General Description

Thank you very much for your special patronage of LG products.

A high-grade, high-quality, advanced individual air-conditioning system that is able to respond to expanding,
more sophisticated housing environment needs.

Large size indoor units are required for coping with the large space like the condominiums or the big houses
where systems are used at present. Besides, there are needs to provide the room air conditioners
owing to the sophisticated interior and small rooms.

On the background of these needs, the new multi outdoor unit, which can connect both the residential indoor
units and the light commercial indoor units, has been developed.

LG Electronics Inc., has developed "MPS(Multi Power System) Variable Multi" system that can efficiently
control air-conditioning ensuring a better environment.

A lot of information regarding the design and the installation of "MPS Variable Multi" system is included in this
publication.

We hope that with this information you would become an expert of the "MPS Variable Multi" system and be
more comprehensive to the system.

LG Electronics Inc.
Air Conditioning Division

2004 Product Data 1


2 MPS(Multi Power System) Variable Multi
LG Airconditioners Product Data

TABLE OF CONTENTS
Table of contents Page

Part 1 General Information............................................................................5


1. Model Names ...................................................................................................................6
2. Model Number Nomenclature . ........................................................................................7
3. Outline of System ............................................................................................................8
4. Features ........................................................................................................................13
5. Control System ..............................................................................................................24

Part 2 Indoor Units ......................................................................................27


1. Wall Mounted ................................................................................................................28
2. Ceiling Cassette 4-way...................................................................................................45
3. Ceiling Concealed Duct - High Static Pressure..............................................................62
4. Ceiling Concealed Duct - Low Static Pressure ..............................................................79

Part 3 Outdoor Units ...................................................................................93

Part 4 Control .............................................................................................137


1. Basic Control Devices and Function ............................................................................138
2. Central Control .............................................................................................................140

Part 5 Installation.......................................................................................155
1. Refrigerant piping System ...........................................................................................156
2. Electrical Wiring ..........................................................................................................171
3. Drain Pipe Work ..........................................................................................................175

2004 Product Data 3


4 MPS(Multi Power System) Variable Multi
Part 1
General Information

1. Models Name .............................................................................................6


1.1 Indoor Units ..............................................................................................................6
1.2 Outdoor Units............................................................................................................6
2. Model Number Nomenclature...................................................................7
2.1 Indoor Unit ................................................................................................................7
2.2 Outdoor Unit .............................................................................................................7
3. Outline of System ......................................................................................8
3.1 Example of System...................................................................................................8
3.2 Connectability Matrix for Indoor and Outdoor units ................................................11
3.3 External Apperance ................................................................................................12
4. Features....................................................................................................13
4.1 Outdoor Units..........................................................................................................13
4.2 BD Units..................................................................................................................17
4.3 Indoor Units ............................................................................................................18
5. Control System ........................................................................................24
5.1 Various Central Control...........................................................................................24
5.2 Control Device ........................................................................................................25

2004 Product Data 5


1. Models Name

1.1 Indoor Units


Model Name
Capacity, kW(Btu/h)
Category Chasiss
3.5 5.3 7.0 8.8 10.6 14.1
(12000) (18000) (24000) (30000) (36000) (48000)
LMNH/C
SR - - - - -
Wall 126LRL0
General LMNH/C LMNH/C
Mounted - - - -
ST 186LTL0 246LTL0
LMNH/C LMNH/C
TE - - - -
126TEC0 186TEC0
Ceiling LMNH/C LMNH/C
4Way TF - - - -
Cassette 246TFC0 306TFC0
- - - - LMNH/C LMNH/C
TD 366TDC0 486TDC0
LMNH/C LMNH/C
BH - - - -
186BHA0 246BHA0
High LMNH/C LMNH/C
Ceiling BG - - - -
Static 306BGA0 366BGA0
Concealed
Duct LMNH/C
BE - - - - -
486BEA0
Low LMNH/C LMNH/C
BT - - - -
Static 126BTG0 186BTG0

1.2 Outdoor Units


MPS Variable Multi Cooling Only Heat Pump
Model Name L4UC608FA0 L5UC728FA0 L8UC1008FA0 L8UH1008FA0
Cooling Btu/h 60000 72000 100000 100000
Rated Capacity
Heating Btu/h - - - 100000
Number of Indoor Units to be Connected Max.4 Units Max.5 Units Max.8 Units Max.8 Units
Total Capacity of Indoor
Btu/h 12,000~60,000 12,000~78,000 12,000~108,000 12,000~108,000
Units Connected
Power Supply 3, 380-415V, 50Hz

BD(Branch Distributon) Unit PMBD5420L PMBD5430L PMBD5440L


Number of Indoor Units to be Connected Max. 2 Units Max. 3 Units Max. 4 Units
Combination (Min. ~Max.) 12,000~54,000 Btu/h
Capacity of Connectable kW 3.5/5.3/7.0/8.8/10.6
Indoor units Btu/h 12k/18k/24k/30k/36k

6 MPS(Multi Power System) Variable Multi


2. Model Number Nomenclature

2.1 Indoor Unit


LMN H 12 6 L R L 0

Serial Number
Function
A : Basic, L : Nano Plasma (Wall Mounted)
C: Plasma(Ceiling Cassette) G: Low Static
ART COOL(Mirror) Type Front Panel Color
B: Blue, D: Wood, M: Metal, R: Mirror, W: White

Chassis Name

Indoor Unit Type


L : Wall Mounted T : Ceiling Cassette A : ART COOL
B : Ceiling Concealed Duct D : ART COOL Mirror

Electrical Rating
6 : 1, 220-240V, 50Hz

Nominal Cooling Capacity in Btu/h


Ex) 12,000 Btu/h '12', 48,000 Btu/h '48'
Model Type
H : Heat Pump C : Cooling Only

MPS Variable Multi System Indoor Unit


2.2 Outdoor Unit

L8U H 100 8 F A 0

Serial Number

Function
A : Basic

Multi Type
F : Free Joint Multi Type

Electrical Ratings
8 : 3, 380-415V, 50Hz

Nominal Cooling Capacity in Btu/h


Ex) 100,000 Btu/h '100'

Model Type
H : Heat Pump
C : Cooling Only

R22 MPS Variable Multi System Outdoor Unit.


And No. of Connectable Indoor Units
Ex) L8U : Connectable max. 8 Indoor Units

2004 Product Data 7


3. Outline of System

Unlike traditional multi-type units, it is a next-generation multi type air-conditioner designed to be installed
under any circumstrance, combining with wall-mounted, ceiling-mounted units.

3.1 Example of System


L4UC608FA0 Multi System
Circuit 1 can be connected up to max. 3 indoor units. When installing single 36,000 Btu/h indoor unit for
circuit 1, use the short tube connector(Not branch distributor unit).
Circuit 2 can be only connected up single 24,000 Btu/h indoor unit.

Case 1 [Indoor Unit]

BD(Branch Distributor) Unit [12,000 Btu/h]

[12,000 Btu/h]

[Outdoor Unit] [12,000 Btu/h]


Circuit 1

[24,000 Btu/h]

Circuit 2

Case 2
[Indoor Unit]

Short tube connector


(Accessory)
[36,000 Btu/h]

Circuit 1
[Outdoor Unit]

[24,000 Btu/h]

Circuit 2

8 MPS(Multi Power System) Variable Multi


3. Outline of System

L5UC728FA0 Multi System


Circuit 1 can be connected up to max. 4 indoor units. When installing single 48,000 Btu/h indoor unit for circuit 1,
use the short tube connector(Not branch distributor unit).
Circuit 2 can be only connected up single 24,000 Btu/h indoor unit.

Case 1 [Indoor Unit]

[12,000 Btu/h]
BD(Branch Distributor) Unit

[12,000 Btu/h]

[12,000 Btu/h]

[Outdoor Unit]
[12,000 Btu/h]
Circuit 1

[24,000 Btu/h]

Circuit 2

Case 2
[Indoor Unit]

Short tube connector


(Accessory)
[48,000 Btu/h]

[Outdoor Unit]

Circuit 1

[24,000 Btu/h]

Circuit 2

2004 Product Data 9


3. Outline of System

L8UC/H1008FA0 Multi System


Both circuit 1 and circuit 2 can be connected up to max. 4 indoor units. When installing single 48,000 Btu/h
indoor unit for each circuit, use the short tube connector(Not branch distributor unit).

[Indoor Unit]
Case 1

[48,000 Btu/h]
Short tube connector
(Accessory) Circuit 1

[Outdoor Unit]

[48,000 Btu/h]

Circuit 2

Case 2 [Indoor Unit]

[12,000 Btu/h]
BD(Branch Distributor) Unit

[12,000 Btu/h]

[12,000 Btu/h]

[12,000 Btu/h]
Circuit 1

[12,000 Btu/h]
[Outdoor Unit]

[12,000 Btu/h]

[12,000 Btu/h]

Circuit 2
[12,000 Btu/h]

10 MPS(Multi Power System) Variable Multi


3. Outline of System
3.2 Connectability Matrix for Indoor and Outdoor units
Outdoor Units
Indoor Units
L4UC608FA0 L5UC728FA0 L8UC1008FA0 L8UH1008FA0
Capacity Number of connectible Indoor Units
Model Type
Index Btu/h kW up to 4 up to 5 up to 8 up to 8
12 12000 3.5 O O O O
Wall Mounted 18 18000 5.3 O O O O
24 24000 7.0 O O O O
12 12000 3.5 - - O O
18 18000 5.3 - - O O
Ceiling 24 24000 7.0 - - O O
4 Way
Cassette 30 30000 8.8 - - O O
36 36000 10.6 - - O O
48 48000 14.1 - - O O
18 18000 5.3 O O O O
24 24000 7.0 O O O O
High
Ceiling Static 30 30000 8.8 - O O O
Concealed 36 36000 10.6 O O O O
Duct 48 48000 14.1 - O O O
Low 12 12000 3.5 - - O O
Static 18 18000 5.3 - - O O

Note :
1. See the chapter 3 combination table of "Part 3 Outdoor Units" for possible combinations of indoor units.
2. The total capacity index of indoor units is the sum of capacity index of each units and should be within the
maximum capacity index of the outdoor unit.

2004 Product Data 11


3. Outline of System

3.3 External Apperance


3.3.1 Outdoor Units

BD Unit (Branch Distributor Unit)


-Accessory

L4UC608FA0 L5UC728FA0 L8UC1008FA0 PMBD5420L


L8UH1008FA0 PMBD5430L
PMBD5440L

3.3.2 Indoor Units

Wall Mounted Ceiling Mounted Cassette 4 way

LMNH/C126LRL0 LMNH/C126TEC0
LMNH/C186TEC0
LMNH/C186LTL0
LMNH/C246TFC0
LMNH/C246LTL0 LMNH/C306TFC0
LMNH/C366TDC0
LMNH/C486TDC0

Ceiling Concealed Duct High Static Ceiling Concealed Duct - Low Static

LMNH/C186BHA0 LMNH/C126BTG0
LMNH/C246BHA0 LMNH/C186BTG0
LMNH/C306BGA0
LMNH/C366BGA0
LMNH/C486BEA0

12 MPS(Multi Power System) Variable Multi


4. Features

4.1 Outdoor Unit


MPS Variable System
- High Efficiency
- Low Noise
- High Reliability
Can be Combined with Various Indoor Units
Max. Total 120 meters Piping Length(100k model)
Available to Max.8 Indoor Units by Simple Piping
Powerful Cooling & Heating Capacity
Low Operation Sound
Central Control
Easy Installation
L4UC608FA0 L5UC728FA0 L8UC1008FA0
L8UH1008FA0 Low Electric Fee

MPS(Multi Power System) Variable Control :


Big Energy Saving with MPS Control

Basic Principle of MPS Control


MPS control provides comfortable and convenient environment as there are two compressors with 60&40%
load sharing with on compressor of small capacity always working to maintain the set temperature conditions
& meanwhile other compressor is at rest if the load is low whereas in conventional system the only
compressor is working with ON/OFF cycles.
Conventional (On/Off Operation) MPS Control

100% 40% 60%

Power Consumption Comparison


MPS Variable Multi system opeates in one cycle with two compressors.
Only one compressor or two compressors run together, according to the load conditions.
With small load. only one compressor completes the cycle. It saves power consumption at low operation.
This concept is explained in the picture below.
Conventional (On/Off Operation) MPS

100% 100%
100%
Cooling Capacity

Cooling Capacity

Power Loss Zone Saving Zone


Cooling Cooling
Load Max. 60% Load

35%
Energy Saving
40%

Operating Ratio Operating Ratio

2004 Product Data 13


4. Features

Various Multi Connecting : (100k size shown)


Both 1Room Type and Distributor Type
2Room Type Distributor Type

Flexible Design and Simple Piping


For 2 Indoor For 3 Indoor For 4 Indoor
- Distributor Type Units Units Units

Various BD unit for flexible design


Available up to max.8 indoor units by simple piping
Connecting to the BD unit without Brazing

Indoor unit tubing Flare nut Pipes

Open-end wrench (fixed)

Flare nut

Wrench Connection pipe

Indoor unit tubing

Central Control :
Centralized Controller Deluxe Central Controller
First, We have a simple central controller that can And especially, with an intuitively designed GUI and a
operate up to 16 units simultaneously. user-friendly touch panel, you can simultaneously
control up to 256 indoor units, and the system can be
linked to the building management system.
- Indoor unit max 256
CNU
- 8.0 TFT LCD (800*600)
- Touch screen panel
- Available Ethernet
protocol
- Time schedule function
PC Based Controller - Error display and lock function
- Length max 1km
And especially, with an intuitively designed GUI and a
user-friendly touch panel, you can simultaneously
control up to 256 indoor units, and the system can be
linked to the building management system.

IP I-Gateway

14 MPS(Multi Power System) Variable Multi


4. Features

Long and High Elevation Piping(100k Btu/h models shown)


It's an MPS Variable multi system with simple connecting refrigerant pipe, which is composed of one
outdoor unit and some indoor units in series, so it saves energy greatly and makes the installation easy.
( Refer to "Part 5 Installation" for other models)

Direct Piping
[Outdoor Unit]

Installation of the outdoor unit


in an upper position

A [Indoor Unit]

B 30m

Piping length : 50m( A ), 50m( B )


Total system piping length : 100m(50+50)

[Indoor Unit]

Installation of the outdoor unit


in a lower position B

[Outdoor Unit]
30m

2004 Product Data 15


4. Features

Distributor Piping
[Outdoor Unit]

Installation of the outdoor unit


in an upper position

A BD Unit [Indoor Unit]


L1

L2

B L3

BD Unit 30m
L4

L5

L6

Total main piping length : 30m( A ), 30m( B )


Total branch piping length : 30m(L1+L2+ L3), 30m(L4 +L5+ L6)
Each branch piping length : 15m(L1,L2,L3,L4 ,L5,L6)
Total system piping length : 60m(30+30), 60m(30+30)

[Indoor Unit]

BD Unit

Installation of the outdoor unit


in a lower position

[Outdoor Unit]
BD Unit 30m

16 MPS(Multi Power System) Variable Multi


4. Features

4.2 BD Unit
Branch Distributor Unit - For Distributor piping
- Unit for Variable Refrigerant Volume System

Compact Size
Various models
Quiet Operation
(reduced refrigerant running noise of indoor unit)
Flare Connection - No Brazing
No need of drainage
PMBD5420L(For 2 indoor units)
Installation Pattern
PMBD5430L(For 3 indoor units)
PMBD5440L(For 4 indoor units)

Installation Pattern
Ceiling-suspended type Wall-mounted type

Screws(M5)
ws(M5)
(locally procude)

Connection of Piping(Flare Work)


- No Brazing & Easy Installation
While connecting indoor units, make sure to connect
refrigerant pipes and connection wires to the
appropriate connection ports maked with matching Indoor unit tubing Flare nut Pipes
alphabets. (A, B, C, D)
NOTICE : Be sure to mark all the local refrigerant
piping(liquid pipes, gas pipes, etc.) for Open-end wrench (fixed)
each indoor unit designating clearly which
room it belongs in.(A, B, C, D) Flare nut

A B C D Wrench Connection pipe

Indoor unit tubing

E F G H
[PMBD5440L]

2004 Product Data 17


4. Features

4.3 Indoor Unit


Wall Mounted Type
Innovative Quiet Operation
CHAOS Swing
JET Cool
Healthy Dehumidification
Triple Deodorizing Filter
Nano Plasma Air Purifying System
Auto Restart
Wireless Remote Control

Innovative Quiet Operation


To provide a comfortable, pleasant and well
balanced environment, LG air conditioners utilize a
streamlined air fan and a unique design which create
smooth air flow from the air conditioner so that it
operates under the lowest noise level. The cross flow
fan, stabilizer, and rear guide which are the causes
of noise, have been redesigned by hydraulic
engineering. The number of revolutions have been
decreased or increased while the amount of friction
has been decreased providing the most quiet air
conditioners in the world.

CHAOS Swing
The most pleasant air flow for the human body can
be found within nature. Countless data and
verification resulted in the application of the new Up Speed :Slow
CHAOS theory to LG Air conditioners. Down Speed :Fast
Wind-up effect is controlled by vane angle and speed
to evenly distribute nature-like air throughout the
room. This function analyzes the characteristic of air
flow distribution and creates the pleasant feeling of Angle of vane
natural wind. movement

JET Cool
Jet Cooling function is for quick cooling. In this mode, Normal Jet Cool
strong and cool air is blown at high speeds for 30
3.8 M 5.8 M
minutes until the room temperature reaches to 18C.

18 MPS(Multi Power System) Variable Multi


4. Features

Healthy Dehumidification
The hot and humid air has a tendency to rise by convection.
Healthy Dehumidification optimizes this algorithm to keep an
optimum humidity without feeling cold in indoor place.

Composition of Triple Deodorizing Filter


Triple Deodorizing Filter
- Triple Deodorizing Filter is adopted for absorbing
VOC Ingredient, Structural material ingredient, Common
Odor
- Deodorizing efficiency
: 10% up compared to normal Deodorization Filter Nasty smell Formaldehyde V.O.C.
Deodorizing Deodorizing Deodorizing

Dust
electrode
Dust particles discharge
Pre-filter Ionizer Dusts Collection

+
+6.5KV +
Air Purifying System Polluted
Air
discharge
+ Purified
fresh Air
+
- It not only removes microscopic contaminants & dust, but it +
also removes house mites, pollen, and pet fur to help Odour
Generating dusts aluminum coated
plasma Odor molecule electrode(-)
prevent allergic diseases like asthma.It provides odor free, (3.25KV discharge)

dust free and allergy free air.


(ppm)
500
Normal Filter
400 + + + +

300 + + + +

Effect of carbon Nano Ball 200 + + + +

Deodorizing efficieny: 8~10times compared to conventional 100 + + + +


carbon filter. Nano Filter
0 30 60 90(Min)

What is Carbon Nano Ball?


Nano(1/1 Bil) ball structure, (200~500nm) consisted of
carbon, is adopted as deodorizing material at first in the
world.

2004 Product Data 19


4. Features

Ceiling Cassette 4 way

Compact Design and Easy Installation


Low noise
Hygienic and Easy-to-Clean Filter
2-Thermistor; Unit Body and Remote Control
Jet Cool
Plasma Air Purifying System
High Head Drain Pump(700mm)
High-Ceiling Corresponding Operation
LCD Wired Remote Control
Wireless Remote Control(Accessory:LCD/Button)
Group Control

Group Control
1 2 16
1) Operation Summary
- Where several products are linked, one specific control
device can control a specific number of products.
Remote
2) Specific Operation Controller

- Connecting line is linked to each of the indoor equipments


for communication. A specific control device is connected
to each of them and this control device can control the
same function.
- Group control function is enabled by cutting an optional
jump wire in the wired remote control. At this time, the
main system will not respond in order to prevent data
collision.
- While executing group control command, use the random
data (0-3minutes) in the main body of indoor equipment for
limiting starting current.
- Control device can control up to 16 indoor equipments.

Low Noise
The most advanced low-noise design.
The adoption of turbo-fan and round type heat exchanger
provides the quietest operation.

Hygienic and Easy-to-Clean Filter


Washable and anti bacteria filter is adopted.
It is easy to open grille and replace clean filter.

20 MPS(Multi Power System) Variable Multi


4. Features

Plasma Air Purifying System


The PLASMA Air Purifying Function not only removes
microscopic contaminants and dust, but also removes
house mites, pollen, and pet fur helps to prevent
allergic diseases like asthma.
Dust electrode discharge
Dust particles
Ionizer Photo-Catalyst Coated Mesh
+4.8KV discharge +
+
Polluted Air + Purified fresh Air
+

Generating plasma
Odour
Odour molecule

High Head Drain Pump(700mm)


Built-in Drain Pump drains out water automatically.
A standard drain-head height of up to 700 mm is possible, creating the ideal solution for perfect water drainage.

Pipe fixture

Slope 1/50~1/100
Maximum 700mm

Flexible drain hose


Hard Tube(ex.PVC)
Drain Pump

Drain Pan Ceiling Board

High-Ceiling Corresponding Operation


According to the height of the installation, it provides
variability of indoor fan motor rpm. If the height of
installation is low then you can adjust low rpm of
indoor fan motor. On the other hand if the height of
the installation is high you can adjust high rpm of
indoor fan motor. Selection of speed can be done by
slide switch at the back of the LCD wired remote.

2004 Product Data 21


4. Features

Ceiling Concealed Duct High Static Pressure


Compact Design and Easy Installation
(Phase Control Motor)
2-Thermistor Control; Unit Body & Remote Control
LCD Wired Remote Control
Wireless Remote Control(Accessory)
Plasma Air Purifying Kit(Accessory)
High Head Drain Pump(Accessory:700mm)
Zone Control(Accessory)
Electric Heater(Accessory)

Ceiling Concealed Duct Low Static Pressure

Compact and Light design and Easy Installation


(Phase Control Motor)
2-Thermistor Control; Unit Body & Remote Control
LCD Wired Remote Control
Wireless Remote Control(Accessory)
High Head Drain Pump(Accessory)

Easy Installation
Flexible Duct is easy to install, regardless of room Canvas Indoor Unit
Ceiling
size or heater position. Duct

It can be installed even in a limited space and saves Intake


Discharge
Flexible Duct
construction cost with slim thickness Duct

Air Discharge
Air Intake Ceiling Port
Port Board Ceiling Board
Inspection
Port

Innovative Design of Fan and Housing System


Low Noise ! Easy Serviceability!
Plastic Fan and Housing Assembly
- Designed for low noise
- Designed to reduce weight
- Designed for easy service

This product guarantees lower sound level and gives


lesser service expenses.

22 MPS(Multi Power System) Variable Multi


4. Features

LGs High Technology provide Easy and Low cost Design


of Duct work
Generally, when External Static Pressure increases
air volume decreases. But by controlling the phase of
motor while installing the product E.S.P. is controlled
from 8~10 mmAq linearly. E.S.P. control provides
required constant air volume irrespective of ESP
change. Desired ESP can also be set through LCD
wired remote control. Setting of the desired ESP
gives required combination of ESP and airflow.

Plasma Air Purifying Kit (Accessory)


The PLASMA Air Purifying Function not only removes
microscopic contaminants and dust, but also removes
house mites, pollen, and pet fur helps to prevent
allergic diseases like asthma.

High Head Drain


Pump(Accessory:700mm)
In some of the places natural drainage is not
possible. For such places drain pump is very useful. It
removes condensed water from the unit.

Zone Control(Accessory)
It controls the temperature of each zone. Opening or
closing of the damper is controlled by sensing the
temperature of each zone. In the cooling mode, if the
temperature of a particular zone is lower than set
temperature then the damper is closed. On the other
hand if the temperature of a particular zone is higher
than the set temperature, damper is opened to
provide cooling to the zone and vice versa in the
heating mode.

2004 Product Data 23


5. Control System

5.1 Various central control


Unit name Image Function Remarks
Control & Monitoring of 16 PQCSA101S0
Simple Indoor Units. : 16 indoor units,
It is possible to use max. 128 Simple central control,
Central IEEE 485 transmission
indoor units by connecting 8
Control Simple Centrol Controller.
Basic Model No.:
PQCSA101S0

Control & Monitoring of 256 PQCSW501A0


Central control

Deluxe Indoor Units. : Control / Monitoring


Schedule funcion(Option)
Central PQCSW502A0
Control : Control / Monitoring
/ Schedule
Basic Model No.:
PQCSW501A0

Control & Monitoring of 256 PQCSS501A0


PC Indoor Units. : Control / Monitoring
Schedule funcion(Option)
Central PQCSS502A0
Control : Control / Monitoring
Software / Schedule
Basic Model No.:
PQCSS501A0

Gate-Way for Deluxe/PC


Centrol Controller
CNU1) It is possible to use max.
16 outdoor units.
Interface Device

Basic Model No.:


PQNFG00A0

Gate-Way for Simple/Deluxe/PC


Centrol Controller
It is used 1 unit per I outdoor unit.
PI4852)
Basic Model No.:
PMNFP00A0

1) CNU: Central contral Network intertace unit.


2) PI485: Product Interface unit for IEEE 485 transmission.

Note: All the central control devices listed above are optional accessory,
so these should be purchased separately when needed.

