit
including an optional Pakscan Field must be allocated a unique loop node baud rate must be set to the loop baud
Control Unit check wiring diagram for address. rate. For a Pakscan 2-wire control loop
inclusion. the selected baud rate must be common
The actuator must be in Loopback Baud Rate
to the master station and all the field
Before setting the parameters for and isolated from Pakscan loop traffic
control units included in the loop. 2400 Baud
for its address to be set or changed.
Option Pakscan ensure Remote
Loopback can be achieved in two ways: The actuator must be in Loopback
Control Source [Od] has been and isolated from Pakscan loop traffic
1. Turn OFF the master station. PRESS THE KEY.
selected to [oP] in Section 9.7. for its baud rate to be set or changed.
(refer to page 40) 2. Isolate the actuator from the The displayed option will flash (stored)
Loopback can be achieved in two ways: indicating that it has been set.
2-wire control loop both in & out.
1. Turn OFF the master station. Press the k key to display:
Using the + or - keys display the
required loop address. 2. Isolate the actuator from the [PF] Aux I/P Mask .
2-wire control loop both in & out.
Address to be set within the range
01-240 (01F0 Hexadecimal). (refer to
table on page 81).
Using the + or - keys display the
required baud rate.
[01] = 110 baud
Node Address [03] = 300 baud
Hex 01 : Dec 001 [06] = 600 baud
[12] = 1200 baud
PRESS THE KEY.
[24] = 2400 baud
The displayed option will flash (stored)
indicating that it has been set.
Press the k key to display:
[Pb] Baud Rate .
42
AA
PF Pakscan Remote
Auxiliary Input Mask
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These Rules
are used when supplementary remote control or digital auxiliary inputs are required
in addition to the standard control and feedback features incorporated into the 1. Function bit set to 0
Pakscan card. It is also possible to have a combination of both remote control and Any function bit set to 0 indicates that the particular aux input is to be treated as
volt-free inputs to provide, for example, open and close control as well as a high a digital signal for field status reporting, e.g. a level switch or motor running status.
and low tank level alarm indication, supplied via an external transducer.
If the corresponding invert bit is set to a 0, an open contact is reported as a logic
The hexadecimal number displayed under PF can be considered as a software "1" and a closed contact is reported as a logic 0 (i.e. this will invert the input).
mask. It is this mask that tells the Pakscan card what type of input to expect,
control or input signal, and what form the input will be, normally open or normally If the corresponding invert bit is set to a 1, an open contact is reported as a logic
closed (refer to page 81 for Binary, Hexadecimal and Decimal Conversion Table). "0" and a closed contact is reported as a logic 1 (i.e. this gives a noninverting
input).
To decipher the mask the number needs to be split into two separate hexadecimal
characters, each of which can be sub-divided into 4 binary bits. The first 4 bits 2. Function bit set to 1
represent the function and the second 4 represent the input source (known as Any function bit set to 1 indicates that the particular aux input is to be treated as
invert). Pictorially this can be represented as: a digital command to operate the actuator.
Left side hex character Right side hex character When the corresponding invert bit is set to a 0 this represents an N.C. contact
Aux 4 to 1 (function) AUX 4 to 1 (Invert) as being the command source, i.e. a closing contact de-energises the input and an
Bits 4 3 2 1 4321 opening contact energises the input.
When used for remote control of the actuator bits 4 to 1 of the function character When the corresponding invert bit is set to a 1, this represents an N.O. contact
have been designated as follows: as being the command source, i.e. a closing contact energises the input and an
opening contact de-energises the input.
Bit 4 (AUX4) ESD
Bit 3 (AUX3) Stop (Maintain) 3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to
Bit 2 (AUX2) Close the default value of [nO]. The [A1]ESD direction setting should be set to either
Bit 1 (AUX1) Open Open or Close the valve (refer to page 32).
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1) 4. Stop (Maintain) Control
When energised this will make the Aux input Open/Close/ESD control push-to-run,
(non-maintained). When de-energised, the Aux input Open/Close/ESD control will
be maintained.
43
AA
PF Pakscan Remote
Heading PF Pakscan Remote
Auxiliary Input (continued) Auxiliary Input
5. Remote I/P Setting Using the + or - keys display the
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting.
For Pakscan this is [oP] Network .
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 .
Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD Aux I/P Mask
and Stop/maintain is NC. Bits: 0000 1111
Node Address
Hex 01 : Dec 001 Baud Rate
2400 Baud
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.) 4. Stop (Maintain) Control
When energised this will make the Aux input Open/Close control push-to-run.
When de-energised, the Aux input Open/Close control will be maintained. ESD is
always push to run (non maintained).
46
AA
PF Modbus Remote
Heading PP Modbus Parity
Auxiliary Input (continued)
5. Remote I/P Setting Using the + or - keys display the Where Modbus parity bit detection is
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting. used the module must be set with the
parity bit setting of the host.
For Modbus this is [OP] Network .
Using the + or - keys display the
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 . required parity bit:
Examples [no] None (no) parity bit
1. The full range of remote controls is needed. Open and Close are NO and ESD Aux I/P Mask
Bits: 0000 1111 [En] Even parity bit
and Stop/maintain is NC.
[Od] Odd parity bit
Aux I/P 4 3 2 1
Function 1 1 1 1 =F
PRESS THE KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [F3]
The displayed option will flash (stored)
2. Open and close control is required along with 2 inverted digital signal inputs.
indicating that it has been set. Modbus Parity
(Note that with this setting the open and close commands will be maintained.)
Press the k key to display: None
Aux I/P 4 3 2 1
[PP] Modbus Parity .
Function 0 0 1 1 =3 No Parity Bit
Invert 0 0 1 1 = 3 i.e. set [PF] to [33]
PRESS THE KEY.
