Sei sulla pagina 1di 92

IQT Range

Installation and
Maintenance Instructions

This manual contains important safety


information. Please ensure it is thoroughly
read and understood before installing,
operating or maintaining the equipment.

PUB002-004-00
Date of issue 08/13
I

The Rotork Setting Tool allows actuator control, indication and


protection functions to be configured to suit site requirements.
In addition, the new Setting Tool Pro also allows downloading
of datalogger and uploading/downloading of configuration
files. Files are transferred to and from the Setting Tool Pro via
Rotork Insight.

It is essential that all the actuator settings are checked for


compatibility with the valve, process and control system
requirements before the actuator is put into service. Please read
this publication.
Rotork Setting Tool Pro
When Rotork personnel or nominated agents are contracted to
carry out site commissioning and/or acceptance, documentation
of commissioned actuator configuration can be made available
for customer records.

Rotork Setting Tool


II

This manual covers IQT range actuators: THE ROTORK IQT RANGE THE FIRST 1/4 TURN VALVE ACTUATOR
THAT YOU CAN COMMISSION AND INTERROGATE WITHOUT
* IQT - Operation of isolating/regulating 1/4 turn valves.
REMOVING ELECTRICAL COVERS.
* IQTM - Operation of modulating 1/4 turn valves.
* IQTF - Operation of part-turn and slow speed multi-turn valves. Using the supplied infra-red Setting Tool to access the actuator set up
* IQTFS - Battery failsafe. procedures, point and shoot setting of torque levels, position limits and
all other control and indication functions can be made safely, quickly and
It provides instruction on: conveniently, even in hazardous locations. The IQT allows commissioning
and adjustment to be carried out with the main power supply to the
* Manual and electrical (local and remote) operation. actuator switched on or off.

* Preparation and installation of the actuator onto the Standard diagnostics access information about the control system, valve
valve. and actuator status in the form of display icons and help screens.

* Commissioning and adjustment of the Instantaneous valve torque and position can be monitored on the actuator
Primary Settings for correct valve operation. with a single key press of the Setting Tool.

* Commissioning and adjustment of the Secondary The on board Datalogger captures operational and valve torque data
enabling informed maintenance choices to be made. IQ Insight software
Settings to suit site-specific control and indication
for PC allows the Datalogger to be interrogated, as well as the complete
requirements. actuator set up to be configured and recorded.
* Maintenance Troubleshooting. The actuator containing the Setting Tool will be identified with a yellow
* Sales and Service. label on the terminal cover.

Visit our web site at www.rotork.com for more information on the IQT and
other Rotork actuator ranges.
Refer to Publication E185E for repair, overhaul and
spare part instructions.
III

Identifying Actuator Parts

Display window
Conduit entries
Battery sealing plug
Metal (8mm Allen key required)
Plastic (10mm Allen key required)
as appropriate.
Control Cover

Hand / Auto
lever
IQelecCvr IQelecCvr

Name plate Hand wheel


Terminal Cover
Local / Remote / Stop
selector
Base Motor cover
Open / Close selector

Stop Bolts
1
CONTENTS
Page Page Page
1 Health and Safety 2 6 Cable Connections 10 10 IQT Battery Failsafe Instructions 62
6.1 Earth/Ground Connections 10 10.1 Introduction 62
2 Storage 3
6.2 Removing Terminal Cover 10 10.2 Specification 63
3 Operating your IQT Actuator 3 6.3 Cable Entry 10 10.1 Commissioning instructions 64
3.1 Operating by Hand 3 6.4 Connecting to Terminals 10 11 Maintenance, Monitoring
3.2 Operating Electrically 3 6.5 Replacing Terminal Cover 10 and Troubleshooting 67
3.3 Display Local Indication 4
7 Commissioning 11 11 Torque-reference profile 69
3.4 Display Status Indication Travel 5
7.1 The Setting Procedure 11 11.1 Setting Tool Pro Download & Upload 70
3.5 Display Status Indication Control 5
7.2 The Rotork Setting Tools 12 11.2 Help Screens 73
3.6 Display Alarm Indication 5
7.3 Entering the Actuator 15 11.3 IQT Infrared Diagnostic & Configuration 78
4 Preparing Drive Bush 7 Setting Procedure 11.4 Environmental 79
4.1 Bases F05 to F07 7 7.4 Setting Mode Password 15 12 Weights and Measures 80
and FA05 to FA07 7.5 New Password 15 Binary, Hexadecimal and Decimal
4.2 Bases F10 to F14 7 7.6 Checking Mode 15 Conversion Table 81
and FA10 to FA14
7.7 Crossroad 16
4.3 Machining the Drive Bush 7
7.8 The Actuator Display 16 13 IQT Approvals 82
4.4 Fitting the Drive Bush 7 Setting/Checking Mode Approved Fuses 83
Maximum Flamepath Gaps 83
5 Mounting the Actuator 8 7.9 Returning to Valve Position Display 16
5.1 IQT Actuators 8 8 Commissioning Appendix A 84
5.2 IQTM Actuators 8 Basic Settings 17
5.3 IQTF Actuators 8 Basic Settings Contents 18
5.4 Lifting the Actuator 8 9 Commissioning
5.5 Securing Actuator to Valve 8 Configuration Settings 27
5.6 Stop Bolts 9 Configuration Settings Contents 29
Default Options 60
2
1 Health and Safety

This manual is produced to enable a given in the applicable edition of the No inspection or repair should be
competent user to install, operate, IEE Wiring Regulations should be undertaken unless it conforms to the WARNING: Enclosure Materials
adjust and inspect Rotork IQT applied. Also the user should be fully specific hazardous area certification IQT actuators are manufactured from
range valve actuators. Only persons aware of his duties under the Health requirements. Under no circumstances aluminium alloy with stainless steel.
competent by virtue of their training and Safety Act 1974. should any modification or alteration be The user must ensure that the operating
or experience should install, maintain carried out on the actuator as this could environment and any materials
For the USA: NFPA70, National Electrical
and repair Rotork actuators. Work invalidate the actuators hazardous surrounding the actuator cannot lead
Code is applicable.
undertaken must be carried out in area approval certification. Access to to a reduction in the safe use of, or the
accordance with the instructions in The mechanical installation should be live electrical conductors is forbidden protection afforded by, the actuator.
this and any other relevant manuals. carried out as outlined in this manual in the hazardous area unless this is Where appropriate the user must
The user and those persons working and also in accordance with relevant done under a special permit to work, ensure the actuator is suitably protected
on this equipment should be familiar standards such as British Standard otherwise all power should be isolated against its operating environment.
with their responsibilities under any Codes of Practice. If the actuator has and the actuator moved to a non-
statutory provisions relating to the nameplates indicating that it is suitable hazardous area for repair or attention. WARNING: Operating by Hand
Health and Safety of their workplace. for installation in hazardous areas then
Due consideration of additional the actuator may be installed in Zone With respect to handwheel operation of
hazards should be taken when using 1, Zone 21, Zone 2 and Zone 22 (or Div Rotork electric actuators, see warning
the IQT range of actuators with other 1 or Div 2, class I or Class II) classified on p3.
equipment. Should further information hazardous area locations only. It should
and guidance relating to the safe use not be installed in hazardous area This actuator must only be
of the Rotork IQT range of actuators be locations with an ignition temperature located in areas where the risk of
required, it will be provided on request. less than 135C, unless suitability for impact to the viewing window
lower ignition temperatures has been is low.
The electrical installation, maintenance
indicated on the actuator nameplate.
and use of these actuators should be Actuator may start and
It should only be installed in hazardous WARNING: Thermostat Bypass
carried out in accordance with the operate when remote control is
area locations compatible with the gas
National Legislation and Statutory If the actuator is configured to bypass selected, depending on remote
groups stated on the nameplate.
Provisions relating to the safe use of the motor thermostat then the hazardous control signal status and actuator
this equipment, applicable to the site of The electrical installation, maintenance area certification will be invalidated. configuration.
installation. and the use of the actuator should be Additional electrical hazards may occur
carried out in accordance with the code when using this configuration. The
For the UK: Electricity at Work
of practice relevant for that particular user should ensure that any necessary
`Regulations 1989 and the guidance
Hazardous Area certification. additional safety measures are considered.
3
2 Storage 3 Operating your
IQT Actuator
If your actuator cannot be installed 3.1 Operating by Hand To engage handwheel drive, turn When the selector is locked in the Local
immediately store it in a dry place until the Hand/Auto lever clockwise whilst or Remote positions the Stop facility is still
you are ready to connect incoming turning the handwheel, see Fig 3. The available. The selector can also be locked
cables. WARNING lever can now be released upon which in the Stop position to prevent electrical
With respect to handwheel it will return to its original position. The operation by Local or Remote control.
If the actuator has to be installed but
handwheel will remain engaged until
cannot be cabled it is recommended operation of Rotork electric
the actuator is operated electrically
that the plastic transit cable entry plugs actuators, under no circumstances when it will automatically disengage
are replaced with metal plugs which are should any additional lever and return to motor drive. If required
sealed with PTFE tape. device such as a wheel-key the Hand/Auto lever can be locked in
The Rotork double-sealed construction or wrench be applied to the either position using a padlock with a
will preserve internal electrical handwheel in order to develop 6.5mm hasp.
components perfectly if left more force when closing or
undisturbed. opening the valve as this may 3.2 Operating Electrically
cause damage to the valve and/or Check that power supply voltage agrees
It is not necessary to remove any with that stamped on the actuator
electrical compartment covers in order actuator or may cause the valve
to become stuck in the seated/ nameplate. Switch on power supply. It
to commission the IQT actuator. is not necessary to check phase rotation.
backseated position.
Rotork cannot accept responsibility for Fig. 3.1
deterioration caused on-site once the Do not operate the actuator
covers are removed. Local Control
electrically without first checking, With the red selector positioned at
Every Rotork actuator has been fully using the infra-red Setting Tool, Local (anti-clockwise) the adjacent black
tested before leaving the factory to that at least the Primary Settings knob can be turned to select Open or
give years of trouble free operation, have been made (refer to Section Close. To Stop, turn red knob clockwise.
providing it is correctly commissioned, 8 page 17).
installed and sealed.
Selecting Local/Stop/Remote Remote Control
Operation Rotate the red selector to the Remote
The red selector enables either Local or position (clockwise), this gives remote
Remote control, lockable in each position control only for Open and Close but
using a padlock with a 6.5mm hasp. local Stop can still be used by turning
Fig. 3 the red knob anti-clockwise.
4

3.3 DisplayLocal Indication description text in the lower display. Open Closed
The two tri-colour LED's will be Red, The two tri-colour LED's will be Green,
6. Battery Alarm Icon - This icon will be
the open symbol and "Open Limit" will closed symbol and "Closed Limit" will
displayed when a battery is detected as
be displayed be displayed.
low or flat. "Battery low" or "flat" will
also be displayed in the lower display.
7. IR Icon - This icon flashes during infra
red communication activity.
8. Percentage Open Icon - This icon will
be displayed when a percentage Open Open Limit Closed Limit
value is in the upper display.

The liquid crystal display screen has 2 Fig. 3.3 Fig. 3.5
modes of position indication:
Fig. 3.2 The Actuator Display With the main power supply switched
1. Valve position power on Mid Travel off, the display screen is powered by
The display consists of: 2. Valve position power off The two tri-colour LED's will be Amber, a battery and continues to display
percentage open value will be shown actuator position. However, the battery
1. Position Display - This is the main On power up the actuators liquid and "Stopped" will be displayed when
7-segment position display with icons. does not support screen back-lighting,
crystal display screen is back-lit with an there is no actuator movement. position indicator lamps or dot matrix
2. Text Display - This is a 2 line, 16 amber light and one of the indicator display.
characters dot matrix display which lamps will be on, dependent on
allows text to be used to compliment position. The display screen will show LED Indicators
the position display and icons. percentage open or an end of travel
symbol. (See Figs 3.3, 3.4 and 3.5)
3. Infra Red LED's. WARNING: Mid Travel LED
As standard, red lamp signifies valve colour may be affected by viewing
4. 1 x Bi colour LED, 1 x Amber colour open, amber intermediate, and green Stopped angle and lighting level.
LED for position indication. lamp signifies valve closed. Open and
The Close LED colour can be changed
5. Alarm Icon - This will be displayed closed colour functions can be reversed
to red if required. The Mid Travel amber
for Valve, Control, and Actuator alarms. on request.
LED can be switched off if required.
Alarm indication is supported by fault Fig. 3.4
Refer to Section 9.16, page 58.
5

3.4 Display Status Indication Timer Active Interrupter Timer option Remote Control Remote control 3.6 Display Alarm Indication
Travel enabled only. Interrupter Timer has selected red selector. The IQT display provides alarm indication
The IQT display provides real time stopped the actuator mid travel for a in the form of text and alarm icons.
Local Close Local close signal applied
status indication. The top line of the period equal to the set Timer Off
black selector.
text display is reserved for travel status time. Refer to 9.13 page 55. There are 2 alarm icons:
indication. Fig 3.6 shows the travel Local Open Local open signal applied
status example Closed Limit . black selector.
3.5 Display Status Indication Remote Close Remote close (hardwired General Alarm:
Control or analogue) signal applied.
The bottom line of the text display is
Remote Open Remote open (hardwired Battery Alarm:
reserved for control status indication
or analogue) signal applied.
and is displayed for approximately 2
Closed Limit seconds after the control mode or Remote ESD Remote hardwired
signal is applied. Fig 3.7 shows the emergency shut down signal applied.
control status example Remote Control . General Alarm
Remote Bus Open Remote Bus * open
signal applied. The general alarm icon will be
Fig. 3.6 supported with text in the bottom line
Available travel status conditions displayed: Remote Bus Close Remote Bus* signal indicating the particular alarm, or if
applied. more than one is present, each alarm
Closed Limit Actuator has reached the will be displayed in sequence.
Remote Bus ESD Remote Bus*
set closed limit position. Closed Limit emergency shut down signal applied. Fig 3.8 shows the status example
Open Limit Actuator has reached the Remote Control * Bus Control option fitted may be TORQUE TRIP CL .
set open limit position.
Pakscan, Profibus, Modbus,
Moving Open Actuator is traveling in Fig. 3.7 DeviceNet or Foundation Fieldbus.
the open direction. Refer to actuator wiring diagram.
Available control status conditions displayed:
Moving Closed Actuator is traveling in
the closed direction. Local Control Local control selected -
red selector. Stopped
Stopped Actuator has stopped in a
Local Stop Local stop selected red
TORQUE TRIP CL
mid travel position, indicated in the
top display (%open). selector.
Fig. 3.8
6

Available alarm conditions displayed: Actuator Alarms TORQ SENSOR FAIL Detected failure When a low or flat battery
in the torque sensing system alarm is displayed the battery
Valve Alarms THERMOSTAT TRIP Motor control contact Rotork.
thermostat has tripped due to should be replaced immediately. It
TORQUE TRIP CL tripped off on torque is essential that the correct battery
extended motor operation. EEPROM MISSING Contact Rotork
while moving in the close direction. type is fitted to maintain actuator
Operation is inhibited until the
TORQUE TRIP OP tripped off on torque thermostat resets automatically certification. Refer to page 67.
while moving in the open direction. when the motor control cools. Battery Alarm After replacing a battery the
Check actuator duty cycle against alarm icon will continue to be
MOTOR STALLED no movement process requirements (running time,
detected after a signal to move. displayed until the next check and
torque, ambient temperature). may take up to 1 hour. Cycling the
Control Alarms PHASE LOST (3-phase models only). power will force a battery check
The phase supply the actuator and clear the alarm.
ESD ACTIVE ESD signal applied. When connected to terminal 3 is lost.
present the ESD signal overrides all Operation is inhibited. Open Limit
local and remote control signals.
Once the ESD action is carried out 24V LOST The 24 volt customer BATTERY LOW PWR LOSS INHIBIT
operation is inhibited while the ESD supply (terminals 4 & 5) has tripped. If, on power up, the actuator detects
signal is maintained. Refer to 9.3 Check remote control wiring. Supply Fig. 3.7 a discharged battery and actuator
ESD Action page 32. is protected with a resettable fuse. power loss inhibit feature [OS] is
The actuator checks the battery level enabled (refer to page 57), both
INTERLOCK ACTIVE Open and/or close LOCAL CONTROL FAIL Check operation
at approximately 1 hour intervals. The battery and general alarm icons will
interlocks are configured on and are of control selectors (black and red).
battery alarm icon is displayed when be displayed and the bottom line will
active. Refer to 9.3 Interlock page 34. CONFIG ERROR There may be an error the actuator detects its battery as being indicate alternately PWR LOSS INHIBIT and
Operation in the direction of an in the configuration (set up) of the low and the display will indicate BATTERY BATTERY FLAT . Electrical operation will be
active interlock(s) is inhibited. actuator. Check and reset basic LOW . inhibited. The battery must be replaced
Note that when conditional control is setting and check configuration and the limits must be reset. Refer to
configured, an active interlock will settings. If the battery is flat or missing the
display will indicate BATTERY FLAT . Section 11, page 67 and Section 8,
not inhibit local control operation. page 17.
POS SENSOR FAIL Detected failure in
the position sensing system contact
Rotork.
7
4 Preparing Drive Bush

4.1 Bases F05 to F07 4.3 Machining the Drive Bush


and FA05 to FA07 Once removed, the drive bush can
The base adaptor must be removed to be machined to suit the valve stem.
give access to the drive bush. Remove Ensure machined position allows correct
the four capscrews and base adaptor as orientation of actuator-to valve flange
shown in figure 4. and correct direction to close the valve.

4.4 Fitting the Drive Bush


Note: The drive bush can be fitted in
four possible positions, 90 apart. Fit
the drive bush into the centre column
ensuring that the stem orientation,
Fig. 4.1 Fig. 4.2 actuator position and direction
of operation are correct for valve
4.2 Bases F10 to F14 The range of IQT drive bushes is shown operation. Secure the drive bush with
in figure 4.3. Please refer to PUB002- the capscrews. For F05, FA05, F07 and
and FA10 to FA14 001 for maximum stem acceptance
Removal of the drive bush does not FA07 bases, refit the base adaptor and
details. secure with the four capscrews.
require the removal of the actuator
Fig. 4 base. Using a 3mm allen key, unscrew
the two capscrews retaining the drive
Clear access to the drive bush is now bush.
available as shown in figure 4. Using
the a 3mm allen key, unscrew the two Capscrews can be used to remove the
capscrews retaining the drive bush drive bush by screwing into the drive
and remove the drive bush from the bush as shown in figure 4.2.
actuator.