24 MPS(Multi Power System) Variable Multi


5. Control System

5.2 Control device

Unit name Interface Gateway Functions

Simple On/Off control for 16 indoor units


Simple PI485 Individual / simultaneous operation control
Central
Set lock for each indoor unit
Control
Group control
Monitoring operating state
Basic Model No. 1 Outdoor unit : 1 Gateway
: PQCSA101S0
Error display

Central control and monitoring for


CNU PI485
Deluxe 256 indoor units
Central 8.0 TFT LCD
Control Touch screen panel
Individual room temperature setting
Group control
Basic Model No. Connection: Webpad
Set lock for each indoor unit
: PQCSW501A0 CNU PI485(Outdoor)
Error display

Central control and monitoring for


256 indoor units
PC CNU PI485
Easy installation and operation using LAN
Central cable and user friendly simple GUI
Control Individual room temperature setting
Software Group control
Set lock for each indoor unit
Basic Model No. Connection: Webpad
Error display
: PQCSS501A0 CNU PI485(Outdoor)
Scheduling(option)
Peak power control(option)

2004 Product Data 25


26 MPS(Multi Power System) Variable Multi
Part 2
Indoor Units

1. Wall Mounted ................................................................................................................28


2. Ceiling Cassette 4-way...................................................................................................45
3. Ceiling Concealed Duct - High Static Pressure..............................................................62
4. Ceiling Concealed Duct - Low Static Pressure ..............................................................79

2004 Product Data 27


LMNC-LR, LT
LMNH-LR, LT

1. Wall Mounted

1. List of Functions.................................................................29
2. Specifications.....................................................................30
3. Dimensional Drawings .......................................................31
4. Wiring Diagrams ................................................................32
5. Piping Diagrams ................................................................33
6. Air Velocity and Temperature Distribution ..........................34
7. Sound Levels .....................................................................35
8. Installation..........................................................................36
9. Accessories .......................................................................44

28 MPS(Multi Power System) Variable Multi


1. List of Functions

Model
Features LMNC-LR/ LT, LMNH-LR/LT
Airflow Direction Control(Left & Right) Manual
Airflow Direction Control(Up & Down) Automatic
Airflow Outlet 1
Airflow Steps(Fan / Cool / Heat) 3/4/3
Auto Changeover(Operation) -
Auto Cleaning -
Auto Restart Operation O
Central Control Accessory
CHAOS Wind(Auto Wind) O
Child Lock Function -
Cooling & Heating Fan Operation -
Deice Control O(Only Heat Pump)
Deodorizing Filter O(Triple)
Drain Pump -
E.S.P Control -
Forced Operation O
Group Control -
High Ceiling Operation -
Hot Start Function O(Only Heat Pump)
Jet Cool O
Plasma Air Purifying Filter O(NANO)
Plasma Heat Exchanger -
Prefilter(Washable / Anti-fungus) O
Self Diagnosis Function O
Sleep Mode Operation O
Soft Dry Operation O
Soft Start Function -
Test Function O
Time Delay Safety Function O
Timer(24 Hour, On/Off) O
Timer(Weekly, On/Off) -
Two Thermistor Control -
Wired LCD Remote Control -
Wireless LCD Remote Control O
Zero Stanby Power -
Zone Control -

Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system

2004 Product Data 29


2. Specification

Heat Pump
Indoor Unit Type Wall Mounted

Model LMNH126LRL0 LMNH186LTL0 LMNH246LTL0


Nominal Cooling Capacity kcal/hr(W) 3024(3515) 4536(5275) 5796(6740)
Btu/hr 12,000 18,000 23,000
Nominal Heating Capacity kcal/hr(W) 3024(3515) 4536(5275) 5796(6740)
Btu/hr 12,000 18,000 23,000
Air Circulation H/M/L CMM(CFM) 9.0(318) 13(459) 14(494)
Setting temperature range C 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30
Fan motor Output W 14.4 27 28
Model IC-8420LG48A AMR-023E2 AMR-023E5
No. of Poles 4 4 4
Input W 37 34 63
Running Current A 0.16 0.15 0.28
Capacitor F/Vac 0.9 / 400 2.0 / 370 2.0 / 370
Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan
No. Used / Diameter EA/inch(mm) 1/3.43(87) 1/3.74(95) 1/3.74(95)
Noise Level(Sound Press,1m) H/M/L dBA 38 / 36 / 34 42 / 38 / 35 46 / 42 / 38
Temperature controller Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.197(5.0) 0.276(7.0) 0.276(7.0)
Fins per inch 20 20 20
No. of Rows & Column 2R,12C 2R,13C 2R,13C
Dehumidification Rate l/h 1.2 2.3 3.0
Dimensions (W*H*D) inch(mm) 35.4*11.2*6.1(900*285*156) 42.9*12.4*6.8(1090*314*172) 42.9*12.4*6.8(1090*314*172)
Net Weight kg(lbs) 9(19.8) 12(26.5) 12(26.5)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Connection Gas inch(mm) 1/2 (12.7) 1/2 (12.7) 5/8(15.88)
Drain hose (ID ) mm 20 20 20
Packing Dimension (W*H*D) inch(mm) 38.4*9.2*14.6(976*233*372) 45.9*10.0*15.3 (1165*255*388) 45.9*10.0*15.3 (1165*255*388)
Stuffing Quantity Without S/Parts 20/40ft 340/720 270/540 270/540

Cooling Only
Indoor Unit Type Wall Mounted

Model LMNC126LRL0 LMNC186LTL0 LMNC246LTL0


Nominal Cooling Capacity kcal/hr(W) 3024(3515) 4536(5275) 5796(6740)
Btu/hr 12,000 18,000 23,000
Nominal Heating Capacity kcal/hr(W) - - -
Btu/hr - - -
Air Circulation H/M/L CMM(CFM) 9.0(318) 13(459) 14(494)
Setting temperature range C 18~30 / - 18~30 / - 18~30 / -
Fan motor Output W 14.4 27 28
Model IC-8420LG48A AMR-023E2 AMR-023E5
No. of Poles 4 4 4
Input W 37 34 63
Running Current A 0.16 0.15 0.28
Capacitor F/Vac 0.9 / 400 2.0 / 370 2.0 / 370
Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan
No. Used / Diameter EA/inch(mm) 1/3.43(87) 1/3.74(95) 1/3.74(95)
Noise Level(Sound Press,1m) H/M/L dBA 38 / 36 / 34 42 / 38 / 35 46 / 42 / 38
Temperature controller Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.197(5.0) 0.276(7.0) 0.276(7.0)
Fins per inch 20 20 20
No. of Rows & Column 2R,12C 2R,13C 2R,13C
Dehumidification Rate l/h 1.2 2.3 3.0
Dimensions (W*H*D) inch(mm) 35.4*11.2*6.1(900*285*156) 42.9*12.4*6.8(1090*314*172) 42.9*12.4*6.8(1090*314*172)
Net Weight kg(lbs) 9(19.8) 12(26.5) 12(26.5)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Connection Gas inch(mm) 1/2 (12.7) 1/2 (12.7) 5/8(15.88)
Drain hose (ID ) mm 20 20 20
Packing Dimension (W*H*D) inch(mm) 38.4*9.2*14.6(976*233*372) 45.9*10.0*15.3 (1165*255*388) 45.9*10.0*15.3 (1165*255*388)
Stuffing Quantity Without S/Parts 20/40ft 340/720 270/540 270/540

Notes:- Conversion Formula


1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB kcal/h = kW x 860
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB Btu/h = kW x 3412
- Interconnecting Piping Length 7.5m cfm = m3/min x 35.3
- Level Difference of Zero.
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. : See the page "Combination Table"

30 MPS(Multi Power System) Variable Multi


3. Dimensional Drawings

LMNC-LR/LT, LMNH-LR/LT

H
More than
More than 5cm
5cm

D
W
More than 2.3m More than
5cm

Installation plate Note:


1. Pipe Specification(mm)
Model Liquid Gas
12k/18k 6.35 12.7
24k 6.35 15.88

CHASSIS Distance(mm)

C (Grade) A B C D
Installation plate SR(12k) 0 40 20 40
D

A ST(18/24k) 105 0 210 0


70mm 70mm

Left rear piping Right rear piping

(unit : mm)
Model W H D
LMNC126LRL0 900 285 156
LMNH126LRL0
LMNC186LTL0
LMNH186LTL0
1090 314 172
LMNC246LTL0
LMNH246LTL0

2004 Product Data 31


4. Wiring Diagrams

AC PCB ASM DC PCB ASM

CN-U/D CN-TH1 CN-TH2


THERMISTOR(OUT-PIPE)

CN-MOTOR
THERMISTOR(IN-PIPE)
THERMISTOR(ROOM)

ZNR

FUSE
250V 2A
CN-POWER

3854A20135W

CONNECTOR NUMBER LOCATION


CN-POWER AC POWER SUPPLY
CN-MOTOR AC FAN MOTOR OUTPUT
CN-ACDC AC/DC CONNECTION
CN-DISP DISPLAY
CN-UD STEP MOTOR
CN-LR STEP MOTOR
CN-TH1 ROOM/PIPE SENSOR
CN-TH2 DISCHARGE PIPE SENSOR

32 MPS(Multi Power System) Variable Multi


5. Piping Diagrams

:Cooling
Heat Exchanger :Heating

C.F.F

lndoor unit

: Thermistor

Refrigerant pipe connection port diameter


[unit:mm(inch)]
Model Gas Liquid
LMNC126LRL0
LMNH126LRL0
12.7(1/2)
LMNC186LTL0
LMNH186LTL0 6.35(1/4)
LMNC246LTL0
15.88(5/8)
LMNH246LTL0

2004 Product Data 33


6. Air Velocity and Temperature Distributions(Reference Data)

12k Btu/h Model


Cooling Heating
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m

1.5 0.5
1.5
1m 1.0 1m
1.0

0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

Temperature [C] Temperature [C]


2.7m 2.7m

2m 2m
21 24
18 33

20 30
1m 1m
27

22
24
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m

18k Btu/h Model

Cooling Heating
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2m

2.5 1m 1m
2.0
1.0 1.5
0.5 1.0 1.5 0.5
0m 0m
8m 7m 6m 5m 4m 3m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [C] Temperature [C]


2.7m 2.7m

2m 2m
18 33
20 1m 30 1m
21
24 27
24 22
0m 0m
8m 7m 6m 5m 4m 3m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m

34 MPS(Multi Power System) Variable Multi


7. Sound Levels

Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
1m - Reference accoustic pressure 0dB=20Pa.
- Sound level will vary depending on a range of factors such as
0.8m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
Microphone - The operating conditions are assumed to be standard(KS conditions).

Sound Levels(dBA)
Model
H M L
LMNC126LRL0
38 36 34
LMNH126LRL0
LMNC186LTL0
42 38 35
LMNH186LTL0
LMNC246LTL0
46 40 38
LMNH246LTL0

Sound Pressure Level


LMNC126LRL0 LMNC186LTL0 LMNC246LTL0
LMNH126LRL0 LMNH186LTL0 LMNH246LTL0
90 90 90

80 80 80

70 70 70
NC-70 NC-70 NC-70
Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
NC-20 NC-20 NC-20

NC-15 NC-15 NC-15


10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

2004 Product Data 35


8. Installation

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Type "A" screw


2. Installation Plate

3. Type "B" screw


4. Holder Remote Control
Cooling & Heating Model has
included Drain Elbow.

Required Parts Required Tools


Installation plate Level gauge
Four type "A" screws Screw driver
Connecting cable Electric drill
Hole core drill(70mm)

Pipes: Gas side.............................12.7, 15.88mm


Liquid side.......................................6.35 mm
Insulation materials
Additional drain pipe Flaring tool set
(Inner Diameter ...............................................20mm) Specified torque wrenches
1.8kg.m, 4.2kg.m, 5.5kg.m, 6.6kg.m
(different depending on model No.)
Spanner......................................................Half union

A glass of water
Screw driver

Two type "B" screws Owner's manual


Thermometer
Holder Remote Control

36 MPS(Multi Power System) Variable Multi


8. Installation

8.1 Selection of the best location Front


There should not be any heat source or steam near
the unit. Left
There should not be any obstacles to prevent the air
circulation. Rear left

There should be easy provision of condensate drain.


Down right
Taking into account the noise prevention criteria,
spot the installation location. Right Rear right
Do not install the unit near the door way.
Keep proper distance, of the unit, from ceiling fence,
floor, walls & other obstacles as shown in figure. Lower than 2.3m
More than 5 cm
More than
The mounting wall should be strong and solid enough to 5 cm
protect it from the vibration.
More than
5 cm
1) Mount the installation plate on the wall with four Higher than eye-level
Type "A" screws.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
Installation Plate
Always mount the Installation plate horizontally by
aligning the marking-off line by means of the thread
and a level.

Type "A" screw marking-off line


Thread
Weight

The lower left and the right side of Installation Plate

CHASSIS Distance(mm)

C (Grade) A B C D
Installation plate 0 40 20 40
SR(12k)
D

A ST(18/24k) 105 0 210 0


70mm 70mm

Left rear piping Right rear piping

2004 Product Data 37


8. Installation

8.2 Connection of pipings


Preparing the indoor unit's piping and drain hose for 3. Tape the tubing, drain hose and the connecting
installation through the wall. cable. Be sure that the drain hose is located at the
Remove the plastic tubing retainer(see illustration lowest side of the bundle. Locating at the upper
below) and pull the tubing and drain hose away from side can cause drain pan to overflow inside the
chassis. unit.
Replace the plastic tubing holder in the original position.

Loop
Tubing holder Connecting Gas side
cable piping
To remove the holder, Liquid side
press the bottom of Drain hose piping
chassis near the holder 2 Pull
upward and pull the tab
out of its hole. 1 Press
NOTE: If the drain hose is routed inside the room, insulate
the hose with an insulation material* so that dripping from
CAUTION "sweating"(condensation) will not damage furniture or
When install, make sure that the floors.
remaining parts must be removed
*Foamed polyethylene or equivalent is recommended.
clearly so as not to damage the piping
and drain hose, especially power cord
and connecting cable. 4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
For left rear piping top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are properly
1. Route the indoor tubing and the drain hose in the seated on the installation plate by moving it left and
direction of rear left. right.

Connecting
cable

Drain hose

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
Drain hose
slots(clicking sound).
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole. 5. Connecting the pipings to the indoor unit and drain
Do not connect the cable to the indoor unit. hose to drain pipe.
Make a small loop with the cable for easy connection Align the center of the pipings and sufficiently tighten
later. the flare nut by hand.

Indoor unit tubing Flare nut Pipings

38 MPS(Multi Power System) Variable Multi


8. Installation
Tighten the flare nut with a wrench. Wrap the area which accommodates the rear pip-
ing housing section with vinyl tape.
Spanner (fixed) Connection Indoor
pipe unit pipe
Flare nut Wrap with vinyl tape
Vinyl tape
Torque Connection (wide)
wrench pipe
Connecting cable
Indoor
unit tubing
Pipe

Vinyl tape(narrow)

Bundle the piping and drain hose together by


wrapping them with vinyl tape over the range with-
in which they fit into the rear piping housing sec-
When extending the drain hose at the indoor unit, tion.
install the drain pipe. Wrap with vinyl tape

Pipe

Drain pipe
Vinyl tape(wide)
Drain hose

Indoor unit
drain hose
Vinyl tape(narrow)
Adhesive

6. Wrap the insulation material around the connect- 1. Route the indoor tubing and the drain hose to the
ing portion. required piping hole position.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands
Insulation material

2. Insert the piping, drain hose and the connecting


cable into the piping hole.

Connecting cable
Drain pipe

2004 Product Data 39


8. Installation

3. Insert the connecting cable into the indoor unit.


Don't connect the cable to the indoor unit. Pipe Size[Torque]
Make a small loop with the cable for easy connec- GAS LIQUID
tion later. 12.7[5.5kg.m] 6.35[1.8kg.m]
15.88[6.6kg.m] 9.52[4.2kg.m]
4. Tape the drain hose and the connecting cable.
Connecting cable
When extending the drain hose at the indoor unit,
install the drain pipe.

Drain hose

Indoor unit drain hose


Vinyl tape(narrow)
5. Indoor unit installation Adhesive
Hang the indoor unit from the hooks at the top of
the installation plate. 7. Wrap the insulation material around the connect-
Insert the spacer etc. between the indoor unit and ing portion.
the installation plate and separate the bottom of Overlap the connection pipe heat insulation and
the indoor unit from the wall. the indoor unit pipe heat insulation material. Bind
them together with vinyl tape so that there is no
gap.
Indoor unit Plastic bands
Spacer Insulation material

Installation plate
8cm

6. Connecting the pipings to the indoor unit and


the drain hose to drain pipe. Wrap the area which accommodates the rear pip-
Align the center of the pipings and sufficiently ing housing section with vinyl tape.
tighten the flare nut by hand. Connection Indoor
pipe unit piping
Vinyl tape
(wide) Wrap with vinyl tape

Indoor unit tubing Flare nut Pipings Pipe


Vinyl tape
Connecting (narrow)
Tighten the flare nut with a wrench. cable

Spanner (fixed)

Flare nut
Torque Connection
wrench pipe

Indoor
unit tubing

40 MPS(Multi Power System) Variable Multi


8. Installation
Bundle the piping and drain hose together by 10. Indoor unit installation
wrapping them with cloth tape over the range Remove the spacer.
within which they fit into the rear piping housing Ensure that the hooks are properly seated on the
section. installation plate by moving it left and right.
Pipe
Drain hose
Vinyl tape Connecting
(narrow) cable

Wrap with
vinyl tape(wide) Drain hose

Press the lower left and right sides of the unit


against the installation plate until the hooks engage
8. Adjust the pipings and the drain hose across the into their slots(clicking sound).
back of the chassis.

Piping for passage through


piping hole

9. Set the pipings and the drain hose to the back of


the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.

Tubing holder

1 Hook

2 Push

2004 Product Data 41


8. Installation

8.3 Checking the drainage


1. To remove the front panel from the indoor unit,
remove the front panel from the indoor unit 2. To check the drainage.
cabinet. Pour a glass of water on the evaporator.
Set the air direction louvers up-and-down to the Ensure the water flows through the drain hose of
position(horizontally) by hand. the indoor unit without any leakage and goes out
Remove the securing screws that retain the front the drain exit.
panel. Pull the lower left and right sides of the
grille toward you and lift it off.
(2.1/7, 2.6/9, 3.5/12 kW/Btu models: 2EA,
3.5/18 kW/Btu models: 3EA)

Pull the right and


the left side.

Screw

8.4 Connecting the cable


1) Connect the wires to the terminals on the
control board individually according to the
outdoor unit connection.
Ensure that the color of the wires of outdoor
unit and the terminal No. are the same as
those of indoor unit respectively.

Connecting cable

42 MPS(Multi Power System) Variable Multi


8. Installation

Terminal Block in Indoor

1(L) 2(N) 3 4

Connected to Outdoor Unit(or BD Unit)

2) Attach the Grille onto the cabinet.


Grasp lower the left and right side of the Grille
and engage four tabs on the top inside edge of
the chassis.
Press the Grille toward the chassis until it will be
back into place.

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the
wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.)
7) In a wet or moist area, always install an earth leakage circuit breaker.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the
normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.

2004 Product Data 43


9. Accessories

Standard Accessories

Insulating tape Insulation for


Name Installation panel Clamp Securing screws
fitting

Quantity 1 set 1 EA 4 EA 2 EA 1 set

Shape for gas pipe

M4 x 12L
for liquid pipe

Name
(Other)
Quantity Owner's manual
Installation manual

Shape

44 MPS(Multi Power System) Variable Multi


LMNC-TE, TF, TD
LMNH-TE, TF, TD

2. Ceiling Cassette 4-way

1. List of Functions.................................................................46
2. Specifications.....................................................................47
3. Dimensional Drawings .......................................................48
4. Wiring Diagrams ................................................................51
5. Piping Diagrams ................................................................52
6. Air Velocity and Temperature Distribution ..........................53
7. Sound Levels .....................................................................54
8. Installation..........................................................................55
9. Accessories .......................................................................60

2004 Product Data 45


1. List of Functions

Model LMNC-TE/TF/TD, LMNH-TE/TF/ TD


Features
Airflow Direction Control(Left & Right) Manual
Airflow Direction Control(Up & Down) Automatic
Airflow Outlet 4
Airflow Steps(Fan / Cool / Heat) 3/4/3
Auto Changeover(Operation) -
Auto Cleaning -
Auto Restart Operation O
Central Control Accessory
CHAOS Wind(Auto Wind) -
Child Lock Function O
Cooling & Heating Fan Operation O
Deice Control O(Only Heat Pump)
Deodorizing Filter O
Drain Pump O
E.S.P Control -
Forced Operation O
Group Control O
High Ceiling Operation O
Hot Start Function O(Only Heat Pump)
Jet Cool O
Plasma Air Purifying Filter O
Plasma Heat Exchanger -
Prefilter(Washable / Anti-fungus) O
Self Diagnosis Function O
Sleep Mode Operation -
Soft Dry Operation O
Soft Start Function -
Test Function O
Time Delay Safety Function O
Timer(24 Hour, On/Off) O
Timer(Weekly, On/Off) O
Two Thermistor Control O
Wired LCD Remote Control O
Wireless LCD Remote Control Accessory
Zero Stanby Power -
Zone Control -

Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system

46 MPS(Multi Power System) Variable Multi


2. Specification

Heat Pump
Indoor Unit Type Ceilling Cassette - 4way

Model LMNH126TEC0 LMNH186TEC0 LMNH246TFC0


Nominal Cooling Capacity kcal/hr(W) 3024(3515) 4536(5275) 6048(7033)
Btu/hr 12000 18000 24000
Nominal Heating Capacity kcal/hr(W) 3024(3515) 4536(5275) 6048(7033)
Btu/hr 12000 18000 24000
Air Circulation H/M/L CMM(CFM) 9.5/8/7(336/283/247) 13/12/11(459/424/388) 15/14/13(530/494/459)
Setting temperature range (cool/heat) C 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30
Fan motor Output W 18.4 22.4 40.3
Model IC-9630LGAE IC-9630LGAC OBM-350292
No. of Poles 6 6 6
Input W 75 90 121
Running Current A 0.35 0.75 0.53
Capacitor F/Vac 2.5/440 2.5/440 4/450
Fan Type Turbo Fan Turbo Fan Turbo Fan
No. Used / Diameter EA/inch(mm) 1/13.0(330) 1/13.0(330) 1/15.0(382)
Noise Level(Sound Press,1m) H/M/L dBA 38/35/32 41/39/37 43/41/39
Temperature controller Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.275(7) 0.275(7) 0.275(7)
Fins per inch 19 19 21
No. of Rows & Column 2R11C 2R11C 2R12C
Dehumidification Rate l/h 1.2 2.4 2.5
Dimensions (W*H*D) Indoor Unit inch(mm) 22.4*10.5*22.4 (570*269*570) 22.4*10.5*22.4 (570*269*570) 29.3*11.5*29.4 (744*292*744)
Decorative panel inch(mm) 26.4*1.2*26.4 (670*30*670) 26.4*1.2 *26.4(670*30*670) 33.5*1.2 *33.5(850*30*850)
Net Weight Body kg(lbs) 19(41.9) 19(41.9) 24(52.9)
Panel kg(lbs) 3(6.6) 3(6.6) 3(6.6)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Connection Gas inch(mm) 1/2 (12.7) 1/2 (12.7) 5/8 (15.88)
Drain hose (OD ) mm 1.26(32) 1.26(32) 1.26(32)
Packing Dimension Body inch(mm) 25.2*13.0*25.2(640*330*640) 25.2*13.0*25.2(640*330*640) 32.6*14.4*32.6(828*365*828)
(W*H*D) Panel inch(mm) 29.5*3.1*29.5(750*80*750) 29.5*3.1*29.5(750*80*750) 36.8*3.5*36.8(935*90*935)
Stuffing Quantity With(without) S/Parts 20/40ft 189/378 189/378 84/168

Indoor Unit Type Ceilling Cassette - 4way

Model LMNH306TFC0 LMNH366TDC0 LMNH486TDC0


Nominal Cooling Capacity kcal/hr(W) 7055(8204) 9072(10549) 12095(14065)
Btu/hr 28000 36000 48000
Nominal Heating Capacity kcal/hr(W) 7055(8204) 9072(10549) 12095(14065)
Btu/hr 28000 36000 48000
Air Circulation H/M/L CMM(CFM) 19/17/15(671/600/530) 25/23/21(883/812/742) 33/30/27(1164/1059/953)
Setting temperature range (cool/heat) C 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30
Fan motor Output W 52.5 52.5 58.5
Model IC-1630LGPJ IC-1630LGPJ IC-1630LGPH
No. of Poles 6 6 6
Input W 175 175 195
Running Current A 0.76 0.76 0.89
Capacitor F/Vac 4/450 4/450 6/450
Fan Type Turbo Fan Turbo Fan Turbo Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Noise Level(Sound Press,1m) H/M/L dBA 40/38/36 40/38/36 43/41/39
Temperature controller Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.275(7) 0.275(7) 0.275(7)
Fins per inch 21 21 21
No. of Rows & Column 2R12C 2R12C 2R12C
Dehumidification Rate l/h 3 3 3
Dimensions (W*H*D) Indoor Unit inch(mm) 29.3*11.5*29.4 (744*292*744) 33.1*11.3*33.1 (840*288*840) 33.1*11.3*33.1 (840*288*840)
Decorative panel inch(mm) 33.5*1.2 *33.5(850*30*850) 37.4*1.2 *37.4(950*30*950) 37.4*1.2 *37.4(950*30*950)
Net Weight Body kg(lbs) 33(72.7) 33(72.7) 33(72.7)
Panel kg(lbs) 5(11) 5(11) 5(11)
Piping Liquid inch(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Connection Gas inch(mm) 5/8 (15.88) 5/8 (15.88) 3/4 (19.05)
Drain hose (OD ) mm 1.26(32) 1.26(32) 1.26(32)
Packing Dimension Body inch(mm) 32.6*14.4*32.6(828*365*828) 36.4*13.8*36.4(925*350*925) 36.4*13.8*36.4(925*350*925)
(W*H*D) Panel inch(mm) 36.8*3.5*36.8(935*90*935) 40.6*3.5*40.6(1,030*90*1,030) 40.6*3.5*40.6(1,030*90*1,030)
Stuffing Quantity With(without) S/Parts 20/40ft 84/168 71/144 71/144

Notes:-
1. Capacities are based on the following conditions: 2. Capacities are Net Capacities.
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB 3. Due to our policy of innovation some specifications may be changed without notifi-
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB cation.
- Interconnecting Piping Length 7.5m 4. : See the page "Combination Table"
- Level Difference of Zero.
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.