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input. The displayed option will flash (stored)
indicating that it has been set.
Aux I/P 4 3 2 1
Function 1 1 0 0 =C For Modbus module positioning
settings and action on loss of signal
Invert 1 0 0 0 = 8 i.e. set [PF] to [C8] setting, refer to Section 9.12 page 53.
If Modbus positioning control and
action on loss of communication are
required, PRESS THE m KEY.
Display [FL] Low Set Point Position
(refer to page 53).
47
9.10
AA Bus System PA Profibus Node
Option Profibus DP [OP] Address
Setting instructions for actuators The Profibus DP module must be
including an optional Profibus DP allocated a unique address.
module check wiring diagram for
To set the address the Profibus module
inclusion.
must be isolated from the host by Node Address
disconnecting the RS485 highway or Hex 01 : Dec 001
Before setting the parameters for turning off the host device.
Option Profibus ensure Remote
Using the + or - keys display the PRESS THE KEY.
Control Source [Od] has been required address.
selected to [oP] in Section 9.7. The displayed option will flash (stored)
(refer to page 40). Address to be set within the range indicating that it has been set.
(01-126 to 7E Hexadecimal) (refer to
page 81 for conversion). If an address Press the k to display:
Any settings made locally at value outside this range is entered, the [Pb] Baud Rate .
the actuator may be overwritten by address set will revert to 01 (for 00) or
the host on startup unless the GSD 7E (for value above 7E). [Pb] has no relevance for the
files are locked on the Profibus card. Rotork Profibus DP Mk.2 card.
Refer to publication S420E available
from www.rotork.com Therefore, if the Rotork Profibus DP Mk.2
card is fitted, press the k to display:
[PF] Aux I/P Mask .
The actuator power must be
cycled for the changes to take effect.
48
AA
PF Profibus Remote
Auxiliary Input
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These Rules
are used when supplementary remote control or digital auxiliary inputs are required
in addition to the standard control and feedback features incorporated into the 1. Function bit set to 0
Profibus module. It is also possible to have a combination of both remote control Any function bit set to 0 indicates that the particular aux input is to be treated as
and volt-free inputs to provide, for example, open and close control as well as a a digital signal for field status reporting, e.g. a level switch or motor running status.
high and low tank level alarm indication, supplied via an external transducer.
If the corresponding invert bit is set to a 0, an open contact is reported as a logic
The hexadecimal number displayed under PF can be considered as a software 1 and a closed contact is reported as a logic "0" (i.e. this will invert the input).
mask. It is this mask that tells the Profibus module what type of input to expect,
control or input signal, and what form the input will be, normally open or normally If the corresponding invert bit is set to a 1, an open contact is reported as a logic
closed (refer to page 81 for Binary, Hexadecimal and Decimal Conversion Table). 0 and a closed contact is reported as a logic 1 (i.e. this gives a noninverting
input).
To decipher the mask the number needs to be split into two separate hexadecimal
characters, each of which can be sub-divided into 4 binary bits. The first 4 bits 2. Function bit set to 1
represent the function and the second 4 represent the input source (known as Any function bit set to 1 indicates that the particular aux input is to be treated as
invert). Pictorially this can be represented as: a digital command to operate the actuator.
Left side hex character Right side hex character When the corresponding invert bit is set to a 0 this represents an N.C. contact
Aux 4 to 1 (function) AUX 4 to 1 (Invert) as being the command source, i.e. a closing contact de-energises the input and an
Bits 4 3 2 1 4321 opening contact energises the input.
When used for remote control of the actuator bits 4 to 1 of the function character When the corresponding invert bit is set to a 1, this represents an N.O. contact
have been designated as follows: as being the command source, i.e. a closing contact energises the input and an
opening contact de-energises the input.
Bit 4 (AUX4) ESD
Bit 3 (AUX3) Stop (Maintain) 3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to
Bit 2 (AUX2) Close the default value of [nO]. The [A1]ESD direction setting should be set to either
Bit 1 (AUX1) Open open or close the valve (refer to page 32).
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.) 4. Stop/Maintain Control
When energised this will make the Aux input Open/Close control push to run When
de-energised, the Aux input Open/Close control will be maintained. ESD is always
push to run (non maintained).
49
AA
PF Profibus Remote
Heading PF Profibus Remote
Auxiliary Input (continued) Auxiliary Input
5. Remote Source Setting [Od] Using the + or - keys display the
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting.
For Profibus this is [OP] Network .
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 .
Examples
Aux I/P Mask
1. The full range of remote controls is needed. Open and Close are NO and ESD
Bits: 0000 1111
and Stop/maintain is NC.
Aux I/P 4 3 2 1
Function 1 1 1 1 =F PRESS THE KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [F3]
The displayed option will flash (stored)
2. Open and close control is required along with 2 inverted digital signal inputs. indicating that it has been set.
(Note that with this setting the open and close commands will be maintained.)
If Profibus positioning control and
Aux I/P 4 3 2 1 action on loss of communication are
Function 0 0 1 1 =3 required, PRESS THE m KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [33] Display [FL] Low Set Point Position
(refer to page 53).
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input.
Aux I/P 4 3 2 1
Function 1 1 0 0 =C
Invert 1 0 0 0 = 8 i.e. set [PF] to [C8]
50
9.11
AA Option DeviceNet PA DeviceNet Node Pb DeviceNet Baudrate
Address
Setting instructions for actuators The DeviceNet module must be The DeviceNet module must be set to
including an optional DeviceNet DFU allocated a unique address. the DeviceNet highway baudrate.
module check wiring diagram for
Using the + or - keys display the Using the + or - keys display the
inclusion.
required address. required baudrate:
Before setting the parameters for Address to be set within the range (01- [01] = 125 k baud
Option DeviceNet ensure Remote 63 to 3F Hexadecimal). See page 81 for
[03] = 250 k baud
Control Source [Od] has been conversion. If an address value outside
selected to [oP] in section 9.7. this range is entered, the address set [06] = 500 k baud
(refer to page 40). will revert to 01 (for 00) or 3F (for value
above 3F).