Fig. 4.3
8
5 Mounting the Actuator

5.1 IQT Actuators 5.4 Lifting the Actuator WARNING:


The IQT range of actuators are suitable (Refer to Weights and Measures page Do not lift the actuator and valve
for part turn applications requiring up 80 for actuator weight.) combination via the actuator.
to 60 starts per hour. Always lift the valve/actuator
Ensure the valve is secure before fitting
the actuator, as the combination may assembly via the valve.
5.2 IQTM Actuators
The IQTM range of actuators are be top heavy and therefore unstable.
suitable for modulating control If it is necessary to lift the actuator
duty of up to 1200 starts per hour using mechanical lifting equipment
in accordance with IEC 34-1 to S4 certified slings should be attached
50%. Commissioning of IQTM range as indicated in Figure 5. At all times
actuators is identical to the standard trained and experienced personnel
IQT (refer to Sections 7, 8 and 9). should ensure safe lifting, particularly
when mounting actuators. Fig. 5.1
5.3 IQTF Actuators
The IQTF range of actuators are suitable WARNING: 5.5 Securing Actuator to Valve
for part-turn and multi-turn, non-thrust Do not lift the actuator by the Before engagement ensure that the
applications requiring low speed and handwheel. actuator and valve are in the same
low operating turns. Commissioning position (i.e. closed) and the drive bush-
of IQTF range actuators is similar to A suitable mounting flange conforming Fig. 5 machining matches the stem position.
the standard IQT (refer to Sections 7, to ISO 5210 or USA Standard MSS Actuator position can be determined
8 and 9). SP101 must be fitted to the valve. WARNING: using the display (refer to section 3.3
Actuator to valve fixing must conform The actuator should be fully page 4) and if necessary can be moved
to; Material Specification ISO Class 8.8, supported until full valve stem using the handwheel (refer to section
yield strength 628 N/sq mm. engagement is achieved and the 3.1 page 3). It may be necessary to
actuator is secured to the valve adjust the stop bolts to enable sufficient
flange. travel. Refer to section 5.6 page 9.
9

Secure actuator to valve with four The IQT stop bolts are located below Stop Bolt sizes.
fixing bolts. Check that the cast groove the terminal compartment. Stop bolt IQT 125 to 500: M12 bolt requiring
in actuator base is not obstructed see adjustment allows +/ 5 variation of 19mm AF spanner.
Fig 5.1. Its purpose is to protect the travel at each end position. Screwing
actuator in the event of a product leak bolts in reduces movement, out IQT1000 & 2000: M20 bolt requiring
from the valve stem/gland packing. increases movement. For clockwise 30mm AF spanner.
Check base fixing bolts are tight. closing valves the right hand bolt is the
closed stop as shown with spanner in Adjustment for non seating
valves types
5.6 Stop Bolts fig 5.2. The left is the open stop. Stop
For closed and open stop position
It is recommended that stop bolt bolts are factory set to give a nominal
adjustment:
adjustment be carried out by the 90 travel.
valvemaker/supplier before the valve Undo stop bolt lock-nut. Move actuator
is fitted into pipework. Once installed, and valve to the required stopping
the valve maker/supplier should position (it may be necessary to
be consulted before stop bolt re- unscrew stop bolt to allow more travel).
adjustment is carried out. Stop bolts Screw stop bolt in until a stop is felt.
can be wired to prevent tampering. Tighten stop bolt lock nut.
After setting or adjustment of stop
bolts the actuator limits must be reset, Adjustment for seating valves
refer to Limits LC, LO page 24. types
For closed and open stop position
adjustment:
Undo stop bolt lock-nut. Move
actuator and valve to the required
seating position of the valve (it may be
Fig. 5.2 necessary to unscrew stop bolt to allow
more travel). Screw stop bolt in until
a stop is felt and then back off by 3
turns. Tighten stop bolt lock-nut.

Reset actuator limits


Refer to Limits LC, LO page 24.
10
6 Cable Connections

6.1 Earth/Ground Connections The cable entries on the actuator


WARNING: A lug with a 6mm diameter hole is terminal housing are tapped M25
Ensure all power supplies cast adjacent to the conduit entries for x 1.5p.
are isolated before removing attachment of an external protective
actuator covers. earthing strap by a nut and bolt. An 6.4 Connecting to Terminals
internal earth terminal is also provided, On EExde enclosure units connections
Check that the supply voltage agrees however it must not be used alone as to the power and control terminals
with that stamped on actuator the protective Earth Connection. must be made using AMP type 160292
nameplate. ring tabs for power and earth terminals
A switch or circuit breaker must be 6.2 Removing Terminal Cover and AMP type 34148 ring tabs for the
included in the wiring installation of Using a 6mm Allen key loosen the four control terminals.
the actuator. The switch or circuit captive screws evenly. Do not attempt Refer to the wiring diagram inside the
to lever off the cover with a screwdriver Fig. 6
breaker shall be mounted as close terminal cover to identify functions of
to the actuator as possible and shall as this will damage the O ring seal A plastic bag in the terminal terminals. Check that supply voltage
be marked to indicate that it is the and may damage the flamepath on a compartment contains: Terminal screws is the same as that marked on the
disconnecting device for that particular certified unit. and washers, spare cover O ring actuator nameplate.
actuator. The actuator must be Actuators containing a Setting Tool seal,wiring diagram and instruction
protected with overcurrent protection book. Remove power terminal screen.
fitted to the inside of the terminal
devices rated in accordance with compartment cover are identified with Begin by connecting these cables and
Rotork publication No. E135E Electric a self-adhesive yellow label on the 6.3 Cable Entry replace screen.
motor performance data for IQT range outside of the terminal compartment Only appropriate certified Explosion-
actuators. Proof entry reducers, glands or conduit When all connections are made ensure
cover. wiring diagram is replaced in the
may be used in hazardous locations.
WARNING: The wiring code card fixed in the cover terminal compartment.
is particular to each actuator and must Remove red plastic transit plugs. Make
Actuators for use on phase to cable entries appropriate to the cable
not be interchanged with any other 6.5 Replacing Terminal Cover
phase voltages greater than 600V actuator. If in doubt check the serial type and size. Ensure that threaded Ensure cover O ring seal and spigot
A.C.must not be used on supply number on the code card with that of adaptors, cable glands or conduit joint are in good condition and lightly
systems such as floating, or earth- the actuator. are tight and fully waterproof. Seal greased before re-fitting cover.
unused cable entries with a steel or
phase systems, where phase to
brass threaded plug. In hazardous areas
earth voltages in excess of 600V an appropriately certified threaded
A.C. could exist. blanking plug must be used.
11
7 Commissioning

7.1 The Setting Procedure 2. Configuration Settings Actuator Display


The Rotork IQT range of actuators is the Settings covering the control,
first that enables commissioning to be indication and optional 50
Position Display This may be an open or closed symbol
carried out without removing covers. equipment functions.
or a percentage open value.
Setting torque, limit and other functions m
is achieved by using the Infra-Red NOTE: For IQT Battery Failsafe Torque and Position 50 Refer to Section 11.
Setting Tool. The Setting Tool is certified instructions, see Section 10 page 62. Torque

Intrinsically Safe to allow commissioning


in hazardous areas. m
All the commissioning functions are WARNING: Password P? k PC k Ir k tP
stored in non-volatile memory in the All IQT actuator functions are m
configured before dispatch to
actuator. The Setting Tool enables the
user to view all the functions in turn Rotork standard default settings
Crossroad cr k

via the actuator display window. As unless alternatives have been
m
each function is viewed its setting can specified with the order. Should
be checked and, if required, changed
within the bounds of that function. difficulty be encountered during
commissioning the default
Commissioning may be carried out with Basic Settings Configuration Settings
settings can be reinstated,
main power switched on or off. Refer Direction Indication Contacts
to page 17 for Power Off Setting. returning the actuator
configuration to its original Limit Actions Control Mode
The setting procedure is divided into Torque Values Options
two stages:
manufactured state. Site
commissioning can then begin Limit Positions HelpScreens
1. Basic Settings again (refer to Section 9.18 page 59). Defaults
Settings for end of travel limit
actions, torque values, limit The default function should be used
positions etc. with caution as settings selected after
manufacture may be essential for the Note: The Basic Settings must be commissioned first.
safe operation of the valve and/or plant.
12
7 Commissioning continued

7.2 The Setting Tool (old version) 8 2


Specification 4
Enclosure IP67
6
Certification EEx ia IIC T4 (intrinsically safe)
FM, INT SAFE, Class I & II Div 1 Groups A B C D E F G, T4A
CSA, Exia, Class I, II Div 1 Groups A B C D
Power supply 9V Battery (supplied and fitted)
Operating range 0.75m (from actuator display window)
1
3
Name Instruction 5
7
1. m Key* Display next function down
2. k Key* Display next function across
3. - Key Decrease/change displayed functions value or option setting Fig. 7.1 The Setting Tool
4. + Key Increase/change displayed functions value or option setting Setting Tool Battery Replacement
5. Key Enter displayed value or option setting Battery status can be checked by looking at the Infra-red transmitter window while
depressing any Setting Tool button. A flashing red indicator should be seen.
* Pressing the two arrow keys together returns the actuator display to the position Battery replacement must be carried out in a safe area. To replace
indication mode the battery remove the six caphead screws in the back of the Setting Tool.
Remove the back cover to expose the battery.
Infra-red local operation (when enabled)
In order to maintain hazardous area certification fit only Duracell
5. Key Stop actuator
MN1604 or Rayovac Alkaline Maximum NoAL-9V battery types. Refit cover
6. Key Open actuator ensuring red indicator LED faces the transmitter window in the back cover.

7. Key Close actuator When a button is depressed the Setting Tool transmits the relevant instruction
to the actuator by infra-red pulses and must therefore be directly in front of the
8. Infra-red Transmitter Window actuator indicator window and at a distance no greater than 0.75m.
13

7.2 The Setting Tool Pro (new version) 2


3
Specification 12
Enclosure IP54 6
This Setting Tool Pro has been built in accordance with the following standards:
7
USA - Hazardous Area. 10
Factory Mutual - Explosion Proof to NEC Article 500. 8
Intrinsically Safe, Class 1, Div 1, Groups A, B, C & D, T4.
Canada - Hazardous Area.
CSA - Exia Intrinsically Safe, Class 1, Div 1, Groups A, B, C & D, T4.
Temperature Tamb = -30C to 50C
Power supply 2x 1.5V Batteries (supplied and fitted)
4
5
Operating range 0.75m (from actuator display window) 1
11
Name Instruction
1. m Key* Display next function down
2. i Key Display previous function up Fig. 7.2 The Setting Tool Pro
3. k Key* Display next function across
4. o Key Display previous function across Infra-red local operation (when enabled)
5. - Key Decrease/change displayed functions value or option setting 9. Key Stop actuator
6. + Key Increase/change displayed functions value or option setting 10. Key Open actuator
7. m Key Initiate download/upload mode 11. Key Close actuator
8. Key Enter displayed value or option setting 12. Infra-red Transmitter Window

* Pressing these two arrow keys together returns the actuator display to the
position indication mode
14
7 Commissioning continued

Download / Upload Function Duracell, Coppertop, type MN1500 When a button is depressed the Function Setting
Duracell, Procell, type MN1500 Setting Tool Pro transmits the relevant Code Code
This new feature has been introduced
with the new Rotork Setting Tool GP, Super Alkaline, type GP15A instruction to the actuator by infra-red
Pro. It allows the user to download pulses and must therefore be directly in
Other types of AA size batteries,
datalogger files and download/upload front of the actuator indicator window
including Duracell, Ultra, type
configuration files. The new tool is MN1500, must not be fitted. For
and at a distance no greater than Close Action
weatherproof and intrinsically safe battery replacement see Section 7.
0.75m.
Function Close on Torque Setting
and so it can be used safely in all Option
environments. For more information Refit cover ensuring red indicator LED
refer to Section 11.1, page 70. faces the transmitter window in the Display Set-Up Mode
back cover. The Setting Tool and Setting Tool Pro Function Setting
The enclosure of the actuator Setting arrow keys are used to access and Code Value
Setting Tool Pro Battery Tool Pro is manufactured from the navigate through the actuator set-up
Replacement materials: procedure using the actuator display.
Battery status can be checked by looking Each actuator function with it's current
Polycarbonate, ABS blend setting is represented on screen by
at the Infra-red transmitter window
while depressing any Setting Tool Pro
Polycarbonate a combination of code and text. The Open Torque
button except the download button. A
Silicon Rubber Setting Tool change keys (+ and ) Function 40% Setting
flashing red indicator should be seen. If the actuator Setting Tool Pro is likely allow the user to view the available Value
to come into contact with aggressive setting options.
Battery replacement must be substances (e.g. solvents that may
carried out in a safe area. To replace The examples of displayed functions
affect polymetric materials), then it is Close Action , [C2] and Open Torque , [tO]
the battery remove the six cap head the responsibility of the user to take
screws in the back of the Setting are shown to the right. Note that a
suitable precautions (e.g. regular checks setting option or value is highlighted.
Tool Pro. Remove the back cover to as part of the routine inspections or
expose the battery. establishing that the materials are This instruction manual uses both code
In order to maintain hazardous resistant to the specific chemical) and text for description.
area certification the actuator that prevent it from being adversely
Setting Tool Pro shall only be affected, thus ensuring that the type of
fitted with the following AA size, protection is not too compromised.
alkaline-manganese, approved No form of repair must be attempted
battery types: on the actuator Setting Tool Pro.
15

7.3 Entering the Actuator 7.4 Setting Mode Password 7.5 New Password [PC] 7.6 Checking Mode
Setting Procedure To enable setting and adjustment of the To configure a new password, the The actuator function settings can be
With the actuator securely mounted actuator functions the correct password actuator must be in setting mode with checked without entering the correct
on the valve, the mains supply on and must be entered. The factory set (default) the password display setting mode password. The settings can only be
Local control or Stop selected. password is [ld]. If the actuator has enabled showing, viewed and not altered. The setting bars
previously been set with a site password will not be seen.
PRESS THE m KEY. this must be entered.
PRESS THE k KEY.
The actuator upper display will remain The display will change to [PC]. Using the
Use the + or - keys to scroll through the + or - key scroll through the available
the same and the lower display will available passwords 00FF (hexadecimal).
change to Torque value. This will be passwords until the desired password is
With the correct password displayed press
represented by Torque = XX% and a displayed. Enter Password
the enter key.
bar graph. (For instantaneous torque PRESS THE KEY. ID Hex
& position monitoring, refer to Section PRESS THE KEY.
11, page 68.) Two setting bars will appear and will Password Display, Checking Mode
remain visible on every function display
Once the procedure has been completed
screen. In addition, "Password Correct"
PRESS THE m KEY. in the required mode
will be displayed for 3 seconds.
Change Password
The actuator display will change and IE Hex
PRESS THE m KEY.
the password protection display will be The procedure branch [Cr] (crossroad)
seen. Password Changed to [IE] display can now be seen (refer to Section
7.7 page 16).
NOTE: The new password becomes
Enter Password
effective the next time setting mode is
Password Correct
entered.
Enter Password Default Password,
ID Hex Setting Mode Enabled

The Actuator Function Settings


can be protected by the Use
of a Password
16
7 Commissioning continued

7.7 Crossroad [Cr] 7.8 The Actuator Display In setting mode the Setting Tool + 7.9 Returning to
Setting/Checking Mode or - keys will cause the setting to be Valve Position Display
Actuator functions as laid out in the changed. In checking mode the settings There are five ways of returning to valve
Basic and Configuration commissioning cannot be altered. position display:
stages, can be individually displayed by
In setting mode, once displayed, a new 1. Approximately 5 minutes after the
Basic Setup using the Setting Tool arrow keys.
Config Setup
setting can be entered into the actuator last Setting Tool operation the
The m arrow key will always display memory by pressing the key. display will automatically return to
the FIRST function on the next level The setting will flash off and back on, position display.
To access the Basic Settings press DOWN within the procedure. confirming its selection, and "Stored "
the arrow m key (refer to Section 8 will be displayed for 2 seconds in the 2. Press the m and k arrow keys
Commissioning Basic Settings page 17). The k arrow key will always display text display. together.
the NEXT function on the SAME level
To access the Configuration Settings and will wrap around the functions on 3. Press the m arrow key until the
TOP LEFT display returns to position.
press the arrow k key (refer to the same level. PORTION
Section 9 Commissioning Configuration Function e.g. 4. Select Remote control using the
Settings page 27). The actuator display indicator lamps will
continue to indicate valve position but tC = Torque Close red Local/Stop/Remote selector.
will also flash during IR communication. 5. If you have the new Setting Tool
TOP RIGHT Pro then you can use the iarrow
Actuator functions are displayed in PORTION
code form in the top left portion of the key to return to position display.
Close Torque Function Setting
liquid crystal display screen. e.g. Value = 40%
40%
The setting for the displayed function is
shown in the top right hand portion of LOWER DISPLAY
the screen. Depending on the actuator Function: Close Torque
function displayed, its setting may be Setting Value: 40%
an option or a value.
Text relating to the function and setting Typical Actuator Function Display
values will be displayed in the lower Setting Mode Enabled
display.
17
8 Commissioning
Basic Settings
ELECTRICAL OPERATION MUST Power Off Setting
NOT TAKE PLACE UNTIL THE BASIC IQT allows settings to be viewed and
SETTINGS HAVE BEEN MADE AND set without main power. To enable this
CHECKED. function, engage handwheel drive and
rotate until the output drive moves
The actuators Basic Settings affect
(refer to page 3). The Setting Tool can
the correct operation of the valve by
now be used. As long as a Setting
the actuator. If the actuator has been
Tool key press takes place within the
supplied with the valve, the valve
30 seconds timeout period, Power
maker or supplier may have already
Off Setting will remain enabled. If no
made these settings.
infra-red Setting Tool communication
This instruction assumes setting mode takes place the display will return to
has been entered (refer to section 7.4 indicating position. The actuator must
page 15). then be operated by handwheel to
re-enable Power Off Setting.
Viewing the Basic Settings
With the actuator mounted on the Settings and operation must
valve, the power supply on and Local be verified by electric operation
or Stop control selected, point the
Setting Tool at the actuator indicator and function test of the actuator
window from a distance of no more to ensure correct operation.
than 0.75m. By pressing the m key
and, when appropriate, the k key,
it is possible to move through the
procedure, displaying the various
functions and their settings as shown
in Fig. 8.1 (refer to page 18).The
right-hand side of Fig.8.1 explains the
function of each LCD display.
18

Viewing the Basic Settings

Function Description

50 Position Display REFER TO SECTION 7, COMMISSIONING
(This may be an open or closed symbol or a % open value.)
m m
50
Torque Torque and Position Display
m m
P? k PC k Ir k tP Password k Password Change k IrDA k Torque Reference Profile
m m
Cr k Configuration Crossroad k Configuration Settings, refer to page 32.

C1 k C2 k C3 Direction to Close k Close Action k Open Action BASIC SETTINGS CONTENTS


m m page
C1 Direction to Close 19
tC k tO Torque Value Closing k Torque Value Opening
C2 Close Action 20
m m C3 Open Action 21
LC k LO Limit Closed k Limit Open tC Torque Value Closing 22
m m tO Torque Value Opening 23
50 LC Set Limit Closed 24
Position Display
LO Set Limit Open 24
AA Speed Setting 25
Fig. 8.1 Basic Setting Displays
19
C1 Direction to Close

The actuator can be configured to be Using the + or - key, display the Having ensured that the display
clockwise or anti-clockwise to close. character conforming to correct closing corresponds to the established
Manually operate actuator and valve direction. closing direction
to establish correct closing direction.
Conversion Handwheel direction labels
PRESS THE KEY.
are available. The displayed option will flash (stored),
indicating that it has been set.
50 PRESS THE k KEY.
Close Direction
m Clockwise
50 [C] in the Setting Field Indicating
Torque

Clockwise to Close
m
P? k PC k Ir k tP
m
cr
m Close Direction
Anticlockwise
c1 k c2 k c3
[A] in the Setting Field Indicating
m Anti-clockwise to Close
tC k tO
m
LC k LO
m
50
20
C2 Close Action

IQT actuators are designed to stop at 50 Using the + or - key, display the NOTE: When set to close on torque,
the end of travel by torque limitation required option. the actuator will apply the level of
against the actuator stop bolts. Stop m torque as set for [tC] in seating the
bolts should therefore be set to the 50 valve (refer to [tC] page 22).
precise stopping position required, refer Torque

to section 5.6. m
IQTF actuators can be configured to P? k PC k Ir k tP Close Action
close on torque or limit. Refer to valve
m Close on Torque
manufacturers instructions.
cr [Ct] in the Setting Field Indicating
Refer to valve manufacturer Close on Torque - default setting.
for recommended setting.
m
c1 k c2 k c3
m
tC k tO
Close Action
m Close on Limit
LC k LO [CL] in the Setting Field Indicating
m Close on Limit.
50

Having selected the required option


PRESS THE KEY.
The displayed option will flash (stored),
indicating that it has been set.
PRESS THE k KEY.
21
C3 Open Action

IQT actuators are designed to stop at 50 Using the + or - key display the NOTE: When set to open on torque,
the end of travel by torque limitation required option. the actuator will apply the level of
against the actuator stop bolts. Stop m torque as set for [tO] in back seating
bolts should therefore be set to the 50 the valve (refer to [tO] page 23).
precise stopping position required, refer Torque

to section 5.6. m
IQTF actuators can be configured to P? k PC k Ir k tP Open Action
close on torque or limit. Refer to valve
m Open on Torque
manufacturers instructions.
cr [Ot] in the Setting Field Indicates
Refer to valve manufacturer Open on Torque - defualt setting.
for recommended setting. In the
m
absence of valvemaker instructions c1 k c2 k c3
set Open Limit.
m
tC k tO
Open Action
m Open on Limit
LC k LO [OL] in the Setting Field Indicates
m Open on Limit.
50

PRESS THE KEY.