2004 Product Data 47


2. Specification

Cooling Only
Indoor Unit Type Ceilling Cassette - 4way

Model LMNC126TEC0 LMNC186TEC0 LMNC246TFC0


Nominal Cooling Capacity kcal/hr(W) 3024(3515) 4536(5275) 6048(7033)
Btu/hr 12000 18000 24000
Nominal Heating Capacity kcal/hr(W) - - -
Btu/hr - - -
Air Circulation H/M/L CMM(CFM) 9.5/8/7(336/283/247) 13/12/11(459/424/388) 15/14/13(530/494/459)
Setting temperature range (cool/heat) C 18~30 / - 18~30 / - 18~30 / -
Fan motor Output W 18.4 22.4 40.3
Model IC-9630LGAE IC-9630LGAC OBM-350292
No. of Poles 6 6 6
Input W 75 90 121
Running Current A 0.35 0.75 0.53
Capacitor F/Vac 2.5/440 2.5/440 4/450
Fan Type Turbo Fan Turbo Fan Turbo Fan
No. Used / Diameter EA/inch(mm) 1/13.0(330) 1/13.0(330) 1/15.0(382)
Noise Level(Sound Press,1m) H/M/L dBA 38/35/32 41/39/37 43/41/39
Temperature controller Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.275(7) 0.275(7) 0.275(7)
Fins per inch 19 19 21
No. of Rows & Column 2R11C 2R11C 2R12C
Dehumidification Rate l/h 1.2 2.4 2.5
Dimensions (W*H*D) Indoor Unit inch(mm) 22.4*10.5*22.4 (570*269*570) 22.4*10.5*22.4 (570*269*570) 29.3*11.5*29.4 (744*292*744)
Decorative panel inch(mm) 26.4*1.2*26.4 (670*30*670) 26.4*1.2 *26.4(670*30*670) 33.5*1.2 *33.5(850*30*850)
Net Weight Body kg(lbs) 19(41.9) 19(41.9) 24(52.9)
Panel kg(lbs) 3(6.6) 3(6.6) 3(6.6)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Connection Gas inch(mm) 1/2 (12.7) 1/2 (12.7) 5/8 (15.88)
Drain hose (OD ) mm 1.26(32) 1.26(32) 1.26(32)
Packing Dimension Body inch(mm) 25.2*13.0*25.2(640*330*640) 25.2*13.0*25.2(640*330*640) 32.6*14.4*32.6(828*365*828)
(W*H*D) Panel inch(mm) 29.5*3.1*29.5(750*80*750) 29.5*3.1*29.5(750*80*750) 36.8*3.5*36.8(935*90*935)
Stuffing Quantity With(without) S/Parts 20/40ft 189/378 189/378 84/168

Indoor Unit Type Ceilling Cassette - 4way

Model LMNC306TFC0 LMNC366TDC0 LMNC486TDC0


Nominal Cooling Capacity kcal/hr(W) 7055(8204) 9072(10549) 12095(14065)
Btu/hr 28000 36000 48000
Nominal Heating Capacity kcal/hr(W) - - -
Btu/hr - - -
Air Circulation H/M/L CMM(CFM) 19/17/15(671/600/530) 25/23/21(883/812/742) 33/30/27(1164/1059/953)
Setting temperature range (cool/heat) C 18~30 / - 18~30 / - 18~30 / -
Fan motor Output W 52.5 52.5 58.5
Model IC-1630LGPJ IC-1630LGPJ IC-1630LGPH
No. of Poles 6 6 6
Input W 175 175 195
Running Current A 0.76 0.76 0.89
Capacitor F/Vac 4/450 4/450 6/450
Fan Type Turbo Fan Turbo Fan Turbo Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Noise Level(Sound Press,1m) H/M/L dBA 40/38/36 40/38/36 43/41/39
Temperature controller Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.275(7) 0.275(7) 0.275(7)
Fins per inch 21 21 21
No. of Rows & Column 2R12C 2R12C 2R12C
Dehumidification Rate l/h 3 3 3
Dimensions (W*H*D) Indoor Unit inch(mm) 29.3*11.5*29.4 (744*292*744) 33.1*11.3*33.1 (840*288*840) 33.1*11.3*33.1 (840*288*840)
Decorative panel inch(mm) 33.5*1.2 *33.5(850*30*850) 37.4*1.2 *37.4(950*30*950) 37.4*1.2 *37.4(950*30*950)
Net Weight Body kg(lbs) 33(72.7) 33(72.7) 33(72.7)
Panel kg(lbs) 5(11) 5(11) 5(11)
Piping Liquid inch(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Connection Gas inch(mm) 5/8 (15.88) 5/8 (15.88) 3/4 (19.05)
Drain hose (OD ) mm 1.26(32) 1.26(32) 1.26(32)
Packing Dimension Body inch(mm) 32.6*14.4*32.6(828*365*828) 36.4*13.8*36.4 (925*350*925) 36.4*13.8*36.4 (925*350*925)
(W*H*D) Panel inch(mm) 36.8*3.5*36.8(935*90*935) 40.6*3.5*40.6(1,030*90*1,030) 40.6*3.5*40.6(1,030*90*1,030)
Stuffing Quantity With(without) S/Parts 20/40ft 84/168 71/144 71/144

Notes:-
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notifi-
cation.
4. : See the page "Combination Table"

48 MPS(Multi Power System) Variable Multi


3. Dimensional Drawings

LMNC-TE, LMNH-TE
600 (Ceiling opening)

39.5 521(Hanging bolt) 39.5

450 (Hanging bolt) 75

600 (Ceiling opening)


269
570 Unit size

570 Unit size


670
670

75
Unit:mm

670 570
450
5

570

521
670

6 40
4
1 2
30

110 110
269

90

90

190.5
30

160
120.4

52

(unit : mm)
Number Name Descripition
1 Liquid pipe connection 6.35 flare
2 Gas pipe connection 12.7 flare
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill
6 Air suction grill

2004 Product Data 49


3. Dimensional Drawings

LMNC-TF, LMNH-TF 790 (Ceiling opening)


572(Hanging bolt)
109 109

66
790 (Ceiling opening)
658 (Hanging bolt)
292 744 Unit size

744 Unit size


850
850

66
Unit:mm

850
744
658

5
850

572
744
6

70
4
1 2
117

110 110
292

90

90

150
212
192

54
30

(unit : mm)
Number Name Descripition
1 Liquid pipe connection 6.35 flare
2 Gas pipe connection 15.88 flare
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill
6 Air suction grill

50 MPS(Multi Power System) Variable Multi


3. Dimensional Drawings

LMNC-TD, LMNH-TD

875 (Ceiling opening)

45 785(Hanging bolt) 45

101.5 672 (Hanging bolt) 101.5


288

875 (Ceiling opening)


950
950
840 Unit size

840 Unit size


950

5
Unit:mm

840
678
950

785
840

4
30

40
1
2
30

110 110
290

210.5
52 180
90

90
140

(unit : mm)

Number Name Descripition


1 Liquid pipe connection 36k: 6.35flare, 48k: 9.52flare
2 Gas pipe connection 36k: 15.88flare, 48k: 19.05flare
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill
6 Air suction grill

2004 Product Data 51


4. Wiring Diagrams

WIRING DIA GRA M

A/CL UNIT
HVB
DOOR S/W
OUT-PIPE ROOM IN-PIPE
THERMISTOR THERMISTOR THERMISTOR
STEP STEP STEP STEP
MOTOR MOTOR MOTOR MOTOR
CENTRAL CONTROL
TELE CONTROL

CN-PIPE2 CN-ROOM CN-PIPE1 CN-HVB CN-UD1 CN-UD2 CN-LR1 CN-LR2

TO OUTDOOR UNIT
RD

3
GN/YL GN/YL

1(L) 2(N)
BL
GRILL CONTROL

BR
FUSE
CN-
CN-REMO CN-PTC CN-FLOATCN-DISP DPUMP
CN- CN-
MOTOR VENTIL
CAPACITOR

PTC DISPLAY VENTIL OPTION


INDOOR DRAIN
REMOTE HEATER PCB ASSY MOTOR PUMP
UNIT
CONTROL FLOAT S/W
3854A20419C

CONNECTOR NUMBER LOCATION


CN-POWER AC POWER SUPPLY
CN-MOTOR BLDC FAN MOTOR OUTPUT
CN-D/PUMP DRAIN PUMP OUTPUT
CN-DISP DISPLAY
CN-FLOAT FLOAT SWITCH INPUT
CN-PTC PTC HEATER INUT
CN-REMO REMOTE CONTROL
CN-GRILL GRILL CONTROL
CN-CC CENTRAL CONTROL
CN-PIPE2 DISCHARGE PIPE SENSOR
CN-ROOM ROOM SENSOR
CN-PIPE1 PIPE SENSOR
CN-HVB AIR CLEANER
CN-UD1 STEP MOTOR
CN-UD2 STEP MOTOR
CN-LR1 STEP MOTOR
CN-LR2 STEP MOTOR

52 MPS(Multi Power System) Variable Multi


5. Piping Diagrams

:Cooling
Heat Exchanger :Heating

Turbo Fan

lndoor unit

: Thermistor

Refrigerant pipe connection port diameter


[unit: mm(inch)]
Model Gas Liquid

LMNC126TEC0

LMNH126TEC0
12.7(1/2)
LMNC186TEC0

LMNH186TEC0

LMNC246TFC0
6.35(1/4)
LMNH246TFC0

LMNC306TFC0
15.88(5/8)
LMNH306TFC0

LMNC366TDC0

LMNH366TDC0

LMNC486TDC0
19.05(3/4) 9.52(3/8)
LMNH486TDC0

2004 Product Data 53


6. Air Velocity and Temperature Distributions(Reference Data)

18k Btu/h Model


Cooling Heating
Discharge angle:45 Discharge angle:50

Air velocity [m/s] Air velocity [m/s]


2.7m 2.7m
2.0 2.0
2m 2.0 2.0 2m
1.5 1.5 1.5 1.5
1.0 1.0 1m 1.0 1.0 1m
0.5 0.5 0.5 0.5
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m

Temperature [C] Temperature [C]


2.7m 2.7m
33 33
18 18
20 20 2m 30 30 2m
21 21
22 22
1m 24 27 27 24 1m
24 24
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m

36k Btu/h Model


Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m

2m 2.0 2.0 2m
2.0 2.0
1.5 1.5
1.5 1.5
1m 1m
1.0 1.0 1.0 1.0
0.5 0.5
0.5 0.5
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m

Temperature [C] Temperature [C]


2.7m 2.7m
33 33
2m 2m
20 20 30 30
21 21
22 22 1m 1m
24 27 27 24
24 24
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m

54 MPS(Multi Power System) Variable Multi


7. Sound Levels

Overall
Notes:
- Sound measured at 1.5m below
the center of the unit.
- Data is valid at free field condition
Ceiling - Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
1.5m
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard(KS conditions)

Sound Levels(dBA) Sound Levels(dBA)


Model Model
H M L H M L
LMNC/H126TEC0 38 35 32 LMNC/H306TFC0 45 42 39
LMNC/H186TEC0 41 39 37 LMNC/H366TDC0 40 38 36
LMNC/H246TFC0 43 41 39 LMNC/H486TDC0 43 41 39

Sound Pressure Level


LMNC/H126TEC0 LMNC/H186TEC0 LMNC/H246TFC0
90 90 90

80 80 80
Sound Pressure Level (dB re 20uPa)

Sound Pressure Level (dB re 20uPa)

70 70 70
NC-70 NC-70
Sound Pressure Level (dB re 20uPa) NC-70

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
NC-20 NC-20 NC-20

NC-15 NC-15 NC-15


10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

LMNC/H306TFC0 LMNC/H366TDC0 LMNC/H486TDC0


90 90 90

80 80 80
Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )


Sound Pressure Level (dB re 20Pa )

70 70 70
NC-70 NC-70 NC-70

NC-65 NC-65 NC-65


60 60 60

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
NC-20 NC-20 NC-20

NC-15 NC-15 NC-15


10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

2004 Product Data 55


8. Installation

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Anti-bacteria filter
Air
Intake
Air Outlet

Required Parts Required Tools


Connecting cable Level
Pipes: Gas side Screw driver
Liquid side Electric drill
Hanging Bolt Hole core drill (70mm)
(W 3/8 or M10 length 650mm)
Flaring Tools set
Insulated drain hose
Torque Wrenches
Additional Drain hose
Hexagonal Wrench (4mm, 5mm)
(Outer Diameter ..........................32mm)
Gas-leak detector
Owners Manual
Thermometer

8.1 Selection of the best location


There should not be any heat source or steam near the
unit.
There should not be any obstacles to the air circula-
30 or more

Ceiling Ceiling Board


tion. Ceiling Board
There should be provision of easy condensate drain.
30 or less

Taking into accounting the noise prevention criteria,


or more

50 or 50 or
spot the installation location. more more
400 or less
Above 250
100

Do not install the unit near the door way.


Keep proper distances, of the unit, from ceiling, fence,
Unit:cm
floor, walls and other obstacles as shown in figure.
The indoor unit must have the maintenance space.
Floor

56 MPS(Multi Power System) Variable Multi


8. Installation

8.2 Ceiling opening dimensions and hanging bolt location


The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.

Ceiling
Ceiling board

Level gauge

TE Model TF Model TD Model


600 (Ceiling opening) 790 (Ceiling opening)
875 (Ceiling opening)
39.5 521(Hanging bolt) 572(Hanging bolt)
39.5 109 109 45 785(Hanging bolt) 45

66

101.5 672 (Hanging bolt) 101.5


790 (Ceiling opening)
672 (Hanging bolt) 75

875 (Ceiling opening)


600 (Ceiling opening)

658 (Hanging bolt)


744 Unit size 840 Unit size
570 Unit size
744 Unit size

840 Unit size


570 Unit size

66
75

Unit:mm
Unit:mm Unit:mm

CAUTION Select and mark the position for fixing bolts and
piping hole.
This air-conditioner uses a drain pump.
Decide the position for fixing bolts slightly tilted to
Install the unit horizontally using a level gauge.
the drain direction after considering the direction
During the installation, care should be taken not to
of drain hose.
damage electric wires.
Drill the hole for anchor bolt on the wall.

NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

2004 Product Data 57


8. Installation

Ceiling

Hanging bolt Keep the length of the bolt

150mm
(W3/8 or M10) from the bracket to 40mm
Nut
Flat washer for M10 Air Conditioner body
(W3/8 or M10)
(accessory) Ceiling board Ceiling board
Spring washer
(M10)

Flat washer for M10


(accessory) Paper pattern Set screw of
Nut for installation paper pattern (4 pieces)
(W3/8 or M10)

Adjust the same height Open the ceiling board


along the outer edge of the
paper pattern.

The following parts are local purchasing.


CAUTION
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10 Tighten the nut and bolt to prevent unit from
Spring Washer - M10 falling off.
Plate Washer - M10

8.3 Wiring Connection


Open the control box cover and connect the remote control cord and Indoor power wires.

Indoor
power cord

Remote Control box cover


controller [Air inlet side view]
cord

Control box cover


fitting screw(2 units)

Terminal Block in Indoor

1(L) 2(N) 3 4

Connected to Outdoor Unit(or BD Unit)

WARNING
Make sure that the screws of the terminal are free from looseness.

58 MPS(Multi Power System) Variable Multi


8. Installation

8.4 Installation of Decoration Panel


The decoration panel has its installation Before installing the decoration panel,
direction. always remove the paper template.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by
amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so
that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).

Air conditioner unit Piping side

Decoration panel fixing screws Control box cover


(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)
Inlet Grille
Louver motor

Decoration panel
Display
Key holes

Lead wire for


louver motor and
display

Decoration panel fixing screws


(Hexagon M5 screw)

Inlet Grille
CAUTION
Install certainly the decoration Good example Bad example
Air conditioner unit
panel.
Cool air leakage causes sweating. Air conditioner Air
unit Cool air leakage
Water drops fall. (no good)

Ceiling Ceiling
board board
Decoration panel Decoration
Fit the insulator (this part) and panel
be careful for cool air leakage

2004 Product Data 59


8. Installation

8.5 Indoor Unit Drain Piping Upward


Pipe clamp
Drain piping must have down-slope (1/50 to 1/100): be sure routing
not allowed
not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra Indoor unit
force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor
unit is 32mm. Maintenance
drain port
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
Be sure to install heat insulation on the drain piping.
1/50~1/100
Heat insulation material: Polyethylene foam with MAX 700mm
thickness more than 8 mm.

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Connect the main drain pipe to the exterior
Feed water Flexible drain hose
(accessory) and leave it provisionally until the test comes
Main to an end.
drain pipe Feed water to the flexible drain hose and
check the piping for leakage.
Drain Be sure to check the drain pump for normal
Drain Pump port Glue the joint
operating and noise when electrical wiring is
Drain hose connection complete.
Use the clip (accessory)
When the test is complete, connect the flexi-
ble drain hose to the drain port on the indoor
unit.
Drain pan
Flexible drain hose
CAUTION 1/50~1/100
The supplied flexible drain hose should not be curved,
MAX 700mm
neither screwed. The curved or screwed hose may
cause a leakage of water.
Flexible drain hose
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows: Flexible drain hose
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the
circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the
unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a
overload protection device.
Proper starting power is not given to the compressor.

60 MPS(Multi Power System) Variable Multi


9. Accessories

Standard Accessories
Washer for Insulation for
Name Drain hose Clamp metal Clamp (Other)
hanging backet fitting

Quantity 1 EA 1 EA 8 EA 8 EA 1 SET

Paper pattern for


installation
Owner's manual
Installation manual
Shape for gas pipe

for liquid pipe

Optional Accessories(For Unit)

No. Item Type Model No. Component Parts

Wireless remote control : 1EA


1 Wireless remote With air purifying Holder : 1EA
AHWRHD
control function Battery : 2EA
Screw : 2EA

2004 Product Data 61


LMNC-BH, BG, BE
LMNH-BH, BG, BE

3. Ceiling Concealed Duct - High Static Pressure

1. List of Functions.................................................................63
2. Specifications.....................................................................64
3. Dimensional Drawings .......................................................65
4. Wiring Diagrams ................................................................66
5. Piping Diagrams ................................................................67
6. External Static Pressure & Air Flow...................................68
7. E.S.P. Setting for Phase Control Motor ..............................69
8. Sound Levels .....................................................................72
9. Installation..........................................................................73
10. Accessories .....................................................................78

62 MPS(Multi Power System) Variable Multi


1. List of Functions

LMNC-BH/BG LMNC-BE
Model
Features LMNH-BH/BG LMNH-BE
Airflow Direction Control(Left & Right) - -
Airflow Direction Control(Up & Down) - -
Airflow Outlet 1 1
Airflow Steps(Fan / Cool / Heat) 3/3/3 3/3/3
Auto Changeover(Operation) - -
Auto Cleaning - -
Auto Restart Operation O O
Central Control Accessory Accessory
CHAOS Wind(Auto Wind) - -
Child Lock Function O O
Cooling & Heating Fan Operation O O
Deice Control O(Only Heat Pump) O(Only Heat Pump)
Deodorizing Filter - -
Drain Pump Accessory Accessory
E.S.P Control O -
Forced Operation O O
Group Control O O
High Ceiling Operation - -
Hot Start Function O(Only Heat Pump) O(Only Heat Pump)
Jet Cool - -
Plasma Air Purifying Filter Accessory Accessory
Plasma Heat Exchanger - -
Prefilter(Washable / Anti-fungus) O O
Self Diagnosis Function O O
Sleep Mode Operation - -
Soft Dry Operation O O
Soft Start Function - -
Test Function O O
Time Delay Safety Function O O
Timer(24 Hour, On/Off) O O
Timer(Weekly, On/Off) O O
Two Thermistor Control O O
Wired LCD Remote Control O O
Wireless LCD Remote Control Accessory Accessory
Zero Stanby Power - -
Zone Control Accessory Accessory

Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system

2004 Product Data 63


2. Specification

Heat Pump
Indoor Unit Type Ceilling Concealed Duct - High Static

Model LMNH186BHA0 LMNH246BHA0 LMNH306BGA0 LMNH366BGA0 LMNH486BEA0


Nominal Cooling Capacity kcal/hr(W) 4536(5275) 6048(7034) 7560(8792) 9072(10551) 12096(14064)
Btu/hr 18,000 24,000 30000 36000 48000
Nominal Heating Capacity kcal/hr(W) 4536(5275) 6048(7034) 7560(8792) 9072(10551) 12096(14064)
Btu/hr 18,000 24,000 30000 36000 48000
Air Circulation H/M/L CMM(CFM) 16.5/14.5/13(583/512/459) 18/16.5/14(636/583/494) 26.5/23/20(936/812/706) 32/29/26.5(1130/1024/936) 40/36/30(1412/1270/1059)
External Static Pressure mmAq 8 8 10 10 10
Setting temperature range (cool/heat) C 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30 18~30 / 16~30
Fan motor Output W 118 118 272 272 604
Model IC-13450LG13C IC-13450LG13C IC-13450LG13E IC-13450LG13E 808555AVA-A12EX
No. of Poles 4 4 4 4 4
Input W 180 180 323 323 500
Running Current A 0.92 0.92 1.42 1.42 2.7
Capacitor F/Vac 6/370 6/370 6/370 6/370 12/450
Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
No. Used / Diameter EA/inch(mm) 2/6.97(177) 2/6.97(177) 2/6.97(177) 2/6.97(177) -
Noise Level(Sound Press,1m) H/M/L dBA 36 / 34 / 32 38/36/34 40/38/35 42/39/36 43/41/39
Temperature controller Thermistor Thermistor Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.275(7) 0.275(7) 0.275(7) 0.275(7) 0.275(7)
Fins per inch 21 21 21 21 21
No. of Rows & Column 3R10C 3R10C 3R,12C 3R,12C 3R,14C
Dehumidification Rate l/h 2.0 2.5 3.0 3.5 5.5
Dimensions (W*H*D) Indoor Unit inch(mm) 34.6*10.2*17.7(880*260*450) 34.6*10.2*17.7 (880*260*450) 46.4*11.7 *17.7 (1180*298*450) 46.4*11.7 *17.7(1180*298*450) 48.43*41.57*26.77(1230*370*680)
Net Weight kg(lbs) 35(77.2) 35(77.2) 38(83.8) 38(83.8) 70(154.3)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8(9.52)
Connection Gas inch(mm) 1/2 (12.7) 5/8(15.88) 5/8(15.88) 5/8(15.88) 3/4(19.05)
Drain hose (ID ) mm 22.6 22.6 22.6 22.6 22.6
Packing Dimension (W*H*D) inch(mm) 44.7*13.4*23.0 (1135*340*585) 44.7*13.4*23.0 (1135*340*585) 56.5*14.8*23.0(1435*375*585) 56.5*14.8*23.0 (1435*375*585) 58.3*18.1*31.9(1480*460*810)
Stuffing Quantity With(Without) S/Parts 20/40ft 120/252 120/252 95/191 95/191 50/110

Cooling Only
Indoor Unit Type Ceilling Concealed Duct - High Static

Model LMNC186BHA0 LMNC246BHA0 LMNC306BGA0 LMNC366BGA0 LMNC486BEA0


Nominal Cooling Capacity kcal/hr(W) 4536(5275) 6048(7034) 7560(8792) 9072(10551) 12096(14064)
Btu/hr 18,000 24,000 30000 36000 48000
Nominal Heating Capacity kcal/hr(W) - - - - -
Btu/hr - - - - -
Air Circulation H/M/L CMM(CFM) 16.5/14.5/13(583/512/459) 18/16.5/14(636/583/494) 26.5/23/20(936/812/706) 32/29/26.5(1130/1024/936) 40/36/30(1412/1270/1059)
External Static Pressure mmAq 8 8 10 10 10
Setting temperature range (cool/heat) C 18~30 / - 18~30 / - 18~30 / - 18~30 / - 18~30 / -
Fan motor Output W 118 118 272 272 604
Model IC-13450LG13C IC-13450LG13C IC-13450LG13E IC-13450LG13E 808555AVA-A12EX
No. of Poles 4 4 4 4 4
Input W 180 180 323 323 500
Running Current A 0.92 0.92 1.42 1.42 2.7
Capacitor F/Vac 6/370 6/370 6/370 6/370 12/450
Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
No. Used / Diameter EA/inch(mm) 2/6.97(177) 2/6.97(177) 2/6.97(177) 2/6.97(177) -
Noise Level(Sound Press,1m) H/M/L dBA 36 / 34 / 32 38/36/34 40/38/35 42/39/36 43/41/39
Temperature controller Thermistor Thermistor Thermistor Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.275(7) 0.275(7) 0.275(7) 0.275(7) 0.275(7)
Fins per inch 21 21 21 21 21
No. of Rows & Column 3R10C 3R10C 3R,12C 3R,12C 3R,14C
Dehumidification Rate l/h 2.0 2.5 3.0 3.5 5.5
Dimensions (W*H*D) Indoor Unit inch(mm) 34.6*10.2*17.7(880*260*450)" 34.6*10.2*17.7 (880*260*450) 46.4*11.7 *17.7 (1180*298*450) 46.4*11.7 *17.7 (1180*298*450) 48.43*41.57*26.77(1230*370*680)
Net Weight kg(lbs) 35(77.2) 35(77.2) 38(83.8) 38(83.8) 70(154.3)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8(9.52)
Connection Gas inch(mm) 1/2 (12.7) 5/8(15.88) 5/8(15.88) 5/8(15.88) 3/4(19.05)
Drain hose (ID ) mm 22.6 22.6 22.6 22.6 22.6
Packing Dimension (W*H*D) inch(mm) 44.7*13.4*23.0 (1135*340*585) 44.7*13.4*23.0 (1135*340*585) 56.5*14.8*23.0(1435*375*585) 56.5*14.8*23.0(1435*375*585) 58.3*18.1*31.9(1480*460*810)
Stuffing Quantity With(Without) S/Parts 20/40ft 120/252 120/252 95/191 95/191 50/110

Notes:- Conversion Formula


1. Capacities are based on the following conditions:
kcal/h = kW x 860
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
Btu/h = kW x 3412
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
cfm = m3/min x 35.3
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. : See the page "Combination Table"

64 MPS(Multi Power System) Variable Multi


3. Dimensional Drawings

LMNC-BH/BG/BE, LMNH-BH/BG/BE

k
A
B
h
i l
C j
E

f
J
K

e
(G) a b c d
D
F

H
Note:
1. Pipe Specification(mm)
Model Liquid Gas
18k 12.7
6.35
24k, 30k, 36k 15.88
48k 9.52 19.05

(Unit: mm)
Model A B C D E F (G) H J K a b c d e f h i j k l
LMNC18/246BHA0
932 882 355 45.5 450 30 87 750 163 260 61.5 243 212.3 243 110 130 52 66 81 30 158.5
LMNH18/246BHA0
LMNC30/366BGA0 1232 1182
355 45.5 450 30 87 830 186 298 229.5 243 232 243 116 160 53 59 81 19 158.5
LMNH30/366BGA0
LMNC486BEA0 1292 1230
570.5 54 680 30 120 1006 294 370 253.5 253 217 253 152 186 42 143 82 50 172
LMNH486BEA0

Top view Front view


Inspection hole
(unit: mm) (600X600)
Control box

H
1000

600 600
Suitable dimension "H" is necessary
to get a slope to drain as figure.
Front

2004 Product Data 65


4. Wiring Diagrams
4.1 LMNC-BH/BG, LMNH-BH/BG

CENTRAL CONTROL IN-PIPE. OUT-PIPE. ROOM.


REMOTE A/CL PTC
TELE CONTROL THERMISTOR CONTROL THERMISTOR THERMISTOR UNIT HEATER
DRY CONTACT

CN-OUT
CN-CC CN-PIPE1 CN-REMO CN-PIPE2 CN-ROOM CN-AIRC CN-PTC VENTILATION
E/HEATER
ZONE CONTROL

CN-ZONE

5
4

TO OUTDOOR UNIT
RD

3
GN/YL
FLOAT S/W

CN-FLOAT

BL

1(L) 2(N)
BR
FUSE
CN-POWER
CN-DISP
CN-MOTOR CN-DPUMP

OPTION
RF-REMOTE
CONTROL
3854A20419B

4.2 LMNC-BE, LMNH-BE

BR

SENSOR
INDOOR DRAIN
ROOM
GN/YL

MOTOR PUMP
YL
BL
BL
OR
RD

BK
BL

FUSE
1(L) 2(N)

BR 250V10A

BL
TO OUTDOOR UNIT

COMP

PIPE
GN/YL RD SENSOR
3
4

FLOAT S/W
5

REMOTE
TERMINAL CONTROL
BLOCK

A/CL TELECONTROL/ ZONE


UNIT CENTRAL CONTROL CONTROL

CONNECTOR NUMBER LOCATION CONNECTOR NUMBER LOCATION


CN-POWER AC POWER SUPPLY CN-PIPE1 PIPE SENSOR
CN-MOTOR BLDC FAN MOTOR OUTPUT CN-PIPE2 DISCHAGE PIPE SENSOR
CN-D/PUMP DRAIN PUMP OUTPUT CN-REMO REMOTE CONTROL
CN-DISP RF-REMOTE CONTROL CN-ROOM ROOM SENSOR
CN-FLOAT FLOAT SWITCH INUT CN-AIRC AIR CLEAN
CN-ZONE ZONE CONTROL OUTPUT CN-PTC PTC HEATER
CN-CC CENTRAL CONTROL OUTPUT CN-OUT VENTILATION /ELECTRIC HEATER

66 MPS(Multi Power System) Variable Multi


5. Piping Diagrams

:Cooling
Heat Exchanger :Heating

Sirocco Fan

lndoor unit

: Thermistor

Refrigerant pipe connection port diameter


[unit: mm(inch)]
Model Gas Liquid

LMNC186BHA0
12.7(1/2)
LMNH186BHA0

LMNC246BHA0
6.35 (1/4)
LMNH246BHA0
15.88(5/8)
LMNC30/366BGA0

LMNH30/366BGA0

LMNC486BEA0
19.05(3/4) 9.52(3/8)
LMNH486BEA0

2004 Product Data 67


6. External Static Pressure & Air Flow

6.1 LMNC-BE, LMNH-BE Models

Static Pressure(mmAq) 0 2 4 6 8 10 15

Model Name Step CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CCMM(CFM)

High 48.5(1,722) 46.5(1,642) 45(1,598) 43.5(1,544) 42(1,491) 40(1,420) *40(1,420)


LMNC486BEA0
Med 43(1,527) 41.5(1,466) 39.5(1,402) 38(1,349) 36.5(1,296) 35(1,243) *35(1,243)
LMNH486BEA0
Low 39(1,385) 37.5(1,324) 36(1,278) 34.5(1,225) 33(1,172) 31(1,101) *31(1,101)

External static pressure given after substracting coil losses motor step factory installed.
External static pressure can be higher than the maximum given in the table, but the unit faces the problem of
freezing the coil.
The assured range of air-conditioner is in the only shady part and in the other part, the specification of
air-conditioner may differ with the above table.
If the static pressure of air-conditioner is out of the shady part, please adjust the static pressure.
* Change the connection of the indoor fan motor connector to increase the motor speed to obtain similar CFM
at 15 mmAq Static Pressure as at 10 mmAq Static pressure.