The actuator power must be
cycled for the changes to take effect.
Baud Rate
Node Address 500k baud
Hex 01 : Dec 001
When the timer option is available an Timer Start PRESS THE KEY.
additional series of settings can be Closing
accessed by pressing the m key. The displayed option will flash (stored)
indicating that it has been set.
NOTE: If the timer option is not Pulsed Operation Around the
available pressing the m key will not Closed Position If the timing is not required in the
access setting. closing stroke select [JC] to [ ] [ ] valve
NOTE: Instructions [JC] and [JO] are closed position.
Press the m key to display interrupter for timer operation around the Closed
timer set-up screens. Press the k key to display:
position. For timing around the Open [JO] Timer Stop Position .
position, read stop for start [JC] and
start for stop [JO].
Press the k key to display:
[JC] Timer Start Position .
56
AA
JO Position in Valve Opening Jn Contactor OnTime JF Contactor OffTime JE ESD Override
Stroke for Timer to Stop Interrupter Timer
Using the + or - key select the position Using the + or - key select the actuator Using the + or - key select the actuator The interrupter timer may be overridden
for the TIMER TO STOP WHEN THE run period in the range 199 seconds. stop period in the range 199 seconds. when the actuator is under ESD signal
VALVE IS OPENING. command. This will mean the actuator
will run to limit without stop/start
[ ] [ ] Closed = valve closed action under ESD command.
[00] to [99] = percentage open
Refer to [A1] [A3] (refer to page 32
[ ] Open = valve open Timer On Time Timer Off Time for ESD settings).
05 Seconds 25 Seconds The default for ESD override interrupter
timer is [OF] No . The interrupter timer
Actuator Run Period Actuator OFF Period
will continue stop/start action during
Set for 5 Seconds Set for 25 Seconds
Timer Stop ESD action.
Position: 25% PRESS THE KEY. PRESS THE KEY. If ESD must override the timer use the
+ or - to display [On] Yes .
The displayed option will flash (stored) The displayed option will flash (stored)
Timer Set to Stop Pulsing indicating that it has been set. indicating that it has been set.
when Opening Valve
Reaches 25% Open Press the k key to display: Press the k key to display:
[JF] Timer Off Time . [JE] Timer Override ESD
PRESS THE KEY. (refer to note on Page 57).
Timer Override
The displayed option will flash (stored) ESD: No
indicating that it has been set.
ESD Override Timer OFF
If timing is not required in the opening
stroke select [JO] to [ ] [ ]. PRESS THE KEY.
Press the k key to display: The displayed option will flash (stored)
[Jn] Timer On Time . indicating that it has been set.
57
AA Example 9.14 Setting Tool 9.15 Inhibit Operation
Local Control [Or] After Power Loss [OS]
An actuator fitted with the interrupter The default setting for Setting Tool When protection is enabled, on power
timer and set as the example shown in Local Control is [OF] Control Disabled . The default setting for this up if a low battery is detected, the
these instructions would operate at: protection option is disabled [OF]. actuator will inhibit electrical operation
To enable Setting Tool Control press the When disabled it is important
+ or - key to select [On]. and display Power Loss Inhibit via
Rated speed from full Open to 25% that the actuator is not manually actuator alarm display (refer to page 5)
Open. operated during a power failure
PRESS THE KEY. and the monitor relay will de-energise.
1/6 if the battery is low as changes in Limits must reset and the battery
rated speed from 25% Open to Fully
The displayed option will flash (stored) position cannot be tracked - refer replaced refer to page 67.
Closed and from Fully Closed to 25%
indicating that it has been set. to page 6 for battery level status
Open.
display. Should this occur the
With the red control selector in Local, Press the k key to display:
Rated speed from 25% Open to Fully limits must be reset before electric
the Setting Tool control keys are active [OH] Close Colour .
Open. operation takes place- refer to LC/
(refer to page 12). LO page 27. Locking the hand auto
lever can prevent manual operation
- refer to Section 3.1, page 3.
Note
I-R Tool Control
On
With a Folomatic option fitted and
the Interrupter Timer enabled, the Local Setting Tool Control Enabled Power Loss
Folomatic Motion Inhibit Timer must Inhibit : Off
be adjusted to the same time as that Vandal resistant actuators ONLY
set for the Interrupter Timer contactor (red/black selectors not supplied). The protection may be enabled by using
off. For control, the selection of [Or] Vandal the + or - key to select [On]
Failure to do so will cause the actuator Resist is as follows:
response to defer to the lower time
PRESS THE KEY.
[On] Local Only .
which may cause control or process The displayed option will flash (stored)
problems. [OF] Control Disabled . indicating that it has been set.
For ON and OFF times in excess of [rE] Remote Only .
99 seconds apply to Rotork.
58
9.16
AA Indicator LEDs OH Close LED Colour OU Mid-Travel LED 9.17 Display Language
The colour of the LEDs on the IQT The default close limit position indicator The default for mid travel position
display are user configurable. These colour is [gr] Green . indicator colour is [OF] Off . UL
menu sceens allow you to set the Close Language
If red indication is required at the close If mid-travel LED indication is required,
LED colour and the Mid-Travel LED
limit position, press the + or - key. press the + or - key.
being on or off. The default display text language is
The display will change to [rE] Red . The display will change to [On] On . English. If the language was specified
at time of order the actuator will be
PRESS THE KEY. PRESS THE KEY. despatched with the specified language
The displayed option will flash (stored) The displayed option will flash (stored) set.
indicating that it has been set indicating that it has been set.