The displayed option will flash (stored),
indicating that it has been set.
PRESS THE k KEY.
22
tC Close Torque

The value of torque available in the Using the + and - keys, the display
close direction can be configured. recommended value. In the absence of
a recommended torque value, try a low
Refer to valve manufacturer
setting and increase until satisfactory
for recommended value. Close Torque
valve operation is achieved.
40%
The closing torque value can be varied
between 40% and Rated (100%), in If the actuator fails to 40% of Rated Torque
1% increments. complete a closed valve operation
due to the set torque being
reached (Torque Trip CL Alarm, page 5)
50 this may indicate a valve and/or
m process problem or change. It is the
responsibility of the user to ensure Close Torque
50 the valve and process conditions are 99%
Torque

m within specified operational limits


before increasing the Set Close 99% of Rated Torque
P? k PC k Ir k tP torque value.
m PRESS THE KEY.
cr The displayed value will flash (stored),
Close Torque
m indicating that it has been set.
100%
c1 k c2 k c3 Should the set level of torque be
developed in closing, the actuator will Rated Torque
m torque trip and stop.
tC k tO PRESS THE k KEY.
m NOTE: Rated torque is quoted on the
LC k LO actuator nameplate.
m
50
23
tO Open Torque

The value of torque available in the The opening torque value can be NOTE: Rated torque is quoted on the
open direction can be configured. varied between 40% and Rated, in 1% actuator nameplate. Boost torque is at
increments. In addition Boost can least 140% of Rated torque.
Refer to valve manufacturer
be configured when no open torque
for recommended value.
protection is required. PRESS THE KEY. Open Torque
100%
The displayed value will flash (stored),
BOOST SHOULD NOT BE indicating that it has been set. Rated
50 SELECTED WHEN THE ACTUATOR
HAS BEEN CONFIGURED TO OPEN
m ON TORQUE (refer to [C3] page 21)
50 UNLESS BACK SEATING AT RATED Should the set level of torque be
developed in opening, the actuator will Open Torque
Torque

TORQUE IS ACCEPTABLE.
m torque trip and stop. Boost
Using the + and - keys, display the
P? k PC k Ir k tP
recommended torque value.
PRESS THE m KEY. Boost
m
In the absence of a recommended
cr torque value, try a low setting and In checking mode, on pressing the m
m increase until satisfactory valve key after reviewing open torque setting,
operation is achieved. Open Torque the display will revert to valve position.
c1 k c2 k c3
40%
m If the actuator fails to
complete a open valve operation 40%
tC k tO
due to the set torque being
m reached (Torque Trip OP Alarm, page 5)
this may indicate a valve and/or
LC k LO
process problem or change. It is the
m responsibility of the user to ensure
the valve and process conditions are Open Torque
50
within specified operational limits 99%
before increasing the Set Open 99%
torque value.
24
LC Set Limit Closed LO Set Limit Open

NOTE: It is possible to set the Open With [LC] displayed 50 With [LO] displayed
Limit Position [LO] first.
m
50
50 Torque

m
m Set Close Limit Set Open Limit
Move to Close P? k PC k Ir k tP Move to Open
50
m
Torque

m Limit Closed Limit Open


cr
P? k PC k Ir k tP Move valve manually to the closed Move valve manually to the open
position. Allow for overrun by m position. Allow for overrun by
m winding actuator output open by winding actuator output closed by
cr 1/2 to 1 turn. c1 k c2 k c3 1/2 to 1 turn.
m
m PRESS THE KEY. PRESS THE KEY.
c1 k c2 k c3
tC k tO
The two bars will flash (stored) and the The two bars will flash (stored) and the
closed indicator lamp will illuminate, m open indicator lamp will illuminate,
m
indicating closed limit position has been LC k LO indicating open limit position has been
tC k tO set. set.
m
m PRESS THE k KEY. 50 PRESS THE m KEY.
LC k LO To check closed limit position hand The open symbol (refer to Fig. 3.3.
m wind valve open until the amber lamp page 4) should now appear.
illuminates. Wind valve back closed NOTE: When in checking mode Set
50 until the closed lamp illuminates. Limit Open [LO] does not appear.

NOTE: When in checking mode Set


Limit Closed [LC] does not appear.
25
AA Speed Setting

50 Positional Display IQT operating time can be adjusted between 25% and 100% of the maximum
m time (50% and 100% for IQT2000). IQT are factory set at the maximum speed.
To access speed setting [AA] screen, bus system [OP] has to be set to [On],
using the + and - key.
IQT Speed
IrDA
m comms
P? k PC k Ir k tP After this setting, proceed to screen [AA]. 100%
m Contact Function To meet full duty cycle performance, IQTM actuators are despatched with the With [AA] displayed
cr k Contact S1 r1 minimum speed set.
m Use the + and - key to select the
m required actuator operating time. The
Contact S2 r2

Primary m settings are displayed in percentage of
Functions
Contact S3 r3 maximum rated speed.
m PRESS THE KEY.
Contact S4 r4 The displayed value will flash, indicating
m

ESD Action that it has been set.
Control Mode
Configuration A1 All speed settings are adjustable in
m percentage increments. Any value of %

Extra Indication Remote
Contacts CPT Control Source outside of the range stated will not be
Option Selection OE k OI k Od accepted into the actuator memory.
m
FL
m NOTE: Mains power has to be on
PA
for speed setting to be carried out.
m

IQT Speed IQT Type
Setting Setting
AA k Ab
26
Return to
Positional Display
50 If the procedure has been followed as
described, the positional display will
m indicate that the actuator is in the open
50 position.
Torque

m Select Remote control momentarily,


using the red selector to exit setting
P? k PC k Ir k tP procedure and then select required
control: Local, Stop or Remote.
m
With the correct settings made electric
cr
operation can now be carried out
m safely.
c1 k c2 k c3
m
tC k tO
m
LC k LO
m
50
27
9 Commissioning
Configuration Functions
The Configuration Settings can be Power Off Setting
configured to suit site control and IQT allows settings to be viewed and
indication requirements. It is important set without mains power. To enable
that Basic Settings such as limits and this function, engage handwheel drive
torque switch settings are set before and rotate until the output drive moves
work commences on commissioning by one turn (refer to page 3).The
the Configuration Settings (refer to SettingTool can now be used. As
page 17). long as a Setting Tool key press takes
place within the 30 seconds timeout
The layout of the Configuration
period, Power Off Setting will remain
Settings accessed with the Setting Tool
enabled. If no infra-red Setting Tool
are detailed in Fig. 9.1. To successfully
communication takes place the display
commission the Configuration Settings,
will return to indicating position. The
information about the site or process
actuator must then be operated by
control system will be required.
handwheel to re-enable Power Off
The supplied actuator Wiring Diagram Setting.
details control and indication devices
fitted to the actuator along with Settings and operation must
terminal connection detail and standard be verified by electric operation
remote control wiring systems.
and function test of the actuator
to ensure correct operation.

NOTE: For IQT Battery Failsafe


instructions, see Section 10 page 61.

Fig. 9
50
Positional Display 28
m
Torque

IrDA Torque Reference


m comms Profile
P? k PC k Ir k tP
m Contact Function Value Contact Form
cr k Contact S1 r1 k r1 k r1

m m
Contact S2 r2 k r2 k r2
Primary

Functions m
Contact S3 r3 k r3 k r3
m
Contact S4 r4 k r4 k r4
m ESD ESD Thermostat ESD Overide ESD Override Maintained 2-wire External Interlocks Conditional Torque Switch
ESD Action Contact Type Bypass Interlocks Local Stop Local Control Control & Partial Stroke Control Bypass
Control Mode
Configuration A1 k A2 k A3 k A4 k A5 k A6 k A7 k A8 k A9 k At
m

Extra Indication 4-20mA Remote Interrupter Setting Tool Power Loss Close Mid-Travel
Contacts CPT Control Source Timer Local Control Inhibit LED Colour LED Language
Option Selection OE OI k Od k OJ k k
Or OS k OH k OU k UL k
m
Option Functions If Analogue, Bus System or Interrupter Timer control options are fitted their appropriate set-up screens will be automatically inserted here.
m

IQT Speed IQT Type
Setting Setting
AA k Ab
m

Software Option 1 Option 2 Service
Version Version Version Reset Password
Service Mode U n k UI k U2 k Ur k UP
m
Help Screens H1 k H2 k H3 k H4 k H5 k H6 k H7 k H8
m
Default Option d1 k d2
m
Return to Positional Display Fig. 9.1 Configuration Settings
29
9.1 Accessing the
Configuration Settings
CONFIGURATION SETTINGS Having established that the Basic In order to display the Configuration
Settings have been correctly set, the Settings it is necessary to press the m
page Configuration Settings can now be key until [Cr] appears.
configured to suit site control and
9.1 Accessing the Configuration Settings 29 If you have chosen to enter
indication requirements.
Configuration Settings in the checking
9.2 Indication Contacts S1, S2, S3 and S4 30 It is possible to move through the mode the display will be as Fig. 9.2.
9.3 Control Mode Configuration 32 various Configuration Settings as shown
If you have chosen to enter
9.4 Option Extra Indication Contacts S5S8 35 in Fig. 9.1 using the k and m keys.
Configuration Settings in the setting
9.5 Option CPT (4-20mA Indication) 36 The actuator wiring diagram will mode the display will be as Fig. 9.3
indicate any options fitted. (refer to Section 7).
9.6 Option Folomatic (Analogue Position Control) 37
9.7 Remote Control Source 40 Options Setting Tool Local Control
[Or] and Power Loss Inhibit [OS] are
9.8 Bus System Option Pakscan 41 standard features, their use being
9.9 Bus System Option Modbus 44 optional.
9.10 Bus System Option Profibus DP 47 Basic Setup Basic Setup
Config Setup Config Setup
9.11 Bus System Option DeviceNet 50
9.12 Bus System Positioning Control Settings 53 Fig. 9.2 Fig. 9.3
9.13 Option Interrupter Timer 55
9.14 Setting Tool Local Control 57 PRESSTHEk KEY.
9.15 Inhibit Operation After Power Loss 57
9.16 Indicator LEDs 58
9.17 Display Language 58
9.18 Default Options 59
9.19 Actuator Type Setting 61
10.3 IQT Battery Failsafe Commissioning Instructions 64
11.2 Help Screens 73
11.3 IrDA Diagnostics and Configuration 78
30
AA
9.2 Indication Contacts
Heading r1 Contact S1 - Function
S1, S2, S3 and S4
Indication contacts S1 [r1], S2 [r2], S3 [Ol] Open Interlock Active Using the + or - key display the desired
[r3] and S4 [r4] may each be set to trip function.
for any one of the following functions: [Cl] Close Interlock Active
[lL] Interlock Active PRESS THE KEY.
Code Function (as displayed) [AA] Actuator Alarm The displayed function will flash
[Ht] Thermostat Tripped indicating that it has been set.
[CL] Closed Limit
[OP] Open Limit [24] 24V Power Failure
[Po] Position % Open [bA] Battery Low
[rr] Motor Running [rP] Relay Parity
[dC] Closing [PA] Partial Stroke Active
[PE] Partial Stroke Error S1 Function
[dO] Opening
Close Limit
[d?] Moving
[HA] Hand Operation The S contact form can be set normally Contact S1 Configured to Trip
[bL] Moving-Blinker open [no] or normally closed [nc]. at Valve Closed Limit
[UA] Valve Alarm The procedures for setting up contacts PRESS THE k KEY.
[tC] Torque Trip Close (direction) S2, S3 and S4 are the same as those
shown for S1.
[tO] Torque Trip Open (direction)
[tt] Torque Trip (any position) Unless specified with order, the
[tl] Torque Trip Mid (travel) default settings for indication
[St] Motor Stalled contacts are as follows:
[LS] Stop Selected S1 [CL] Closed Limit [no]
[Lo] Local Selected
S2 [OP] Open Limit [no]
[rE] Remote Selected
[CA] Control Alarm S3 [CL] Closed Limit [nc]
[ES] ESD Active S4 [OP] Open Limit [nc]
31
AA
r1 Contact S1 - Value r1 Contact S1
Contact Form
This screen will only display if relay Use the + or - keys to select between
function is set to [P0] Position Open . [nO] Normally Open and [nC] Normally
When the S contact function is set to
Closed .
[P0], the required intermediate position PRESS THE KEY.
value must be set.
The displayed option will flash (stored)
No other contact function requires indicating that it has been set.
a value to be set.
The value can be set from 1% open to
99% open in 1% increments.
Using the + or - key, display the
required value. S1 Contact
Normally Open
PRESS THE KEY.
The displayed value will flash (stored) Contact S1 Configured as a
indicating that it has been set. Normally Open Contact
NOTE: If function [PO] Position Open
is selected and it is configured as a
normally open contact it will make at
the set value with the actuator moving
S1 % Position in the open direction.
25% To access S2S4
Value Set to Indicate PRESS THE m KEY.
25% Open

PRESS THE k KEY.


32
AA
9.3 Control Mode A1 ESD Action A2 ESD Contact Type A3 ESD Override
Configuration Thermostat
The Control Mode Configuration affects An active ESD signal applied to the The default setting for ESD Contact The default setting for ESD Override
how the actuator will respond under actuator will override any existing or Type is [nO] Normally Open . Thermostat is [OF] No during ESD.
conditions of emergency shut down, applied local or remote control signal. The thermostats remain in circuit and
For actuators set to ESD [nO] Normally
local control, remote control interlocks, ESD can be configured to override the enabled during ESD.
and 2-wire remote control. Also motor thermostat, active interlocks or
Open the ESD Signal must be applied
to activate the ESD command. For ESD The motor control thermostats can be
included is an unseating torque switch local stop selection. Refer to A3, A4
[nC] Normally Closed the signal must be bypassed during ESD as a factory set,
bypass function. Unless specified with and A5.
removed to activate the command. hard-wired option only. Contact Rotork
order, the control mode configuration
The default action under an active ESD Press the + or - key to choose the for information.
will be set as shown for default
signal is to stay put [SP] Stay Put . contact type.
configuration on page 59. Danger: Actuator hazardous
Press the + or - key to select the PRESS THE KEY. area certification is invalidated
If it is necessary to change the
configuration follow the instructions in
required ESD action: while the thermostats are
The displayed option (stored) will flash
bypassed.
this section. [OF] Off on ESD indicating that it has been set.
[A3] should be set to reflect the factory
There are 10 configurable control [CL] Close on ESD
set configuration of thermostat bypass.
functions:
[SP] Stay Put on ESD
During an ESD event:
Code Function (as displayed) [OP] Open on ESD
[A3] = [OF] No , thermostats enabled
ESD Contact Type
[A1] ESD Action PRESS THE KEY. Normally Open [A3] = [On] Yes , thermostats bypassed
[A2] ESD Contact Type The displayed option will flash (stored)
indicating that it has been set. Actuator Responds to a Normally
[A3] ESD Override Stat Open ESD Contact (Signal Applied)
[A4] ESD Override Interlocks
[A5] ESD Override Local Stop ESD Override
[A6] Maintain Local Control Stat: No
[A7] 2-wire Remote Priority ESD Action
Close
[A8] Interlocks
[A9] Conditional Control
[At] Torque Switch Bypass.
33
AA
A4 ESD Override A5 ESD Override A6 Maintain A7 2-wire Remote
Interlocks Local Stop Local Control Priority
The default setting for ESD Override The default setting for ESD Override The default setting for Local Actuator The default setting for 2-wire Remote
Interlocks is [OF] No . ESD action will not Local Stop is [OF] No . ESD will not Pushbutton control is self-maintained Priority is [SP] Stay Put . If an open and
override an active interlock applied to override local stop when selected. [On] Yes . closed remote control signal are applied
the actuator. simultaneously the actuator will stay
If an applied ESD signal is required to If non-maintained actuator pushbutton
put (stop if running). Refer to actuator
If an applied ESD signal is required to override local stop causing the ESD control is required (jogging, inching,
wiring diagram or PUB002-002.
override active interlocks causing the action as set for A1, press the + or - key. push to run), press the + or - key. The
ESD action as set for A1, press the The display will change to [On] Yes . display will change to [OF] No .
+ or - key. The display will change to
PRESS THE KEY. PRESS THE KEY. Use the + or - key to select the
[On] Yes .
required priority:
The displayed option will flash (stored) The displayed option will flash (stored)
PRESS THE KEY.
indicating that it has been set. indicating that it has been set. [OP] Open
The displayed option will flash (stored)
[SP] Stay Put
indicating that it has been set.
[CL] Close
PRESS THE KEY.
ESD Override Maintain Local
The displayed option will flash (stored)
Local Stop: No Control: Yes
indicating that it has been set.
ESD Override
Interlocks: No

2-Wire Remote
Priority: Stay

2-wire Control Stay Put Priority


34
AA
A8 Interlocks A8 Partial Stroke A9 Conditional Control At Torque Switch Bypass

Actuators are delivered with the The actuator can be set to carry out a Where a high level of safety integrity The default setting for Torque Switch
interlock facility disabled [OF] Disabled . partial stroke test using a signal applied is required, Conditional Control can Bypass is [OF] Off , the torque switches
Refer to the actuator wiring diagram to the open interlock input to initiate be configured. In this mode two are not bypassed during the unseating
or PUB002-002 for interlock control a partial stroke test. Refer to wiring discreet signals are required for remote movement.
circuits. diagram. operation. Remote control will be
To bypass the torque switches during
conditional on both a control signal
To enable remote external interlocks The default for partial stroke/interlocks the unseating movement press the +
(open or close) and the appropriate
press the + or - key. is [OF] Disabled . or - key.
interlock signal being applied
The display will change to [On] Enabled . To enable partial stroke testing press simultaneously. Failure of either or a The display will change to [On].
the + or - key. spurious signal will not cause operation.
PRESS THE KEY. PRESS THE KEY.
The display will change to [PS] Partial Interlocks [A8] must be set [On]
The displayed option will flash (stored) Enabled . Interlock signals are not The displayed option will flash (stored)
Stroke .
indicating that it has been set. required for local operation. indicating that it has been set.
PRESS THE KEY.
The default setting for conditional The torque switches will be bypassed
The displayed option will flash (stored) control is [OF] Disabled . To enable from closed limit to 5% open when
indicating that it has been set. conditional control press the + or - key. opening and from open limit to 95%
The display will change to [On] Enabled . when closing. Bypassing the torque
Interlocks switches makes torque in excess of
Disabled PRESS THE KEY. rated and up to actuator stall available
for unseating a sticky valve. Outside
The displayed option will flash (stored)
these positions the torque setting will
Interlocks
indicating that it has been set.
revert to the values set for [tC] Close
Note: If interlocking is required in only Partial Stroke Torque , see page 22 and [tO] Open
one direction, it will be necessary to
Torque , page 23.
connect a link between the actuator
terminals associated with the other To access partial stroke test settings
direction. Refer to wiring diagram. PRESS THE m KEY.
Conditional
Refer to Appendix A, page 84 for Control: Disabled
instructions on partial stroke settings. Torque Switch
Bypass: Off
35
AA
9.4 Option Extra OE Display Extra Contact
Indication Contacts Set-up Screens
Extra indication contacts S5 [r5], S6 The action of turning on the Extra
[r6], S7 [r7] and S8 [r8] are available as Contact Option makes an additional
an option. series of set-up screens available
Check actuator circuit diagram for
inclusion.
When the Extra Contact Option is
included the set-up procedure and
Extra Contacts Extra Contacts
available contact functions for S5 S8
Menu: On Menu: Off
are identical to S1S4 (refer to Section
9.2 page 30).
Press the + or - key to select the Extra
Unless specified with order the default
Contact Option set-up screens [On].
setting for the extra indication contacts
will be as follows: PRESS THE KEY.
S5 [r5] Close limit The displayed option will flash (stored)
indicating that it has been set.
S6 [r6] Open limit
PRESS THE m KEY TO ACCESS S5
S7 [r7] Torque trip mid
TO S8 SET-UP DISPLAYS.
S8 [r8] Remote selected
The procedure for setting S5 to
NOTE: If the Extra Contact Option is S8 is the same as that for S1 to S4
not included in the actuator build, any (refer to Section 9.2 page 30).
settings made for S5S8 will have no
effect on the indication output of the
actuator.
36
AA
9.5 Option CPT [OI]
4-20mA Indicator
Setting instructions for actuators NOTE: If the actuator has options
including a CPT providing 4-20mA Folomatic and CPT, redefining the
analogue position feedback. CPT, will require the Folomatic to be
recommissioned (refer to Section 9.6
The CPT is an optional extra. It may be Folomatic [OI] page 37).
internally or externally powered.
Check wiring diagram for inclusion and
connection details.