68 MPS(Multi Power System) Variable Multi


7. E.S.P. Setting for Phase Control Motor

7.1 Ceiling Concealed Duct(LMNC-BH/BG, LMNH-BH/BG Model)

(1) Open the rear cover of the wired remote-controller to set the mode.

(2) Select one of three selectable modes as follows.

Without Zone System


1. Position V-H, F-H:
This position sets the maximum E.S.P as a default set.
2. Position V-L:
This position sets the minimum E.S.P as a default set.

With Zone System


1. Position V-H:
Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
2. Position F-H:
Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers.
3. Position V-L:
Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.

*Maximum: 18K/24K - 8mmAq, 30K/36K - 10mmAq


Minimum: All-0mmAq

(3) Move the slide switch to set position.

TH R13H R12H OP5R16H OP4


CO1H

R15H
OP2 OP1
R14H OP3 R19H
SW TH R11H

V-H REMO
MAIN
2TH OP7
R18H
R17H
F-H OP6

V-L LO
C070

STAND
HI R03S
R04S

R01S
R02S

SW HIGH

Slide switch for ceiling height

(4) Close the rear cover and check if it works normally.

CAUTION

Select
the position after checking duct work and E.S.P of the unit.
Maunfactured in the position F-H.

2004 Product Data 69


7. E.S.P. Setting for Phase Control Motor

How to Set E.S.P?

Procedure of RPM change:


Ex) External Static pressure is 4mmAq for Model Name LMNH246BHA0.
To protect the unit, compressor is designed to be off during E.S.P. setting.

Push the "On/Off" button. AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION

1 The unit will start.


Room Temp
HI
MED
LO
AUTO Heater Preheat
JET Defrost Humidify
Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
2 AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
Timer LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Push the "Up" of "Down" button for E.S.P adjustment.


3 And, adjust the number which you want.(In this example, the number is "190".
Refer to the table 7-1 on the next page.) AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Room Temp
HI AUTO Heater Preheat
MED JET Defrost Humidify
LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.

Shift the fan speed mode by pressing the fan speed button.
4 And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "220" and "235" respectively.

Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
5 Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
LO Filter Out door
Timer
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

70 MPS(Multi Power System) Variable Multi


7. E.S.P. Setting for Phase Control Motor

Table-7-1
Static Pressure(mmAq) 0 2 4 6 8 10
Model Name Step CMM(CFM) Setting Value
High 16.5 (583) 235 230 225 215 180
LMNC186BHA0
Med 14.5 (512) 245 238 235 230 215
LMNH186BHA0
Low 13.0 (459) 254 252 248 245 240
High 18.0 (636) 220 205 190 50 1
LMNC246BHA0
Med 16.5 (583) 235 230 220 200 100
LMNH246BHA0
Low 14.0 (494) 250 240 235 230 210
High 26.5(936) 153 150 150 148 130 1
LMNC306BGA0
Med 23(812) 173 173 175 175 170 155
LMNH306BGA0
Low 20(706) 190 190 190 190 190 190
High 32.0(1130) 230 230 230 220 150 1
LMNC366BGA0
Med 29.0(1024) 240 240 240 235 230 220
LMNH366BGA0
Low 26.5(936) 245 245 245 245 240 240

Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from
the table. Value other than that in table will not give the combinations of airflow & ESP
which are mentioned in the table.
2. Table 7-1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.

Table-7-2
Static Pressure(mmAq) Setting 0 2 4 6 8 10
Model Name Step Value CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM)
High 180 22 (777) 21.0 (742) 19.8 (699) 18.3 (646) 16.5 (583)
LMNC186BHA0
Med 215 18.5 (653) 17.8 (629) 17.1 (604) 16.2 (572) 14.5 (512)
LMNH186BHA0
Low 240 16.1 (569) 15.6 (551) 15.1 (533) 14.2 (501) 13.0 (459)
High 1 24.0 (848) 22.5 (795) 20.8 (735) 19.0 (671) 18.0 (636)
LMNC246BHA0
Med 100 21.3 (752) 19.9 (703) 18.7 (660) 17.2 (607) 16.5 (583)
LMNH246BHA0
Low 210 17.0 (600) 16.1 (569) 15.36 (551) 14.7 (519) 14.0 (494)
High 1 34.2(1208) 33.1(1169) 31.7(1119) 29.9(1056) 27.7(978 26.5(936)
LMNC306BGA0
Med 155 27(954) 26.3(929) 26.1(922) 25.8(911) 24.8(876) 23(812)
LMNH306BGA0
Low 190 21(742) 20.8(735) 20.6(727) 20.4(720) 20.4(720) 20(706)
High 1 42(1483) 40(1413) 38(1342) 35.5(1254) 33.5(1183) 32(1130)
LMNC366BGA0
Med 220 39(1377) 37(1307) 35(1236) 33(1165) 31(1095) 29(1024)
LMNH366BGA0
Low 240 34(1201) 32.5(1148) 31(1095) 29.5(1042) 27(954) 26.5(936)

Note: 1. The above table shows the correlation of External Static Pressure & Air Flow.
2. Duct work must be desined within the shaded range of on installing the table.
3. If duct work is designed under External Static Pressure adjust the External Static
Pressure applying air damper.

2004 Product Data 71


8. Sound Levels

Overall
Notes:
DISCHARGE SUCTION - Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
DUCT DUCT - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
2m 1.5m
1m - The operating conditions are assumed to be standard(KS conditions)
1m

Sound Levels(dBA) Sound Levels(dBA)


Model Model
H M L H M L
LMNC/H186BHA0 36 34 32 LMNC/H306BGA0 40 38 35
LMNC/H246BHA0 38 36 34 LMNC/H366BGA0 42 39 36
LMNC/H486BEA0 43 41 39

Sound Pressure Level


LMNC/H186BHA0 LMNC/H246BHA0 LMNC/H306BGA0
90 90 90

80 80 80

70 70 70
NC-70 NC-70 NC-70
Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
NC-20 NC-20 NC-20

NC-15 NC-15 NC-15


10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

LMNC/H366BGA0 LMNC/H486BEA0
90 90

80 80

70 70
NC-70 NC-70
Sound Pressure Level (dB re 20Pa )
Sound Pressure Level (dB re 20Pa )

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
NC-20 NC-20

NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

72 MPS(Multi Power System) Variable Multi


9. Installation

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air outlet vents Air filters

Air intake vents

Wired LCD Remote Control

Required Parts Required Tools


Connecting cable Level
Pipes: Gas side Screw driver
Liquid side Electric drill
Hanging Bolt Hole core drill (70mm)
(W 3/8 or M10 length 650mm)
Flaring Tools set
Insulated drain hose
Torque Wrenches
Additional Drain hose
Hexagonal Wrench (4mm, 5mm)
(Inner Dia .................................25.4mm)
Gas-leak detector
Owners Manual
Thermometer
9.1 Selection of the best location
Top view Inspection hole
Install the air conditioner in the location that satisfies the fol- (unit: mm) (600X600)
lowing conditions. Control box
The place shall easily bear a load exceeding four times the
indoor units weight.
The place should have enough area for inspection as shown
in figure.
1000

600 600
The place where the unit shall be leveled.
Front
The place shall allow easy water drainage.(Suitable dimen-
Front view
sion H is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical
noise.
The place where air circulation in the room will be good . H
There should not be any heat source or steam near the unit.

2004 Product Data 73


9. Installation

9.2 Ceiling dimension and hanging bolt


location A
Installation of Unit B
Install the unit above the ceiling correctly.

CASE 1

C
E
POSITION OF SUSPENSION BOLT

D
Apply a joint-canvas between the unit and duct to absorb
(G)

F
unnecessary vibration.
Apply a filter Accessory at air return hole.
Refer toDimensinal Drawings.

1-3 mm
I
H
Drainage hole

Install the unit leaning to a drainage hole side as a figure


for easy water drainage. M10 Nut X4
(Local
M10 SP. washer X 4 supply)
M10 washer X4

M10 washer X4
(Local
M10 SP. washer X 4 supply)
CASE 2 M10 Nut X4

POSITION OF CONSOLE BOLT

A place where the unit will be leveled and that can sup-
port the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.

74 MPS(Multi Power System) Variable Multi


9. Installation
Select and mark the position for fixing bolts. Insert the set anchor and washer onto the suspen-
Drill the hole for set anchor on the face of ceiling. sion bolts for locking the suspension bolts on the
ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.
Old building New building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
CAUTION 5 Suspension
bolts
Tighten the nut and bolt to prevent unit falling.

9.3 Connecting Cables


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively

Terminal Block in Indoor

1(L) 2(N) 3 4

Connected to Outdoor Unit( or BD Unit)

WARNING
Make sure that the screws of the terminal are free from looseness.

Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control
panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of
live pin on the power plug should be over 1.8m.

2004 Product Data 75


9. Installation

9.4 Insulation

THERMAL INSULATION All thermal insulation must comply with local requirement.

INDOOR UNIT

Union for liquid pipe Thermal insulator for refrigerant pipe


(Local supply) Thermal insulator for
Refrigerant pipe and thermal
piping(Local supply)
insulator(Local supply)

Hose crip for thermal insulator


(Local supply)
Overlap with thermal
Thermal insulator for refrigerant pipe insulator for piping.
(Local supply) Hose crip for thermal insulator(Local supply)
Union for gas pipe Make sure that there is no clearance here.

9.5 Checking the Drainage


1) Checking the Drainage

1. Remove the Air Filter.

2. Check the drainage.


Spray one or two glasses of water on the evapo-
rator.
Ensure that water flows to drain hose from indoor
unit without any leakage.

76 MPS(Multi Power System) Variable Multi


9. Installation

CAUTION

1. Decline Installation of indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe should be 5mm.

Front of view
The unit must be or declined to wards drain hose while installation.

Ceiling

1~3mm

CORRECT Drainage hole INCORRECT Drainage hole

CAUTION FOR GRADIENT OF Lay the drain hose with a downware


UNIT AND DRAIN PIPING inclination so water will drain out.

Alway lay the drain with downward inclination Thermal insulator


(1/50 to 1/100). (Local supply)
Prevent any upward flow or reverse flow in any Drainage pipe
part. (Local supply)
5mm or thicker formed thermal insulator shall Unit
always be provided for the drain pipe.

Make sure to be closed. Drainage hole

CORRECT INCORRECT
Install the P-Trap (or U-Trap) to prevent
Applied U-Trap Dimension
a water leakage caused by the blocking
of intake air filter. A 70mm
B 2C
C 2 x SP
SP = External Pressure B
(mmAq) C
1/50~1/100
Ex) External Pressure
Drain Pipe = 10mmAq U-Trap
A 70mm A
MAX 700mm B 40mm
C 20mm

Drain Pump

2004 Product Data 77


10. Accessories

Standard Accessories
Insulation for Screws for
Name Clamp metal Drain hose Clamp (Other)
fitting duct flanges

Quantity 1 EA 1 EA 1 set 6 EA 1 set

Owner's manual
Installation manual
Washers(8 pcs.)
Shape for gas pipe

for liquid pipe

Optional Accessories(For Unit)

No. Item Type Model No. Component Parts

Wireless remote control : 1EA


1 Wireless remote With air purifying AHWRHS Holder : 1EA
control function AHWRHD(LCD) Battery : 2EA
Screw : 2EA

Plasma air puirifying Plasm Air Purifier Kit: 1EA


2 - ABPAHH
filter Wired Remote Control: 1EA

Factory sypplied-Zone control PCB


3 Zone Control - ABZCA Durchased Locally-Damper,
Damper Moter, thermostat

4 Drain Pump - ABDPG Drain Pump Assembly: 1EA

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature
control, etc.).

78 MPS(Multi Power System) Variable Multi


LMNC-BT
LMNH-BT

4. Ceiling Concealed Duct - Low Static Pressure

1. List of Functions.................................................................80
2. Specifications.....................................................................81
3. Dimensional Drawings .......................................................82
4. Wiring Diagrams ................................................................83
5. Piping Diagrams ................................................................84
6. E.S.P. Setting for Phase Control Motor ..............................85
7. Sound Levels .....................................................................87
8. Installation..........................................................................88
9. Accessories .......................................................................92

2004 Product Data 79


1. List of Functions

Model
Features LMNC-BT, LMNH-BT
Airflow Direction Control(Left & Right) -
Airflow Direction Control(Up & Down) -
Airflow Outlet 1
Airflow Steps(Fan / Cool / Heat) 3/3/3
Auto Changeover(Operation) -
Auto Cleaning -
Auto Restart Operation O
Central Control Accessory
CHAOS Wind(Auto Wind) -
Child Lock Function O
Cooling & Heating Fan Operation O
Deice Control O
Deodorizing Filter -
Drain Pump Accessory
E.S.P Control O
Forced Operation O
Group Control O
High Ceiling Operation -
Hot Start Function O
Jet Cool -
Plasma Air Purifying Filter -
Plasma Heat Exchanger -
Prefilter(Washable / Anti-fungus) O
Self Diagnosis Function O
Sleep Mode Operation -
Soft Dry Operation O
Soft Start Function -
Test Function O
Time Delay Safety Function O
Timer(24 Hour, On/Off) O
Timer(Weekly, On/Off) O
Two Thermistor Control O
Wired LCD Remote Control O
Wireless LCD Remote Control Accessory
Zero Stanby Power -
Zone Control -

Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system

80 TPS Inverter Multi


2. Specification
Heat Pump
Indoor Unit Type Ceiling Concealed Duct - Low Static

Model LMNH126BTG0 LMNH186BTG0


Nominal Cooling Capacity kcal/hr(W) 3024(3516) 4536(5274)
Btu/hr 12000 18000
Nominal Heating Capacity kcal/hr(W) 3024(3516) 4536(5274)
Btu/hr 12000 18000
Air Circulation H/M/L CMM(CFM) 10/9/8(352/317/282) 13.5/12/10(477/424/353)
External Static Pressure mmAq 2 2
Setting temperature range (cool/heat) C 18~30 / 16~30 18~30 / 16~30
Fan motor Output W 35 47
Model YDK110-35-4L YSK110-70-4L
No. of Poles 4 4
Input W 68 126
Running Current A 0.31 0.58
Capacitor F/Vac 2.5/400 2.5/370
Fan Type Sirocco Fan Sirocco Fan
No. Used / Diameter EA/inch(mm) 1/7.8(197) 2/7.8(197)
Noise Level(Sound Press,1m) H/M/L dBA 37/34/31 38/36/34
Temperature controller Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.276(7.0) 0.276(7.0)
Fins per inch 18 18
No. of Rows & Column 3R,12C 2R, 12C
Dehumidification Rate l/h 1.2 2
Dimensions (W*H*D) Indoor Unit inch(mm) 25.6*9.0*21.1(650*230*535) 39.4*9.0*21.1(1000*230*535)
Net Weight kg(lbs) 22(48.5) 29(63.9)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35)
Connection Gas inch(mm) 1/2 (12.7) 1/2 (12.7)
Drain hose (ID ) mm 25.4 25.4
Packing Dimension (W*H*D) inch(mm) 29.9*24.6*11.8(760*625*300) 29.9*24.6*11.8(760*625*300)
Stuffing Quantity Without S/Parts 20/40ft 172/356 123/251

Cooling Only
Indoor Unit Type Ceiling Concealed Duct - Low Static

Model LMNC126BTG0 LMNC186BTG0


Nominal Cooling Capacity kcal/hr(W) 3024(3516) 4536(5274)
Btu/hr 12000 18000
Nominal Heating Capacity kcal/hr(W) - -
Btu/hr - -
Air Circulation H/M/L CMM(CFM) 10/9/8(352/317/282) 13.5/12/10(477/424/353)
External Static Pressure mmAq 2 2
Setting temperature range (cool/heat) C 18~30 / 16~30 18~30 / 16~30
Fan motor Output W 35 47
Model YDK110-35-4L YSK110-70-4L
No. of Poles 4 4
Input W 68 126
Running Current A 0.31 0.58
Capacitor F/Vac 2.5/400 2.5/370
Fan Type Sirocco Fan Sirocco Fan
No. Used / Diameter EA/inch(mm) 1/7.8(197) 2/7.8(197)
Noise Level(Sound Press,1m) H/M/L dBA 37/34/31 38/36/34
Temperature controller Thermistor Thermistor
Coil Tube Size (OD) inch(mm) 0.276(7.0) 0.276(7.0)
Fins per inch 18 18
No. of Rows & Column 3R,12C 2R, 12C
Dehumidification Rate l/h 1.2 2
Dimensions (W*H*D) Indoor Unit inch(mm) 25.6*9.0*21.1(650*230*535) 39.4*9.0*21.1(1000*230*535)
Net Weight kg(lbs) 22(48.5) 29(63.9)
Piping Liquid inch(mm) 1/4 (6.35) 1/4 (6.35)
Connection Gas inch(mm) 1/2 (12.7) 1/2 (12.7)
Drain hose (ID ) mm 25.4 25.4
Packing Dimension (W*H*D) inch(mm) 29.9*24.6*11.8(760*625*300) 29.9*24.6*11.8(760*625*300)
Stuffing Quantity Without S/Parts 20/40ft 172/356 123/251
Notes:-
Conversion Formula
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB kcal/h = kW x 860
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB Btu/h = kW x 3412
- Interconnecting Piping Length 7.5m cfm = m3/min x 35.3
- Level Difference of Zero.
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. : See the page "Combination Table"

2004 Product Data 81


3. Dimensional Drawings

LMNC-BT, LMNH-BT

A
B

C
E
D
F
H
G

Note:
1. Pipe Specification(mm)
Dimension Model Liquid Gas
A B C D E F G H
Capacity
12k, 18k 6.35 12.7
12k 708 678 434 51 537 455 230 172
(unit: mm)
18k 1060 1030 434 51 535 805 230 172

Top view Front view


(unit: mm)
Inspection hole
(600X600)
Control box

H
600 600
Suitable dimension "H" is necessary to get
a slope to drain as figure

82 TPS Inverter Multi


4. Wiring Diagrams

CENTRAL CONTROL IN-PIPE. OUT-PIPE. ROOM.


REMOTE A/CL PTC
TELE CONTROL THERMISTOR CONTROL THERMISTOR THERMISTOR UNIT HEATER
DRY CONTACT

CN-OUT
CN-CC CN-PIPE1 CN-REMO CN-PIPE2 CN-ROOM CN-AIRC CN-PTC VENTILATION
E/HEATER
ZONE CONTROL

CN-ZONE

5
4

TO OUTDOOR UNIT
RD

3
GN/YL
FLOAT S/W

CN-FLOAT

BL

1(L) 2(N)
BR
FUSE
CN-POWER
CN-DISP
CN-MOTOR CN-DPUMP

OPTION
RF-REMOTE
CONTROL
3854A20419A

CONNECTOR NUMBER LOCATION


CN-POWER AC POWER SUPPLY
CN-MOTOR BLDC FAN MOTOR OUTPUT
CN-D/PUMP DRAIN PUMP OUTPUT
CN-DISP RF-REMOTE CONTROL
CN-FLOAT FLOAT SWITCH INUT
CN-ZONE ZONE CONTROL OUTPUT
CN-CC CENTRAL CONTROL OUTPUT
CN-PIPE1 PIPE SENSOR
CN-PIPE2 DISCHAGE PIPE SENSOR
CN-ROOM ROOM SENSOR
CN-REMO REMOTE CONTROL
CN-AIRC AIR CLEAN
CN-PTC PTC HEATER
CN-OUT VENTILATION/ELECTRIC HEATER

2004 Product Data 83


5. Piping Diagrams

:Cooling
Heat Exchanger :Heating

Sirocco Fan

lndoor unit

: Thermistor

Refrigerant pipe connection port diameter


[unit: mm(inch)]
Model Gas Liquid
LMNC126BTG0
LMNH126BTG0
12.7 (1/2) 6.35 (1/4)
LMNC186BTG0
LMNH186BTG0

84 TPS Inverter Multi


6. E.S.P. Setting for Phase Control Motor

6.1 Ceiling Concealed Duct(LMNC-BT, LMNH-BT Model)

(1) Open the rear cover of the wired remote-controller to set the mode.

(2) Select one of three selectable modes as follows.

Without Zone System


1. Position V-H, F-H:
This position sets the maximum E.S.P as a default set.
2. Position V-L:
This position sets the minimum E.S.P as a default set.

With Zone System


1. Position V-H:
Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
2. Position F-H:
Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers.
3. Position V-L:
Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.

*Maximum: 12k/18k - 3mmAq


Minimum: All-0mmAq

(3) Move the slide switch to set position.

TH R13H R12H OP5R16H OP4


CO1H

R15H
OP2 OP1
R14H OP3 R19H
SW TH R11H

V-H REMO
MAIN
2TH OP7
R18H
R17H
F-H OP6

V-L LO
C070

STAND
HI R03S
R04S

R01S
R02S

SW HIGH

Slide switch for ceiling height

(4) Close the rear cover and check if it works normally.

CAUTION

Select
the position after checking duct work and E.S.P of the unit.
Maunfactured in the position F-H.

2004 Product Data 85


6. E.S.P. Setting for Phase Control Motor

How to Set E.S.P?

Procedure of RPM change:


Ex) External Static pressure is 1mmAq for Model Name "LMNH186BTG0".
To protect the unit, compressor is designed to be off during E.S.P. setting.

Push the "On/Off" button. AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION

1 The unit will start.


Room Temp
HI
MED
LO
AUTO Heater Preheat
JET Defrost Humidify
Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
2 AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
Timer LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Push the "Up" of "Down" button for E.S.P adjustment.


3 And, adjust the number which you want.(In this example, the number is "150".
Refer to the table 6-1) AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Room Temp
HI AUTO Heater Preheat
MED JET Defrost Humidify
LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.

Shift the fan speed mode by pressing the fan speed button.
4 And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "165" and "180" respectively.

Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
5 Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
LO Filter Out door
Timer
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Table-6-1
Static Pressure(mmAq) 0 1 2
Model Name Step(Hi/Med/Lo) Setting Value
10 CMM 210 85 150
LMNC126BTG0
9 CMM 215 190 170
LMNH126BTG0
8 CMM 220 200 175
14 CMM 170 150 130
LMNC186BTG0
13 CMM 185 165 145
LMNH186BTG0
12 CMM 200 180 160

86 TPS Inverter Multi


7. Sound Levels

Overall
Notes:
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
Ceiling
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular

1.5m
room in which the equipment is installed.
2.0m
- The operating conditions are assumed to be standard(KS conditions)
Microphone

Sound Levels(dBA)
Model
H M L
LMNC/H126BTG0 37 34 31
LMNC/H186BTG0 38 36 34

Sound Pressure Level


LMNC/H126BTG0 LMNC/H186BTG0
90 90

80 80

70 70
NC-70 NC-70
Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
NC-20 NC-20

NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

2004 Product Data 87


8. Installation

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air intake vents Remote Controller

Air intake vents Air filters

Required Parts Required Tools


Connecting cable Level
Pipes: Gas side Screw driver
Liquid side Electric drill
Hanging Bolt Hole core drill (70mm)
(W 3/8 or M10 length 650mm)
Flaring Tools set
Insulated drain hose
Torque Wrenches
Additional Drain hose
Hexagonal Wrench (4mm, 5mm)
(Inner Dia .................................25.4mm)
Gas-leak detector
Owners Manual
Thermometer
8.1 Selection of the best location
Inspection hole
Install the air conditioner in the location that satisfies the fol- Top view (600X600)
lowing conditions. (unit: mm) Control box

The place shall easily bear a load exceeding four times the
indoor units weight.
The place shall be able to inspect the unit as the figure. 600 600

The place where the unit shall be leveled.


The place shall allow easy water drainage.(Suitable dimen-
sion H is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit. Front view
The place where the unit is not affected by an electrical
noise.
The place where air circulation in the room will be good . H
There should not be any heat source or steam near the unit.

88 TPS Inverter Multi


8. Installation

8.2 Ceiling dimension and hanging bolt A


location B
Installation of Unit
Install the unit above the ceiling correctly.

C
E
CASE 1

D
POSITION OF SUSPENSION BOLT

Apply a joint-canvas between the unit and duct to absorb


unnecessary vibration.

(Unit:mm)

1-3 mm
G
H
Dimension
Capacity A B C D E F G H
(Btu/h) F
12k 708 678 434 51 537 455 230 172
Drainage hole
18k 1060 1030 434 51 535 805 230 175

M10 Nut X4
(Local
M10 SP. washer X 4 supply)
M10 washer X4

Install the unit leaning to a drainage hole side as a figure


M10 washer X4
for easy water drainage. (Local
M10 SP. washer X 4 supply)
M10 Nut X4
CASE 2
POSITION OF CONSOLE BOLT

A place where the unit will be leveled and that can sup-
port the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.

2004 Product Data 89


8. Installation

Select and mark the position for fixing bolts. Insert the set anchor and washer onto the suspen-
Drill the hole for set anchor on the face of ceiling. sion bolts for locking the suspension bolts on the
ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.
Old building New building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
CAUTION
5 Suspension
Tighten the nut and bolt to prevent unit falling. bolts

8.3 Connecting Cables


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively

Terminal Block in Indoor

1(L) 2(N) 3 4

Connected to Outdoor Unit( or BD Unit)

Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control
panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of
live pin on the power plug should be over 1.8m.

8.4 Insulation
Union for liquid pipe Thermal insulator for refrigerant pipe
(Local supply) Thermal insulator for
Refrigerant pipe and thermal
piping(Local supply)
insulator(Local supply)

Hose clip for thermal insulator


(Local supply)
Overlap with thermal
Thermal insulator for refrigerant pipe insulator for piping.
(Local supply) Hose clip for thermal insulator(Local supply)
Union for gas pipe Make sure that there is no clearance here.

90 TPS Inverter Multi


8. Installation
8.5 Checking the Drainage
Spray one or two glasses of water upon the evapo-
rator.
Ensure that water flows drain hose of indoor unit
without any leakage.

CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view

The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling
1~3mm

CORRECT Drainage hole Drainage hole


INCORRECT

CAUTION FOR GRADIENT OF Lay the drain hose with a downward


UNIT AND DRAIN PIPING inclination so water will drain out.
Thermal insulator
Always lay the drain with downward incli- (Local supply)
nation (1/50 to 1/100).
Drainage pipe
Prevent any upward flow or reverse flow
(Local supply)
in any part. Unit
5mm or thicker formed thermal insulator
shall always be provided for the drain
pipe. Make sure to be closed. Drainage hole

Upward routing not


allowed

INCORRECT
Applied U-Trap Dimension
CORRECT
A 70mm
Install the P-Trap (or U-Trap) to prevent B 2C
C 2 x SP
a water leakage caused by the blocking SP = External Pressure B
of intake air filter. (mmAq) C
Ex) External Pressure
= 10mmAq U-Trap
A 70mm A
B 40mm
C 20mm

2004 Product Data 91


9. Accessories

Standard Accessories

Insulation for Screws for


Name Clamp metal Clamp (Other)
fitting duct flanges

Quantity 1 EA 1 set 1 set 8 EA

Owner's manual
Installation manual

Shape for gas pipe

for liquid pipe

Optional Accessories(For Unit)

No. Item Type Model No. Component Parts

Wireless remote control : 1EA


1 Wireless remote With air purifying Holder : 1EA
AHWRHD
control function Battery : 2EA
Screw : 2EA

2 Drain Pump ABDPG Drain Pump assembly: 1EA

92 TPS Inverter Multi


Part 3
Outdoor Units

MPS Variable Multi

1. Power Supply.....................................................................94
2. Specifications.....................................................................95
3. Combination Table .............................................................98
4. Dimensional Drawings .....................................................100
5. Wiring Diagrams ..............................................................104
6. Piping Diagrams ..............................................................109
7. Capacity Tables ...............................................................114
8. Capacity Coefficient Factor..............................................121
9. Operation Limit ................................................................126
10. Sound Levels .................................................................127
11. Installation......................................................................128
12. Accessories ...................................................................135

2004 Product Data 93


1. Power Supply

Type Outdoor Unit Power Supply


Heat Pump L8UH1008FA0
L4UC608FA0
3, 380-415V, 50Hz
Cooling Only L5UC728FA0
L8UC1008FA0

Note : Power Supply Intake ; Outdoor Unit Only

External wiring procedure


- The power supply work is needed only to the outdoor unit. The power supply to the BD unit and the indoor
unit is conducted through the transmission wiring. Therefore, the power supply work can be carried out at just
one place of the outdoor unit. It will contribute to simplify the work procedure and to save cost.

Power Supply Intake ; 3 , 380-415V, 50Hz


1) Direct Piping Type (100k Btu/h model shown)
[Indoor Unit]
Power source

[Outdoor Unit]
Circuit Breaker
60k: 25A
72k, 100k : 30A

Earth Wire
[Indoor Unit]
2) Distributor Piping Type (100k Btu/h model shown)

BD Unit

Power source

BD Unit
[Outdoor Unit]
Circuit Breaker
60k: 25A
72k, 100k : 30A

Earth Wire

94 MPS(Multi Power System) Variable Multi


2. Specifications

2.1 Outdoor Unit


Model L4UC608FA0 L5UC728FA0
Btu/h 12000~60000 12000~72000
Cooling Capacity W 3517~17581 3517~21097
kcal/h 3024~15120 3024~18143
Btu/h - -
Heating Capacity W - -
kcal/h - -
Input Cooling/Heating W 1300~6100 /- 1300~6600 /-
Running Current Cooling/Heating A 3.4~10.0/3.4~10.0 3.4~11.0/3.4~11.0
Starting Current Cooling/Heating A 24 24
Power Supply ,V,Hz 3,380~415,50 3,380~415,50
Power Factor % 90~91 90~92
Locked Rotor Amp. A 22 24 24
Type Rotary Rotary Rotary
Quantity No 1 1 2
Model QP325Y QP425Y QP425Y
Compressor A+B Maker LG LG LG
(MPS Cycle 1) Capacity kcal/h(Btu/h) 4776(18950) 6212(24650) 6212(24650)
Motor Type Three Phase Induction Motor Three Phase Induction Motor
Motor Input W 1763 2340 2340
Oil Type ATMOS M60/SUNISO 4GSI ATMOS M60/SUNISO 4GSI
Oil Charge cc 700 700
O.L.P Type(model name) Internal Internal
Locked Rotor Amp. A 24 24
Type Rotary Rotary
Quantity No 1 1
Model QP425Y QP425Y
Compressor C Maker LG LG
(MPS Cycle 2) Capacity kcal/h(Btu/h) 6212(24650) 6212(24650)
Motor Type Three Phase Induction Motor Three Phase Induction Motor
Motor Input W 2340 2340
Oil Type ATMOS M60/SUNISO 4GSI ATMOS M60/SUNISO 4GSI
Oil Charge cc 700 700
O.L.P Type(model name) Internal Internal
Charge g(oz) Cycle 1: 2100(74.1), Cycle 2: 1900(67.0) Cycle 1: 3800(134.0), Cycle 2: 1900(67.0)
Refrigerant charge Type R22 R22
Control L.E.V & Short Tube L.E.V & Short Tube
Tube Size (OD) inch(mm) 0.276(7.0) 0.276(7.0)
Coil Fins per inch 18 18
No. of Rows & Column/No. 2R,36C 2R,17C/2 : 2R,36C/2
Output W 123 400
Model AMR250E** ARE676E01
No. of Poles 6 6
Fan Motor Input 230 270
Running Current A 1.44 1.8
Capacitor F/Vac 6/400 10/370
Type Axial FAN Axial FAN
No. Used / Diameter EA/inch(mm) 1/526 1/526
Fan Discharge Side / Top Top Discharge Top Discharge
Speed rpm 900 900
Air Circulation Outdoor CMM(CFM) 85(3002) 90(3179)
Noise Level(Sound Press,1m) dB(A)1 63 60
Liquid(Circuit 1) inch(mm) 1/4(6.35) 3/8(9.52)
Gas(Circuit 1) inch(mm) 5/8(15.88) 3/4(19.05)
SVC Valve Liquid(Circuit 2) inch(mm) 1/4(6.35) 1/4(6.35)
Gas(Circuit 2) inch(mm) 5/8(15.88) 5/8(15.88)
Drain(ID ) mm - -
Dimensions W*H*D inch(mm) 28.0*32.6*27.1(711*828*686) 31.7*59.5*28.7 (806*1512*730)
Net Weight Outdoor kg(lbs) 130(287) 160(353)
Power Supply Cable No.* mm2 5*3.5(Includes earth) 5*3.5(Includes earth)
Interunit Cable No.* mm2 4*0.75(Includes earth) 4*0.75(Includes earth)
Total Piping m 30(Direct piping) / 50(Distributor piping) 30(Direct piping) / 60(Distributor piping)
Max. Interunit Total Main Piping m 25(Distributor piping) 30(Distributor piping)
Piping Length Total Branch Piping m 25(Distributor piping) 30(Distributor piping)
For One Room m 15 15
Max. Installation Indoor Unit~Outdoor Unit m 20 30
Height Difference Indoor Unit~Indoor Unit m 7.5 7.5
Packing Dimension W*H*D inch(mm) 33.5*35.0*30.1(850*890*765) 33.9*61.0*28.7 (860*1550*730)
Stuffing Quantity With(Without) S/Parts 20/40ft 40/84 20/42

Notes: 1. Capacities are based on the following conditions:


Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB - Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
Piping Length - Main Piping Length 5m(Distributor piping)
- Branch Piping Length 5m(Distributor piping)
- Interconnecting Piping Length 7.5 m(Direct piping)
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. : See Page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.

2004 Product Data 95


2. Specifications

Model L8UC1008FA0 L8UH1008FA0


Btu/h 12000~100000 12000~100000
Cooling Capacity W 3517~29307 3517~29307
kcal/h 3024~25200 3024~25200
Btu/h - 12000~100000
Heating Capacity W - 3517~29307
kcal/h - 3024~25200
Input Cooling/Heating W 1300~9500 /- 1300~9500 /1300~9500
Running Current Cooling/Heating A 3.4~15.2/- 3.4~15.2/3.4~15.2
Starting Current Cooling/Heating A - -
Power Supply ,V,Hz 3,380~415,50 3,380~415,50
Power Factor % 90~92 90~92
Locked Rotor Amp. A 24 24
Type Rotary Rotary
Quantity No 2 2
Model QP425Y QP425Y
Compressor A+B Maker LG LG
(MPS Cycle 1) Capacity kcal/h(Btu/h) 6212(24650) 6212(24650)
Motor Type Three Phase Induction Motor Three Phase Induction Motor
Motor Input W 2340 2340
Oil Type ATMOS M60/SUNISO 4GSI ATMOS M60/SUNISO 4GSI
Oil Charge cc 700 700
O.L.P Type(model name) Internal Internal
Locked Rotor Amp. A 24 24
Type Rotary Rotary
Quantity No 2 2
Model QP425Y QP425Y
Compressor C+D Maker LG LG
(MPS Cycle 2) Capacity kcal/h(Btu/h) 6212(24650) 6212(24650)
Motor Type Three Phase Induction Motor Three Phase Induction Motor
Motor Input W 2340 2340
Oil Type ATMOS M60/SUNISO 4GSI ATMOS M60/SUNISO 4GSI
Oil Charge cc 700 700
O.L.P Type(model name) Internal Internal
Charge g(oz) 4000(141.1) / Circuit(Standard piping length) 4000(141.1) / Circuit(Standard piping length)
Refrigerant charge Type R22 R22
Control L.E.V & Short Tube L.E.V & Short Tube
Tube Size (OD) inch(mm) 0.375(9.52) 0.375(9.52)
Coil Fins per inch 18 18
No. of Rows & Column/No. 2R,14C/2 : 1R,30C/2 2R,14C/2 : 1R,30C/2
Output W 400*2 400*2
Model ARE676E01 ARE676E01
No. of Poles 6 6
Fan Motor Input 270*2 270*2
Running Current A 1.8*2 1.8*2
Capacitor F/Vac 10/370 10/370
Type Axial FAN Axial FAN
No. Used / Diameter EA/inch(mm) 2/526 2/526
Fan Discharge Side / Top Top Discharge Top Discharge
Speed rpm 900 900
Air Circulation Outdoor CMM(CFM) 180(6357) 180(6357)
Noise Level(Sound Press,1m) dB(A)1 60 60
Liquid inch(mm) 3/8(9.52)*2EA 3/8(9.52)*2EA
SVC Valve Gas inch(mm) 3/4(19.05)*2EA 3/4(19.05)*2EA
Drain(ID ) mm - -
Dimensions W*H*D inch(mm) 50.4*59.8*28.7(1280*1520*730) 50.4*59.8*28.7(1280*1520*730)
Net Weight Outdoor kg(lbs) 250(551) 250(551)
Power Supply Cable No.* mm2 4*3.5 4*5.5
Interunit Cable No.* mm2 4*0.75(Includes earth) 4*0.75(Includes earth)
Total Piping m 50(Direct piping) / 60(Distributor piping) 50(Direct piping) / 60(Distributor piping)
Max. Interunit Total Main Piping m 30(Distributor piping) 30(Distributor piping)
Piping Length Total Branch Piping m 30(Distributor piping) 30(Distributor piping)
For One Room m 15 15
Max. Installation Indoor Unit~Outdoor Unit m 30 30
Height Difference Indoor Unit~Indoor Unit m 7.5 7.5
Packing Dimension W*H*D inch(mm) 52.0*61.0*29.3(1320*1550*745) 52.0*61.0*29.3(1320*1550*745)
Stuffing Quantity With(Without) S/Parts 20/40ft 12/27 12/27

Notes: 1. Capacities are based on the following conditions:


Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB - Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
Piping Length - Main Piping Length 5m(Distributor piping)
- Branch Piping Length 5m(Distributor piping)
- Interconnecting Piping Length 7.5 m(Direct piping)
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. : See Page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.

96 MPS(Multi Power System) Variable Multi


2. Specifications

2.2 BD Unit
Model PMBD5440L PMBD5430L PMBD5420L
Connectable Indoor Units 1~4 1~3 1~2
Combination(Min~Max.) Btu/h 12000~54000 12000~54000 12000~54000
Casing color Paintingless Paintingless Paintingless
Powre Source 1 , 50/60Hz ,220~240/220V 1 , 50/60Hz ,220~240/220V 1 , 50/60Hz ,220~240/220V
Power Consumption W 10 10 10
Runing Current A 0.05 0.05 0.05
Dimensions W*H*D inch(mm) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252)
Packing Dimension W*H*D inch(mm) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300)
Net Weight kg 5.0 4.9 4.8
Connecting Cable Direction Indoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Direction Outdoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Piping Conntcion Liquid inch(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
(To Outdoor Unit) Gas inch(mm) 3/4(19.05) 3/4(19.05) 3/4(19.05)
Piping Conntcion Liquid inch(mm) 1/4 (6.35)*4 1/4 (6.35)*3 1/4 (6.35)*2
(To Indoor Unit) Gas inch(mm) 1/2 (12.7)*4 1/2 (12.7)*3 1/2 (12.7)*2
Piping Length m - - -
Piping Elevation m - - -
Drain hose Unusable
Heat Insulation Both Liquid and Gas pipes
Accessories Hanger EA 4 4 4
Screw EA 8 8 8
Connector EA - - -
Manual EA 1 1 1

Note :
1. BD unit BD unit, Indoor Unit Indoor Unit : Max. Height - 10m
Set up the BD unit and Indoor Unit in 15m.
2. The piping connection must be suit the piping sizes of the indoor unit which will be connected.
(If need, use the connector which is included in the indoor unit)
3. The BD unit should be installed inside the building.

2004 Product Data 97


3. Combination Table

3.1 L4UC608FA0
Cooling
Combination of Indoor unit Cooling
Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1Unit 36 - - - 36 36000 - - - 36000 4500 7.2
12 18 - - 30 12000 18000 - - 30000 4400 7
1 2Unit 12 24 - - 36 12000 24000 - - 36000 4500 7.2
18 18 - - 36 18000 18000 - - 36000 4500 7.2
3Unit 12 12 12 - 36 12000 12000 12000 - 36000 4500 7.2
2 1Unit 24 - - - 24 24000 - - - 24000 2900 4.6
Notes:
1. Cooling Capacity is based on : indoor temp.27C(80.6F) DB, 19C(66.2F) WB; outdoor temp. 35C(95F) DB
2. The total capacity of indoor unit of "Circuit 1" is up to 36000 Btu/h (10.6kW).
The total capacity of indoor unit of "Circuit 2" is up to 24000 Btu/h (7.1kW).
3. The capacity is based on standard length of interconnecting refrigerant line.
[Standard length : Direct Piping - 7.5m (25ft), Distributor Piping - Main 5m(16.4ft), Branch 5m (16.4ft)]

3.2 L5UC728FA0
Cooling
Combination of Indoor unit Cooling
Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1Unit 48 - - - 48 48000 - - - 48000 5300 8.5
12 36 - - 48 12000 36000 - - 48000 5300 8.5
18 18 - - 36 18000 18000 - - 36000 3800 6
18 24 - - 42 18000 24000 - - 42000 4500 7.2
2Unit 18 30 - - 48 18000 30000 - - 48000 5300 8.5
18 36 - - 54 16000 34000 - - 50000 5400 8.6
24 30 - - 54 22000 28000 - - 50000 5400 8.6
24 24 - - 48 24000 24000 - - 48000 5300 8.5
1 12 12 12 - 36 12000 12000 12000 - 36000 3800 6
12 12 18 - 42 12000 12000 18000 - 42000 4500 7.2
12 12 24 - 48 12000 12000 24000 - 48000 5300 8.5
3Unit 12 12 30 - 54 11110 11110 27780 - 50000 5400 8.6
12 18 18 - 48 12000 18000 18000 - 48000 5300 8.5
12 18 24 - 54 11110 16670 22220 - 50000 5400 8.6
18 18 18 - 54 16670 16670 16670 - 50000 5400 8.6
12 12 12 12 48 12000 12000 12000 12000 48000 5300 8.5
4Unit
12 12 12 18 54 11000 11000 11000 17000 50000 5400 8.6
2 1Unit 24 - - - 24 24000 - - - 24000 2700 4.4
Notes:
1. Cooling Capacity is based on : indoor temp.27C(80.6F) DB, 19C(66.2F) WB; outdoor temp. 35C(95F) DB
2. The total capacity of indoor unit of "Circuit 1" is up to 54000 Btu/h (15.8kW).
The total capacity of indoor unit of "Circuit 2" is up to 24000 Btu/h (7.1kW).
3. The capacity is based on standard length of interconnecting refrigerant line.
[Standard length : Direct Piping - 7.5m (25ft), Distributor Piping - Main 5m(16.4ft), Branch 5m (16.4ft)]

98 MPS(Multi Power System) Variable Multi


3. Combination Table
3.3 L8UC1008FA0/L8UH1008FA0
Cooling

Combination of Indoor unit Cooling


Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1 Unit 48 - - - 48 48000 - - - 48000 5300 8.5
12 36 - - 48 12000 36000 - - 48000 5300 8.5
18 18 - - 36 18000 18000 - - 36000 3800 6.0
18 24 - - 42 18000 24000 - - 42000 4500 7.2
2 Unit 18 30 - - 48 18000 30000 - - 48000 5300 8.5
18 36 - - 54 16000 34000 - - 50000 5400 8.6
24 30 - - 54 22000 28000 - - 50000 5400 8.6
1 24 24 - - 48 24000 24000 - - 48000 5300 8.5
or 12 12 12 - 36 12000 12000 12000 - 36000 3800 6.0
2 12 12 18 - 42 12000 12000 18000 - 42000 4500 7.2
12 12 24 - 48 12000 12000 24000 - 48000 5300 8.5
3 Unit 12 12 30 - 54 11110 11110 27780 - 50000 5400 8.6
12 18 18 - 48 12000 18000 18000 - 48000 5300 8.5
12 18 24 - 54 11110 16670 22220 - 50000 5400 8.6
18 18 18 - 54 16670 16670 16670 - 50000 5400 8.6
12 12 12 12 48 12000 12000 12000 12000 48000 5300 8.5
4 Unit
12 12 12 18 54 11000 11000 11000 17000 50000 5400 8.6

Heating
Combination of Indoor unit Heating
Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1 Unit 48 - - - 48 48000 - - - 48000 4600 7.3
12 36 - - 48 12000 36000 - - 48000 4600 7.3
18 18 - - 36 18000 18000 - - 36000 3100 4.9
18 24 - - 42 18000 24000 - - 42000 3800 6.0
2 Unit 18 30 - - 48 18000 30000 - - 48000 4600 7.3
18 36 - - 54 16000 34000 - - 50000 4700 7.5
24 30 - - 54 22000 28000 - - 50000 4700 7.5
1 24 24 - - 48 24000 24000 - - 48000 4600 7.3
or 12 12 12 - 36 12000 12000 12000 - 36000 3100 4.9
2 12 12 18 - 42 12000 12000 18000 - 42000 3800 6.0
12 12 24 - 48 12000 12000 24000 - 48000 4600 7.3
3 Unit 12 12 30 - 54 11110 11110 27780 - 50000 4700 7.5
12 18 18 - 48 12000 18000 18000 - 48000 4600 7.3
12 18 24 - 54 11110 16670 22220 - 50000 4700 7.5
18 18 18 - 54 16670 16670 16670 - 50000 4700 7.5
12 12 12 12 48 12000 12000 12000 12000 48000 4600 7.3
4 Unit
12 12 12 18 54 11000 11000 11000 17000 50000 4700 7.5

Notes:
1. Cooling Capacity is based on : indoor temp.27C(80.6F) DB, 19C(66.2F) WB; outdoor temp. 35C(95F) DB
2. Heating Capacity is based on : indoor temp.20C(60F) DB; outdoor temp. 7C(44.6F) DB, 6C(42.8F) WB
3. The total capacity of indoor unit is up to 54000 Btu/h (15.8kW) per circuit.
4. The capacity is based on standard length of interconnecting refrigerant line.
[Standard length : Direct Piping - 7.5m (25ft), Distributor Piping - Main 5m(16.4ft), Branch 5m (16.4ft)]

2004 Product Data 99


4. Dimensional Drawings

4.1 Outdoor Unit

L4UC608FA0

W D

(unit : mm)

Model
L4UC608FA0
Dimension
W 711
H 828
D 687

Number Name Descripition


1 Liquid side service valve(mm) 6.35 x 2EA
2 Gas side service valve(mm) 15.88 x 2EA
3 Control Cover
4 Air discharge grill
5 Air inlet

100 MPS(Multi Power System) Variable Multi


4. Dimensional Drawings

L5UC728FA0

806
153 500(bolt hole) 153
15
700(bolt hole)
730

690

Air outlet
40

Air
inlet

Air
inlet
1444
1512

Service Panel
670

Knockout hole
(For the control wiring,
the power supply,
refrigerant connecting
pipe)
100

220
28

Knockout hole
(For the control wiring, the power supply,
refrigerant connecting pipe) (Unit : mm)

2004 Product Data 101


4. Dimensional Drawings

L8UC1008FA0/L8UH1008FA0

L4
L3
L2
D

L7
H

L1
L6

D
L8

Model
L8UC1008FA0, L8UH1008FA0
Dimensions
W mm 1,280
H mm 1,520
D mm 730
L1 mm 1,444
L2 mm 700
L3 mm 690
L4 mm 900
L5 mm 10
L6 mm 670
L7 mm 48
L8 mm 28

102 MPS(Multi Power System) Variable Multi


4. Dimensional Drawings

4.2 BD Unit

PMBD5420L, PMBD5430L, PMBD5440L

(Unit: mm)
6.35 flare
12.7 flare
(298)

(337)
9.52 flare
250

19.05 flare

245
Suspension bolt pitch.

Main Pipe
(36) 50 50 50 40 30 50
(150)
(38) 50

(111)

(56) 50 50 50 45 300 50
Branch Pipe Cover Control

Min 400 Min 400


(Servicing space)
Min 30

Min 300

Inspection opening

2004 Product Data 103


5. Wiring Diagrams

5.1 Outdoor Unit


L4UC608FA0

OUTDOOR WIRING DIAGRAM

MAGNETIC CONTACTOR
BK
U
WH
V
LEV
W RD

COMP(A)
WH
RD

BK

1
BL

CN-COMP
CN-LEV-SINGLE
(BL)
MAGNETIC CONTACTOR
RD

3
BK

(RD)
U
WH
V
W RD

COMP(B)
MAIN PCB ASSY
BR
WH
RD

BK

(COMP-S)CN-FAN1(4WAY-S)
(WH)

MAGNETIC CONTACTOR
BK
U
WH
V BK
W RD BL
COMP(C) CN-FAN2
BR
YL
FMo
(WH) OR

(WH)

FUSE 250V

(OUT(AIR)) (PIPE S,DISCHARGE)


T3.15A
CN_TH2

(YL)
CN_TH1

CN_POWER CN_COM
3 1 1 2 3 4 5 6 (WH) (RD)
(WH)
OR

RD
BR

BL

BK

WH
OR
RD GN/YL
BL GN/YL
BK BK

BR BR BR BL OR

TB1 HP LP

R S T N 1(L) 2(N) 3(A) 1(L) 2(N) 3(B)

GN/YL

Main Power
TO INDOOR TO INDOOR
380-415V3N~50Hz UNIT-A UNIT-B
(DISTRIBUTOR)

NOTE
LEV LINEAR EXPANSION VALVE
FMo FAN MOTOR CN/YL GREEN & YELLOW
COMP COMPRESSOR OR ORANGE
BK BLACK RD RED
BR BROWN WH WHITE
BL BLUE YL YELLOW
3854A20392H

104 MPS(Multi Power System) Variable Multi


5. Wiring Diagrams

L5UC728FA0

OUTDOOR WIRING DIAGRAM

BK
WH
RD

CN_COMP CN_3PHASE
MAGNETIC CONTACTOR
BK
U OR OR
WH BL BL
V CN_FAN1 BK BK
W RD BR BR
FAN1
YL YL
COMP (C) BL
YL BK
RD BL BK SV Solenoid Valve2
RD
TB2
CN_4,S
BK
BL BK SV Solenoid Valve1
MAGNETIC CONTACTOR MAIN
BK
U
PCB
WH
V
W RD
COMP (B)

WH
WH

WH
RD

RD
BK

BK

CN_PRESS
MAGNETIC CONTACTOR
BK
U
WH
V
W RD
COMP (A)
CN_COM CN_POWER CN_TH1 CN_TH2 CN_TH3
BL

BK
WH

BK

BL
BR

BK

WH (AIR/PIPE A,B) (PIPE C,D/COMP A,B) (COMP C,D)

RD
BL
BL BL
BR BR BR

R S T N 3(L) 4(N) 5(A) 3(L) 4(N) 5(B)

GN/YL

A ROOM B ROOM
Main Power
TO INDOOR UNIT (DISTRIBUTOR)

NOTE
LEV LINEAR EXPANSION VALVE
FMo FAN MOTOR CN/YL GREEN & YELLOW
COMP COMPRESSOR OR ORANGE
BK BLACK RD RED
BR BROWN WH WHITE
BL BLUE YL YELLOW

2004 Product Data 105


5. Wiring Diagrams

L8UH1008FA0

OUTDOOR WIRING DIAGRAM

MAGNETIC CONTACTOR BK RELAY


BK
U WH 1 2
WH
V RD 3 4
W RD
5 6
COMP (D) BL
BL 7 8

BR
WH
RD

BK

OR OR
CN_COMP CN_3PHASE BL BL
CN_FAN2 BK BK
BR BR FAN2
MAGNETIC CONTACTOR BK YL YL
BK
TB1
U OR OR
WH BL BL
V CN_FAN1 BK BK
W RD BR BR
FAN1
YL YL
COMP (C) BL
YL BK
RD BL BK SV Solenoid Valve2
RD
TB2
CN_4,S WH
BK
BK BL BK SV Solenoid Valve1
MAGNETIC CONTACTOR MAIN
BK
U
PCB
WH BL BK
V BK 4WV 4Way Valve2
W RD
COMP (B)
BL BK
WH BK 4WV 4Way Valve1
WH

WH
RD

RD
BK

BK

CN_PRESS
MAGNETIC CONTACTOR
BK
U
WH
V
W RD
COMP (A)
CN_COM CN_POWER CN_TH1 CN_TH2 CN_TH3
BL

BK
WH

BK

BL
BR

BK

WH (AIR/PIPE A,B) (PIPE C,D/COMP A,B) (COMP C,D)

RD
BL
BL BL
BR BR BR

R S T N 3(L) 4(N) 5(A) 3(L) 4(N) 5(B)

GN/YL

A ROOM B ROOM
Main Power
TO INDOOR UNIT (DISTRIBUTOR)

3854A20354S

106 MPS(Multi Power System) Variable Multi


5. Wiring Diagrams

L8UC1008FA0

OUTDOOR WIRING DIAGRAM

MAGNETIC CONTACTOR BK RELAY


BK
U WH 1 2
WH
V RD 3 4
W RD
5 6
COMP (D) BL
BL 7 8

BR
WH
RD

BK

OR OR
CN_COMP CN_3PHASE BL BL
CN_FAN2 BK BK
BR BR FAN2
BK YL YL
MAGNETIC CONTACTOR
BK
TB1
U OR OR
WH BL BL
V CN_FAN1 BK BK
W RD BR BR
FAN1
YL YL
COMP (C) BL
YL BK
RD BL BK SV Solenoid Valve2
RD
TB2
CN_4,S
BK
BL BK SV Solenoid Valve1
MAGNETIC CONTACTOR MAIN
BK
U
PCB
WH
V
W RD
COMP (B)

WH
WH

WH
RD

RD
BK

BK

CN_PRESS
MAGNETIC CONTACTOR
BK
U
WH
V
W RD
COMP (A)
CN_COM CN_POWER CN_TH1 CN_TH2 CN_TH3
BL

BK
WH

BK

BL
BR

BK

WH (AIR/PIPE A,B) (PIPE C,D/COMP A,B) (COMP C,D)

RD
BL
BL BL
BR BR BR

R S T N 3(L) 4(N) 5(A) 3(L) 4(N) 5(B)

GN/YL

A ROOM B ROOM
Main Power
380-415V3N~50Hz TO INDOOR UNIT (DISTRIBUTOR)

3854A20354V

2004 Product Data 107


5. Wiring Diagrams

5.2 BD Unit

PMBD5420L, PMBD5430L, PMBD5440L

WIRING DIAGRAM

CN_JIG3 CN_JIG2 LED1 LED2 LED3 LED4 PCB PARTS LAYOUT

CN_JIG1

FUSE_2 FUSE_3 FUSE_4 FUSE_5 FUSE_1

CN_LEV_A CN_LEV_B CN_LEV_C CN_LEV_D CN_ROOM_A CN_ROOM_B CN_ROOM_C CN_ROOM_D CN_PWR


S N L S N L S N L S N L S N L

LEV LEV LEV LEV


A B C D A B C D OUTDOOR

FROM OUTDOOR
TO INDOOR UNIT
UNIT

TROUBLE DIAGNOSIS

LED DIAGNOSIS

NORMAL

ABNORMALITY -->CHECK BRANCH DISTRIBUTOR UNIT

ABNORMALITY -->CHECK INDOOR OR OUTDOOR UNIT


CHECK CONNECTING CABLE

3854A22003A

Notes;
1. 'PMBD5420L' unit : "A,B" parts available.
2. 'PMBD5430L' unit : "A,B,C" parts available.
3. 'PMBD5440L' unit : "A, B, C, D" parts available.