Press the + or - keys to view alternative
languages.
Available standard languages:
German Deutsch
Close Colour Mid-Travel LED
Green Off French Franais
Spanish Espaol
Press the k key to display: Press the k key to display: Depending on the specified language,
[OU] Mid-Travel LED . [UL] Language . only English and one other may be
supplied with the actuator.
Language
English
59
9.18
AA Default Options
[d1] and [d2]
All IQT functions are configured to a set of Rotork default (standard) settings before Rotork standard [d1] Default settings for IQT:
despatch, see the table opposite. When requested, alternative settings specified
with the order will be used. When site commissioning takes place, entered settings Function [d1] Default Setting
overwrite Rotork defaults and these current settings are used for operation along [P?] Password Unaffected will remain as set
with the remaining unadjusted defaults. [Ir] IrDA Insight [On] IrDA Enabled
Should difficulty be encountered during commissioning the default settings can be
reinstated, returning the actuator configuration to its original manufactured state. Basic Settings
Site commissioning must then begin again. [C1] Close Direction [C] Clockwise
There are two levels of default: [C2] Close Action [Ct] Close on Torque
d1 Rotork standard or customer specified Basic and Configuration Settings. [C3] Open Action [Ot] Open on Torque
[tC] Close Torque [40] 40% of rated
d2 Limit positions only factory set limits.
[tO] Open Torque [40] 40% of rated
NOTE: Settings associated with control options Folomatic, Pakscan, Modbus
Profibus and Foundation Fieldbus are not affected by d1 or d2. Configuration Settings
Functions will remain as set. [r1] Indication Contact S1 [CI]/[nO] Close, Normally Open
If d1 is entered, all Basic and Configuration Settings except limit positions [r2] Indication Contact S2 [OP]/[nO] Open, Normally Open
will return to their default setting. See the table opposite for Rotork
[r3] Indication Contact S3 [CI]/[nC] Close, Normally Closed
standard settings. Basic settings (except limits) and Configuration Settings
must then be checked and reset as required (refer to Basic Settings page 17 [r4] Indication Contact S4 [OP]/[nO] Open, Normally Closed
and Configuration Settings page 27). [A1] ESD Action [SP] Stay put on ESD
If d2 is entered the limits will be reset, with the actuator positioned at 50%. [A2] ESD Contact Type [nO] Normally Open (make for ESD)
Limits must then be reset to the suit the valve (refer to Basic Settings page 17).
[A3] ESD Thermostat Override [OF] Thermostats Active during ESD
[A4] ESD Override Interlocks [OF] Interlocks Active during ESD
[A5] ESD Override Local Stop [OF] Local Stop Active during ESD
[A6] Maintained Local Control [On] Maintains in Local Control
60
9.18
AA Default Options
[d1] and [d2] cont.
Rotork standard [d1] Default settings continued: The Rotork standard default settings are subject to change without notice.
If specified with order, [d1] settings will be configured as requested.
Function [d1] Default Setting
To reinstate [d1] settings, with [d1] displayed.
[A7] 2-wire Remote Control [SP] Stay Put on 2-wire signal
[A8] Interlocks [OF] I/L function disabled PRESS THE KEY.
[A9] Conditional Control [OF] Function disabled
The setting bars will flash, indicating the [d1] default settings have been reinstated.
[AE] Torque Switch Bypass [OF] Function disabled
[OE] Option Extra Indication Contacts [OF] Unless fitted. See wiring diagram To reinstate factory set limits (actuator positioned at 50%) with [d2] displayed,
[OI] Option CPT [HI] 4mA at Closed PRESS THE KEY.
[Od] Remote Source [rE] Unless option fitted
(refer to 9.7 page 40.) The setting bars will flash, indicating the [d2] default limits have been reinstated.
[OJ] Option Interrupter Timer [OF] Unless fitted. See wiring diagram Limits must now be reset. Refer to page 24.
[Or] Setting Tool Local Control [OF] Setting Tool Control disabled
[OS] Power Loss Inhibit [OF] Protection off
50 Positional Display Actuator type determines the speed range and is factory set. Should the actuator
m Motor Speed Control PCB be replaced with a spare, the actuator type must be set.
Failure to set the correct type will invalidate the actuator performance specification
and warranty. To set the actuator types go to setting [Ab] in the secondary
IQT Type
IrDA
m comms functions.
P? k PC k Ir k tP IQT 125
m Contact Function With [Ab] displayed
cr k Contact S1 r1
m Use the + and - key to select the
m required actuator type. The selectable
Contact S2 r2 values are related to actuator type as
Primary m
Functions follows:
Contact S3 r3
m Value Type
Contact S4 r4 1 IQT125
m
3 IQT250
ESD Action
Control Mode 6 IQT500
Configuration A1
m 12 IQT1000
Extra Indication Remote 24 IQT2000
Contacts CPT Control Source
Option Selection OE k OI k Od PRESS THE KEY.
m The displayed value will flash,
FL indicating that it has been set.
m
PA Any value of hex outside of the range
m stated will not be accepted into the
IQT Speed IQT Type
actuator memory.
Setting Setting
AA k Ab
NOTE: Mains power has to be on for
actuator type setting to be carried out.