Analog Feedback
CL=4ma OP=20mA

With [HI] Displayed, the CPT operates


Close=4mA , Open=20mA
If Close=20mA , Open=4mA is required, use
the + or - key to change to [LO].
PRESS THE KEY.
The displayed option will flash (stored)
indicating that the option has been set.
37
AA
9.6 Option Folomatic OI Folomatic Feedback FI Analogue
Analogue Control Signal Type
Setting instructions for This instruction lists the Folomatic Before commissioning of the Folomatic Using the + or - key select [ l] Current
actuators including a Folomatic function displays in their sequence and functions can begin, the Folomatic for current input signal or [ U] Voltage
proportional controller for use in assumes that all Folomatic functions are Feedback must be set to suit the for voltage input signal.
to be checked/set. applied set point signal.
analogue valve position control.
The actuator should be selected in Local
The Folomatic is an optional or Stop with the analogue input signal
control device. Check actuator connected to terminals 26 (+ve) and
wiring diagram for inclusion. 27 (ve) (refer to wiring diagram).
Analog Signal
Analog Feedback
Before setting the parameters for Type: Current
CL=4ma OP=20mA
Option Folomatic ensure Remote
Control Source [Od] has been With [HI] displayed, a 20mA signal will PRESS THE KEY.
selected to [bo] in Section 9.7. correspond to the valve opening.
The displayed option will flash (stored)
If a high input signal is required to indicating that it has been set.
Folomatic set up screens will be correspond to valve closing use the
automatically displayed when the + or - key to change to [LO] CL=20mA . The signal type selected will determine
option is fitted. Refer to actuator wiring what is displayed on the input signal
diagram. PRESS THE KEY. range screen [Fr] Analog Signal .
The displayed option will flash (stored) Press the k key to display:
indicating that it has been set. [Fr] Analog Signal .
If setting [OI] is modified after
commissioning the Folomatic, it will
be necessary to recommission the
Folomatic.
Press the m key to access the
Folomatic set-up display menus.
38
AA
Fr Input FL Valve Position FH Valve Position Fd Deadband
Signal Range LOW Set Point HIGH Set Point Adjustment
Using the + or - key select for required If the actuator hunts or responds
signal within the range of 05mA or
APPLY MINIMUM APPLY MAXIMUM unnecessarily to a fluctuating input
volts, 010mA or volts or 020mA or SET POINT SIGNAL SET POINT SIGNAL signal the deadband must be increased.
volts (i.e. 420mA). Using the + or - key select: Using the + or - key select: If more accurate control is required the
deadband may be decreased.
If [FI] is set to current , mA ranges will be [ ] [ ] Closed = valve closed [ ] [ ] Closed = valve closed
displayed. If [FI] is set to Voltage , voltage [00] to [99] = percentage open [00] to [99] = percentage open Use the + or - key to select the
ranges will be displayed. deadband width. Range 0099
[ ] Open = valve open [ ] Open = valve open
corresponds to 09.9% of setpoint
to correspond with the LOW set point to correspond with the HIGH set point signal.
signal. signal.
NOTE: Maximum deadband is 9.9%
of valve stroke. Normally, minimum
Analog Signal deadband should not be less than 1%.
Range: 4-20mA

020mA Range Selected


Low Set Point High Set Point
Position: Closed Position: Open

Deadband
1.2%
PRESS THE KEY. PRESS THE KEY.
Analog Signal
Range: 0-20V The displayed value will flash (stored) The displayed value will flash (stored)
indicating that it has been set. indicating that it has been set. PRESS THE KEY.
0-20V Range Selected
Press the k key to display: Press the k key to display: The displayed value will flash (stored)
[FH] High Set Point Position . [Fd] Deadband . indicating that it has been set.
PRESS THE KEY.
The displayed option will flash (stored) Press the k key to display:
indicating that it has been set. [Ft] Motion Inhibit Time .

Press the k key to display:


[FL] Low Set Point Position .
39
AA
Ft Motion Inhibit FA Action On Loss of FF Failsafe Action FC Manual/Auto
Timer Adjustment Set Point Signal Selection
The motion inhibit timer introduces Use + or - key to enable [On] or Failsafe action when [FA] Loss of Signal Using a switched input you can select
a delay in the actuator response to disable [OF] action on loss of set point set to [On] Failsafe only. between Folomatic (Auto) operation and
a rapidly fluctuating input signal, signal. Manual (hardwired remote) operation.
preventing unnecessary movement. Use + or - key to select, on loss of This can be used in applications where
[On] Failsafe as determined by [FF]. input signal: you want the option to override the
Once the system stabilises the actuator
[OF] Go to Low SP [Lo] Go to Low SP position. Folomatic to allow full manual control of
will respond to steady changes in the
the actuator from the control room.
input signal as necessary. [SP] Stay Put
Actuators dispatched will have this
Use + or - key to adjust motion inhibit [Hl] Go to High SP position. feature disabled as the default in order
time in seconds: range 099. Normally
to minimise commissioning time. If you
it is recommended that motion inhibit
time should not be set to less than 5 Loss of Signal would like this feature enabled, use the
Failsafe + or - key to select [On] Enabled.
seconds (refer to note on page 57).

Failsafe Action
Go to Low SP
PRESS THE KEY.
The displayed option will flash (stored) Manual / Auto
Motion Inhibit
indicating that it has been set. Disabled
Time: 05 seconds
NOTE: Failsafe action ON will be PRESS THE KEY.
effective only for systems using an The displayed option will flash (stored) PRESS THE KEY.
offset or live zero signal range, for indicating that it has been set.
PRESS THE KEY. example 420mA. The displayed option will flash (stored)
Commissioning of the Folomatic is indicating that it has been set.
The displayed value will flash (stored) [FF] will only be displayed if [FA] has now complete. Remote control may be
indicating that it has been set. been set to [On]. selected. Using the wiring diagram supplied with
the actuator, follow the instructions
Press the k key to display: Press the k key to display: on how to connect the Manual / Auto
[FA] Loss of Signal . [FF] Failsafe Action . selection switch.
Commissioning of the Folomatic is
now complete. Remote control may be
selected.
40
AA
9.7 Remote Control Source Od Remote Control Source

The available forms of remote control The setting of Remote Control Source To change the remote source press the
are listed below: will be determined by the option that + or - key until the required setting is
has been fitted, if any. displayed.
1 - Standard hardwired control
2 - Analogue control-Option Folomatic [rE] Hard-Wired Only : Pushbutton/relay PRESS THE KEY.
3 - Network control including: contact control.
The displayed option will flash (stored)
Option Pakscan
[oP] Network : Pakscan, Profibus, indicating that it has been set.
Option Modbus Modbus, Foundation Fieldbus or
Option Profibus DeviceNet control.
Option Foundation Fieldbus
Option DeviceNet [bo] Folomatic : Analogue Proportional
control.
The setting for Remote Control Source
[OF] Remote Disabled : Remote control Control Type
will depend on the type of remote
Hard-wired Only
control required and the option disabled.
specified and fitted. Check actuator Standard Hardwired
circuit diagram for remote control form. Remote Control
41
AA
9.8 Bus System PA Pakscan Node Pb Pakscan
Option Pakscan Address Baud Rate
Setting instructions for actuators The actuator Pakscan Field Control Unit The actuator Pakscan Field Control Unit
including an optional Pakscan Field must be allocated a unique loop node baud rate must be set to the loop baud
Control Unit check wiring diagram for address. rate. For a Pakscan 2-wire control loop
inclusion. the selected baud rate must be common
The actuator must be in Loopback Baud Rate
to the master station and all the field
Before setting the parameters for and isolated from Pakscan loop traffic
control units included in the loop. 2400 Baud
for its address to be set or changed.
Option Pakscan ensure Remote
Loopback can be achieved in two ways: The actuator must be in Loopback
Control Source [Od] has been and isolated from Pakscan loop traffic
1. Turn OFF the master station. PRESS THE KEY.
selected to [oP] in Section 9.7. for its baud rate to be set or changed.
(refer to page 40) 2. Isolate the actuator from the The displayed option will flash (stored)
Loopback can be achieved in two ways: indicating that it has been set.
2-wire control loop both in & out.
1. Turn OFF the master station. Press the k key to display:
Using the + or - keys display the
required loop address. 2. Isolate the actuator from the [PF] Aux I/P Mask .
2-wire control loop both in & out.
Address to be set within the range
01-240 (01F0 Hexadecimal). (refer to
table on page 81).
Using the + or - keys display the
required baud rate.
[01] = 110 baud
Node Address [03] = 300 baud
Hex 01 : Dec 001 [06] = 600 baud
[12] = 1200 baud
PRESS THE KEY.
[24] = 2400 baud
The displayed option will flash (stored)
indicating that it has been set.
Press the k key to display:
[Pb] Baud Rate .
42
AA
PF Pakscan Remote
Auxiliary Input Mask
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These Rules
are used when supplementary remote control or digital auxiliary inputs are required
in addition to the standard control and feedback features incorporated into the 1. Function bit set to 0
Pakscan card. It is also possible to have a combination of both remote control and Any function bit set to 0 indicates that the particular aux input is to be treated as
volt-free inputs to provide, for example, open and close control as well as a high a digital signal for field status reporting, e.g. a level switch or motor running status.
and low tank level alarm indication, supplied via an external transducer.
If the corresponding invert bit is set to a 0, an open contact is reported as a logic
The hexadecimal number displayed under PF can be considered as a software "1" and a closed contact is reported as a logic 0 (i.e. this will invert the input).
mask. It is this mask that tells the Pakscan card what type of input to expect,
control or input signal, and what form the input will be, normally open or normally If the corresponding invert bit is set to a 1, an open contact is reported as a logic
closed (refer to page 81 for Binary, Hexadecimal and Decimal Conversion Table). "0" and a closed contact is reported as a logic 1 (i.e. this gives a noninverting
input).
To decipher the mask the number needs to be split into two separate hexadecimal
characters, each of which can be sub-divided into 4 binary bits. The first 4 bits 2. Function bit set to 1
represent the function and the second 4 represent the input source (known as Any function bit set to 1 indicates that the particular aux input is to be treated as
invert). Pictorially this can be represented as: a digital command to operate the actuator.
Left side hex character Right side hex character When the corresponding invert bit is set to a 0 this represents an N.C. contact
Aux 4 to 1 (function) AUX 4 to 1 (Invert) as being the command source, i.e. a closing contact de-energises the input and an
Bits 4 3 2 1 4321 opening contact energises the input.
When used for remote control of the actuator bits 4 to 1 of the function character When the corresponding invert bit is set to a 1, this represents an N.O. contact
have been designated as follows: as being the command source, i.e. a closing contact energises the input and an
opening contact de-energises the input.
Bit 4 (AUX4) ESD
Bit 3 (AUX3) Stop (Maintain) 3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to
Bit 2 (AUX2) Close the default value of [nO]. The [A1]ESD direction setting should be set to either
Bit 1 (AUX1) Open Open or Close the valve (refer to page 32).
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1) 4. Stop (Maintain) Control
When energised this will make the Aux input Open/Close/ESD control push-to-run,
(non-maintained). When de-energised, the Aux input Open/Close/ESD control will
be maintained.
43
AA
PF Pakscan Remote
Heading PF Pakscan Remote
Auxiliary Input (continued) Auxiliary Input
5. Remote I/P Setting Using the + or - keys display the
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting.
For Pakscan this is [oP] Network .
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 .

Examples
1. The full range of remote controls is needed. Open and Close are NO and ESD Aux I/P Mask
and Stop/maintain is NC. Bits: 0000 1111

Aux I/P 4321 Auxiliary Input Mask [OF]


Function 1 1 1 1 =F
PRESS THE KEY.
Invert 0 0 1 1 =3 i.e. set [PF] to [F3]
The displayed option will flash (stored)
2. Open and close control is required along with 2 inverted digital signal inputs indicating that it has been set.
(Note that with this setting the open and close commands will be maintained.)
For Pakscan module positioning settings
Aux I/P 4321 [OF], refer to page 53.
Function 0 0 1 1 = 3 If Pakscan positioning control is
Invert 0011 =3 i.e. set [PF] to [33] required, PRESS THE m KEY.
3. Only an ESD input is needed. The requirement is for push to run control with a Display [FL] Low Set Point Position
NO contact input. (refer to page 53).
Aux I/P 4321
Function 1 1 0 0 =C
Invert 1000 =8 i.e. set [PF] to [C8]
44
AA
9.9 Bus System PA Modbus Node Pb Modbus Baudrate
Option Modbus [OP] Address
Setting instructions for actuators The Modbus module must be allocated The Modbus module must be set to the
including an optional Modbus RTU a unique address. RS485 highway baudrate. To set the
module check wiring diagram for baudrate the Modbus module must be
To set the address the Modbus module
inclusion. isolated from the host by disconnecting
must be isolated from the host by
the RS485 highway or turning off the
disconnecting the RS485 highway or
Before setting the parameters for host device.
turning off the host device.
Option Modbus ensure Remote Using the + or - keys display the
Using the + or - keys display the
Control Source [Od] has been required address.
required baudrate:
selected to [oP] in Section 9.7. [01] = 110
(refer to page 40). Address to be set within the range (01-
247 to F7 Hexadecimal). If an address [03] = 300 [06] = 600
value outside this range is entered, the [12] = 1200 [24] = 2400
The actuator power must be address set will revert to 01 (for 00) or [48] = 4800 [96] = 9600
cycled for the changes to take effect. F7 (for value above F7). [19] = 19200 [38] = 38400
[57] = 57600 [11] = 115200

Node Address
Hex 01 : Dec 001 Baud Rate
2400 Baud

PRESS THE KEY.


PRESS THE KEY.
The displayed option will flash (stored)
indicating that it has been set. The displayed option will flash (stored)
indicating that it has been set.
Press the k key to display:
[Pb] Baud Rate . Press the k key to display:
[PF] Aux I/P Mask .
45
AA
PF Modbus Remote
Auxiliary Input
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1 AUX4). These Rules
are used when supplementary remote control or digital auxiliary inputs are required
in addition to the standard control and feedback features incorporated into the 1. Function bit set to 0
Modbus module. It is also possible to have a combination of both remote control Any function bit set to 0 indicates that the particular aux input is to be treated as
and volt-free inputs to provide, for example, open and close control as well as a a digital signal for field status reporting, e.g. a level switch or motor running status.
high and low tank level alarm indication, supplied via an external transducer.
If the corresponding invert bit is set to a 0, an open contact is reported as a logic
The hexadecimal number displayed under PF can be considered as a software 1 and a closed contact is reported as a logic 0 (i.e. this will invert the input).
mask. It is this mask that tells the Modbus module what type of input to expect,
control or input signal, and what form the input will be, normally open or normally If the corresponding invert bit is set to a 1, an open contact is reported as a logic
closed (refer to page 81 for Binary, Hexadecimal and Decimal Conversion Table). "0" and a closed contact is reported as a logic 1 (i.e. this gives a noninverting
input).
To decipher the mask the number needs to be split into two separate hexadecimal
characters, each of which can be sub-divided into 4 binary bits. The first 4 bits 2. Function bit set to 1
represent the function and the second 4 represent the input source (known as Any function bit set to 1 indicates that the particular aux input is to be treated as
invert). Pictorially this can be represented as: a digital command to operate the actuator.
Left side hex character Right side hex character When the corresponding invert bit is set to a 0 this represents an N.C. contact
Aux 4 to 1 (function) AUX 4 to 1 (Invert) as being the command source, i.e. a closing contact de-energises the input and an
Bits 4 3 2 1 4321 opening contact energises the input.
When used for remote control of the actuator bits 4 to 1 of the function character When the corresponding invert bit is set to a 1, this represents an N.O. contact
have been designated as follows: as being the command source, i.e. a closing contact energises the input and an
opening contact de-energises the input.
Bit 4 (AUX4) ESD
Bit 3 (AUX3) Stop (Maintain) 3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to
Bit 2 (AUX2) Close the default value of [nO]. The [A1]ESD direction setting should be set to either
Bit 1 (AUX1) Open Open or Close the valve (refer to page 32).