108 MPS(Multi Power System) Variable Multi


6. Piping Diagrams

6.1 Outdoor Unit


L4UC608FA0

OUTDOOR UNIT

Field Piping
Gas (15.88)

Field Piping
Liquid (6.35) Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor A Compressor B

Field Piping
Gas (15.88)

Field Piping
Liquid (6.35) LEV Heat
Exchanger

Compressor C

Refrigerant Flow

Cooling

2004 Product Data 109


6. Piping Diagrams

L5UC728FA0
OUTDOOR UNIT

Field Piping
Gas (19.05)

Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor A Compressor B

Field Piping
Gas (15.88)

Field Piping
Liquid (6.35) LEV Heat
Exchanger

Compressor C

Refrigerant Flow

Cooling

110 MPS(Multi Power System) Variable Multi


6. Piping Diagrams

L8UC1008FA0
OUTDOOR UNIT

Field Piping
Gas (19.05)

Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor A Compressor B

Field Piping
Gas (19.05)

Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor C Compressor D

Refrigerant Flow

Cooling

2004 Product Data 111


6. Piping Diagrams

L8UH1008FA0
OUTDOOR UNIT
Reversing
Valve
Field Piping
Gas (19.05)

Field Piping
Liquid (9.52) LEV Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor A Compressor B

Field Piping
Gas (19.05)

Field Piping
Liquid (9.52) LEV Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor C Compressor D

Refrigerant Flow

Cooling
Heating

112 MPS(Multi Power System) Variable Multi


6. Piping Diagrams

6.2 BD Unit

Refrigerant Flow

Cooling
Heating

19.05 Main Gas


Piping

Outdoor
Unit
9.52 Main Liquid
Piping
12.7
D Gas
12.7 LEV-A
C Gas

B Gas 12.7
LEV-B
12.7
A Gas

LEV-C

Indoor
Unit LEV-D

6.35
D Liquid

6.35
C Liquid

6.35
B Liquid

6.35
A Liquid

(Unit : mm)

Notes;
1. Flare connection for the field piping connection
2. Adjust to indoor unit and outdoor unit piping size. Use the connector if the pipe size is
not matched when connecting indoor unit.
3. L.E.V.: Linear Expansion Valve
4. PMBD5420L : A, B
PMBD5430L : A, B, C
PMBD5440L : A, B, C, D

2004 Product Data 113


7. Capacity Table

7.1 L4UC608FA0
[Cooling Capacity(English Unit)]

Combination Outdoor Indoor Air Temp.: FWB


Circuit Capacity Index Air Temp.: 57 61 64 66 72 75
(kBtu/h) FDB TC PI TC PI TC PI TC PI TC PI TC PI
70 34.3 3.08 36.8 3.13 38.3 3.17 39.7 3.23 41.6 3.28 42.6 3.32
75 33.8 3.38 36.3 3.44 37.8 3.48 39.1 3.55 41.0 3.6 41.9 3.64
85 32.6 3.88 34.9 3.95 36.4 4.0 37.7 4.07 39.5 4.13 40.4 4.18
36 95 31.2 4.29 33.4 4.36 34.8 4.42 36.0 4.5 37.7 4.57 38.6 4.62
105 29.8 4.59 31.9 4.67 33.2 4.73 34.4 4.82 36.1 4.89 36.9 4.95
115 28.1 4.85 30.1 4.94 31.4 5.0 32.5 5.09 34.0 5.17 34.8 5.23
125 26.1 5.07 27.9 5.16 29.1 5.23 30.1 5.32 31.6 5.4 32.3 5.47
70 28.6 3.01 30.6 3.06 31.9 3.1 33.1 3.16 34.7 3.2 35.5 3.24
75 28.2 3.31 30.2 3.36 31.5 3.41 32.6 3.47 34.2 3.52 35.0 3.56
85 27.2 3.79 29.1 3.86 30.3 3.91 31.4 3.98 32.9 4.04 33.7 4.09
12+18 95 26.0 4.19 27.8 4.27 29.0 4.32 30.0 4.4 31.4 4.46 32.2 4.52
105 24.8 4.49 26.6 4.57 27.7 4.62 28.7 4.71 30.1 4.78 30.8 4.84
115 23.4 4.75 25.1 4.83 26.1 4.89 27.1 4.98 28.4 5.05 29.0 5.11
125 21.7 4.96 23.3 5.05 24.2 5.11 25.1 5.21 26.3 5.28 26.9 5.35
70 34.3 3.08 36.8 3.13 38.3 3.17 39.7 3.23 41.6 3.28 42.6 3.32
75 33.8 3.38 36.3 3.44 37.8 3.48 39.1 3.55 41.0 3.6 41.9 3.64
85 32.6 3.88 34.9 3.95 36.4 4.0 37.7 4.07 39.5 4.13 40.4 4.18
1 12+24 95 31.2 4.29 33.4 4.36 34.8 4.42 36.0 4.5 37.7 4.57 38.6 4.62
105 29.8 4.59 31.9 4.67 33.2 4.73 34.4 4.82 36.1 4.89 36.9 4.95
115 28.1 4.85 30.1 4.94 31.4 5.0 32.5 5.09 34.0 5.17 34.8 5.23
125 26.1 5.07 27.9 5.16 29.1 5.23 30.1 5.32 31.6 5.4 32.3 5.47
70 34.3 3.08 36.8 3.13 38.3 3.17 39.7 3.23 41.6 3.28 42.6 3.32
75 33.8 3.38 36.3 3.44 37.8 3.48 39.1 3.55 41.0 3.6 41.9 3.64
85 32.6 3.88 34.9 3.95 36.4 4.0 37.7 4.07 39.5 4.13 40.4 4.18
18+18 95 31.2 4.29 33.4 4.36 34.8 4.42 36.0 4.5 37.7 4.57 38.6 4.62
105 29.8 4.59 31.9 4.67 33.2 4.73 34.4 4.82 36.1 4.89 36.9 4.95
115 28.1 4.85 30.1 4.94 31.4 5.0 32.5 5.09 34.0 5.17 34.8 5.23
125 26.1 5.07 27.9 5.16 29.1 5.23 30.1 5.32 31.6 5.4 32.3 5.47
70 34.3 3.08 36.8 3.13 38.3 3.17 39.7 3.23 41.6 3.28 42.6 3.32
75 33.8 3.38 36.3 3.44 37.8 3.48 39.1 3.55 41.0 3.6 41.9 3.64
85 32.6 3.88 34.9 3.95 36.4 4.0 37.7 4.07 39.5 4.13 40.4 4.18
12+12+12 95 31.2 4.29 33.4 4.36 34.8 4.42 36.0 4.5 37.7 4.57 38.6 4.62
105 29.8 4.59 31.9 4.67 33.2 4.73 34.4 4.82 36.1 4.89 36.9 4.95
115 28.1 4.85 30.1 4.94 31.4 5.0 32.5 5.09 34.0 5.17 34.8 5.23
125 26.1 5.07 27.9 5.16 29.1 5.23 30.1 5.32 31.6 5.4 32.3 5.47
70 22.9 1.98 24.5 2.02 25.5 2.04 26.4 2.08 27.7 2.11 28.4 2.14
75 22.6 2.18 24.2 2.22 25.2 2.24 26.1 2.29 27.3 2.32 28.0 2.35
85 21.7 2.5 23.3 2.54 24.3 2.58 25.1 2.62 26.3 2.66 27.0 2.69
2 24 95 20.8 2.76 22.2 2.81 23.2 2.85 24.0 2.9 25.2 2.94 25.7 2.98
105 19.9 2.96 21.3 3.01 22.2 3.05 22.9 3.1 24.0 3.15 24.6 3.19
115 18.7 3.13 20.1 3.18 20.9 3.22 21.7 3.28 22.7 3.33 23.2 3.37
125 17.4 3.27 18.6 3.33 19.4 3.37 20.1 3.43 21.0 3.48 21.5 3.52

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping - 16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC : Total Cooling Capacity(1,000 Btu/h)
4. PI : Power Input(kW)

114 MPS(Multi Power System) Variable Multi


7. Capacity Table

7.2 L5UC728FA0
[Cooling Capacity(English Unit)]

Combination Outdoor Indoor Air Temp.: FWB


Circuit Capacity Index Air Temp.: 57 61 64 66 72 75
(kBtu/h) FDB TC PI TC PI TC PI TC PI TC PI TC PI
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
48 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+36 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 34.3 2.6 36.8 2.64 38.3 2.68 39.7 2.73 41.6 2.77 42.6 2.8
75 33.8 2.86 36.3 2.9 37.8 2.94 39.1 3.0 41.0 3.04 41.9 3.08
85 32.6 3.28 34.9 3.33 36.4 3.37 37.7 3.44 39.5 3.49 40.4 3.53
18+18 95 31.2 3.62 33.4 3.68 34.8 3.73 36.0 3.8 37.7 3.85 38.6 3.9
105 29.8 3.88 31.9 3.94 33.2 3.99 34.4 4.07 36.1 4.13 36.9 4.18
115 28.1 4.1 30.1 4.17 31.4 4.22 32.5 4.3 34.0 4.36 34.8 4.42
125 26.1 4.28 27.9 4.36 29.1 4.41 30.1 4.5 31.6 4.56 32.3 4.62
70 40.1 3.08 42.9 3.13 44.7 3.17 46.3 3.23 48.5 3.28 49.6 3.32
75 39.5 3.38 42.3 3.44 44.1 3.48 45.6 3.55 47.8 3.6 48.9 3.64
85 38.1 3.88 40.8 3.95 42.5 4.0 44.0 4.07 46.1 4.13 47.2 4.18
18+24 95 36.4 4.29 38.9 4.36 40.6 4.42 42.0 4.5 44.0 4.57 45.0 4.62
105 34.7 4.59 37.2 4.67 38.8 4.73 40.1 4.82 42.1 4.89 43.1 4.95
115 32.8 4.85 35.1 4.94 36.6 5.0 37.9 5.09 39.7 5.17 40.6 5.23
125 30.4 5.07 32.6 5.16 33.9 5.23 35.1 5.32 36.8 5.4 37.7 5.47
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
18+30 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
1
70 47.7 3.7 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.8 52.3 4.88 54.9 4.96 56.1 5.02
18+36 95 43.3 5.15 46.4 5.23 48.3 5.3 50.0 5.4 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.6 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.0 45.1 6.11 47.3 6.2 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 47.7 3.7 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.8 52.3 4.88 54.9 4.96 56.1 5.02
24+30 95 43.3 5.15 46.4 5.23 48.3 5.3 50.0 5.4 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.6 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.0 45.1 6.11 47.3 6.2 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
24+24 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 34.3 2.6 36.8 2.64 38.3 2.68 39.7 2.73 41.6 2.77 42.6 2.8
75 33.8 2.86 36.3 2.9 37.8 2.94 39.1 3.0 41.0 3.04 41.9 3.08
85 32.6 3.28 34.9 3.33 36.4 3.37 37.7 3.44 39.5 3.49 40.4 3.53
12+12+12 95 31.2 3.62 33.4 3.68 34.8 3.73 36.0 3.8 37.7 3.85 38.6 3.9
105 29.8 3.88 31.9 3.94 33.2 3.99 34.4 4.07 36.1 4.13 36.9 4.18
115 28.1 4.1 30.1 4.17 31.4 4.22 32.5 4.3 34.0 4.36 34.8 4.42
125 26.1 4.28 27.9 4.36 29.1 4.41 30.1 4.5 31.6 4.56 32.3 4.62
70 40.1 3.08 42.9 3.13 44.7 3.17 46.3 3.23 48.5 3.28 49.6 3.32
75 39.5 3.38 42.3 3.44 44.1 3.48 45.6 3.55 47.8 3.6 48.9 3.64
85 38.1 3.88 40.8 3.95 42.5 4.0 44.0 4.07 46.1 4.13 47.2 4.18
12+12+18 95 36.4 4.29 38.9 4.36 40.6 4.42 42.0 4.5 44.0 4.57 45.0 4.62
105 34.7 4.59 37.2 4.67 38.8 4.73 40.1 4.82 42.1 4.89 43.1 4.95
115 32.8 4.85 35.1 4.94 36.6 5.0 37.9 5.09 39.7 5.17 40.6 5.23
125 30.4 5.07 32.6 5.16 33.9 5.23 35.1 5.32 36.8 5.4 37.7 5.47

2004 Product Data 115


7. Capacity Table

Combination Outdoor Indoor Air Temp.: FWB


Circuit Capacity Index Air Temp.: 57 61 64 66 72 75
(kBtu/h) FDB TC PI TC PI TC PI TC PI TC PI TC PI
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+12+24 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.7 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.8 52.3 4.88 54.9 4.96 56.1 5.02
12+12+30 95 43.3 5.15 46.4 5.23 48.3 5.3 50.0 5.4 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.6 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.0 45.1 6.11 47.3 6.2 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+18+18 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.7 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.8 52.3 4.88 54.9 4.96 56.1 5.02
1 12+18+24 95 43.3 5.15 46.4 5.23 48.3 5.3 50.0 5.4 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.6 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.0 45.1 6.11 47.3 6.2 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 47.7 3.7 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.8 52.3 4.88 54.9 4.96 56.1 5.02
18+18+18 95 43.3 5.15 46.4 5.23 48.3 5.3 50.0 5.4 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.6 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.0 45.1 6.11 47.3 6.2 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.1 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+12+12+12 95 41.5 5.05 44.5 5.14 46.4 5.2 48.0 5.3 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.5 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.0 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.7 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.8 52.3 4.88 54.9 4.96 56.1 5.02
12+12+12+18 95 43.3 5.15 46.4 5.23 48.3 5.3 50.0 5.4 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.6 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.0 45.1 6.11 47.3 6.2 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 22.9 1.85 24.5 1.88 25.5 1.9 26.4 1.94 27.7 1.97 28.4 1.99
75 22.6 2.03 24.2 2.06 25.2 2.09 26.1 2.13 27.3 2.16 28.0 2.19
85 21.7 2.33 23.3 2.37 24.3 2.4 25.1 2.44 26.3 2.48 27.0 2.51
2 24 95 20.8 2.57 22.2 2.62 23.2 2.65 24.0 2.7 25.2 2.74 25.7 2.77
105 19.9 2.75 21.3 2.8 22.2 2.84 22.9 2.89 24.0 2.93 24.6 2.97
115 18.7 2.91 20.1 2.96 20.9 3.0 21.7 3.06 22.7 3.1 23.2 3.14
125 17.4 3.04 18.6 3.1 19.4 3.14 20.1 3.19 21.0 3.24 21.5 3.28

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping -16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC : Total Cooling Capacity(1,000 Btu/h)
4. PI : Power Input(kW)

116 MPS(Multi Power System) Variable Multi


7. Capacity Table

7.3 L8UC1008FA0/L8UH1008FA0
[Cooling Capacity(English Unit)]

Combination Outdoor Indoor Air Temp.: FWB


Capacity Index Air Temp.: 57 61 64 66 72 75
(kBtu/h) FDB TC PI TC PI TC PI TC PI TC PI TC PI
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
48 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+36 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 34.3 2.60 36.8 2.64 38.3 2.68 39.7 2.73 41.6 2.77 42.6 2.80
75 33.8 2.86 36.3 2.90 37.8 2.94 39.1 3.00 41.0 3.04 41.9 3.08
85 32.6 3.28 34.9 3.33 36.4 3.37 37.7 3.44 39.5 3.49 40.4 3.53
18+18 95 31.2 3.62 33.4 3.68 34.8 3.73 36.0 3.80 37.7 3.85 38.6 3.90
105 29.8 3.88 31.9 3.94 33.2 3.99 34.4 4.07 36.1 4.13 36.9 4.18
115 28.1 4.10 30.1 4.17 31.4 4.22 32.5 4.30 34.0 4.36 34.8 4.42
125 26.1 4.28 27.9 4.36 29.1 4.41 30.1 4.50 31.6 4.56 32.3 4.62
70 40.1 3.08 42.9 3.13 44.7 3.17 46.3 3.23 48.5 3.28 49.6 3.32
75 39.5 3.38 42.3 3.44 44.1 3.48 45.6 3.55 47.8 3.60 48.9 3.64
85 38.1 3.88 40.8 3.95 42.5 4.00 44.0 4.07 46.1 4.13 47.2 4.18
18+24 95 36.4 4.29 38.9 4.36 40.6 4.42 42.0 4.50 44.0 4.57 45.0 4.62
105 34.7 4.59 37.2 4.67 38.8 4.73 40.1 4.82 42.1 4.89 43.1 4.95
115 32.8 4.85 35.1 4.94 36.6 5.00 37.9 5.09 39.7 5.17 40.6 5.23
125 30.4 5.07 32.6 5.16 33.9 5.23 35.1 5.32 36.8 5.40 37.7 5.47
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
18+30 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.70 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.80 52.3 4.88 54.9 4.96 56.1 5.02
18+36 95 43.3 5.15 46.4 5.23 48.3 5.30 50.0 5.40 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.60 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.00 45.1 6.11 47.3 6.20 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 47.7 3.70 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.80 52.3 4.88 54.9 4.96 56.1 5.02
24+30 95 43.3 5.15 46.4 5.23 48.3 5.30 50.0 5.40 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.60 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.00 45.1 6.11 47.3 6.20 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
24+24 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 34.3 2.60 36.8 2.64 38.3 2.68 39.7 2.73 41.6 2.77 42.6 2.80
75 33.8 2.86 36.3 2.90 37.8 2.94 39.1 3.00 41.0 3.04 41.9 3.08
85 32.6 3.28 34.9 3.33 36.4 3.37 37.7 3.44 39.5 3.49 40.4 3.53
12+12+12 95 31.2 3.62 33.4 3.68 34.8 3.73 36.0 3.80 37.7 3.85 38.6 3.90
105 29.8 3.88 31.9 3.94 33.2 3.99 34.4 4.07 36.1 4.13 36.9 4.18
115 28.1 4.10 30.1 4.17 31.4 4.22 32.5 4.30 34.0 4.36 34.8 4.42
125 26.1 4.28 27.9 4.36 29.1 4.41 30.1 4.50 31.6 4.56 32.3 4.62
70 40.1 3.08 42.9 3.13 44.7 3.17 46.3 3.23 48.5 3.28 49.6 3.32
75 39.5 3.38 42.3 3.44 44.1 3.48 45.6 3.55 47.8 3.60 48.9 3.64
85 38.1 3.88 40.8 3.95 42.5 4.00 44.0 4.07 46.1 4.13 47.2 4.18
12+12+18 95 36.4 4.29 38.9 4.36 40.6 4.42 42.0 4.50 44.0 4.57 45.0 4.62
105 34.7 4.59 37.2 4.67 38.8 4.73 40.1 4.82 42.1 4.89 43.1 4.95
115 32.8 4.85 35.1 4.94 36.6 5.00 37.9 5.09 39.7 5.17 40.6 5.23
125 30.4 5.07 32.6 5.16 33.9 5.23 35.1 5.32 36.8 5.40 37.7 5.47

2004 Product Data 117


7. Capacity Table

Combination Outdoor Indoor Air Temp.: FWB


Capacity Index Air Temp.: 57 61 64 66 72 75
(kBtu/h) FDB TC PI TC PI TC PI TC PI TC PI TC PI
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+12+24 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.70 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.80 52.3 4.88 54.9 4.96 56.1 5.02
12+12+30 95 43.3 5.15 46.4 5.23 48.3 5.30 50.0 5.40 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.60 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.00 45.1 6.11 47.3 6.20 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+18+18 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.70 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.80 52.3 4.88 54.9 4.96 56.1 5.02
12+18+24 95 43.3 5.15 46.4 5.23 48.3 5.30 50.0 5.40 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.60 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.00 45.1 6.11 47.3 6.20 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 47.7 3.70 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.80 52.3 4.88 54.9 4.96 56.1 5.02
18+18+18 95 43.3 5.15 46.4 5.23 48.3 5.30 50.0 5.40 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.60 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.00 45.1 6.11 47.3 6.20 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56
70 45.8 3.63 49.0 3.69 51.1 3.74 52.9 3.81 55.4 3.86 56.7 3.91
75 45.1 3.98 48.3 4.05 50.4 4.10 52.1 4.18 54.7 4.24 55.9 4.29
85 43.5 4.57 46.6 4.65 48.5 4.71 50.3 4.79 52.7 4.86 53.9 4.92
12+12+12+12 95 41.5 5.05 44.5 5.14 46.4 5.20 48.0 5.30 50.3 5.38 51.5 5.44
105 39.7 5.41 42.5 5.50 44.3 5.57 45.9 5.67 48.1 5.76 49.2 5.82
115 37.5 5.72 40.1 5.81 41.8 5.89 43.3 6.00 45.4 6.08 46.5 6.16
125 34.7 5.98 37.2 6.08 38.8 6.16 40.1 6.27 42.1 6.36 43.1 6.44
70 47.7 3.70 51.1 3.76 53.2 3.81 55.1 3.88 57.8 3.93 59.1 3.98
75 47.0 4.06 50.4 4.13 52.5 4.18 54.3 4.26 56.9 4.32 58.3 4.37
85 45.3 4.66 48.5 4.74 50.6 4.80 52.3 4.88 54.9 4.96 56.1 5.02
12+12+12+18 95 43.3 5.15 46.4 5.23 48.3 5.30 50.0 5.40 52.4 5.48 53.6 5.54
105 41.4 5.51 44.3 5.60 46.2 5.67 47.8 5.78 50.1 5.86 51.3 5.93
115 39.0 5.82 41.8 5.92 43.6 6.00 45.1 6.11 47.3 6.20 48.4 6.27
125 36.2 6.09 38.8 6.19 40.4 6.27 41.8 6.39 43.8 6.48 44.8 6.56

Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping -16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC : Total Cooling Capacity(1,000 Btu/h)
4. PI : Power Input(kW)
5. This table is the capacity of circuit 1. Circut 2 is same.

118 MPS(Multi Power System) Variable Multi


7. Capacity Table

[Heating Capacity(English Unit)]

Combination Indoor Outdoor Air Temp.: FWB


Capacity Index Air Temp.: 14 23 32 42.8 50 59
(kBtu/h) FDB
TC PI TC PI TC PI TC PI TC PI TC PI
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
48 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
12+36 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 24.3 2.26 28.7 2.47 33.1 2.69 38.5 2.91 41.7 3.06 46.1 3.28
64.4 23.6 2.34 27.7 2.55 32.1 2.78 37.3 3.00 40.4 3.16 44.6 3.39
18+18 68 22.8 2.41 26.9 2.64 31.1 2.87 36.0 3.10 39.2 3.27 43.3 3.50
71.6 22.0 2.49 25.9 2.72 30.0 2.96 34.9 3.20 37.8 3.37 41.7 3.61
75.2 21.3 2.57 25.1 2.81 29.0 3.06 33.7 3.30 36.5 3.47 40.3 3.72
60.8 28.4 2.77 33.4 3.03 38.7 3.30 45.0 3.56 48.7 3.75 53.7 4.02
64.4 27.5 2.86 32.4 3.13 37.4 3.41 43.5 3.68 47.1 3.88 52.0 4.15
18+24 68 26.7 2.96 31.4 3.23 36.3 3.52 42.0 3.80 45.7 4.00 50.5 4.29
71.6 25.7 3.05 30.3 3.34 35.0 3.63 40.7 3.92 44.1 4.13 48.7 4.42
75.2 24.8 3.15 29.2 3.44 33.8 3.75 39.3 4.04 42.6 4.26 47.0 4.56
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
18+30 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 33.8 3.43 39.8 3.74 46.0 4.08 53.5 4.41 57.9 4.64 64.0 4.97
64.4 32.7 3.54 38.5 3.87 44.6 4.22 51.8 4.55 56.1 4.79 61.9 5.14
18+36 68 31.7 3.66 37.4 4.00 43.3 4.36 50.0 4.70 54.4 4.95 60.1 5.30
71.6 30.6 3.78 36.0 4.13 41.7 4.49 48.5 4.85 52.5 5.11 57.9 5.47
75.2 29.5 3.89 34.8 4.25 40.3 4.63 46.8 5.00 50.7 5.27 55.9 5.64
60.8 33.8 3.43 39.8 3.74 46.0 4.08 53.5 4.41 57.9 4.64 64.0 4.97
64.4 32.7 3.54 38.5 3.87 44.6 4.22 51.8 4.55 56.1 4.79 61.9 5.14
24+30 68 31.7 3.66 37.4 4.00 43.3 4.36 50.0 4.70 54.4 4.95 60.1 5.30
71.6 30.6 3.78 36.0 4.13 41.7 4.49 48.5 4.85 52.5 5.11 57.9 5.47
75.2 29.5 3.89 34.8 4.25 40.3 4.63 46.8 5.00 50.7 5.27 55.9 5.64
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
24+24 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 24.3 2.26 28.7 2.47 33.1 2.69 38.5 2.91 41.7 3.06 46.1 3.28
64.4 23.6 2.34 27.7 2.55 32.1 2.78 37.3 3.00 40.4 3.16 44.6 3.39
12+12+12 68 22.8 2.41 26.9 2.64 31.1 2.87 36.0 3.10 39.2 3.27 43.3 3.50
71.6 22.0 2.49 25.9 2.72 30.0 2.96 34.9 3.20 37.8 3.37 41.7 3.61
75.2 21.3 2.57 25.1 2.81 29.0 3.06 33.7 3.30 36.5 3.47 40.3 3.72
60.8 28.4 2.77 33.4 3.03 38.7 3.30 45.0 3.56 48.7 3.75 53.7 4.02
64.4 27.5 2.86 32.4 3.13 37.4 3.41 43.5 3.68 47.1 3.88 52.0 4.15
12+12+18 68 26.7 2.96 31.4 3.23 36.3 3.52 42.0 3.80 45.7 4.00 50.5 4.29
71.6 25.7 3.05 30.3 3.34 35.0 3.63 40.7 3.92 44.1 4.13 48.7 4.42
75.2 24.8 3.15 29.2 3.44 33.8 3.75 39.3 4.04 42.6 4.26 47.0 4.56
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
12+12+24 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 33.8 3.43 39.8 3.74 46.0 4.08 53.5 4.41 57.9 4.64 64.0 4.97
64.4 32.7 3.54 38.5 3.87 44.6 4.22 51.8 4.55 56.1 4.79 61.9 5.14
12+12+30 68 31.7 3.66 37.4 4.00 43.3 4.36 50.0 4.70 54.4 4.95 60.1 5.30
71.6 30.6 3.78 36.0 4.13 41.7 4.49 48.5 4.85 52.5 5.11 57.9 5.47
75.2 29.5 3.89 34.8 4.25 40.3 4.63 46.8 5.00 50.7 5.27 55.9 5.64
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
12+18+18 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 33.8 3.43 39.8 3.74 46.0 4.08 53.5 4.41 57.9 4.64 64.0 4.97
64.4 32.7 3.54 38.5 3.87 44.6 4.22 51.8 4.55 56.1 4.79 61.9 5.14
12+18+24 68 31.7 3.66 37.4 4.00 43.3 4.36 50.0 4.70 54.4 4.95 60.1 5.30
71.6 30.6 3.78 36.0 4.13 41.7 4.49 48.5 4.85 52.5 5.11 57.9 5.47
75.2 29.5 3.89 34.8 4.25 40.3 4.63 46.8 5.00 50.7 5.27 55.9 5.64

2004 Product Data 119


7. Capacity Table

Combination Indoor Outdoor Air Temp.: FWB


Capacity Index Air Temp.: 14 23 32 42.8 50 59
(kBtu/h) FDB
TC PI TC PI TC PI TC PI TC PI TC PI
60.8 33.8 3.43 39.8 3.74 46.0 4.08 53.5 4.41 57.9 4.64 64.0 4.97
64.4 32.7 3.54 38.5 3.87 44.6 4.22 51.8 4.55 56.1 4.79 61.9 5.14
18+18+18 68 31.7 3.66 37.4 4.00 43.3 4.36 50.0 4.70 54.4 4.95 60.1 5.30
71.6 30.6 3.78 36.0 4.13 41.7 4.49 48.5 4.85 52.5 5.11 57.9 5.47
75.2 29.5 3.89 34.8 4.25 40.3 4.63 46.8 5.00 50.7 5.27 55.9 5.64
60.8 32.4 3.35 38.2 3.67 44.2 3.99 51.4 4.31 55.6 4.54 61.4 4.86
64.4 31.4 3.47 37.0 3.79 42.8 4.13 49.8 4.46 53.9 4.69 59.5 5.03
12+12+12+12 68 30.5 3.58 35.9 3.91 41.5 4.26 48.0 4.60 52.3 4.85 57.7 5.19
71.6 29.4 3.70 34.6 4.04 40.0 4.40 46.5 4.75 50.4 5.00 55.6 5.36
75.2 28.4 3.81 33.4 4.16 38.6 4.53 44.9 4.90 48.6 5.15 53.7 5.52
60.8 33.8 3.43 39.8 3.74 46.0 4.08 53.5 4.41 57.9 4.64 64.0 4.97
64.4 32.7 3.54 38.5 3.87 44.6 4.22 51.8 4.55 56.1 4.79 61.9 5.14
12+12+12+18 68 31.7 3.66 37.4 4.00 43.3 4.36 50.0 4.70 54.4 4.95 60.1 5.30
71.6 30.6 3.78 36.0 4.13 41.7 4.49 48.5 4.85 52.5 5.11 57.9 5.47
75.2 29.5 3.89 34.8 4.25 40.3 4.63 46.8 5.00 50.7 5.27 55.9 5.64

Notes : 1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7CDB/6CWB(44.6FDB/42.8FWB)
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping -16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC=Total heating capacity(Unit:1,000 Btu/h)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. This table is the capacity of circuit 1. Circut 2 is same.

Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity" Table above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.

Correction Factor

Outdoor Air Temperature


(FWB, RH=85%) 14 21.2 24.8 28.4 32 35.6 39.2 42.8

Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00

120 MPS(Multi Power System) Variable Multi


8. Capacity Coefficient Factor

8.1 Rate of Change in Capacity by the Main Piping(Distributor) Length and


the Direct Piping Length

L4UC608FA0

Rate of Cooling Change in Capacity by Main Piping Length & Direct Piping Length
100.0%
Rate of Change in Cooling Capacity(%)

95.0%
Main Piping

90.0% 36k

85.0%

80.0%

75.0%

70.0%
0 5 10 15 20 25 30 35 40 45 50
Piping Length(m)

L5UC728FA0

Rate of Cooling Change in Capacity by Main Piping Length & Direct Piping Length
100.0%
Rate of Change in Cooling Capacity(%)

95.0%
Main Piping

90.0%
48k

85.0%

80.0%

75.0%

70.0%
0 5 10 15 20 25 30 35 40 45 50
Piping Length(m)

2004 Product Data 121


8. Capacity Coefficient Factor

L8UC1008FA0/L8UH1008FA0

Rate of Change in Cooling Capacity


Main Piping Length(m) 5 10 15 20 25 30 35 40 45 50

Rate of Change
in Cooling Capacity 100.0% 98.8% 97.3% 95.8% 94.3% 92.8% 91.3% 89.8% 88.3% 86.8%

Rate of Change in Heating Capacity

Main Piping Length(m) 5 10 15 20 25 30 35 40 45 50

Rate of Change
in Cooling Capacity 100.0% 99.6% 99.2% 98.7% 98.3% 97.8% 97.4% 96.9% 96.5% 96.0%

Rate of Change in Capacity by Main Piping Length & Direct Piping Length
100.0%
Rate of Change in Cooling Capacity(%)

95.0%

90.0%

85.0%

80.0%

75.0%

70.0%
0 5 10 15 20 25 30 35 40 45 50
Piping Length(m)

: Rate of Change in Cooling Capacity


: Rate of Change in Heating Capacity

122 MPS(Multi Power System) Variable Multi


8. Capacity Coefficient Factor

8.2 Rate of Change in Capacity by the Branch(Distributor) Piping Length


12k Btu/h(3.5 kW) models 18k Btu/h(5.3 kW) models
Piping Length Rate of Change in Capacity Piping Length Rate of Change in Capacity
(m) Cooling Heating (m) Cooling Heating
7.5 100.0% 100.0% 7.5 100.0% 100.0%
11.25 97.0% 98.3% 11.25 98.3% 99.5%
15 94.0% 96.5% 15 96.5% 99.0%

24k Btu/h(7.0 kW) models 30k Btu/h(8.8 kW) models


Piping Length Rate of Change in Capacity Piping Length Rate of Change in Capacity
(m) Cooling Heating (m) Cooling Heating
7.5 100.0% 100.0% 7.5 100.0% 100.0%
11.25 97.8% 99.2% 11.25 98.4% 99.1%
15 95.5% 98.4% 15 96.8% 98.2%

36k Btu/h(10.6 kW) models


Piping Length Rate of Change in Capacity
(m) Cooling Heating
7.5 100.0% 100.0%
11.25 97.9% 98.8%
15 95.7% 97.6%

12k Btu/h(3.5 kW) Models Rate of Change by Branch Piping Length


100.0% : Cooling
Rate of Change in Cooling Capacity(%)

: Heating
99.0%

98.0%

97.0%

96.0%

95.0%

94.0%
0 7.5 11.25 15
Branch Piping Length(m)

2004 Product Data 123


8. Capacity Coefficient Factor

18k Btu/h(5.3 kW) Models Rate of Change by Branch Piping Length


100.0% : Cooling
Rate of Change in Cooling Capacity(%)

99.5% : Heating
99.0%

98.5%

98.0%

97.5%

97.0%

96.5%

96.0%

95.5%

95.0%
0 7.5 11.25 15
Branch Piping Length(m)

24k Btu/h(7.0 kW) Models Rate of Change by Branch Piping Length

100.0% : Cooling
99.5% : Heating
Rate of Change in Capacity(%)

99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)

30k Btu/h(8.8 kW) Models Rate of Change by Branch Piping Length

100.0% : Cooling
99.5% : Heating
Rate of Change in Capacity(%)

99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)

124 MPS(Multi Power System) Variable Multi


8. Capacity Coefficient Factor

36k Btu/h(10.6 kW) Models Rate of Change by Branch Piping Length

100.0% : Cooling
99.5% : Heating
Rate of Change in Capacity(%)

99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)

Method of calculating cooling / heating capacity :


Total capacity from capacity tables x (Rate of Change in capacity by main piping length x Rate of Change in capacity by branch
piping length)

2004 Product Data 125


9. Operation Limits

Item Range

Outdoor air temperature C D.B.(F)


Inlet air temperature
(Cooling)

54(129.2)

Standard operation

21(69.8)

14(57.2) 24(75.2)
Indoor air temperature C W.B.(F)
Outdoor air temperature C W.B.(F)

Inlet air temperature


(Heating)
15.5(59.9)

Standard operation

0(32)

14(57.2) 28(82.4)
Indoor air temperature C D.B.(F)

Power source voltage Rating 10%

Voltage at starting Min. 85% of rating

126 MPS(Multi Power System) Variable Multi


10. Sound Levels

Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
Center of
Outdoor Unit - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
1m
- The operating conditions are assumed to be standard
D (KS conditions)

1m

50Hz, 380-415V
Model
Sound Levels(dBA)
L4UC608FA0 63
L5UC728FA0 60

L8UC1008FA0
60
L8UH1008FA0

Sound Pressure Level


L4UC608FA0 L5UC728FA0 L8UC1008FA0
L8UH1008FA0
90 90 90

80 80 80

70 70 70
Sound Pressure Level (dB re 20Pa )

Sound Pressure Level (dB re 20Pa )

NC-70 NC-70 NC-70

NC-65 NC-65 NC-65


60 60 60
Sound Pressure Level (dB re 20Pa )

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40
NC-35 NC-35 NC-35
30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
NC-20 NC-20 NC-20

NC-15 NC-15 NC-15


10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

2004 Product Data 127


11. Installation

11.1 Select the best location


If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from
the condenser is not restricted.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the
roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop
mounting.

Model : L4UC608FA0
Ensure that the space around the back is more than 90cm and sides is more than 90cm. The front of the unit
should have more than 90cm of space.

Fence or
obstacles More than 120cm

More than
90cm

Fe
ob nce More than
sta or 90cm
cle
s More than 90cm
More than 90cm

Model : L5UC728FA0
(1) Individual installation
Basic Space required
A space of at least 250 mm is nessary at the back for inlet air. Tacking servicing, a space of about 750 mm
should be provided at the front.

Rear B

A : 750 mm or more
B : 250 mm or more
C : Top discharge(open in principle)
D E
D : Front inlet(open in principle)
E : Rear inlet(open in principle)
Front
service space
A

<Side View> <Top View>

128 MPS(Multi Power System) Variable Multi


11. Installation
When inlet air enters from right and left sides of unit

A : 750 mm or more
B : 250 mm or more
C : 150 mm or more A B

Rear B

C C

Front A

<Top View> <Side View>

When unit is surrounded by walls

B
A : 750 mm or more
B : 250 mm or more B B

When there is an obstructure above the unit

A : 45 or more D : 1000 mm or more


B : 200 mm or more E : Air outlet guide (procured at the site)
C : 250 mm or more F : 250 mm or more

A D
B

C F
E

2004 Product Data 129


11. Installation

(2) Collective installation and continuous installation


Space required for collective installation and continuous installation : When installing several
units, leave the space between each block as show below considering passage for air and people.

A : Open state
B : 750 mm or more
C : 250 mm or more
D : 250 mm or more

Rear
Front

Rear

Front

Model : L8UC1008FA0/L8UH1008FA0
(1) Individual installation
Basic Space required
A space of at least 250 mm is nessary at the back for inlet air. Tacking servicing, a space of about 750 mm
should be provided at the front.

Rear B

A : 750 mm or more
B : 250 mm or more
C : Top discharge(open in principle)
D E
D : Front inlet(open in principle)
E : Rear inlet(open in principle)
Front
service space
A

<Side View> <Top View>

130 MPS(Multi Power System) Variable Multi


11. Installation

When inlet air enters from right and left sides of unit

A : 750 mm or more
B : 250 mm or more
C : 150 mm or more A B

Rear B

C C

Front A

<Top View> <Side View>

When unit is surrounded by walls

B
A : 750 mm or more
B : 250 mm or more B B

When there is an obstructure above the unit

A : 45 or more D : 1000 mm or more


B : 200 mm or more E : Air outlet guide (procured at the site)
C : 250 mm or more F : 250 mm or more

A
D

C F
E

2004 Product Data 131


11. Installation

(2) Collective installation and continuous installation


Space required for collective installation and continuous installation : When installing several
units, leave the space between each block as show below considering passage for air and people.

A : Open state
B : 750 mm or more
C : 250 mm or more

Front
D : 250 mm or more

Rear
Rear

Front

132 MPS(Multi Power System) Variable Multi


11. Installation

11.2 Settlement of outdoor unit


Anchor the outdoor unit with a bolt and nut(10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming
the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.

L5UC728FA0 Individual installation

7002
Installation foot
50
0

5002

Example of collective installation

250 250
5002 556 5002 556 5002

L8UC1008FA0/L8UH1008FA0 Individual installation


7002

Installation foot
90
0

9002

Example of collective installation

250 250
9002 556 9002 556 9002

2004 Product Data 133


11. Installation

11.3 Lifting Method


When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each at the
front and rear.
Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
Attach the ropes to the unit at an angle of 40 or less.
Use two ropes at least 7 m long.

A 40 or less A 40 or less
B Rope suspension part B Rope suspension part

Caution:
Be very careful to carry product.
Do not have only one person carry product if it is more than 20 kg.
PP bands are used to pack some products. Do not use them as a mean for transportation because they are
dangerous.
Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support
may make outdoor unit unstable, resulting in a fall of it.

134 MPS(Multi Power System) Variable Multi


12. Accessories

Standard accessories
Installation manual

Optional accessories
No. Name Model No.
PMBD5420L(For 2 Indoor Units)
1 BD Unit PMBD5430L(For 3 Indoor Units)
PMBD5440L(For 4 Indoor Units)

2004 Product Data 135


Memo

136 MPS(Multi Power System) Variable Multi


Part 4
Control

1. Basic Control Devices and Function..............................138


1.1 Wired Remote Control.................................................................138
1.2 Wireless Remote Control ............................................................139
2. Central Control .................................................................140
2.1 Simple Central Control(PQCSA101S0).......................................140
2.2 Deluxe Central Control(PQCSW501A0, PQCSW502A0)...........147
2.3 PC Central Control(PQCSS501A0, PQCSS502A0))...................153

2004 Product Data 137


1. Basic Control Devices and Function

1.1 Wired Remote Control


1.1.1 Appearance and Functions

Appearance Functions (Button Descriptions)

Ceiling Mounted Cassette Type: No. Name Function

1 Operation display Displays the operation conditions.


Operation starts when this button is pressed, and
2 On/Off
stops when the button is pressed again.
AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION Used to set the temperature when the desired
Room Temp
HI AUTO Heater Preheat
1 3 Set Temperature
MED JET Defrost Humidify temperature is obtained.
LO Filter Out door
Time ZONE 1 2 3 4 Used to circulate room air without cooling or
Timer Operation unit Program set 4 FAN Operation
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23 heating.
3 5 Fan Speed Used to set the desired fan speed
16 2 Operation Mode
6 Used to select the operation mode.
Selection
9 5 Used to swing up and down.
10
Timer Cancel 7 Auto Swing
11 6 Room Temperature
12
Program Week Holiday
4 8 Used to check the room temperature.
Plasma Checking
13 Set/Clr
7
14 9 Timer Cancel Used to cancel the timer.
Hour Min RESET 8
15 Used to set the timer when the desired time is
10 Timer Set
obtained.
17
11 Week Used to set a day of the week
12 Program Used to set the weekly timer.
13 Holiday Used to set a holiday of the week.
Used to set the time of the day and change the
14 Time Set
time in weekly timer Function.
15 Set and Clear Used to set and clear the weekly timer.
16 Jet Cool Used to select jet cool mode.
Used to set the current time and clear the setting
17 Reset
time.

Ceiling Concealed Duct Type: No. Name Function

1 Operation display Displays the operation conditions.


Operation starts when this button is pressed, and
2 On/Off
stops when the button is pressed again.
Used to set the temperature when the desired
3 Set Temperature
temperature is obtained.
AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Room Temp Used to circulate room air without cooling or
HI AUTO Heater Preheat
1 4 FAN Operation
MED
LO
JET Defrost Humidify
Filter Out door
heating.
Time ZONE 1 2 3 4
Timer
On Off
Operation unit Program set 5 Fan Speed Used to set the desired fan speed
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

3 Operation Mode
6 Used to select the operation mode.
Selection
16 2 Used to set the timer when the desired time is
7 Timer Set
8 obtained.
Timer Cancel
5
7 8 Timer Cancel Used to cancel the timer.
9 6
Program Week Holiday
10 4 9 Week Used to set a day of the week
11 SET/CLR
12 10 Program Used to set the weekly timer.
Hour Min RESET 14
13 15 11 Holiday Used to set a holiday of the week.
Used to set the time of the day and change the
12 Time Set
time in weekly timer Function.
13 Set and Clear Used to set and clear the weekly timer.
Room Temperature
14 Used to check the room temperature.
Checking
Used to set the current time and clear the setting
15 Reset
time.
Used to take the signal from wireless remote
16 Signal Receptor
control

138 MPS(Multi Power System) Variable Multi


1. Basic Control Devices and Function

1.2 Wireless Remote Control


1.2.1 Appearance and Functions

Appearance Functions (Button Descriptions)

Wall Mounted Type No. Name Function


Art Cool Type Operation starts when this button is pressed and
1 START/STOP
Art Cool Mirror Type stops when the button is pressed again.
OPERATION MODE
2 Used to select the operation mode.
Signal transmitter SELECTION
ROOM
3 TEMPERATURE Used to select the room temperature.
SETTING
FAN SPEED Used to select fan speed in four steps (low,
4
SELECTOR medium, high, or CHAOS.)
Used to start or stop the speed cooling/heating.
5 JET COOL (Speedcooling/heating operates super high fan
speed in cooling mode.)
5 1
6 Used to stop or start louver movement and set
6 CHAOS SWING
the desired up/down airflow direction.
3
Used to set the time of starting and stopping
4 7 ON/OFF TIMER
operation.
2 10
CANCEL

9 8 TIME SETTING Used to adjust the time.


7 ON OFF SET
AUTO CLEAN
11 Used to set the timer when the desired time is
8 16 9 TIMER SET/CANCEL
obtained and to cancel the Timer operation.
13
12 10 SLEEP MODE AUTO Used to set Sleep Mode Auto operation.
14 15
Used to circulate the room air without cooling or
11 AIR CIRCULATION
heating (turns indoor fan on/off).
ROOM
Flip-up door 12 TEMPERATURE Used to check the room temperature.
(opened) CHECKING

13 PLASMA(OPTIONAL) Used to start or stop the plasma-purification func-


tion.

14 RESET BUTTON Used prior to resetting time or after replacing bat-


teries.

15 2nd F Button Used prior to using modes printed in blue at the


bottom of buttons.

16 AUTO CLEAN Used to set Auto Clean mode.

2004 Product Data 139


2. Central Control

2.1 Simple Central Control(PQCSA101S0)


2.1.1 Features

Easy operation button.


Independent operation for 16 indoor units each.
Simultaneous turn ON/OFF for all of indoor units connected.
Easy change operation mode to cooling or heating
Set and clear lock-mode for each indoor unit
Simultaneously set and clear lock-mode for all of indoor units
connected.
Display function for all of indoor units connected.

2.1.2 Term of Each part and Function

On/Off display LED Individual On/Off button


(TOTAL 16EA) Control ON/OFF of a unit.
On pressing individual on/off
button, display the present
operation state.
-Operation : green.
-Stop : off
-Error mode : blinking

Power display LED


Indicate the state of DC
Power supply in central
control unit. TOTAL Off button
- On : red(Heating), green(Cooling) Stop all linked units sequentially.
- Off : no signal
- Error mode : blinking with red color
TOTAL On button
Operate all linked units sequentially.

140 MPS(Multi Power System) Variable Multi


2. Central Control

2.1.3 Electrical wiring


PICTORIAL VIEW OF THE CONNECTION

Outdoor
Outdoor unit
unit
PI485 : PMNFP14A0

MAIN PCB
L PI485

MAIN PCB Control Box

CN_CENTRAL

MAIN PCB

CN_CENTRAL N
L

10
G
PI485 A
B

VCC CENTRAL
GND
CN OUT C
CONTROL
D UNIT

Special purchase: Central control, PI485(PMNFP14A0)

ONE SIMPLE CENTRAL CONTROL CONNECTION

INDOOR UNIT 1 INDOOR UNIT


INDOOR UNIT 2 SET The Address(Group No. & Indoor No.)
OUTDOOR INDOOR UNIT 3 * Refer to The Following sheet
MAIN PCB INDOOR UNIT 4 (1.3.5 Indoor unit Address setting method)
INDOOR UNIT 5 Vcc GND C D

INDOOR UNIT 6 CN-POWER


GND
BUS CN-COM B
B
BUS CN-POWER CN-COM A
A S1 S2 S4
L
GND LED2
LED3 LED4
+10V IC1P S5 S6 S3
+ + + +
+
LED5 LED7 LED8 TX1
D C GND VCC S9 S10 S11 S12
+ + +

Outdoor
Outdoor unit
unit LED9 LED10

S14
LED11

+ S15
LED12

+ S16
+ +

LED13 LED14 LED15 LED16


PWB:6870A10001A
ASM:6711A20005E
Group Number 0 + S15 S18

ON KSDO4H
Master Mode LED17

L1 2 3 4
S19

All the connections are to be done as shown above.


VCC
A and B are the communication lines for the indoor and GND
CENTRAL
C and D are the communication lines for the Central Control. CONTROL
C
UNIT
Use two shield lines for C/D connecting line.(Earth the shield line) D

2004 Product Data 141


2. Central Control

2 OR MORE SIMPLE CENTRAL CONTROL CONNECTION


INDOOR UNIT 1

INDOOR UNIT 2

OUTDOOR INDOOR UNIT 3


MAIN PCB INDOOR UNIT 4
<Group Number 0>
INDOOR UNIT 5

INDOOR UNIT 6 Vcc GND C D

BUS
B
BUS
A S1
CN-POWER

LED2
S2
L
CN-POWER
GND

CN-COM A
S4
CN-COM B
Master DIP SWITCH
LED3 LED4

GND IC1P
+
S5
+
S6
+ + S3

LED5 LED7 LED8 TX1

+10V
+

LED9
S9
+

LED10
S10
+

LED11
S11

LED12
S12

S16
1. Adhere the PI485 Module(For connecting central control) to the Control Box.
S14 + S15 +
+ +

LED13 LED14 LED15


PWB:6870A10001A
LED16
2. Connect the PI485 Module to central control.
D C GND VCC
ASM:6711A20005E
S15 S18

3. In the case of connecting two more than central control, set the Master/Slave mode
+

LED17 ON KSDO4H

L1 2 3 4

Outdoor unit 1 S19

Master Mode Group Number 0


and then connect each communication lines(C,D) <Refer to above fig>.
*Special purcharse: Central control(PQCSA101S0),
INDOOR UNIT 1
PI485 Module(PMNFP14A0)
INDOOR UNIT 2 * It can be added to 15 Central controls for the slave control.

OUTDOOR INDOOR UNIT 3


MAIN PCB INDOOR UNIT 4 Note
INDOOR UNIT 5 <Group Number 1>

BUS
INDOOR UNIT 6 Vcc GND C D 001
B CN-POWER
GND

BUS
A S1
CN-POWER

LED2
S2

LED3
L

LED4
CN-COM A
S4
CN-COM B

Slave DIP SWITCH


Group No.
GND IC1P
+
S5
+
S6
+ + S3

LED5 LED7 LED8 TX1

+10V +
S9
+
S10
+
S11 S12
Indoor No.
LED9 LED10 LED11 LED12

S14 S15 S16


+ + + +

LED13 LED15 LED16

D C GND VCC
LED14
PWB:6870A10001A
ASM:6711A20005E
S15 S18
+

LED17 ON KSDO4H

Outdoor unit 2 L1 2 3
S19
4

Master Mode Group Number 0

2.1.4 PI485 setting method(LG Air-conditioner Network unit, PMNFP14A0)

Selection of product Selection of network type


unit type

ON KS DO 4H

L1 2 3 4

Settings method of MPS Variable Multi Type


ON KS DO 4H
1 ON + All OFF : Connection of "MPS Variable Multi Connection + General Central
L1 2 3 4 Controller" Case.

ON KS DO 4H
1,4 ON + All OFF : Connection of "MPS Variable Multi Connection +
L1 2 3 4
Central Controller applied LGAP" Case.

* LGAP : LG Air conditioners Protocol

Function of LG Network
- It is possible to connect the network of LG air conditioners and to connect various contents of the network
system, which is simple, deluxe and PC central control.
- Please refer to "LG Control System Manual" about the detail functions and the products possible to network.
- As the Interface for networking, PMNFP14A0 is applied.

142 MPS(Multi Power System) Variable Multi


2. Central Control
2.1.5 Indoor Unit Address setting Method

Using Wired Remote Control 1. Press 13(program) and 16(set and clear) key more
than 3 second then "Address Setting Mode" starts.
2. Set the address of indoor unit by using "Temperature
setting" key.
Range of address : 00 ~ FF
AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Room Temp
HI
MED
AUTO Heater Preheat
JET Defrost Humidify 1
LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

3
17 2 Ex) 3 A
10 Timer Cancel
5
11
12 6
Program Week Holiday
13 4
Plasma
14 Set/Clr
7
15 Hour Min RESET 8 Group Room(Indoor Unit)
16 9 No. No.
18
3. After setting address, press 13(program) and 16(set
Heat Pump Model
and clear) key more than 3 second then "Address
Setting Mode" is finished.

Using Wireless Remote Control


1. Address setting Method
Signal transmitter
1) Press 5(Jet Cool) & 13(Reset) key at the same time more
than 3 seconds then
"Address Setting Mode" starts.
2) Set the address of indoor unit by using
"Temperature setting" key.
Range of address : 00 ~ FF
5 1
6
Ex) 3 A
3

4
2 10
CANCEL

7 9
ON OFF SET

11 AUTO CLEAN
Group Room(Indoor Unit)
8 16
13 No. No.
12
15
14 3) After address setting, pressing 1(On/Off) key, address
setting is finished. The address that is set is displayed on a
Flip-up door
display window of indoor unit.
(opened) * notice : The mothod of display and time is different
according to indoor unit type.
4) If the remote control is reset, normal mode starts.
2. Address Monitoring
2.
1) Press 6(Chaos Swing) & 13(Reset) key at the same time then "Address Monitoring Mode"
starts.
2) At the address monitoring mode, pressing 1(On/Off) key, The address that is set is displayed
on a display window of indoor unit.
* notice : The mothod of display and time is different according to indoor unit type.
3) If the remote control is reset, normal mode starts.

* Notice : Confirm that wired and wireless remote control are able to select the address or not.

2004 Product Data 143


2. Central Control

2.1.6 Test run method


1. Set the wiring of system and indoor unit.
2. Apply power to the setting.
3. Do auto addressing to the outdoor unit.
4. After addressing, initialize the central controller(Manual initialize: Total on + total off + 16 key).
Cooling: Setting basically(Total On + Total Off + 4 key)
Heating: Total On + Total Off + 8 key Red power lamp 'On'
6. Check up On/Off with a related indoor key pressing.

2.1.7 Installation
CAUTIONS

Do not install in this area Keep in mind


Dont install near elevator, computer, auto- Dont operate with wet hands.
matic door. (High noise area).

Dont install near high moisture & high oscilla-


tion area.

Dont pull the connected wire.

Dont install near direct sunlight or heat


source.