62
AA
10 Heading
IQT Battery Failsafe
10.1 Introduction. There are three possible failsafe actions For safety the IQT Failsafe battery
that can be customer configured: WARNING: pack is shipped with DC power fuses
The IQT battery failsafe actuator
provides electrical operation after loss CONTAINS BATTERIES FS3 and FS4 removed. It is essential
Failsafe Close -
of main AC electrical supply, allowing that the fuses are removed before
Close valve on loss of AC supply
the valve to be controlled to a process, FIRE, EXPLOSION AND SEVERE any maintenance work is carried
mains fail safe position. On loss of AC Failsafe Open - BURN HAZARD. DO NOT SHORT out on the actuator or the battery
supply, power is provided from integral Open valve on loss of AC supply CIRCUIT. DO NOT INCINERATE. assembly.
batteries located in a extended version Stayput waiting for command - The Before fitting Fuses FS3 and FS4 the
of the terminal cover. With AC power DO NOT DISASSEMBLE BATTERY
actuator can then be directed to operate IQT actuator must be commissioned
applied to the actuator, the batteries PACK. RECHARGE ONLY AS
via local or standard remote control in accordance with section 7, page
are charged from the actuator. signals* within 30 minutes of AC power PART OF THE IQT. DO NOT 11 of this manual.
being removed. EXPOSE BATTERIES TO AMBIENT
TEMPERATURES ABOVE 60C
*Remote signals must be applied to
standard remote control inputs, close on THE IQT BATTERY FAILSAFE
terminal 33, open on terminal 35 or ESD ACTUATOR CONTAINS HIGH
on terminal 3 of battery pack connector. CAPACITY BATTERIES WHICH
On loss of AC supply remote control via ARE CONNECTED TO ACTUATOR
Folomatic proportional control or serial TERMINALS 14 (+) AND 21
digital network signals are not available. (). DC BATTERY POWER MAY BE
*On loss of AC supply the IQT battery SUPPLIED TO THESE TERMINALS
failsafe does not support customer WHEN THE AC ELECTRICAL
nominal 24V DC supply on terminals SUPPLY IS SWITCHED ON AND
4 (-ve) and 5 (+ve) and therefore SWITCHED OFF.
control signal supply must be externally
powered. Refer to wiring diagram.
On loss of AC supply the IQT battery
failsafe does not support analogue
current position transmitter (CPT)
position feedback or serial network
communication. The IQT monitor relay
will de-energise on loss of AC supply.
63
AA
10 Heading
IQT Battery Failsafe continued
10.2 Battery Failsafe Specification Charging Time typically 4 hours Failsafe Operation Performance:
from a discharged state (depending on Number of operations at 75% rated torque.
Environmental: ambient temperature).
Operating temperature -30C to + 60C.
Charge state The lower line of text Temperature C IQT125 IQT250 IQT500 IQT1000 IQT2000
Enclosure (IQT battery Failsafe actuator): wll display the state of the battery, see
Watertight IP68 7m / 72 Hrs. -30 15 12 6 3 1
fig.2.
-20 50 40 20 10 5
Battery Pack: On loss of AC power, the state of the
Type: Sealed leadacid batteries located battery is not displayed. -0 63 50 25 12 6
in a vented enclosure. DC power supply Fuses FS 3 and FS4 20 75 60 30 15 7
Voltage & Capacity: 28V 2.5Ah. are rated at 20A, automobile type ATO 40 75 60 30 15 7
Fast acting.
Float life: 8 Years at 20C, 3 years at 60 75 60 30 15 7
40 C. Charge/control Fuses FS1 and FS2
are rated 2A, 20mm quick blow.
Storage Life: 2 years at 23C, 2 months
at 60 C. The battery supply will auto disconnect IQT Battery Failsafe Actuator Display
at 20V or 30 minutes after AC supply is
Battery pack assembly weight: 5.5Kg. removed from the actuator to prevent
For total IQT battery failsafe weight, damage caused by deep discharge of
add 5.5Kg to the actuator weights batteries.
listed on page 80.
Maintenance :
Charger : Ensure the two vents located in the
The IQT battery failsafe is despatched battery pack cover are not removed,
with the batteries in a charged state, plugged or covered. The batteries are
however once the IQT is connected to sealed lead acid type and require no
AC power the batteries will automatically maintenance. Refer to section 11, page
begin charging to bring them to the 67 for IQT range maintenance.
float charge state. For correct battery FS Ready
charging, the IQT supply voltage must Fig. 1
not be less than 90% of nominal. FS Boost Charge
FS Charging
Fig. 2
64
AA
10 Heading
IQT Battery Failsafe continued
10.3 Failsafe Commissioning 1. Remove Cover. Figure 3 2. Set Control Links. Figure 4 3. Connect ESD/Interlock
Instructions control wiring. Figure 5
Ensure the AC power supply to the Referring to the label, locate PCB links
Before commissioning actuator is switched OFF. LK1 and LK2. Links determine required If the control of the IQT actuator
action on loss of AC supply to the with AC supply switched ON requires
the failsafe operation it Using a 6mm allen key remove the four actuator. emergency shut down and/or interlocks,
screws securing the IQT battery failsafe
is essential that the IQT cover and remove cover from actuator Using pliers, fit links LK1 and LK2 in
ESD and/or interlock field wiring must
actuator has first been be connected to the green terminal
housing. The cover houses the battery required positions. plug located on the battery pack
commissioned in accordance pack and charging/control circuitry and assembly.
care must be taken that it does not drop. Links bridge between pins 1-2 or 2-3
with the Installation and and must be set for the desired action If ESD and/or interlocks do not form
Commissioning Instructions in Ensure the two 20A fuses located in a as detailed in table the below: part of the IQT control scheme then no
plastic bag are kept safely - DO NOT FIT wiring is necessary.
this manual. *The direction required for failsafe
The cover is restrained with an external operation and ESD contact form Remove plug by pulling it straight up
chain to support its weight (5.5 Kg (if being used) is set with the IQT and connect field wiring for ESD and/or
approx) and prevent interconnecting setting tool. Refer to page 66 of this interlocks as indicated on the label and
cables being damaged. The battery manual. actuator wiring diagram.
failsafe cover assembly is supported
by the restraining chain during Once connected, re-fit the wired plug
commissioning. LK1 LK2 Required action into its socket. The plug and socket
1-2 1-2 Failsafe on loss of supply, are polarised, ensuring they cannot be
ESD [A2] set [NO]* mated incorrectly.