(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.) 4. Stop (Maintain) Control
When energised this will make the Aux input Open/Close control push-to-run.
When de-energised, the Aux input Open/Close control will be maintained. ESD is
always push to run (non maintained).
46
AA
PF Modbus Remote
Heading PP Modbus Parity
Auxiliary Input (continued)
5. Remote I/P Setting Using the + or - keys display the Where Modbus parity bit detection is
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting. used the module must be set with the
parity bit setting of the host.
For Modbus this is [OP] Network .
Using the + or - keys display the
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 . required parity bit:
Examples [no] None (no) parity bit
1. The full range of remote controls is needed. Open and Close are NO and ESD Aux I/P Mask
Bits: 0000 1111 [En] Even parity bit
and Stop/maintain is NC.
[Od] Odd parity bit
Aux I/P 4 3 2 1
Function 1 1 1 1 =F
PRESS THE KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [F3]
The displayed option will flash (stored)
2. Open and close control is required along with 2 inverted digital signal inputs.
indicating that it has been set. Modbus Parity
(Note that with this setting the open and close commands will be maintained.)
Press the k key to display: None
Aux I/P 4 3 2 1
[PP] Modbus Parity .
Function 0 0 1 1 =3 No Parity Bit
Invert 0 0 1 1 = 3 i.e. set [PF] to [33]
PRESS THE KEY.
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input. The displayed option will flash (stored)
indicating that it has been set.
Aux I/P 4 3 2 1
Function 1 1 0 0 =C For Modbus module positioning
settings and action on loss of signal
Invert 1 0 0 0 = 8 i.e. set [PF] to [C8] setting, refer to Section 9.12 page 53.
If Modbus positioning control and
action on loss of communication are
required, PRESS THE m KEY.
Display [FL] Low Set Point Position
(refer to page 53).
47
9.10
AA Bus System PA Profibus Node
Option Profibus DP [OP] Address
Setting instructions for actuators The Profibus DP module must be
including an optional Profibus DP allocated a unique address.
module check wiring diagram for
To set the address the Profibus module
inclusion.
must be isolated from the host by Node Address
disconnecting the RS485 highway or Hex 01 : Dec 001
Before setting the parameters for turning off the host device.
Option Profibus ensure Remote
Using the + or - keys display the PRESS THE KEY.
Control Source [Od] has been required address.
selected to [oP] in Section 9.7. The displayed option will flash (stored)
(refer to page 40). Address to be set within the range indicating that it has been set.
(01-126 to 7E Hexadecimal) (refer to
page 81 for conversion). If an address Press the k to display:
Any settings made locally at value outside this range is entered, the [Pb] Baud Rate .
the actuator may be overwritten by address set will revert to 01 (for 00) or
the host on startup unless the GSD 7E (for value above 7E). [Pb] has no relevance for the
files are locked on the Profibus card. Rotork Profibus DP Mk.2 card.
Refer to publication S420E available
from www.rotork.com Therefore, if the Rotork Profibus DP Mk.2
card is fitted, press the k to display:
[PF] Aux I/P Mask .
The actuator power must be
cycled for the changes to take effect.
48
AA
PF Profibus Remote
Auxiliary Input
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These Rules
are used when supplementary remote control or digital auxiliary inputs are required
in addition to the standard control and feedback features incorporated into the 1. Function bit set to 0
Profibus module. It is also possible to have a combination of both remote control Any function bit set to 0 indicates that the particular aux input is to be treated as
and volt-free inputs to provide, for example, open and close control as well as a a digital signal for field status reporting, e.g. a level switch or motor running status.
high and low tank level alarm indication, supplied via an external transducer.
If the corresponding invert bit is set to a 0, an open contact is reported as a logic
The hexadecimal number displayed under PF can be considered as a software 1 and a closed contact is reported as a logic "0" (i.e. this will invert the input).
mask. It is this mask that tells the Profibus module what type of input to expect,
control or input signal, and what form the input will be, normally open or normally If the corresponding invert bit is set to a 1, an open contact is reported as a logic
closed (refer to page 81 for Binary, Hexadecimal and Decimal Conversion Table). 0 and a closed contact is reported as a logic 1 (i.e. this gives a noninverting
input).
To decipher the mask the number needs to be split into two separate hexadecimal
characters, each of which can be sub-divided into 4 binary bits. The first 4 bits 2. Function bit set to 1
represent the function and the second 4 represent the input source (known as Any function bit set to 1 indicates that the particular aux input is to be treated as
invert). Pictorially this can be represented as: a digital command to operate the actuator.
Left side hex character Right side hex character When the corresponding invert bit is set to a 0 this represents an N.C. contact
Aux 4 to 1 (function) AUX 4 to 1 (Invert) as being the command source, i.e. a closing contact de-energises the input and an
Bits 4 3 2 1 4321 opening contact energises the input.
When used for remote control of the actuator bits 4 to 1 of the function character When the corresponding invert bit is set to a 1, this represents an N.O. contact
have been designated as follows: as being the command source, i.e. a closing contact energises the input and an
opening contact de-energises the input.
Bit 4 (AUX4) ESD
Bit 3 (AUX3) Stop (Maintain) 3. ESD Control
When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to
Bit 2 (AUX2) Close the default value of [nO]. The [A1]ESD direction setting should be set to either
Bit 1 (AUX1) Open open or close the valve (refer to page 32).

(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.) 4. Stop/Maintain Control
When energised this will make the Aux input Open/Close control push to run When
de-energised, the Aux input Open/Close control will be maintained. ESD is always
push to run (non maintained).
49
AA
PF Profibus Remote
Heading PF Profibus Remote
Auxiliary Input (continued) Auxiliary Input
5. Remote Source Setting [Od] Using the + or - keys display the
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting.
For Profibus this is [OP] Network .
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 .

Examples
Aux I/P Mask
1. The full range of remote controls is needed. Open and Close are NO and ESD
Bits: 0000 1111
and Stop/maintain is NC.
Aux I/P 4 3 2 1
Function 1 1 1 1 =F PRESS THE KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [F3]
The displayed option will flash (stored)
2. Open and close control is required along with 2 inverted digital signal inputs. indicating that it has been set.
(Note that with this setting the open and close commands will be maintained.)
If Profibus positioning control and
Aux I/P 4 3 2 1 action on loss of communication are
Function 0 0 1 1 =3 required, PRESS THE m KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [33] Display [FL] Low Set Point Position
(refer to page 53).
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input.
Aux I/P 4 3 2 1
Function 1 1 0 0 =C
Invert 1 0 0 0 = 8 i.e. set [PF] to [C8]
50
9.11
AA Option DeviceNet PA DeviceNet Node Pb DeviceNet Baudrate
Address
Setting instructions for actuators The DeviceNet module must be The DeviceNet module must be set to
including an optional DeviceNet DFU allocated a unique address. the DeviceNet highway baudrate.
module check wiring diagram for
Using the + or - keys display the Using the + or - keys display the
inclusion.
required address. required baudrate:
Before setting the parameters for Address to be set within the range (01- [01] = 125 k baud
Option DeviceNet ensure Remote 63 to 3F Hexadecimal). See page 81 for
[03] = 250 k baud
Control Source [Od] has been conversion. If an address value outside
selected to [oP] in section 9.7. this range is entered, the address set [06] = 500 k baud
(refer to page 40). will revert to 01 (for 00) or 3F (for value
above 3F).
The actuator power must be
cycled for the changes to take effect.

Baud Rate
Node Address 500k baud
Hex 01 : Dec 001

PRESS THE KEY.


PRESS THE KEY.
The displayed option will flash (stored)
The displayed option will flash (stored) indicating that it has been set.
indicating that it has been set.
Press the k key to display:
Press the k key to display: [PF] Aux I/P Mask .
[Pb] Baud Rate .
51
AA
PF DeviceNet Remote
Auxiliary Input
The IQT actuator has the facility to accept 4 auxiliary inputs (AUX1AUX4). These Rules
are used when supplementary remote control or volt free digital auxiliary inputs are
required in addition to the standard control and feedback features incorporated 1. Function bit set to 0
into the DeviceNet module. It is also possible to have a combination of both remote Any function bit set to 0 indicates that the particular aux input is to be treated as
control and volt free inputs to provide, for example, open and close control as well a digital signal for field status reporting, e.g. a level switch or motor running status.
as a high and low tank level alarm indication, supplied via an external transducer. If the corresponding invert bit is set to a "0", an open contact is reported as a logic
1 and a close contact is reported as a logic 0 (i.e. this will invert the input).
The hexadecimal number displayed under PF can be considered as a software
mask. It is this mask that tells the DeviceNet module what type of input to expect, If the corresponding invert bit is set to a 1, an open contact is reported as a logic
control or input signal, and what form the input will be, normally open or normally "0" and a close contact is reported as a logic 1 (i.e. this gives a non-inverting
closed. input).
To decipher the mask the number needs to be split into two separate hexadecimal
2. Function bit set to 1
characters, each of which can be sub-divided into 4 binary bits. The first 4 bits
Any function bit set to 1 indicates that the particular aux input is to be treated as
represent the function and the second 4 represent the input source (known as
a digital command to operate the actuator.
invert). Pictorially this can be represented as:
When the corresponding invert bit is set to a "0" this represents an N.C. contact
Left side hex character Right side hex character
as being the command source, i.e. a closing contact de-energises the input and an
Aux 4 to 1 (function) AUX 4 to 1 (Invert) opening contact energises the input.
Bits 4 3 2 1 4321
When the corresponding invert bit is set to a 1, this represents an N.O. contact
When used for remote control of the actuator bits 4 to 1 of the function character as being the command source, i.e. a closing contact energises the input and an
have been designated as follows: opening contact de-energises the input.
Bit 4 (AUX4) ESD
3. ESD Control
Bit 3 (AUX3) Stop (Maintain) When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to
Bit 2 (AUX2) Close the default value of [nO]. The [A1]ESD direction setting should be set to either
open or close the valve (refer to page 32).
Bit 1 (AUX1) Open
(When used for digital signal inputs they are simply designated as AUX 4 to AUX 1.)
4. Stop (Maintain) Control
When energised this will make the Aux input Open/Close control push-to-run.
When de-energised, the Aux input Open/Close control will be maintained. ESD is
always push to run (non maintained).
52
AA
PF DeviceNet Remote
Heading
Auxiliary Input (continued)
5. Remote I/P Setting Using the + or - keys display the
Ensure that the correct [Od] Control Type setting is selected (refer to page 40). required mask setting.
For DeviceNet this is [OP] Network .
The factory default for [PF] Aux I/P Mask is [OF] 0000 1111 .

Examples Aux I/P Mask


1. The full range of remote controls is needed. Open and Close are NO and ESD Bits: 0000 1111
and Stop/maintain is NC.
Aux I/P 4 3 2 1
Function 1 1 1 1 =F PRESS THE KEY.
Invert 0 0 1 1 = 3 i.e. set [PF] to [F3] The displayed option will flash (stored)
indicating that it has been set.
2. Open and close control is required along with 2 inverted digital signal inputs.
(Note that with this setting the open and close commands will be maintained.) For DeviceNet module positioning
settings and action on loss of signal
Aux I/P 4 3 2 1 setting, refer to page 53).
Function 0 0 1 1 =3
Invert 0 0 1 1 = 3 i.e. set [PF] to [33]
3. Only an ESD input is needed. The requirement is for push to run control with a
NO contact input.
Aux I/P 4 3 2 1
Function 1 1 0 0 =C
Invert 1 0 0 0 = 8 i.e. set [PF] to [C8]
53
9.12
AA Bus System Positioning FL Bus System Valve FH Bus System Valve Fd Bus System
ControlSettings Position at 0% DV Position at 100% DV Deadband Adjustment
If the system control strategy for [FL] Low Set Point Position is the position [FH] High Set Point Position is the position All positioning commands are subject to
Pakscan, Modbus, DeviceNet or to which the actuator will move if a 0% to which the actuator will move if a a deadband tolerance.
Profibus requires intermediate valve command is sent. 100% command is sent. The deadband sets the expected
travel positioning to a "DV" (Desired
Note that the position set for [FL] will Note that the position set for [FH] will positioning accuracy of the actuator
Value - value corresponding to required
be reported to the host as 0%. The be reported to the host as 100%. The and is dependent on various factors
position), the control parameters in this
actuator display will report % open in actuator display will report % open in including, actuator output speed,
section need to be set. Action on Loss
the range set by the limits. the range set by the limits. number of turns and valve torque. If
of Signal parameters apply only to
the deadband is set too low the valve
Modbus and Profibus systems. The default setting is for 0% to be the The default setting is for 100% to be may hunt around the set point.
Limited Range Positioning is a selectable Close limit. the Open limit.
option whereby positioning limits, 0% Use the + or - key to display the
Use the + or - key to select the desired Use the + or - key to select the desired required setting:
and 100%, can be at different positions valve position for a 0% command. valve position for a 100% command.
to those used for digital Closed and [00] to [99] 0% to 9.9% of valve
Open limit commands. Limited range stroke.
positioning can be set using the [FL]
Low Set Point Position and [FH] High Set
Point Position screens.
Low Set Point High Set Point
It should be noted that the actuator will Position: Open
Position: Closed
respond to a digital Open or Close host
command by moving the valve to the Deadband
0% DV = Valve Closed 100% DV = Valve Open 2.5%
set limits irrespective of settings made
for positioning control.
PRESS THE KEY. PRESS THE KEY.
Settings for Deadband and Motion
Inhibit Time affect accuracy and The displayed option will flash (stored) The displayed option will flash (stored) PRESS THE KEY.
response time. indicating that it has been set. indicating that it has been set.
The displayed option will flash (stored)
Any settings made locally at Press the k key to display: Press the k key to display: indicating that it has been set.
the actuator may be overwritten by [FH] High Set Point Position . [Fd] Deadband .
Press the k key to display:
the host on startup unless the GSD [Ft] Motion Inhibit Time .
files are locked on the Profibus card.
Refer to publication S420E available
from www.rotork.com
54
AA
Ft Bus System FA Modbus, Profibus & FF Modbus, Profibus
Motion Inhibit Time (MIT) DeviceNet & DeviceNet
Action on Loss of Signal Failsafe Action
MIT sets the minimum time between Modbus, Profibus & DeviceNet modules Modbus, Profibus & DeviceNet failsafe
successive position commands being can be set to respond on loss of host action when [FA] is enabled.
actioned. It is used in situations to communication by positioning the
Use the + or - key to display the
reduce the number of starts per hour valve. Modbus checks for a loss of
required setting:
and to smooth out fluctuations if general highway communications
continuous positioning is implemented. whereas Profibus & DeviceNet check [Lo] Go to Low SP position.
for a loss of communications addressed
Setting the longest possible time while
specifically to themselves. [SP] Stay put
maintaining acceptable control will
maximise the life of the motorised The default setting is off [OF] and the [HI] Go to High SP position.
valve. default timeout is 255 sec.
Use the + or - key to display the Use the + or - key to display the
required setting: required setting:
[00] to [99] = 0 to 99 seconds. [On] Failsafe as determined by setting [FF] Failsafe Action
[OF] Go to Low SP position. Go to Low SP

PRESS THE KEY.


Motion Inhibit
Time: 05 seconds The displayed option will flash (stored)
Loss of Signal
indicating that it has been set.
Failsafe

Failsafe Action Enabled


PRESS THE KEY.
The displayed option will flash (stored) PRESS THE KEY.
indicating that it has been set.
The displayed option will flash (stored)
Press the k key to display: indicating that it has been set.
[FA] Loss of Signal
Press the k key to display:
(Modbus, Profibus & Devicenet only).
[FF] Failsafe Action .
55
9.13
AA Option OJ Interrupter Timer Jd Interrupter Timer JC Position in Valve
Interrupter Timer Enabled/Disabled Direction Closing Stroke for
Timer to Start
Setting instructions for actuator When fitted, the timer will be The default for timer direction is [CL], Using the + or - key select the position
including an interrupter timer. made available for operation. timer operation will start in closing for the TIMER TO START WHEN THE
and stop in opening pulsing VALVE IS CLOSING.
The interrupter timer enables pulsed The Interrupter cannot be operation around the close position.
stop/start operation by the actuator [ ] [ ] Closed = valve closed
enabled or disabled using the If pulsing operation is required to stop
as a response to local and remote [00] to [99] = percentage open
Setting Tool. in closing and start in opening around
control commands. [ ] Open = valve open
the open position, use the + or - key.
This effectively increases the valve
The display will change to [OP] Opening .
stroke time and can be adjusted to
prevent hydraulic shock (water hammer) PRESS THE KEY.
and flow surges in pipelines.
Int. Timer Int. Timer The displayed option will flash (stored) Timer Start
The interrupter timer is an optional Disabled Enabled indicating that it has been set. Position: 25%
extra check wiring diagram for
inclusion. Interrupter Timer Interrupter Timer Timer Set to Start Pulsing when
Disabled Enabled Closing Valve Reaches 25% Open

When the timer option is available an Timer Start PRESS THE KEY.
additional series of settings can be Closing
accessed by pressing the m key. The displayed option will flash (stored)
indicating that it has been set.
NOTE: If the timer option is not Pulsed Operation Around the
available pressing the m key will not Closed Position If the timing is not required in the
access setting. closing stroke select [JC] to [ ] [ ] valve
NOTE: Instructions [JC] and [JO] are closed position.
Press the m key to display interrupter for timer operation around the Closed
timer set-up screens. Press the k key to display:
position. For timing around the Open [JO] Timer Stop Position .
position, read stop for start [JC] and
start for stop [JO].
Press the k key to display:
[JC] Timer Start Position .
56
AA
JO Position in Valve Opening Jn Contactor OnTime JF Contactor OffTime JE ESD Override
Stroke for Timer to Stop Interrupter Timer
Using the + or - key select the position Using the + or - key select the actuator Using the + or - key select the actuator The interrupter timer may be overridden
for the TIMER TO STOP WHEN THE run period in the range 199 seconds. stop period in the range 199 seconds. when the actuator is under ESD signal
VALVE IS OPENING. command. This will mean the actuator
will run to limit without stop/start
[ ] [ ] Closed = valve closed action under ESD command.
[00] to [99] = percentage open
Refer to [A1] [A3] (refer to page 32
[ ] Open = valve open Timer On Time Timer Off Time for ESD settings).
05 Seconds 25 Seconds The default for ESD override interrupter
timer is [OF] No . The interrupter timer
Actuator Run Period Actuator OFF Period
will continue stop/start action during
Set for 5 Seconds Set for 25 Seconds
Timer Stop ESD action.
Position: 25% PRESS THE KEY. PRESS THE KEY. If ESD must override the timer use the
+ or - to display [On] Yes .
The displayed option will flash (stored) The displayed option will flash (stored)
Timer Set to Stop Pulsing indicating that it has been set. indicating that it has been set.
when Opening Valve
Reaches 25% Open Press the k key to display: Press the k key to display:
[JF] Timer Off Time . [JE] Timer Override ESD
PRESS THE KEY. (refer to note on Page 57).
Timer Override
The displayed option will flash (stored) ESD: No
indicating that it has been set.
ESD Override Timer OFF
If timing is not required in the opening
stroke select [JO] to [ ] [ ]. PRESS THE KEY.
Press the k key to display: The displayed option will flash (stored)
[Jn] Timer On Time . indicating that it has been set.
57
AA Example 9.14 Setting Tool 9.15 Inhibit Operation
Local Control [Or] After Power Loss [OS]
An actuator fitted with the interrupter The default setting for Setting Tool When protection is enabled, on power
timer and set as the example shown in Local Control is [OF] Control Disabled . The default setting for this up if a low battery is detected, the
these instructions would operate at: protection option is disabled [OF]. actuator will inhibit electrical operation
To enable Setting Tool Control press the When disabled it is important
+ or - key to select [On]. and display Power Loss Inhibit via
Rated speed from full Open to 25% that the actuator is not manually actuator alarm display (refer to page 5)
Open. operated during a power failure
PRESS THE KEY. and the monitor relay will de-energise.
1/6 if the battery is low as changes in Limits must reset and the battery
rated speed from 25% Open to Fully
The displayed option will flash (stored) position cannot be tracked - refer replaced refer to page 67.
Closed and from Fully Closed to 25%
indicating that it has been set. to page 6 for battery level status
Open.
display. Should this occur the
With the red control selector in Local, Press the k key to display:
Rated speed from 25% Open to Fully limits must be reset before electric
the Setting Tool control keys are active [OH] Close Colour .
Open. operation takes place- refer to LC/
(refer to page 12). LO page 27. Locking the hand auto
lever can prevent manual operation
- refer to Section 3.1, page 3.

Note
I-R Tool Control
On
With a Folomatic option fitted and
the Interrupter Timer enabled, the Local Setting Tool Control Enabled Power Loss
Folomatic Motion Inhibit Timer must Inhibit : Off
be adjusted to the same time as that Vandal resistant actuators ONLY
set for the Interrupter Timer contactor (red/black selectors not supplied). The protection may be enabled by using
off. For control, the selection of [Or] Vandal the + or - key to select [On]
Failure to do so will cause the actuator Resist is as follows:
response to defer to the lower time
PRESS THE KEY.
[On] Local Only .
which may cause control or process The displayed option will flash (stored)
problems. [OF] Control Disabled . indicating that it has been set.
For ON and OFF times in excess of [rE] Remote Only .
99 seconds apply to Rotork.
58
9.16
AA Indicator LEDs OH Close LED Colour OU Mid-Travel LED 9.17 Display Language

The colour of the LEDs on the IQT The default close limit position indicator The default for mid travel position
display are user configurable. These colour is [gr] Green . indicator colour is [OF] Off . UL
menu sceens allow you to set the Close Language
If red indication is required at the close If mid-travel LED indication is required,
LED colour and the Mid-Travel LED
limit position, press the + or - key. press the + or - key.
being on or off. The default display text language is
The display will change to [rE] Red . The display will change to [On] On . English. If the language was specified
at time of order the actuator will be
PRESS THE KEY. PRESS THE KEY. despatched with the specified language
The displayed option will flash (stored) The displayed option will flash (stored) set.
indicating that it has been set indicating that it has been set.
Press the + or - keys to view alternative
languages.
Available standard languages:
German Deutsch
Close Colour Mid-Travel LED
Green Off French Franais
Spanish Espaol
Press the k key to display: Press the k key to display: Depending on the specified language,
[OU] Mid-Travel LED . [UL] Language . only English and one other may be
supplied with the actuator.

Language
English
59
9.18
AA Default Options
[d1] and [d2]
All IQT functions are configured to a set of Rotork default (standard) settings before Rotork standard [d1] Default settings for IQT:
despatch, see the table opposite. When requested, alternative settings specified
with the order will be used. When site commissioning takes place, entered settings Function [d1] Default Setting
overwrite Rotork defaults and these current settings are used for operation along [P?] Password Unaffected will remain as set
with the remaining unadjusted defaults. [Ir] IrDA Insight [On] IrDA Enabled
Should difficulty be encountered during commissioning the default settings can be
reinstated, returning the actuator configuration to its original manufactured state. Basic Settings
Site commissioning must then begin again. [C1] Close Direction [C] Clockwise
There are two levels of default: [C2] Close Action [Ct] Close on Torque
d1 Rotork standard or customer specified Basic and Configuration Settings. [C3] Open Action [Ot] Open on Torque
[tC] Close Torque [40] 40% of rated
d2 Limit positions only factory set limits.
[tO] Open Torque [40] 40% of rated
NOTE: Settings associated with control options Folomatic, Pakscan, Modbus
Profibus and Foundation Fieldbus are not affected by d1 or d2. Configuration Settings
Functions will remain as set. [r1] Indication Contact S1 [CI]/[nO] Close, Normally Open
If d1 is entered, all Basic and Configuration Settings except limit positions [r2] Indication Contact S2 [OP]/[nO] Open, Normally Open
will return to their default setting. See the table opposite for Rotork
[r3] Indication Contact S3 [CI]/[nC] Close, Normally Closed
standard settings. Basic settings (except limits) and Configuration Settings
must then be checked and reset as required (refer to Basic Settings page 17 [r4] Indication Contact S4 [OP]/[nO] Open, Normally Closed
and Configuration Settings page 27). [A1] ESD Action [SP] Stay put on ESD
If d2 is entered the limits will be reset, with the actuator positioned at 50%. [A2] ESD Contact Type [nO] Normally Open (make for ESD)
Limits must then be reset to the suit the valve (refer to Basic Settings page 17).
[A3] ESD Thermostat Override [OF] Thermostats Active during ESD
[A4] ESD Override Interlocks [OF] Interlocks Active during ESD
[A5] ESD Override Local Stop [OF] Local Stop Active during ESD
[A6] Maintained Local Control [On] Maintains in Local Control
60
9.18
AA Default Options
[d1] and [d2] cont.
Rotork standard [d1] Default settings continued: The Rotork standard default settings are subject to change without notice.
If specified with order, [d1] settings will be configured as requested.
Function [d1] Default Setting
To reinstate [d1] settings, with [d1] displayed.
[A7] 2-wire Remote Control [SP] Stay Put on 2-wire signal
[A8] Interlocks [OF] I/L function disabled PRESS THE KEY.
[A9] Conditional Control [OF] Function disabled
The setting bars will flash, indicating the [d1] default settings have been reinstated.
[AE] Torque Switch Bypass [OF] Function disabled
[OE] Option Extra Indication Contacts [OF] Unless fitted. See wiring diagram To reinstate factory set limits (actuator positioned at 50%) with [d2] displayed,
[OI] Option CPT [HI] 4mA at Closed PRESS THE KEY.
[Od] Remote Source [rE] Unless option fitted
(refer to 9.7 page 40.) The setting bars will flash, indicating the [d2] default limits have been reinstated.
[OJ] Option Interrupter Timer [OF] Unless fitted. See wiring diagram Limits must now be reset. Refer to page 24.
[Or] Setting Tool Local Control [OF] Setting Tool Control disabled
[OS] Power Loss Inhibit [OF] Protection off

Option Extra Indication Contacts (when fitted) - refer to wiring diagram


[r5] Indication Contact S5 [CI]/[nO] Close, normally open Restore Config Reset Limits to
Range 25 Turns
[r6] Indication Contact S6 [OP]/[nO] Open, normally open
[r7] Indication Contact S7 [tI]/[nO] Torque Trip Mid Travel,
normally open [d1] Displayed [d2] Displayed
[r8] Indication Contact S8 [rE]/[nO] Remote Selected,
normally open
61
9.19 Actuator Type Setting

50 Positional Display Actuator type determines the speed range and is factory set. Should the actuator
m Motor Speed Control PCB be replaced with a spare, the actuator type must be set.
Failure to set the correct type will invalidate the actuator performance specification
and warranty. To set the actuator types go to setting [Ab] in the secondary
IQT Type
IrDA
m comms functions.
P? k PC k Ir k tP IQT 125
m Contact Function With [Ab] displayed
cr k Contact S1 r1
m Use the + and - key to select the
m required actuator type. The selectable
Contact S2 r2 values are related to actuator type as

Primary m
Functions follows:
Contact S3 r3
m Value Type
Contact S4 r4 1 IQT125
m

3 IQT250
ESD Action
Control Mode 6 IQT500
Configuration A1
m 12 IQT1000

Extra Indication Remote 24 IQT2000
Contacts CPT Control Source
Option Selection OE k OI k Od PRESS THE KEY.
m The displayed value will flash,
FL indicating that it has been set.
m
PA Any value of hex outside of the range
m stated will not be accepted into the

IQT Speed IQT Type
actuator memory.
Setting Setting
AA k Ab
NOTE: Mains power has to be on for
actuator type setting to be carried out.
62
AA
10 Heading
IQT Battery Failsafe

10.1 Introduction. There are three possible failsafe actions For safety the IQT Failsafe battery
that can be customer configured: WARNING: pack is shipped with DC power fuses
The IQT battery failsafe actuator
provides electrical operation after loss CONTAINS BATTERIES FS3 and FS4 removed. It is essential
Failsafe Close -
of main AC electrical supply, allowing that the fuses are removed before
Close valve on loss of AC supply
the valve to be controlled to a process, FIRE, EXPLOSION AND SEVERE any maintenance work is carried
mains fail safe position. On loss of AC Failsafe Open - BURN HAZARD. DO NOT SHORT out on the actuator or the battery
supply, power is provided from integral Open valve on loss of AC supply CIRCUIT. DO NOT INCINERATE. assembly.
batteries located in a extended version Stayput waiting for command - The Before fitting Fuses FS3 and FS4 the
of the terminal cover. With AC power DO NOT DISASSEMBLE BATTERY
actuator can then be directed to operate IQT actuator must be commissioned
applied to the actuator, the batteries PACK. RECHARGE ONLY AS
via local or standard remote control in accordance with section 7, page
are charged from the actuator. signals* within 30 minutes of AC power PART OF THE IQT. DO NOT 11 of this manual.
being removed. EXPOSE BATTERIES TO AMBIENT
TEMPERATURES ABOVE 60C
*Remote signals must be applied to
standard remote control inputs, close on THE IQT BATTERY FAILSAFE
terminal 33, open on terminal 35 or ESD ACTUATOR CONTAINS HIGH
on terminal 3 of battery pack connector. CAPACITY BATTERIES WHICH
On loss of AC supply remote control via ARE CONNECTED TO ACTUATOR
Folomatic proportional control or serial TERMINALS 14 (+) AND 21
digital network signals are not available. (). DC BATTERY POWER MAY BE
*On loss of AC supply the IQT battery SUPPLIED TO THESE TERMINALS
failsafe does not support customer WHEN THE AC ELECTRICAL
nominal 24V DC supply on terminals SUPPLY IS SWITCHED ON AND
4 (-ve) and 5 (+ve) and therefore SWITCHED OFF.
control signal supply must be externally
powered. Refer to wiring diagram.
On loss of AC supply the IQT battery
failsafe does not support analogue
current position transmitter (CPT)
position feedback or serial network
communication. The IQT monitor relay
will de-energise on loss of AC supply.
63
AA
10 Heading
IQT Battery Failsafe continued

10.2 Battery Failsafe Specification Charging Time typically 4 hours Failsafe Operation Performance:
from a discharged state (depending on Number of operations at 75% rated torque.
Environmental: ambient temperature).
Operating temperature -30C to + 60C.
Charge state The lower line of text Temperature C IQT125 IQT250 IQT500 IQT1000 IQT2000
Enclosure (IQT battery Failsafe actuator): wll display the state of the battery, see
Watertight IP68 7m / 72 Hrs. -30 15 12 6 3 1
fig.2.
-20 50 40 20 10 5
Battery Pack: On loss of AC power, the state of the
Type: Sealed leadacid batteries located battery is not displayed. -0 63 50 25 12 6
in a vented enclosure. DC power supply Fuses FS 3 and FS4 20 75 60 30 15 7
Voltage & Capacity: 28V 2.5Ah. are rated at 20A, automobile type ATO 40 75 60 30 15 7
Fast acting.
Float life: 8 Years at 20C, 3 years at 60 75 60 30 15 7
40 C. Charge/control Fuses FS1 and FS2
are rated 2A, 20mm quick blow.
Storage Life: 2 years at 23C, 2 months
at 60 C. The battery supply will auto disconnect IQT Battery Failsafe Actuator Display
at 20V or 30 minutes after AC supply is
Battery pack assembly weight: 5.5Kg. removed from the actuator to prevent
For total IQT battery failsafe weight, damage caused by deep discharge of
add 5.5Kg to the actuator weights batteries.
listed on page 80.
Maintenance :
Charger : Ensure the two vents located in the
The IQT battery failsafe is despatched battery pack cover are not removed,
with the batteries in a charged state, plugged or covered. The batteries are
however once the IQT is connected to sealed lead acid type and require no
AC power the batteries will automatically maintenance. Refer to section 11, page
begin charging to bring them to the 67 for IQT range maintenance.
float charge state. For correct battery FS Ready
charging, the IQT supply voltage must Fig. 1
not be less than 90% of nominal. FS Boost Charge
FS Charging

Fig. 2
64
AA
10 Heading
IQT Battery Failsafe continued

10.3 Failsafe Commissioning 1. Remove Cover. Figure 3 2. Set Control Links. Figure 4 3. Connect ESD/Interlock
Instructions control wiring. Figure 5
Ensure the AC power supply to the Referring to the label, locate PCB links
Before commissioning actuator is switched OFF. LK1 and LK2. Links determine required If the control of the IQT actuator
action on loss of AC supply to the with AC supply switched ON requires
the failsafe operation it Using a 6mm allen key remove the four actuator. emergency shut down and/or interlocks,
screws securing the IQT battery failsafe
is essential that the IQT cover and remove cover from actuator Using pliers, fit links LK1 and LK2 in
ESD and/or interlock field wiring must
actuator has first been be connected to the green terminal
housing. The cover houses the battery required positions. plug located on the battery pack
commissioned in accordance pack and charging/control circuitry and assembly.
care must be taken that it does not drop. Links bridge between pins 1-2 or 2-3
with the Installation and and must be set for the desired action If ESD and/or interlocks do not form
Commissioning Instructions in Ensure the two 20A fuses located in a as detailed in table the below: part of the IQT control scheme then no
plastic bag are kept safely - DO NOT FIT wiring is necessary.
this manual. *The direction required for failsafe
The cover is restrained with an external operation and ESD contact form Remove plug by pulling it straight up
chain to support its weight (5.5 Kg (if being used) is set with the IQT and connect field wiring for ESD and/or
approx) and prevent interconnecting setting tool. Refer to page 66 of this interlocks as indicated on the label and
cables being damaged. The battery manual. actuator wiring diagram.
failsafe cover assembly is supported
by the restraining chain during Once connected, re-fit the wired plug
commissioning. LK1 LK2 Required action into its socket. The plug and socket
1-2 1-2 Failsafe on loss of supply, are polarised, ensuring they cannot be
ESD [A2] set [NO]* mated incorrectly.
2-3 1-2 Failsafe on loss of supply,
ESD [A2] set [NC]*
1-2 2-3 Stayput waiting for
command (30 Min max)
65
AA
10 Heading
IQT Battery Failsafe continued

4. Fit Battery Fuses. Figure 6


Referring to the label, locate 20A fuses
FS3 and FS4 holders located on the
battery pack assembly.
Remove 20A fuses from the plastic bag
and fit into fuse holders FS3 and FS4
as shown.

5. Refit Cover. Figure 7


Make sure cover O-ring is fitted and the
cover spigot is lightly greased.
Refit cover making sure no field or Fig. 3 Fig. 5 Fig. 7
interconnecting wires are trapped
between cover and gearcase.
Tighten the 4 fixing bolts using a 6mm
allen key.
Set up of the battery pack is now
complete.
To enable failsafe operation, settings
within the IQT actuator must now be
made.