2-3 1-2 Failsafe on loss of supply,
ESD [A2] set [NC]*
1-2 2-3 Stayput waiting for
command (30 Min max)
65
AA
10 Heading
IQT Battery Failsafe continued
Fig. 4 Fig. 6
66
AA
10 Heading
IQT Battery Failsafe continued
H1
With the actuator powered up and For troubleshooting, access the BATTERY LOW ON POWER UP
Local or Stop selected, eight Help following Help Screens and refer to Bar ON = Low battery detected On
Screens can be accessed using the text: Power Up.
Setting Tool (refer to Fig. 9.1 page 29
If [OS] is selected [On] (default is [OF])
Phase Position
H1 Factors inhibiting electrical
for their location). Loss Error
operation. the actuator operation will be inhibited
With Remote selected press the m when powered up with a discharged
key on the Setting Tool twice. The Help H2 Monitor battery level and ESD
battery (refer to [OS] page 57).
Screens will be displayed. control input.
The battery should be replaced at the
Each screen uses bars to indicate H3 Monitor the position limit and
Local earliest opportunity (refer to page 67).
the status of a particular control or actuator power supply status. Controls
indication function. Each bar reacts to H4 Monitor remote control inputs to Error LOCAL CONTROLS ERROR
changes in the status of its actuator the actuator. Battery Low Bar ON = Invalid Local Control
function by turning on or off. on Signals Detected.
H5 Monitor remote interlocks local Power-up
control inputs and motor For example if a Local Open and Close
thermostats. Help Screen 1 signal is detected at the same time this
would be classed as an invalid or fault
H6 Monitor torque switch status and POSITION ERROR condition.
IR Setting Tool communication for Bar ON = Current Position Error
vandal proof applications. Present. PHASE LOSS
H7 Monitor travel limits, centre During power up the actuator position Bar ON = Phase Lost (3 Phase
column and position limit status. processor compares the current position Actuators Only).
H8 Monitor the actuators position- to that stored in the Eeprom. If there is Loss of third monitored power supply
sensing devices. a discrepancy this is shown as a current phase connected to actuator terminal 3.
position error.
H9 Rotork use only.
Re-setting of both actuator limits
Help screen bars shown should now be carried out (refer to
are undefined and may page 24).
be ON, OFF or flashing.
74
AA
H2 Battery Level and H3 Factors Inhibiting H4 Remote Control
ESD ControlInput Electrical Operation Inputs
H2 H3 H4
LOW BATTERY
Bar ON = Battery level low.
Bar OFF = Battery OK.
ESD Clockwise Remote Remote
Active Bar ON when the battery is low but still Limit Maintain 2 Open 1
able to support the necessary actuator
functions. Anti
Low Clockwise ESD 2 Remote
Battery The battery should be replaced at the Limit Close 1
earliest possible opportunity.
Battery Inhibit Remote
Discharged ESD SIGNAL ACTIVE Close 2 ESD 1
Bar ON = ESD Signal is present.
continued...
75
AA
H4 Remote Control H5 Remote Interlocks,
Inputs continued Local Control
Inputs, & T/stat
H5
REMOTE CLOSE 1 CLOSE INTERLOCK THERMOSTAT TRIPPED
Bar OFF = Remote Close Signal Bar ON = Close Interlock Active. Bar ON = Thermostat tripped.
Present. (Actuator disabled)
Local Stop The actuator motor is protected by
ESD 1 not Open
Unauthorised Close electrical operation thermostats.
Bar OFF = ESD signal present. Selected Interlock
can be prevented by interlocking
Should the motor become overheated
the actuator (Close) control with an
REMOTE MAINTAIN 1 Thermostat Close the thermostats will trip and the
external interlock contact.
Bar OFF = Remote Maintain Tripped Interlock actuator will stop. On cooling the
signal present. If external interlocks are not required thermostat will automatically reset,
Bar ON = Remote Maintain not L ocal Open Local not the interlock function must be selected enabling operation. See the actuator
present and/or Remote Stop not Present Selected OFF. nameplate for the motor rating.
active.
Local Close Remote REMOTE NOT SELECTED LOCAL STOP NOT SELECTED
REMOTE OPEN 2 not not Bar ON = Remote control not selected. Bar ON = Local Stop not selected.
Bar OFF = Remote Open signal Present Selected Bar OFF = Remote control selected. Bar OFF = Local stop selected.
present from BUS option pcb. Help Screen 5
LOCAL CLOSE NOT PRESENT LOCAL NOT SELECTED
REMOTE CLOSE 2 OPEN INTERLOCK Bar ON = Local Close signal not present. Bar ON = Local control not selected.
Bar OFF = Remote Close signal Bar ON = Open Interlock Active. Bar OFF = Local Close signal present. Bar OFF = Local control selected.
present from BUS option pcb. (Actutator disabled)
LOCAL OPEN NOT PRESENT
ESD 2 Unauthorised Open electrical operation Bar ON = Local Open signal not present.
Bar OFF = ESD signal present can be prevented by interlocking Bar OFF = Local Open signal present.
from BUS option pcb. the actuator (Open) control with an
external interlock contact.
REMOTE MAINTAIN 2 If external interlocks are not required
Bar OFF = Remote Maintain the interlock function must be selected
signal present from BUS option OFF.
pcb.
76
AA
H6 Torque Switch Status & IR H7 Travel Limits, Centre
Heading
Setting ToolComms for Column & Remote
Vandal Proof Applications Indication Outputs
H6 H7
TORQUE SWITCH TRIPPED IR OPEN SIGNAL NOT PRESENT
Bar ON = Torque switch tripped. Bar OFF = IR Open signal present.
IR Remote When the actuator generates a value IR CLOSE SIGNAL NOT PRESENT
Control not Open
Selected of torque equal to that set for Open Bar OFF = IR Close signal present. Relay 4 Limit
(when opening) or Close (when closing)
IR Local Local it will stop, protecting itself and the IR LOCAL CONTROL DISABLED
Control Controls Relay 3 Close
Disabled not Fitted
valve from damage. This feature is Bar OFF = IR Local control enabled. Limit
known as Over Torque Protection.
To operate the actuator locally with
IR Closed Once a torque trip has occurred further the IR Setting Tool refer to the option Actuator
Signal not operation IN THE SAME DIRECTION is selection screen [Or] Section 9.14,
Relay 2 Moving
Present prevented.
page 57.
IR Open Torque This latching of the event protects Relay 1
Signal not Switch [Or] must be selected to [On].
Present Tripped the actuator and valve from repeated Help Screen 7
hammering against the obstruction IR REMOTE CONTROL NOT
Help Screen 6 as a response to a maintained control OPEN LIMIT
SELECTED
When actuators are supplied for signal. Bar OFF = IR Remote control Bar ON = Actuator has reached
Vandal Proof applications the local To de-latch the actuator it must be selected (vandal-proof units only). open limit.
control knobs are removed to prevent reversed. When actuator is supplied without local CLOSE LIMIT
unauthorised operation.
(For actuator torque adjustment, refer controls for vandal proof applications Bar ON = Actuator has reached
The local control functions are then to [tC ] and [tO] pages 22 and 23) the option selection screen [Or] must Close limit.
carried out by using the Infra-red be set to [rE] for Remote operation
Setting Tool. (refer to Section 9.14 page 57). ACTUATOR MOVING
Bar ON = Actuator moving.
LOCAL CONTROLS NOT FITTED
Bar OFF = Local controls fitted SWITCH CONTACTS S1, S2, S3, S4
(standard). Bar ON = S contact is close circuit.
Bar ON = Local controls not fitted
(vandal proof). Bar indication is real time and reactive
(refer to Section 9.2 [r1] page 30 for
configuration of Scontacts).
77
AA
H8 Actuator Position
Sensing Devices
H8
When the motor is running, ON and
OFF bit duration should be equal.
For the two sensors, A and B, correct
Position
Sensor A
operation is indicated by the following
truth table.
Position To observe this function, select manual
Sensor B operation and turn the actuator
handwheel clockwise, starting with all
sensors OFF:
CLOCKWISE 30 Deg.
Help Screen 8
Sensor B 0 1 1 0 0
POSITION SENSOR A
Senses output rotation. Used for Sensor A 0 0 1 1 0
the position sensing circuit. Correct
operation of the sensor is indicated by
the bar being ON (and OFF) 12 times
per output revolution. When the motor
is running, ON and OFF bit duration
should be equal.
POSITION SENSOR B
Senses output rotation. Used for
the position sensing circuit. Correct
operation of the sensor is indicated by
the bar being ON (and OFF) 12 times
per output revolution.
78
11.3
AA Heading
IQT Infrared
Diagnostic and Configuration
IQT actuators include an IrDA (Infrared To enable communication with IQ
Data Association) interface as standard, Insight the actuator IrDA interface The use of a notebook PC
allowing non-intrusive diagnostics, must be enabled. or PDA with actuators located in
analysis and configuration. hazardous areas will be subject
The default setting for IQT IrDA is [On], to local regulations. It is the
IQ Insight software tool for PC and IQ enabling IrDA. responsibility of the user to seek
Pocket Insight for PDA (Personal Digital guidance and permission.
To disable IrDA and prevent IrDA access,
Assistant) have been developed to
use the + or key. The display will The Rotork Setting Tool and Setting
enable the actuator configuration and
change to [OF]. Tool Pro are certified Intrinsically
onboard datalogger to be reconfigured
and analysed. A PC running IQ Insight Safe (IS) and therefore can be used
software or PDA running IQ Pocket in defined hazardous areas (refer to
Insight can be used to interrogate the PRESS THE KEY. page 12 and 13).
actuator via non-intrusive infra red IrDA The displayed option will flash (stored)
communication. Visit www.rotork.com indicating it has been set.
for information.
Alternatively, the intrinsically safe
Rotork Setting Tool Pro allows the
user to extract and store IQT actuator
configuration and datalogger files
within the Tool. Stored files can be IrDA Comms
uploaded over an IrDA USB interface Enabled
to a PC running Rotork IQ Insight
where they can be viewed, analysed IQ Insight and IQ Pocket Insight
and stored in a safe, clean environment. software are available free of charge
Using the Setting Tool Pro, actuator set from the Rotork web site,
up can be configured on the PC, stored www.rotork.com.
in the tool, transported to the actuator A kit is available from Rotork, which
and uploaded. The tool can transfer includes an IrDA-USB adapter and
the same configuration to multiple drivers for connection to a PC. The Kit
actuators where actuator setup is the also includes IQ Insight software. PDA
same. Refer to page 70. communication is via the internal IrDA port.