Fig. 4 Fig. 6
66
AA
10 Heading
IQT Battery Failsafe continued

6. IQT Actuator Failsafe Settings. NOTE. If ESD is being used for AC


Failsafe action on loss of AC supply LK1* LK2* [A1] [A2] [A4] supply control the user must decide
The actuator can be operated by if ESD is to override local stop. If ESD
standard remote control signals (open/ Close
1-2 1-2 [CL] [NO] [OF] override local stop is required set [A5]
close/interlocks/ESD) under AC supply (no user ESD) to [NO].
control.
Testing
On AC supply loss, the actuator will Open To test the failsafe function, switch off
automatically perform an ESD using 1-2 1-2 [OP] [NO] [OF] AC supply to IQT actuator. Actuator will
battery power. (no user ESD) perform the set failsafe function.
For the required failsafe operation, Refer to page 63.
using the supplied Infra-red Setting Close
Tool, set configuration functions [A1], 1-2 1-2 [CL] [NO] [OF]
[A2] and [A4] for the desired failsafe ESD = N/O contact, makes for ESD
action. Refer to page 32, [A1] ESD
Action, [A2] ESD contact type and [A4] Open
ESD override interlocks actuator settings 1-2 1-2 [OP] [NO] [OF]
must be checked and/or set . ESD = N/O contact, makes for ESD
Switch ON AC supply power to the
IQT actuator. Refer to table below for Close
2-3 1-2 [CL] [NC] [OF]
settings. ESD = N/C contact, breaks for ESD
NOTE. If network option cards are used
with a failsafe setup the auxillary input Open
masks [PF] must be set accordingly. The 2-3 1-2 [OP] [NC] [OF]
ESD setting in the mask must always ESD = N/C contact, breaks for ESD
be set for NO (normally open) type. For
example if only the ESD is required for
an auxillary input, the setting would be
80 (hex). See section 9 configuration
settings. Ensure the remote control
source option [Od] is set to [oP].
67
AA
11 Maintenance, Monitoring
Heading
and Troubleshooting
Maintenance Routine maintenance should include WARNING: Battery Replacement
Every Rotork actuator has been fully the following: If the actuator is located within a
The battery holder in the actuator
tested before dispatch to give years of hazardous area permission must be
* Check actuator to valve fixing bolts gearcase also protects the user from
trouble-free operation providing it is obtained in the form of a hot work
for tightness. the hazardous live connections
installed, sealed and commissioned in permit or other local regulation before
accordance with the instructions given * Ensure valve stems and drive nuts are inside the actuator and therefore it removal and/or replacement of the
in this publication. clean and properly lubricated. must not be damaged. The actuator battery.
must be isolated or disconnected
The IQT actuators unique double * If the motorised valve is rarely WARNING:
sealed, non-intrusive enclosure provides operated, a routine operating if the battery holder has to
complete protection for the actuator schedule should be set up. be removed from the actuator 48 VDC supply only - Actuator
components. gearcase. power supply must be isolated
* Replace actuator battery every before replacing the backup 9V PP3
Covers should not be removed for 5 years. A unique circuit has been incorporated
battery. For all other supplies the
routine inspection as this may be into the battery function of the IQT,
* Check the actuator enclosure for effectively reducing the overall drain power can remain switched on.
detrimental to the future reliability of
damage, loose or missing fasteners. and significantly increasing the battery
the actuator. NOTE: Removal of the battery with the
* Ensure there is not an excessive life. mains electrical power switched off will
The electrical control module cover is
build up of dust or contaminant In normal circumstances result in stored Datalogger record time
bonded by the Rotork quality control
on the actuator. references being lost for the duration
seal. It should not be removed as the battery replacement interval should
module contains no site-serviceable when there is no mains supply or
* Check for any loss of lubricant. not exceed 5 years. Ambient
components. battery power. Therefore for all supplies
temperature and plant operating other than 48 VDC, leaving the power
All electrical power supplies to the
The Actuator Battery conditions may affect battery life.
The battery supports the actuator supply switched on is recommended.
actuator must be isolated before any Battery level status is indicated by an
position updating circuits and the If main electrical power is not available
maintenance or inspection is carried icon on the actuator display, refer to
position (LCD) display when the main or if main power has been switched off
out, except replacement of the battery. Section 3.4 Alarm Indication (refer to
power supply is turned off. It ensures while the battery was discharged, it is
Electrical supplies must be isolated the current position is updated and page 5). recommended that the actuator limits
before actuator covers are removed displayed when manual operation takes If the battery icon is displayed the be checked after battery replacement
refer to Battery replacement place with the main power turned off. battery must be replaced. (refer to Section 8 Commissioning Basic
instructions. Settings, page 17).
The battery is not required to retain any
actuator settings.
68
AA
11 Maintenance, Monitoring
Heading
and Troubleshooting cont.
Battery Removal Battery Types Torque and Position Monitoring
The actuator must be selected to Stop For European hazardous area certified The IQT range of actuators incorporate
using the red selector (refer to page 3). actuators (ATEX) use an Ultralife U9VL real time, instantaneous Torque &
Access to the battery is via a labelled lithium manganese dioxide battery only. Position monitoring as standard.
sealing plug situated on the main
For FM and CSA certified enclosures use Torque & Position can be used to
gearcase near the handwheel hub.
an Ultralife U9VL lithium manganese monitor valve performance during Torque = 19%
Remove the sealing plug using the dioxide battery. Equivalent, UL operation. The effect of process
appropriate Allen key, ensuring the recognised, batteries may be used. changes (differential pressure etc.) can
O ring seal remains on the plug. be evaluated. Tight spots in valve travel
For watertight (WT) actuator enclosures
Disconnect the battery wiring loom can be pinpointed as well as gauging Example shows 19% (of rated) torque
use an Ultralife U9VL lithium
from the battery terminals. Using the torque developed through stroke for at 50% open position. Display torque
manganese dioxide battery or any
black pull strap, lift the battery out of torque value setting (refer to pages range: [00] to [99]% of rated torque
equivalent 9V battery.
the rubber sealing pocket. 22, 23). in 1% increments. For values of torque
If in doubt regarding the correct battery above 99% the display will indicate [HI].
Using the Setting Tool, the display can
type, contact Rotork.
be set to indicate Torque and Position Display position range:
as follows:
Fitting Replacement Battery [ ] [ ] = valve closed
Fit the pull strap around the With the actuator displaying Current
replacement battery and insert into [00] to [99] = percentage open
Position, using the Setting Tool,
the rubber sealing pocket. Reconnect [ ] = valve open
the battery wiring loom to the battery PRESS THE m KEY.
For a stationary actuator the display
terminals. Refit the battery sealing plug The lower display will show the torque will indicate the actual torque value as
ensuring O ring is in good condition value as a percentage and a graphical applied by the actuator.
and correctly fitted. Hand tighten the representation in the form of a bar
Fig. 11.1 sealing plug to 8 Nm (6 lbs.ft) using the graph. To keep the torque & position display
appropriate Allen key. active press the + or - keys. The display
will remain active for approximately 5
minutes from the last key operation.
69
AA
11 Maintenance, Monitoring
Heading
and Troubleshooting cont.
Torque Reference Profile Storing a Reference Profile Enter the correct password and press Pressing the key stores the last
IQT text display models only. the key, "Password Correct measured reference close-open and
The location of torque reference profile
should display briefly and the setting open-close torque profiles within the
Only visible when in Setting Mode. See [tP] screen is shown below:
bars appear. datalogger.
Section 7, page 15.
Press the k arrow key 3 times to Press the k and m keys together to
This feature allows the user to store a 50 display the [tP] screen: return to the positional display.
reference torque profile, which can be
used to plan and determine periodic m The reference profile along with current
maintenance. 50 Torque profiles can be viewed and analysed using
Torque
IQ Insight software as shown in Fig 11.2.
After commissioning has taken place
and the process is running under m Torque Profile IQ Insight is available free, visit
normal conditions, a profile of the as P? k PC k Ir k tP Press To Set www.rotork.com
commissioned torque measurement
over the whole stroke can be taken m
and stored in the Datalogger. The cr k Configuration Settings
stored torque reference profile can be
compared with later torque profiles m
using Rotork Insight in order to Basic Settings
determine changes in performance of
the valve and/or process over time or
under different conditions. Each actuator is supplied without a
reference profile stored. To store a
reference profile, electrically stroke the
actuator under normal process conditions.
Once the reference stroke (close to
open / open to close) is complete stop
the actuator.
Using the supplied Setting Tool, press
the m arrow key twice to display the
password screen. Refer to section 7
page 15. Fig. 11.2
70
AA
11 Maintenance, Monitoring
Heading 11.1 Setting Tool Pro
and Troubleshooting cont. Download & Upload
Troubleshooting (Refer to Section 3.3 page 4 The Setting Tool Pro Download & Download/Upload Menu structure
The IQT range of actuators is the Actuator Display). Upload
worlds first that can be commissioned Setting Tool Pro includes a feature
If the display is blank the actuator
and interrogated without removing which allows the user to extract and
battery must be replaced and the limits dL 01 dC 01
electrical covers. Help Screen diagnostics store IQT actuator configuration
of travel reset (refer to Section 11,
enable fast and complete fault finding and datalogger files within the Tool.
page 67 The Actuator Battery). Extract Extract
to be carried out. Stored files can be viewed using a PC
Datalogger Configuration
running IQ Insight . Using This tool,
Question: With power on, the stored configuration files can also be
actuator display is not backlit. uploaded back to IQT actuators in order
Position indicator lamp not to replicate a setup for multiple units
illuminated. What is wrong? (limits must be set individually).
Answer: With mains power on, the IQ Insight is available free from
actuators display should be backlit www.rotork.com P? Id
(refer to Section 3.3 page 4 The N Actuator password
Actuator Display). Using the new features
entered?
Datalogger and configuration files
Check that 3 phase supply is available
can be extracted and stored in the
and is of the correct voltage as stated
Tool without entering a password. For
on the actuator nameplate. Measure
uploading configuration files from Tool
voltage phase to phase across terminals
to actuator, the actuators password Y
1, 2 and 3 of the actuator terminal
must first be entered correctly see
bung.
section 7, page 15 for details.
Question: With power off, the UC 01
actuator does not display position. Accessing the menus
The download/upload menus are Upload
What is wrong?
accessed when the Setting Tool Pro Configuration
Answer: With mains power off the download key m is pressed. IrDA
actuator battery supports position communication is initialised, the green
indication liquid crystal display only. LED in the tool window will flash. The
user then has 30 seconds to connect
to the actuator.
71
11.1
AA Heading
Setting Tool Pro
Download & Upload cont.
Downloading and storing IQT Downloading and storing IQT Note. IQT actuators with non text
Datalogger Files Configuration Files displays show code/symbols only.
Press the m Key Press the m Key The screen will default to Memory
The green LED visible in the setting Tool Extract Log The green LED visible in the setting Tool
Location 01. There are a total of
Extracting Data ten memory locations available for
window will start flashing. window will start flashing.
Configuration Files, which are selected
Point the Tool at the actuator Display Extracting Log screen Point the Tool at the actuator Display by pressing the + or keys.
Once communication has been Once communication has been When the required location has been
successfully established, the Extract Note. IQT actuators with non text successfully established, the Extract selected, press the key to initiate
Datalogger screen will be displayed: displays show code/symbols only. Datalogger screen will be displayed: the extraction. The following screen will
The extraction takes approximately 35 be displayed:
seconds for a full datalogger (2 minutes
for non text displays). After a successful
extraction, the screen will revert to
Extract Log
the Extract Log screen. If during the Extract Log
downloading an error is encountered, Memory Loc: 01 Extract Config
Memory Loc: 01 Extracting Data
[dL Er] will be displayed along with
Extract Datalogger screen Error , wait for the screen to revert to [dL Extract Datalogger screen
01] and try again. Extracting Configuration screen
Note. IQT actuators with non text Note. IQT actuators with non text
Note. IQT actuators with non text
displays show code/symbols only. The action of downloading the displays show code/symbols only.
displays show code/symbols only.
actuator datalogger file will
The screen will default to Memory automatically download the
PRESS THE k KEY. The extraction takes approximately 3
Location 01. There are a total of configuration file to the Tool. The following screen will be displayed: seconds. After a successful extraction,
four memory locations available for the screen will revert to the Extract
dataloggers, which are selected by configuration screen. If during the
pressing the + or keys. downloading an error is encountered,
When the required location has been [dC Er] will be displayed along with
selected, press the key to initiate Extract Config Error, wait for 5 seconds until the screen
Memory Loc: 01 reverts to [dC 01] and try again.
the extraction. The following screen will
be displayed: Extract Configuration screen
72
11.1
AA Heading
Setting Tool Pro
Download & Upload cont.
Uploading a configuration File to an PRESS THE k KEY. Note. IQT actuators with non text
IQT actuator displays show code/symbols only.
The download configuration screen will
be displayed: [dC 01] The writing process take approximately
12 seconds to complete, after which
Note: Actuator must be set to PRESS THE m KEY. the screen reverts to the Uploading
Local when writing configuration
The upload configuration screen will be Configuration screen. If during the
data.
displayed: writing process an error is encountered,
[UC Er] will be displayed along with
Warning: After uploading a Error , wait for 5 seconds until the screen
configuration file from the tool reverts to [UC 01] and try again.
to the actuator, the actuator basic
and configuration set up will be a
duplicate of the file set up. Write Config
Memory Loc: 01
Refer to sections 8 & 9.
Open and close limit positions and Upload Configuration screen
current position are not copied
and must be set on each individual Note. IQT actuators with non text
actuator. Refer to section 8. displays show code/symbols only.
For access to the Upload Configuration Using the + or keys, select the
screen, the actuators password must memory location where the required
first be set correctly, see section 7. configuration file is stored and press
the key, the following screen will
Press the m Key be displayed:
The green LED visible in the setting Tool
window will start flashing.
Point the Tool at the actuator Display
Once communication has been successfully Write Config
established, the download datalogger Writing Data
screen will be displayed.[dL 01]
Uploading Configuration screen
73
11.2
AA Help Screens H1 Factors Inhibiting
Electrical Operation

H1
With the actuator powered up and For troubleshooting, access the BATTERY LOW ON POWER UP
Local or Stop selected, eight Help following Help Screens and refer to Bar ON = Low battery detected On
Screens can be accessed using the text: Power Up.
Setting Tool (refer to Fig. 9.1 page 29
If [OS] is selected [On] (default is [OF])
Phase Position
H1 Factors inhibiting electrical
for their location). Loss Error
operation. the actuator operation will be inhibited
With Remote selected press the m when powered up with a discharged
key on the Setting Tool twice. The Help H2 Monitor battery level and ESD
battery (refer to [OS] page 57).
Screens will be displayed. control input.
The battery should be replaced at the
Each screen uses bars to indicate H3 Monitor the position limit and
Local earliest opportunity (refer to page 67).
the status of a particular control or actuator power supply status. Controls
indication function. Each bar reacts to H4 Monitor remote control inputs to Error LOCAL CONTROLS ERROR
changes in the status of its actuator the actuator. Battery Low Bar ON = Invalid Local Control
function by turning on or off. on Signals Detected.
H5 Monitor remote interlocks local Power-up
control inputs and motor For example if a Local Open and Close
thermostats. Help Screen 1 signal is detected at the same time this
would be classed as an invalid or fault
H6 Monitor torque switch status and POSITION ERROR condition.
IR Setting Tool communication for Bar ON = Current Position Error
vandal proof applications. Present. PHASE LOSS
H7 Monitor travel limits, centre During power up the actuator position Bar ON = Phase Lost (3 Phase
column and position limit status. processor compares the current position Actuators Only).
H8 Monitor the actuators position- to that stored in the Eeprom. If there is Loss of third monitored power supply
sensing devices. a discrepancy this is shown as a current phase connected to actuator terminal 3.
position error.
H9 Rotork use only.
Re-setting of both actuator limits
Help screen bars shown should now be carried out (refer to
are undefined and may page 24).
be ON, OFF or flashing.
74
AA
H2 Battery Level and H3 Factors Inhibiting H4 Remote Control
ESD ControlInput Electrical Operation Inputs

H2 H3 H4
LOW BATTERY
Bar ON = Battery level low.
Bar OFF = Battery OK.
ESD Clockwise Remote Remote
Active Bar ON when the battery is low but still Limit Maintain 2 Open 1
able to support the necessary actuator
functions. Anti
Low Clockwise ESD 2 Remote
Battery The battery should be replaced at the Limit Close 1
earliest possible opportunity.
Battery Inhibit Remote
Discharged ESD SIGNAL ACTIVE Close 2 ESD 1
Bar ON = ESD Signal is present.

When applied, an Emergency Shutdown Remote Remote


Help Screen 2 Help Screen 3 Open 2 Maintain 1
Signal will override any existing local
or remote control signal, causing the Help Screen 4
BATTERY DISCHARGED CLOCKWISE LIMIT
actuator to respond in the direction
Bar ON = Battery Discharged. Bar ON = Actuator has reached All remote signals designated with 1
selected for ESD.
clockwise limit of travel. are standard hard wired remote inputs.
Bar ON when the battery is no longer
The ESD function will be determined
able to support actuator functions ANTI-CLOCKWISE LIMIT When a Pakscan, Profibus or
by the settings on Control Mode
under loss of power conditions. Bar ON = Actuator has reached Foundation Fieldbus card is fitted,
Configuration screens [A1] to [A5]
The battery must be replaced (refer to (refer to Section 9.3 page 32). Anti-clockwise limit. remote control inputs are designated
Section 11 page 67) and limit positions with a 2.
The actuator will not respond to any INHIBIT
reset (refer to [LC] and [LO] page 24).
local or remote control while an ESD Bar ON = Actuator inhibited. REMOTE OPEN 1
signal is maintained. Bar OFF = Remote Open Signal
Possible Causes: Present.
Phase Loss (3 phase only).
Power Loss Inhibit (page 57).
Internal Failure.

continued...
75
AA
H4 Remote Control H5 Remote Interlocks,
Inputs continued Local Control
Inputs, & T/stat

H5
REMOTE CLOSE 1 CLOSE INTERLOCK THERMOSTAT TRIPPED
Bar OFF = Remote Close Signal Bar ON = Close Interlock Active. Bar ON = Thermostat tripped.
Present. (Actuator disabled)
Local Stop The actuator motor is protected by
ESD 1 not Open
Unauthorised Close electrical operation thermostats.
Bar OFF = ESD signal present. Selected Interlock
can be prevented by interlocking
Should the motor become overheated
the actuator (Close) control with an
REMOTE MAINTAIN 1 Thermostat Close the thermostats will trip and the
external interlock contact.
Bar OFF = Remote Maintain Tripped Interlock actuator will stop. On cooling the
signal present. If external interlocks are not required thermostat will automatically reset,
Bar ON = Remote Maintain not L ocal Open Local not the interlock function must be selected enabling operation. See the actuator
present and/or Remote Stop not Present Selected OFF. nameplate for the motor rating.
active.

Local Close Remote REMOTE NOT SELECTED LOCAL STOP NOT SELECTED
REMOTE OPEN 2 not not Bar ON = Remote control not selected. Bar ON = Local Stop not selected.
Bar OFF = Remote Open signal Present Selected Bar OFF = Remote control selected. Bar OFF = Local stop selected.
present from BUS option pcb. Help Screen 5
LOCAL CLOSE NOT PRESENT LOCAL NOT SELECTED
REMOTE CLOSE 2 OPEN INTERLOCK Bar ON = Local Close signal not present. Bar ON = Local control not selected.
Bar OFF = Remote Close signal Bar ON = Open Interlock Active. Bar OFF = Local Close signal present. Bar OFF = Local control selected.
present from BUS option pcb. (Actutator disabled)
LOCAL OPEN NOT PRESENT
ESD 2 Unauthorised Open electrical operation Bar ON = Local Open signal not present.
Bar OFF = ESD signal present can be prevented by interlocking Bar OFF = Local Open signal present.
from BUS option pcb. the actuator (Open) control with an
external interlock contact.
REMOTE MAINTAIN 2 If external interlocks are not required
Bar OFF = Remote Maintain the interlock function must be selected
signal present from BUS option OFF.
pcb.
76
AA
H6 Torque Switch Status & IR H7 Travel Limits, Centre
Heading
Setting ToolComms for Column & Remote
Vandal Proof Applications Indication Outputs

H6 H7
TORQUE SWITCH TRIPPED IR OPEN SIGNAL NOT PRESENT
Bar ON = Torque switch tripped. Bar OFF = IR Open signal present.
IR Remote When the actuator generates a value IR CLOSE SIGNAL NOT PRESENT

Control not Open
Selected of torque equal to that set for Open Bar OFF = IR Close signal present. Relay 4 Limit
(when opening) or Close (when closing)
IR Local Local it will stop, protecting itself and the IR LOCAL CONTROL DISABLED

Control Controls Relay 3 Close
Disabled not Fitted
valve from damage. This feature is Bar OFF = IR Local control enabled. Limit
known as Over Torque Protection.
To operate the actuator locally with
IR Closed Once a torque trip has occurred further the IR Setting Tool refer to the option Actuator
Signal not operation IN THE SAME DIRECTION is selection screen [Or] Section 9.14,
Relay 2 Moving
Present prevented.
page 57.
IR Open Torque This latching of the event protects Relay 1
Signal not Switch [Or] must be selected to [On].
Present Tripped the actuator and valve from repeated Help Screen 7
hammering against the obstruction IR REMOTE CONTROL NOT
Help Screen 6 as a response to a maintained control OPEN LIMIT
SELECTED
When actuators are supplied for signal. Bar OFF = IR Remote control Bar ON = Actuator has reached
Vandal Proof applications the local To de-latch the actuator it must be selected (vandal-proof units only). open limit.
control knobs are removed to prevent reversed. When actuator is supplied without local CLOSE LIMIT
unauthorised operation.
(For actuator torque adjustment, refer controls for vandal proof applications Bar ON = Actuator has reached
The local control functions are then to [tC ] and [tO] pages 22 and 23) the option selection screen [Or] must Close limit.
carried out by using the Infra-red be set to [rE] for Remote operation
Setting Tool. (refer to Section 9.14 page 57). ACTUATOR MOVING
Bar ON = Actuator moving.
LOCAL CONTROLS NOT FITTED
Bar OFF = Local controls fitted SWITCH CONTACTS S1, S2, S3, S4
(standard). Bar ON = S contact is close circuit.
Bar ON = Local controls not fitted
(vandal proof). Bar indication is real time and reactive
(refer to Section 9.2 [r1] page 30 for
configuration of Scontacts).
77
AA
H8 Actuator Position
Sensing Devices

H8
When the motor is running, ON and
OFF bit duration should be equal.
For the two sensors, A and B, correct
Position
Sensor A
operation is indicated by the following
truth table.

Position To observe this function, select manual
Sensor B operation and turn the actuator
handwheel clockwise, starting with all
sensors OFF:

CLOCKWISE 30 Deg.
Help Screen 8
Sensor B 0 1 1 0 0
POSITION SENSOR A
Senses output rotation. Used for Sensor A 0 0 1 1 0
the position sensing circuit. Correct
operation of the sensor is indicated by
the bar being ON (and OFF) 12 times
per output revolution. When the motor
is running, ON and OFF bit duration
should be equal.