79
11.4
AA Environmental
Electrical & Printed circuit boards All Products Yes Yes 20 01 35 Use specialist recyclers
Electronic Wire All Products Yes Yes 17 04 10
Equipment
Glass Lens/Window Cenelec Qualified IQ/IQT. A Range Prism No Yes 16 01 20 Use specialist recyclers
Metals Aluminium Gearcases and covers most products No Yes 17 04 02 Use licensed recyclers
Copper/Brass Wire, IQ columns (not all sizes), motor windings No Yes 17 04 01
Zinc IQ clutch Ring and associated components No Yes 17 04 04
Iron/Steel Gears and Gearcases (A Range and larger IQ) No Yes 17 04 05
Mixed Metals IQ motor rotors No Yes 17 04 07
Plastics Glass filled nylon Covers, IQT clutch components, electronics chassis No No 17 02 04 Disposal as general comercial waste
Unfilled Gears No Yes 17 02 03 Use specialist recyclers
Oil Mineral & Kerosene Mixed Gearbox lubrication Yes Yes 13 07 03 Will require special treatment before
Mineral Gearbox lubrication Yes Yes 13 02 04 disposal, use specialist recyclers or
Food Grade Gearbox lubrication Yes Yes 13 02 08 waste disposal companies
Rubber Seals & Orings Cover and shaft sealing Yes No 16 01 99 May require special treatment before
disposal, use specialist waste disposal
companies
WARNING: The battery pack contains high capacity lead acid batteries which may have retained their charge. Only persons competent by virtue of
their training or experience should remove these items. For recommended procedures please contact Rotork. (see page 84).
80
AA
12 Heading and Measures
Weights
Refer to actuator nameplate for unit specific approval details USA hazardous Area
FM. Class 1, Division 1, Groups C, D, E, F, G hazardous areas.
European Hazardous area
Factory Mutual - Explosionproof to NEC Article 500.
ATEX (94/9/EC) II 2 GD c Temperature -30C to +60C (-22F to +140F).
Ex d IIB T4 Gb, Ex tb IIIC T120C Db IP68 *Option -40C to +60C (-40F to +40F).
Temperature -20 to +70C (-4 to +158F)
*Alternative for Group B hazardous area. Temperatures as for Groups C and D.
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F),
*Option -50 to +40C (-58 to +104F) Canada hazardous Area
CSA EP. Class 1, Division 1, Groups C and D hazardous areas.
Ex d IIC T4 Gb, Ex tb IIIC T120C Db IP68
Canadian Standard Association - Explosionproof
Temperature -20 to +70C (-4 to +158F)
Temperature -30C to +70C -22F to +158F).
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F),
*Option -50C to +40C (-58F to +104F).
*Option -50 to +40C (-58 to +104F)
*Alternative for Group B hazardous area. Temperatures as for Groups C and D.
Ex de IIB T4 Gb, Ex tb IIIC T120C Db IP68
Temperature -20 to +70C (-4 to +158F) International Non hazardous
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), WT: Standard watertight, BS EN 60529 :1992, IP68, 7 metres/72 hours.
Temperature -30C to +70C (-22F to +158F).
*Option -50 to +40C (-58 to +104F)
*Option -40C to +70C (-40F to +158F).
Ex de IIC T4 Gb, Ex tb IIIC T120C Db IP68 *Option -50C to +40C (-58F to +104F).
Temperature -20 to +70C (-4 to +158F)
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), US Non hazardous
*Option -50 to +40C (-58 to +104F) NEMA 4, 4X and 6.
Temperature -30C to +70C (-22F to +158F).
International Hazardous area *Option -40C to +70C (-40F to +158F).
IEC. Exd IIB T4 *Option -50C to +40C (-58F to +104F).
IEC60079-0 and IEC60079-1 for Exd IIB T4
Temperature -20 to +70C (-4 to +158F) Canada Non hazardous
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), CSA WT: Canadian Standard Association Watertight.
*Option -50 to +40C (-58 to +104F) Wiring and components complying with CSA Enclosure 4 and 4X.
Temperature -30C to +70C (-22F to +158F).
IEC. Exd IIC T4 *Option -40C to +70C (-40F to +158F).
IEC60079-0 and IEC60079-1 for Exd IIC T4
*Option -50C to +40C (-58F to +104F).
Temperature -20 to +70C (-4 to +158F)
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), Rotork can supply actuators to national standards not listed above.
*Option -50 to +40C (-58 to +104F) For details please contact Rotork.
83
13 IQT Approvals cont.
Refer to actuator nameplate for supply voltage and wiring diagram for
applicable transformer type.
In order to maintain hazardous area certification only the fuses listed
below may be used:
The end of travel limit from which the A position can be set between 1% The timeout function allows a
partial stroke test will start and end and 97% to give a set point within the reasonable amount of time to be set
must be set. travel to which the partial stroke runs. for the partial stroke to complete one
cycle. An alarm can be set to activate if
The default limit for partial stroke is To set the partial stroke position, Press
the stroke hasnt been completed in the
Open limit, under test the actuator will the + or - key to scroll between 1%
set time. Refer to Section 9.2 (indication
automatically move closed from the and 97%. A minimum 3% Stroke is
contacts). The Partial Stroke timeout
open limit to the set position and then required from open limit to allow the
must be set to a value greater than that
return to the open limit position. actuator to perform the partial stroke
required to complete the Partial Stroke
adequately.
To set the closed limit for partial stroke under normal operating conditions.
[EL], Press the + or - key to change PRESS THE KEY. To set the partial stroke timeout, press
from Open [EL OP] to Closed [EL CL].
the + or - key to scroll up or down in
PRESS THE KEY. 10 second intervals.
Set the required time and PRESS THE
KEY.
Partial Stroke
Pos: 75%
POWTG0813