POSITION SENSOR B
Senses output rotation. Used for
the position sensing circuit. Correct
operation of the sensor is indicated by
the bar being ON (and OFF) 12 times
per output revolution.
78
11.3
AA Heading
IQT Infrared
Diagnostic and Configuration
IQT actuators include an IrDA (Infrared To enable communication with IQ
Data Association) interface as standard, Insight the actuator IrDA interface The use of a notebook PC
allowing non-intrusive diagnostics, must be enabled. or PDA with actuators located in
analysis and configuration. hazardous areas will be subject
The default setting for IQT IrDA is [On], to local regulations. It is the
IQ Insight software tool for PC and IQ enabling IrDA. responsibility of the user to seek
Pocket Insight for PDA (Personal Digital guidance and permission.
To disable IrDA and prevent IrDA access,
Assistant) have been developed to
use the + or key. The display will The Rotork Setting Tool and Setting
enable the actuator configuration and
change to [OF]. Tool Pro are certified Intrinsically
onboard datalogger to be reconfigured
and analysed. A PC running IQ Insight Safe (IS) and therefore can be used
software or PDA running IQ Pocket in defined hazardous areas (refer to
Insight can be used to interrogate the PRESS THE KEY. page 12 and 13).
actuator via non-intrusive infra red IrDA The displayed option will flash (stored)
communication. Visit www.rotork.com indicating it has been set.
for information.
Alternatively, the intrinsically safe
Rotork Setting Tool Pro allows the
user to extract and store IQT actuator
configuration and datalogger files
within the Tool. Stored files can be IrDA Comms
uploaded over an IrDA USB interface Enabled
to a PC running Rotork IQ Insight
where they can be viewed, analysed IQ Insight and IQ Pocket Insight
and stored in a safe, clean environment. software are available free of charge
Using the Setting Tool Pro, actuator set from the Rotork web site,
up can be configured on the PC, stored www.rotork.com.
in the tool, transported to the actuator A kit is available from Rotork, which
and uploaded. The tool can transfer includes an IrDA-USB adapter and
the same configuration to multiple drivers for connection to a PC. The Kit
actuators where actuator setup is the also includes IQ Insight software. PDA
same. Refer to page 70. communication is via the internal IrDA port.
79
11.4
AA Environmental

End user advice on disposal at end of life of the product

Subject Definition Remarks / examples Hazardous Recyclable EU Waste Code Disposal


Batteries Lithium IQ/IQT standby battery Yes Yes 16 06 06 Will require special treatment before
Alkaline Setting tool Yes Yes 16 06 04 disposal, use specialist recyclers or
Lead Acid Battery Failsafe Units Yes Yes 16 06 01 waste disposal companies

Electrical & Printed circuit boards All Products Yes Yes 20 01 35 Use specialist recyclers
Electronic Wire All Products Yes Yes 17 04 10
Equipment

Glass Lens/Window Cenelec Qualified IQ/IQT. A Range Prism No Yes 16 01 20 Use specialist recyclers

Metals Aluminium Gearcases and covers most products No Yes 17 04 02 Use licensed recyclers
Copper/Brass Wire, IQ columns (not all sizes), motor windings No Yes 17 04 01
Zinc IQ clutch Ring and associated components No Yes 17 04 04
Iron/Steel Gears and Gearcases (A Range and larger IQ) No Yes 17 04 05
Mixed Metals IQ motor rotors No Yes 17 04 07

Plastics Glass filled nylon Covers, IQT clutch components, electronics chassis No No 17 02 04 Disposal as general comercial waste
Unfilled Gears No Yes 17 02 03 Use specialist recyclers

Oil Mineral & Kerosene Mixed Gearbox lubrication Yes Yes 13 07 03 Will require special treatment before
Mineral Gearbox lubrication Yes Yes 13 02 04 disposal, use specialist recyclers or
Food Grade Gearbox lubrication Yes Yes 13 02 08 waste disposal companies

Rubber Seals & Orings Cover and shaft sealing Yes No 16 01 99 May require special treatment before
disposal, use specialist waste disposal
companies

In all cases check local authority regulation before disposal.

WARNING: The battery pack contains high capacity lead acid batteries which may have retained their charge. Only persons competent by virtue of
their training or experience should remove these items. For recommended procedures please contact Rotork. (see page 84).
80
AA
12 Heading and Measures
Weights

Oil Actuator Size Nett Weight Oil Capacity


The IQT range are factory filled kg/lbs litres/pt.-US
with 80% Texaco Texamatic 9330
IQT 125 23/51 0.5/1.1
automatic transmission fluid (ATF)
and 20% Kerosene. Equivalent ATF IQT 250 23/51 0.5/1.1
lubricants meeting the Dexron 2 or
Mercon specification may be used. For IQT 500 23/51 0.5/1.1
operating ambient temperatures below IQT 1000 37/82 0.75/1.6
-30C / -22F (Low temperature option
actuators) Texaco 9330 + 80% BP SHF IQT 2000 37/82 0.75/1.6
LT15 should be used.
Food grade lubricating oil is available as
an alternative: contact Rotork.
81
BHD
AA Heading
Binary, Hexadecimal and
Decimal Conversion Table
BINARY HEX DEC BINARY HEX DEC BINARY HEX DEC BINARY HEX DEC BINARY HEX DEC BINARY HEX DEC BINARY HEX DEC BINARY HEX DEC
0000 0000 00 0 0010 0000 20 32 0100 0000 40 64 0110 0000 60 96 1000 0000 80 128 1010 0000 A0 160 1100 0000 C0 192 1110 0000 E0 224
0000 0001 01 1 0010 0001 21 33 0100 0001 41 65 0110 0001 61 97 1000 0001 81 129 1010 0001 A1 161 1100 0001 C1 193 1110 0001 E1 225
0000 0010 02 2 0010 0010 22 34 0100 0010 42 66 0110 0010 62 98 1000 0010 82 130 1010 0010 A2 162 1100 0010 C2 194 1110 0010 E2 226
0000 0011 03 3 0010 0011 23 35 0100 0011 43 67 0110 0011 63 99 1000 0011 83 131 1010 0011 A3 163 1100 0011 C3 195 1110 0011 E3 227
0000 0100 04 4 0010 0100 24 36 0100 0100 44 68 0110 0100 64 100 1000 0100 84 132 1010 0100 A4 164 1100 0100 C4 196 1110 0100 E4 228
0000 0101 05 5 0010 0101 25 37 0100 0101 45 69 0110 0101 65 101 1000 0101 85 133 1010 0101 A5 165 1100 0101 C5 197 1110 0101 E5 229
0000 0110 06 6 0010 0110 26 38 0100 0110 46 70 0110 0110 66 102 1000 0110 86 134 1010 0110 A6 166 1100 0110 C6 198 1110 0110 E6 230
0000 0111 07 7 0010 0111 27 39 0100 0111 47 71 0110 0111 67 103 1000 0111 87 135 1010 0111 A7 167 1100 0111 C7 199 1110 0111 E7 231
0000 1000 08 8 0010 1000 28 40 0100 1000 48 72 0110 1000 68 104 1000 1000 88 136 1010 1000 A8 168 1100 1000 C8 200 1110 1000 E8 232
0000 1001 09 9 0010 1001 29 41 0100 1001 49 73 0110 1001 69 105 1000 1001 89 137 1010 1001 A9 169 1100 1001 C9 201 1110 1001 E9 233
0000 1010 0A 10 0010 1010 2A 42 0100 1010 4A 74 0110 1010 6A 106 1000 1010 8A 138 1010 1010 AA 170 1100 1010 CA 202 1110 1010 EA 234
0000 1011 0B 11 0010 1011 2B 43 0100 1011 4B 75 0110 1011 6B 107 1000 1011 8B 139 1010 1011 AB 171 1100 1011 CB 203 1110 1011 EB 235
0000 1100 0C 12 0010 1100 2C 44 0100 1100 4C 76 0110 1100 6C 108 1000 1100 8C 140 1010 1100 AC 172 1100 1100 CC 204 1110 1100 EC 236
0000 1101 0D 13 0010 1101 2D 45 0100 1101 4D 77 0110 1101 6D 109 1000 1101 8D 141 1010 1101 AD 173 1100 1101 CD 205 1110 1101 ED 237
0000 1110 0E 14 0010 1110 2E 46 0100 1110 4E 78 0110 1110 6E 110 1000 1110 8E 142 1010 1110 AE 174 1100 1110 CE 206 1110 1110 EE 238
0000 1111 0F 15 0010 1111 2F 47 0100 1111 4F 79 0110 1111 6F 111 1000 1111 8F 143 1010 1111 AF 175 1100 1111 CF 207 1110 1111 EF 239
0001 0000 10 16 0011 0000 30 48 0101 0000 50 80 0111 0000 70 112 1001 0000 90 144 1011 0000 B0 176 1101 0000 D0 208 1111 0000 F0 240
0001 0001 11 17 0011 0001 31 49 0101 0001 51 81 0111 0001 71 113 1001 0001 91 145 1011 0001 B1 177 1101 0001 D1 209 1111 0001 F1 241
0001 0010 12 18 0011 0010 32 50 0101 0010 52 82 0111 0010 72 114 1001 0010 92 146 1011 0010 B2 178 1101 0010 D2 210 1111 0010 F2 242
0001 0011 13 19 0011 0011 33 51 0101 0011 53 83 0111 0011 73 115 1001 0011 93 147 1011 0011 B3 179 1101 0011 D3 211 1111 0011 F3 243
0001 0100 14 20 0011 0100 34 52 0101 0100 54 84 0111 0100 74 116 1001 0100 94 148 1011 0100 B4 180 1101 0100 D4 212 1111 0100 F4 244
0001 0101 15 21 0011 0101 35 53 0101 0101 55 85 0111 0101 75 117 1001 0101 95 149 1011 0101 B5 181 1101 0101 D5 213 1111 0101 F5 245
0001 0110 16 22 0011 0110 36 54 0101 0110 56 86 0111 0110 76 118 1001 0110 96 150 1011 0110 B6 182 1101 0110 D6 214 1111 0110 F6 246
0001 0111 17 23 0011 0111 37 55 0101 0111 57 87 0111 0111 77 119 1001 0111 97 151 1011 0111 B7 183 1101 0111 D7 215 1111 0111 F7 247
0001 1000 18 24 0011 1000 38 56 0101 1000 58 88 0111 1000 78 120 1001 1000 98 152 1011 1000 B8 184 1101 1000 D8 216 1111 1000 F8 248
0001 1001 19 25 0011 1001 39 57 0101 1001 59 89 0111 1001 79 121 1001 1001 99 153 1011 1001 B9 185 1101 1001 D9 217 1111 1001 F9 249
0001 1010 1A 26 0011 1010 3A 58 0101 1010 5A 90 0111 1010 7A 122 1001 1010 9A 154 1011 1010 BA 186 1101 1010 DA 218 1111 1010 FA 250
0001 1011 1B 27 0011 1011 3B 59 0101 1011 5B 91 0111 1011 7B 123 1001 1011 9B 155 1011 1011 BB 187 1101 1011 DB 219 1111 1011 FB 251
0001 1100 1C 28 0011 1100 3C 60 0101 1100 5C 92 0111 1100 7C 124 1001 1100 9C 156 1011 1100 BC 188 1101 1100 DC 220 1111 1100 FC 252
0001 1101 1D 29 0011 1101 3D 61 0101 1101 5D 93 0111 1101 7D 125 1001 1101 9D 157 1011 1101 BD 189 1101 1101 DD 221 1111 1101 FD 253
0001 1110 1E 30 0011 1110 3E 62 0101 1110 5E 94 0111 1110 7E 126 1001 1110 9E 158 1011 1110 BE 190 1101 1110 DE 222 1111 1110 FE 254
0001 1111 1F 31 0011 1111 3F 63 0101 1111 5F 95 0111 1111 7F 127 1001 1111 9F 159 1011 1111 BF 191 1101 1111 DF 223 1111 1111 FF 255
82
133
AA IQT Approvals
Heading

Refer to actuator nameplate for unit specific approval details USA hazardous Area
FM. Class 1, Division 1, Groups C, D, E, F, G hazardous areas.
European Hazardous area
Factory Mutual - Explosionproof to NEC Article 500.
ATEX (94/9/EC) II 2 GD c Temperature -30C to +60C (-22F to +140F).
Ex d IIB T4 Gb, Ex tb IIIC T120C Db IP68 *Option -40C to +60C (-40F to +40F).
Temperature -20 to +70C (-4 to +158F)
*Alternative for Group B hazardous area. Temperatures as for Groups C and D.
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F),
*Option -50 to +40C (-58 to +104F) Canada hazardous Area
CSA EP. Class 1, Division 1, Groups C and D hazardous areas.
Ex d IIC T4 Gb, Ex tb IIIC T120C Db IP68
Canadian Standard Association - Explosionproof
Temperature -20 to +70C (-4 to +158F)
Temperature -30C to +70C -22F to +158F).
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F),
*Option -50C to +40C (-58F to +104F).
*Option -50 to +40C (-58 to +104F)
*Alternative for Group B hazardous area. Temperatures as for Groups C and D.
Ex de IIB T4 Gb, Ex tb IIIC T120C Db IP68
Temperature -20 to +70C (-4 to +158F) International Non hazardous
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), WT: Standard watertight, BS EN 60529 :1992, IP68, 7 metres/72 hours.
Temperature -30C to +70C (-22F to +158F).
*Option -50 to +40C (-58 to +104F)
*Option -40C to +70C (-40F to +158F).
Ex de IIC T4 Gb, Ex tb IIIC T120C Db IP68 *Option -50C to +40C (-58F to +104F).
Temperature -20 to +70C (-4 to +158F)
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), US Non hazardous
*Option -50 to +40C (-58 to +104F) NEMA 4, 4X and 6.
Temperature -30C to +70C (-22F to +158F).
International Hazardous area *Option -40C to +70C (-40F to +158F).
IEC. Exd IIB T4 *Option -50C to +40C (-58F to +104F).
IEC60079-0 and IEC60079-1 for Exd IIB T4
Temperature -20 to +70C (-4 to +158F) Canada Non hazardous
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), CSA WT: Canadian Standard Association Watertight.
*Option -50 to +40C (-58 to +104F) Wiring and components complying with CSA Enclosure 4 and 4X.
Temperature -30C to +70C (-22F to +158F).
IEC. Exd IIC T4 *Option -40C to +70C (-40F to +158F).
IEC60079-0 and IEC60079-1 for Exd IIC T4
*Option -50C to +40C (-58F to +104F).
Temperature -20 to +70C (-4 to +158F)
*Option -30 to +70C (-22 to +158F), *Option -40 to +70C (-40 to +158F), Rotork can supply actuators to national standards not listed above.
*Option -50 to +40C (-58 to +104F) For details please contact Rotork.
83
13 IQT Approvals cont.

Refer to actuator nameplate for supply voltage and wiring diagram for
applicable transformer type.
In order to maintain hazardous area certification only the fuses listed
below may be used:

All Transformer types Transformer Type 2 Transformer Type 4


Fuse FS3 - ATO 20A Fast acting Fuse FS1 - Bussman TDC11, 150mA, Antisurge 1.5" Fuse FS1 - Bussman TDC11, 50mA, Antisurge 1.5"
Fuse FS2 - Siba 70-065-65, 500V, 2.5A, Antisurge, 1.5" Fuse FS2 - Siba 70-065-63, 500V, 1.6A, Antisurge, 1.5"
Transformer Type 1
Fuse FS1 - Bussman TDC11, 250mA, Antisurge 1.5" Transformer Type 3 ATEX actuators only
Fuse FS2 - Siba 70-065-65, 500V, 5A, Antisurge, 1.5" Fuse FS1 - Bussman TDC11, 100mA, Antisurge 1.5" FS4 Bussman TDS (100mA - quick blow) or
Fuse FS2 - Siba 70-065-65, 500V, 1.5A, Antisurge, 1.5" Littel Fuse 217 (100mA quick blow)

Conditions of Safe Use


The following are the maximum constructional flamepath gaps for ATEX and IECEx Approved actuators.

IQT MAXIMUM FLAMEPATH GAPS


Flamepath Max. Gap (mm) Min Length (mm) Actuator Type and Size
Terminal Cover/Gearcase 0.15 26.7 All Types and Sizes
Terminal Bung Gearcase (IIB) 0.20 25.9 All Types and Sizes
Terminal Bung Gearcase (IIC) 0.115 25.9 All Types and Sizes
Electrical Cover/Gearcase 0.15 26.2 All Types and Sizes
Motor Cover/Gearcase 0.15 25.6 All Types and Sizes
Motor Shaft/Motor Shaft Shroud 0.24 25.2 All Types and Sizes
Motor Shaft Shroud/Gearcase -0.05/0.00 25.0 All Types and Sizes
Encoder Shaft/encoder Shaft Shroud 0.24 25.2 All Types and Sizes
Encoder Shaft Shroud/Gearcase -0.05/0.00 25.0 All Types and Sizes

Note Negative Sign denotes an interference fit.
The actuator must only be located where the risk of impact upon the window is low.
84
Appendix A

EL Partial Stroke Limit EP Partial Stroke Position Et Partial Stroke Timeout

The end of travel limit from which the A position can be set between 1% The timeout function allows a
partial stroke test will start and end and 97% to give a set point within the reasonable amount of time to be set
must be set. travel to which the partial stroke runs. for the partial stroke to complete one
cycle. An alarm can be set to activate if
The default limit for partial stroke is To set the partial stroke position, Press
the stroke hasnt been completed in the
Open limit, under test the actuator will the + or - key to scroll between 1%
set time. Refer to Section 9.2 (indication
automatically move closed from the and 97%. A minimum 3% Stroke is
contacts). The Partial Stroke timeout
open limit to the set position and then required from open limit to allow the
must be set to a value greater than that
return to the open limit position. actuator to perform the partial stroke
required to complete the Partial Stroke
adequately.
To set the closed limit for partial stroke under normal operating conditions.
[EL], Press the + or - key to change PRESS THE KEY. To set the partial stroke timeout, press
from Open [EL OP] to Closed [EL CL].
the + or - key to scroll up or down in
PRESS THE KEY. 10 second intervals.
Set the required time and PRESS THE
KEY.
Partial Stroke
Pos: 75%

Partial Stroke The display option will flash [Stored]


Limit: Open indicating it has been set.
P.Stroke Timeout
300 seconds
The display option will flash [Stored]
indicating it has been set.
The display option will flash [Stored]
indicating it has been set.
85
Rotork Sales and Service

If your Rotork actuator has been


correctly installed and sealed, it will give
years of trouble-free service.
Should you require technical assistance
or spares, Rotork guarantees the best
service in the world. Contact your local
Rotork representative or the factory
direct at the address on the nameplate,
quoting the actuator type and serial
number.
A full listing of our worldwide sales
and service network is available on our
website at www.rotork.com

Head Office Local representative:


Rotork Controls Limited
Brassmill Lane
Bath
BA1 3JQ
tel +44 (0)1225 733200
fax +44 (0)1225 333467
email mail@rotork.com
86
Notes
87
Notes
Published and produced in the U.K. by Rotork Controls Ltd.
ATTENTION: RED PLASTIC PLUGS IN CONDUIT ENTRIES ARE FOR TRANSIT ONLY.
FOR LONG TERM PROTECTION FIT SUITABLE METAL PLUGS.

ATTENZIONE: I TAPPI IN PLASTICA ROSSA PER L'ENTRATA CAVI SONO SOLO


TEMPORANEI. PER UNA PROTEZIONE PERMANENTE PREGO SOSTITUIRLI CON
APPOSITI TAPPI METALLICI.

ATENCION: LOS TAPONES ROJOS DE PLASTICO EN LAS ENTRADAS DE CABLE


SON UNICAMENTE PARA TRANSPORTE. PARA PROTECCION PERMANENTE
COLOCAR TAPONES METALICOS APROPIADOS.

ACHTUNG: DIE ROTEN PLASTIKSTOPFEN SIND NUR FR DEN TRANSPORT


GEEIGNET. FR DAVERHAFTEN SCHUTZ SIND DIESE GEGEN GEEIGNETE
BLINDSTOPFEN AUSZTAUSCHEN.

ATTENTION: LES BOUCHONS PLASTIQUES ASSURENT UNE PROTECTION


TEMPORAIRE. POUR UNE PROTECTION DEFINITIVE UTILISER DES BOUCHONS
METALLIQUES.

Formerly E175-3E. As we are continually


developing our products, the design of Rotork
actuators is subject to change without notice.
The latest product and technical information is
available at our website: www.rotork.com.

The name Rotork is a registered trade mark.


Rotork recognises all registered trade marks.

POWTG0813

Potrebbero piacerti anche