144 MPS(Multi Power System) Variable Multi


2. Central Control

INSTALLATION ORDER
1. Remove upper & lower case. 2. Fixate screw in the holes of the 3. For Dip switch, and Rotary
case bottom. switch setting, refer to the page
How to Install.

4. For wiring connection, refer page 5. Adjust the upper case in accor- 6. Check the operation by supply-
Installation Procedure dance with back case while ing the power.
assembling as shown in the fig-
ure.

LINK OF CONNECTING WIRE


1. First, separate the front case from rear case of controller, connect terminal GND
C, D,Vcc, GND on PCB referring to the following table. Vcc D

Maximum length of connecting wire C

Between controller and outdoor unit : 220m(25 )


Between controllers : 220m(25 )

Out door unit Terminal Block Wire Color Central Control Terminal
GND BLUE GND
Vcc Red Vcc
C Brown C
D Yellow D

2. After attaching the supplied wire to terminal, link the connecting wire.
If necessary, Cut the indicated part of front case to draw the lead wire.

2004 Product Data 145


2. Central Control

. ROTARY SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)


The setting of Group Number in the Central Control is done by the rotary switch as shown in the figure below.

It is possible to set 0~15 Group(Total 16 Groups). All the numbers on the rotary switch represent the different
Group Numbers. By changing the knob we can set rotary switch to the group number we want to control.
The above fig. Shows the control of group number 0. Similarly we can control all the 16 Groups.

. DIP SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)


CAUTION
Dip switch is now used only for the setting of master or slave mode.( In the case of two more
than central controls.)
Set one to Master, the others to slave.

Master Mode
Rotary Switch
Dip Switch
ON
OFF Slave Mode

. ACCEASSORY PARTS
Central control and sub PI485(with wire assembly) should be purchased as optional.

Central Control PI485(PQNFP14A0)


(PQCSA101S0) Wire Assembly 1

Screw(4EA) Wire Assembly 2

146 MPS(Multi Power System) Variable Multi


2. Central Control
2.2. Deluxe Central Control(PQCSW501A0, PQCSW502A0)
2.2.1 Introduction
SUMMARY
Deluxe Central control is a product available for individual and integrated monitoring and control of maximum
256 of MPS Variable Multi air conditioner systems. Specially, operation status of the individual air conditioner
can be particularly checked. Individual or simultaneous operation of the air conditioner, operation mode, wind
quantity, user locking and temperature setup are also available.

Specially for this system, installation is simple and user's environment is excellent. Central control is available
by a simple manipulation. In addition, this system have the self-battery built-in and can stably operate in spite
of outside disturbance such as temporary power failure. This system has no need of additional peripheral
equipment like UPS (Undisturbed Power System) and AVR to be purchased for stability when composing the
existing PC central control system, and has so attractive advantage in installation costs.

Using the Deluxe Central control enables the management room to setup lock of each air conditioner and
prevent indoor control of the individual air conditioner and restrain the necessary use. In case of releasing the
lock, you may control the system by using the wire/wireless remote control at the place where the individual
air conditioner is installed.

Setup of a weekly schedule is available and detailed schedule of the individual air conditioner can be easily
setup through the GUI. Details of schedule setup can be immediately checked with a graph. This system is a
product to meet energy saving and convenience at the same time at a place like a school by using this sched-
ule function.

Depending on installation environment, location and conditions of use, you can setup groups. With this setup,
more efficient operation at the center is available. Setup without requiring other equipment is available by
using the GUI and change by the consumer is also available after installation.

You can reduce development time to configure special system upon the request by the consumer and conve-
niently this system by using the touch panel.

Where needs from a new customer occur or where purchase of additional air conditioner is done, the Deluxe
Central control can be smoothly installed.

Deluxe
Central control CNU
PI485

PI485

2004 Product Data 147


2. Central Control

2.2.2 Major Characteristics

Figure 2) Deluxe Central control

1. Individual/Integrated Operation/Monitoring
You can identify operation status of the air conditioner, operation mode, wind quantity, wind direction, lock-
ing, temperature setting and error, etc by selecting the installed air conditioner through individual selection,
group selection or all selection. Individual setup and operation of the detailed functions are available.
Therefore, managing with Deluxe Central control installed at the control room at a building where a number
of air conditioners are installed, is a convenient way.

2. Group Management
Group management for the installed air conditioners is available. Group can be seperated by their nature,
location and size of each air conditioner which enables convenient use. In addition, allotment of respective
name to the setup group allows further intuitive management.

3. Self-diagnosis Function
The air conditioner installed can self-diagnosed its error status and then transmits the result to the central
control. Therefore, a rapid countermeasure against failure of the air conditioner allows easy management
and increases the usage life of air conditioner.

4. Semi-permanent Life / Convenient Maintenance


Since the Deluxe Central control is designed for the semi-permanent use, this system can be used semi-
permanently after installation, different from the existing PC or a large central control system requiring a
continuous management due to the life of peripheral and other PC.

5. Management Costs Down


In absence of the Central Control System, the manager controls a number of air conditioners. In addition,
even if management was done at the center, there is only function of on/off management at best and thus 2
or 3 building managers were actually required. However, manipulation of all functions can be now done at
a control room for the Deluxe Central control and so a manager can easily control all air conditioners.
Automatic operation is also allowed without a manager, by using schedule function.

148 MPS(Multi Power System) Variable Multi


2. Central Control

6. Convenient GUI / Touch Screen


Not requires special education for using the Deluxe Central control, conveniently used only by pressing the
buttons on the screen, and its function can be understood with intuitive pictogram. Especially schedule set-
ting is done by simply by dragging, different from the existing system requiring to press the button by more
than average 30 times to enter a schedule.

7. Schedule Automatic Operation Management / Energy Saving


For the Schedule Automatic Operation, weekly setting is available. Enlisting of the schedule exception pro-
cessing schedule (national holiday) is done for a year prevents the air conditioner from an unnecessary
operation of air conditioner, allowing the system to be controlled at the center so that it can be only used for
a necessary case and enabling to obtain excellent energy saving effect. Fixed schedule places like ele-
mentary school, middle school, high school and college or university will get its excellent working effect.

8. Power Failure Backup Function / Powerful Stability


For the existing Central Control System, additional purchase of expensive UPS equipment in provision for
a temporary power failure must be done in the past but for the Deluxe Central control, since the self-power
failure compensation battery is built-in, power is automatically converted by maximum 2 hours. Therefore,
there is almost no malfunction due to a temporary power failure because stable operation is available.

9. Mobility
A wireless radio system may be installed at the Deluxe Central control, it will control the Airconditioners
directly while going around the building with the wireless radio system and its self-battery function (100 m
where there is no obstacle).

10. Convenient Installation


This system can be freely fixed to the wall surface because of its small size, light weight and thin thickness.
It can also stood up on the desk by using, its dedicated cradle. It is not subjected to spatial restriction in
installation space and location since this system communicates on the basis of the I-GW and the Ethernet.

11. Stable Date Storage/Backup


Setup information is saved as it is, even if no power is supplied then also all data is saved in the built-in
flash memory.

12. Scalability
Scalability of the system is easy in case of additionally purchasing equipment since scalable slot such as
USB, Serial (RS-232c), PCMCIA, CF Type is prepared. This system is designed considering sufficient scal-
ability in provision for special request by the customer.

13. Upgrade
Additional installation of a new program is available via the CF memory card and the existing program can
be upgraded to a new program. Using such upgrade function always enables to construct a modern type of
Central Control System.

2004 Product Data 149


2. Central Control

Figure 3) Deluxe Central control

Table 1) Comparison Between Central control Characteristics

Deluxe
PC Central control
Central control
Dedicate PC Required Non-required
Configuration User S/W, Engine S/W Main Body of Web Pad
Deluxe Central control
Position of program Installation Built-in
Max. installation set 256 sets1) 256 sets
numbers
Remote control - -
Control & monitoring Available Available
Schedule management Available Available
System setup Available Available

System monitoring(overview) Available Available

Users lock Available Available


Upgrade Available Available
Touch screen - Built-in
Built-in Flash DB (backup) - Built-in
Wireless LAN (movable) - Available (option)
Non-interruption device Separately add Built-in
Requirements 2)
JVM (provided by MS) -
Life Peripheral devices & PC life Semi-permanent

1) For the PC central control, installation set numbers may respond up to 1024 sets upon users request.
2) JVM (Java Virtual Machine) is basically installed at the Windows but some versions of Window XP may be
manually installed.

150 MPS(Multi Power System) Variable Multi


2. Central Control

2.2.3 Major Function of Deluxe Central Control

[ System Control ]
To check general monitor function of the air con central control
system such as selection of group and air conditioner, air
conditioner control monitor function etc.

PQCSW501A0, PQCSW502A0

[ System Monitor ]

To check the ctual time status of all air conditioners.

PQCSW501A0, PQCSW502A0

[ System Set-up ]

To manage the air conditioner through grouping and record setup


of group and installation position, etc.

PQCSW501A0, PQCSW502A0

[ Time Schedule ]

Setup of a weekly schedule for all, group and individual air


conditioner enabled operation of the system. Processing through
enlist of extra schedule for a year is available.

PQCSW502A0

2004 Product Data 151


2. Central Control

2.2.4 System Configuration

Scenario 1 : In case of not using Internet access function

B part A part Product


Control System
Interface

Delux Central CNU


Control PI485

PI485
Cross UTP Cable
(Cross LAN Cable)
RS-485 Cable

PI485

PI485

* CNU: Central control Network interface Unit


PI485: Product Interface unit for IEEE485 transmission.

Main Specifications
1. Control System(PQCSW501A0, PQCSW502A0)
- Centralized control of maximum 256 indoor units
- Simple Touch PAD method
- GUI setting considering convenience of use
- Power failure compensation with independent Battery Built-in (Max. 2 hours)

2. CNU (PQNFG00A0)
- Combination of maximum 8 outdoor units
- 485 to Ethernet Converter Built-in

3. PI485(PMNFP14A0)
- 1 pcs per outdoor units (Control of 8 outdoor units per bridge)

Note: - GUI(Graphic User Interface) may be changed without any notice, for improvement or options.
- Deluxe central control, CNU and sub PI485(with wire assembly) should be purchased as optional.

152 MPS(Multi Power System) Variable Multi


2. Central Control
2.3 PC Central Control (PQCSS501A0, PQCSS502A0)
2.3.1 MajorFunction of PC Central Control

[ System Control ]
To check general monitor function of the air con central control
system such as selection of group and air conditioner, air
conditioner control monitor function etc.

PQCSS501A0, PQCSS502A0

[ System Monitor ]

To check the current actual time status of the whole of air


conditioner.

PQCSS501A0, PQCSS502A0

[ System Set-up ]

To manage the air conditioner through grouping and record setup


of group and installation position, etc.

PQCSS501A0, PQCSS502A0

[ Time Schedule ]

Setup of a weekly schedule for all, group and individual air


conditioner enables operation of the system. Processing through
enlist of extra schedule for a year is available.

PQCSS502A0

2004 Product Data 153


2. Central Control

2.3.2 System Configuration


Scenario 1 : In case of not using Internet access function

B part A part Product


Control System
Interface

PC Central CNU
Control PI485

PI485
Cross UTP Cable
(Cross LAN Cable)
RS-485 Cable

PI485

PI485

Main Specifications
1. Control System(PQCSS501A0, PQCSS502A0)
- Centralized control of maximum 256 indoor units
- Simple Touch PAD method
- GUI setting considering convenience of use
- Power failure compensation with independent Battery Built-in (Max. 2 hours)

2. CNU(PQNFG00A0)
- Combination of maximum 8 outside units
- 485 to Ethernet Converter Built-in

3. PI485(PMNFP14A0)
- 1 pcs per outdoor units (control of 8 outdoor units per bridge)
Note: - GUI(Graphic User Interface) may be changed without any notice, for improvement or options.
- PC Central control, CNU and sub PI485(with wire assembly) should be purchased as optional.

154 MPS(Multi Power System) Variable Multi


Part 5
Installation

1.Refrigerant Piping System ...............................................156


1.1 Piping Length and Refrigerant Charge........................................156
1.2 Piping Connection Size ...............................................................165
1.3 Necessity of a trap.......................................................................166
1.4 BD Unit ........................................................................................167
1.5 Thermal Insulation Refrigerant Pipe Fitting.................................170
2.Electrical Wiring................................................................171
2.1 Electrical Wiring ..........................................................................171
2.2 Electrical Wiring of BD Unit .........................................................174
3.Drain Pipe Work ................................................................175

2004 Product Data 155


1. Refrigerant Piping System

1.1 Piping Length and Refrigerant Charge


(1) L4UC608FA0
The maximum allowable level and piping length

CASE 1(Ditributor Piping & Direct Piping)

[Outdoor Unit]

A [Indoor Unit]
BD Unit
L1

L2
B
Circuit 1 20m

L3

Circuit 2

It does not matter which unit is higher.

Max Main Total Branch Each Branch


Model Standard Length Max Total piping length
piping length piping length piping length
[Outdoor Unit]
A B L1, L2, L3 A L1 + L 2 + L 3 L1, L2, L3 A+L1+L2+L3 B
L4UC608FA0 5m 7.5m 7.5m 25m 25m 15m 50m 30m

156 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System

CASE 2(Only Direct Piping)

[Outdoor Unit]

A [Indoor Unit]

Circuit 1

20m
B

Circuit 2

It does not matter which unit is higher.

Standard Length Max piping length each indoor unit


L4UC608FA0
A, B A B
Circuit 1 7.5m 50m -
Circuit 2 7.5m - 30m

2004 Product Data 157


1. Refrigerant Piping System

Refrigerant Charge
Direct Piping Circuit
Indoor Unit Pipe Size Rated Max. Additional
Capacity (Btu/h) Gas Liquid Length Length Refrigerant
24k 5/8" (15.88mm) 1/4" (6.35mm) 7.5m 30m 30g/m
36k 5/8" (15.88mm) 1/4" (6.35mm) 7.5m 50m 40g/m

Extra refrigerant = (Extended length - Rated length) x Additional refrigerant

Distributor Piping Circuit


The calculation of the additional charge should take account of the length of pipe.

Additional charge (g)

= Total Main pipe length - rated length X 40 g/m

A
+ 12k Branch pipe length - rated length X 20g/m

+ 18k Branch pipe length - rated length X 30g/m


a b c
+ 24 k Branch pipe length - rated length X 30g/m
12k 12k 12k

( Rated length : Main=3m, Branch=4.5m)

Ex 1) Additional charge of distributor piping circuit Ex 2) Additional charge of distributor piping circuit
Total main pipe(A) = 30m Total main pipe(A) = 20m
Each branch pipe(a, b, c) = 10m Each branch pipe(a) = 15m, (b,c) = 7m

Additional Charge = (30-3)m x 40g/m Additional Charge = (20-3)m x 40g/m


+ (10-4.5)m x 20g/m x 3 + (15-4.5)m x 20g/m
+ (7-4.5)m x 20g/m x 2
= 1410g = 990g

158 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System
(2) L5UC728FA0
The maximum allowable level and piping length
CASE 1(Ditributor Piping & Direct Piping)
[Outdoor Unit]

A BD Unit [Indoor Unit]


L1

L2

B
L3 Circuit 1
30m

L4

Circuit 2

h It does not matter which unit is higher.

Max Main Total Branch Each Branch


Model Standard Length Max Total piping length
piping length piping length piping length
[Outdoor Unit]
A B L1, L2, L3, L4 A L1 + L2 + L3 + L4 L1, L2, L3, L4 A+L1+L2+L3+L4 B
L5UC728FA0 5m 7.5m 7.5m 30m 30m 15m 60m 30m

2004 Product Data 159


1. Refrigerant Piping System

CASE 2(Only Direct Piping)

[Outdoor Unit]

A [Indoor Unit]

Circuit 1

30m
B

Circuit 2

It does not matter which unit is higher.

Standard Length Max piping length each indoor unit


L5UC728FA0
A, B A B
Circuit 1 7.5m 50m -
Circuit 2 7.5m - 30m

160 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System
Refrigerant Charge

Direct Piping Circuit

Indoor Unit Pipe Size Rated Max. Additional


Capacity (Btu/h) Gas Liquid Length Length Refrigerant
24k 5/8" (15.88mm) 1/4" (6.35mm) 7.5m 30m 30g/m
48k 3/4" (19.05mm) 3/8" (9.52mm) 7.5m 50m 50g/m

Extra refrigerant = (Extended length - Rated length) x Additional refrigerant

Distributor Piping Circuit

The calculation of the additional charge should take account of the length of pipe.

Additional charge (g)

= Total Main pipe length - rated length x 50g/m

+ 12k Branch pipe length - rated length x 20g/m A

+ 18k~36k Branch pipe length - rated length x 30g/m


a b c d
( Rated length : Main=5m, Branch=7.5m)
12k 12k 12k 18k

Ex 1) Additional charge of distributor piping circuit Ex 2) Additional charge of distributor piping circuit
Total main pipe(A) = 30m Total main pipe(B) = 30m
Each branch pipe(a, b, c, d) = 7.5m Each branch pipe(a,b) = 10m, (c,d) = 5m

Additional Charge = (30-5)m x 50g/m Additional Charge = (30-5)m x 50g/m


+ (7.5-7.5)m x 20g/m x 3 + (10-7.5)m x 20g/m x 2
+ (7.5-7.5)m x 30g/m + (5-7.5)m x 20g/m
+ (5-7.5)m x 30g/m
= 1250g = 1225g

2004 Product Data 161


1. Refrigerant Piping System

(3) L8UC/H1008FA0
The maximun allowable level and piping length

CASE 1(Direct Piping)

[Outdoor Unit]

Installation of the outdoor unit


in an upper position

A [Indoor Unit]

B 30m

Model Standard Length Max piping length each indoor unit


Max total piping length
[Outdoor Unit] A,B A B
L8UC1008FA0 7.5m 50m 50m 100m(A+B)
L8UH1008FA0 7.5m 50m 50m 100m(A+B)

162 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System

CASE 2(Distributor Piping)


[Outdoor Unit]

Installation of the outdoor unit


in an upper position

A BD Unit [Indoor Unit]


L1

L2

B L3

BD Unit 30m
L4

L5

L6

Total main piping length : 30m( A ), 30m( B )


Total branch piping length : 30m(L1+L2+ L3), 30m(L4 +L5+ L6)
Each branch piping length : 15m(L1,L2,L3,L4 ,L5,L6)
Total system piping length : 60m(30+30), 60m(30+30)
[Indoor Unit]

BD Unit

Installation of the outdoor unit


in a lower position

[Outdoor Unit] BD Unit 30m

2004 Product Data 163


1. Refrigerant Piping System

Refrigerant Charge
Direct Piping Circuit
Indoor Unit Capacity Pipe Size Rated Max Additional
(Btu/h) Gas Liquid Length Length Refrigerant

48k 3/4"(19.05mm) 3/8"(9.52mm) 7.5m 50m 50g/m


Extra refrigerant per circuit = (Extended length - Rated length) x Additional refrigerant

Distributor Piping Circuit

The calculation of the additional charge should take account of the length of pipe.

Additional charge (g)


Circuit 1
A
= Total Main pipe length - rated length x 50g/m

B a b c
+ 12k Branch pipe length - rated length x 20g/m
18k 18k 18k
Circuit 2
+ 18k~36k Branch pipe length - rated length x 30g/m

Rated length = Main pipe : 5m


Branch pipe : 7.5m
d e

24 k 24 k

Additional Charge of Circuit 1 Additional Charge of Circuit 2

Total main pipe(A) = 30m Total main pipe(B) = 30m


Each branch pipe(a, b, c) = 10m Each branch pipe(d, e) = 10m
Additional Charge = (30-5)m x 50g/m Additional Charge = (30-5)m x 50g/m
+ (10-5)m x 30g/m x 3 + (10-5)m x 30g/m x 2
= 1700g = 1550g

164 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System
1.2 Piping Connection Size
(1) L4UC608FA0
Pipe Unit A B C
Liquid 1/4(6.35) 1/4(6.35) Adjust to indoor unit
Inch(mm)
Gas 5/8(15.88) 5/8(15.88) piping size

BD Unit

C
A

B
C

Circuit 1

Circuit 2

(2) L5UC728FA0
Pipe Unit A B C
Liquid 3/8(9.52) 1/4(6.35) Adjust to indoor unit
Inch(mm)
Gas 3/4(19.05) 5/8(15.88) piping size

BD Unit
C
A

B C

C Circuit 1

Circuit 2

2004 Product Data 165


1. Refrigerant Piping System

(3) L8UC/H1008FA0

Pipe Unit A B
Liquid 3/8(9.52) Adjust to indoor unit
inch(mm)
piping size
Gas 3/4(19.05)

BD Unit
A

L8UC1008FA0 A B
L8UH1008FA0
B B B B B

1.3 Necessity of a trap


Since there is fear of the oil held inside the riser piping
flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of
deterioration of oil return, it will be necessary to pro-
vide a trap at an appropriate place in the riser gas pip-
ing.

In case more then 5m


CAUTION
Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.

166 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System

1.4 BD Unit
1.4.1 Installation of BD unit
This unit may be installed suspended from the ceiling or mounted on the wall.
This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up)
However, it may be freely installed in any direction forward or back, and to the sides.
Be sure to leave a 600mm square opening for service and inspection as shown in the diagram below, for both
ceiling - suspended installation and wall-mounted installation.
This unit "does not require drain treatment" as it uses internal foam treatment as low-pressure piping insulation.
Service direction is the side B and C
The piping for the indoor unit may be led around in direction A
The inclination of side B must be within 5C degrees forward or back or to the sides.

6.35 flare
12.7 flare
(298)

(337)
A 9.52 flare
250

19.05 flare

245
Suspension bolt pitch.

Main Pipe
B
(36) 50 50 50 40 30 50
(150)
(38) 50

(111)

(56) 50 50 50 45 300 50
Branch Pipe Cover Control
C
Min 400 Min 400
(Servicing space)
Min 30

Min 300

Inspection opening

2004 Product Data 167


1. Refrigerant Piping System
1.4.2 Installation of main unit

NOTICE :
This unit has two different installation types:
(1) Ceiling-suspended type and (2) wall-mounted type.
Choose the proper installation pattern according to the
location of installation.
The installation location for printed wiring board can be
changed.
Follow the procedure specified in the "CONNECTING
THE WIRING" section to change the location.
(1) Ceiling-suspended type (2) Wall-mountde type

(1) Ceiling-suspended type


Procedure
(1) Fix the fumished hanger metal with two screws.(4 locations in
total).
(2) Using an insert-hole-in- anchor, hang the hanging bolt.
(3) Install a hexagon nut and a flat washer (locally-procured)to
the hanging bolt as shown in the figure in the left, and ift the
main unit to hang on the hanger metal.
(4) After checking with a level that the unit is level, tighten the
hexagon nut.
* The tilt of the unit should be within 5 in front/back and
left/right.

BD unit
Six-sided Nut 15.00
(M10 or M8)

Hanger metal

Flat washer

Hanging bolt
(M10 or M8)
(2) Wall-mounted type
Procedure
(1) Fix the fumished hanger metal with two screws.
(3 locations in total).
(2) After checking with a level that the unit is level, fix the unit
Screws(M5)
with the furnished wood screws.
(locally procude) * The tilt of the unit should be within 5 in front/back and
left/right.

CAUTION
Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again or cover it with
alumium tape.(This is to prevent condensation)
Be sure to install the unit with the ceiling-sie up.
Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be audible.

168 MPS(Multi Power System) Variable Multi


1. Refrigerant Piping System

1.4.3 Connection of Piping


When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate connection ports
maked with matching alphabets. (A, B, C, D)
NOTICE :
A B C D
Be sure to mark all the local refrigerant piping(liquid pipes, gas pipes,
etc.) for each indoor unit designating clearly which room it belongs
in.(A, B, C, D)

NOTICE :
For flaring work the piping, follow the instructions in the installation manual to each unit.

Connecting the pipings to the in door unit


and drain hose to drain pipe
1. Align the center of the pipings and sufficiently tight-
en the flare nut by hand. BD Unit Socket Flare nut Pipes
2. Tighten the flare nut with a wrench.
Outside diameter Torque
mm inch kg.m Open-end wrench (fixed)

6.35 1/4 1.8


Flare nut
9.52 3/8 4.2
12.7 1/2 5.5 Wrench Connection pipe

15.88 5/8 6.6 BD Unit Socket


19.05 3/4 6.6

Wrap the insulation material around the


connecting portion. BD Unit Indoor unit pipe

1. Overlap the connection pipe insulation material and Vinyl tape (wide) Wrap with vinyl tape
the indoor unit pipe insulation material. Bind them Connecting cable
together with vinyl tape so that there is no gap.
Pipe
2. Wrap the area which accommodates the rear piping
Vinyl tape(narrow)
housing section with vinyl tape.

Close up a socket out of use with a brass


cap.
1. Align the center of the piping and sufficiently tighten
the brass cap by hand.
BD Unit Socket Brass cap
2. Tighten the brass cap with a wrench.
3. Wrap the area contacted with insulation.

CAUTION
Never use the plastic cap for closing.

2004 Product Data 169


1. Refrigerant Piping System

1.5 Thermal insulation of refrigerant pipe


Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough
thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating
material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of con-
densation drip, etc. Pay special attention to insulation work to ceiling plenum.
B A C Glass fiber + Steel wire
Heat
insulation Adhesive + Heat - resistant polyethylene foam +
material A Adhesive tape
Indoor Vinyl tape
Outer
Floor exposed Water-proof hemp cloth + Bronze asphalt
covering B
A Steel wire Outdoor Water-proof hemp cloth + Zinc plate + Oily paint
B Piping D E Note:
C Asphaltic oily mastic or asphalt When using polyethylene cover as covering material, asphalt roof-
D Heat insulation material A ing shall not be required.
E Outer covering B
Do not insulate gas or low pressure pipe and liquid or high Be sure to fully insulate connecting portion.
pressure pipe together.
B A
A Liquid pipe
A F B Gas pipe
Bad example
C Electric wire
C D Finishing tape
E Insulating material
D F Transmission cable
E A These parts are not insulated.

E F E A Liquid pipe
B Gas pipe
B A C Electric wire
D Finishing tape
D E Insulating material
C F Transmission cable

Good example E A Liquid pipe


C
B Gas pipe
A
C Electric wire
D
D Finishing rectangular pipe
F E Insulating material
B F Transmission cable

Penetrations
Inner wall (concealed) Outer wall Outer wall (exposed) Sleeve
D Heat insulating material
C E
A A B B Lagging
B
Caulking material
Band
I Waterproofing layer
Sleeve with edge
Penetrating portion on fire
Lagging material
Floor (fireproofing) Roof pipe shaft limit and boundary wall
Mortar or other incombustible caulking
D I Incombustible heat insulation material
G J
F
D When filling a gap with mortar, cover the
B
penetration part with steel plate so that
H the insulation material will not be caved in.
G A For this part, use incombustible materials
B for both insulation and covering.(Vinyl
1m 1m
covering should not be used.)

170 MPS(Multi Power System) Variable Multi


2. Electrical Wiring

2.1 Electrical Wiring


2.1.1 Caution
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.

WARNING:
Be sure to have authorized electric engineers to do electrical work using special circuits in accor-
dance with regulations and this installation manual. If power supply circuit has a lack of capacity or
electric work deficiency, it may cause an electric shock or fire.
2. Install the outdoor unit transmission line away from the power source wiring so that it is not affected by elec-
tric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to outdoor unit.

CAUTION:
Be sure to put outdoor unit to earth. Do not connect earth line to any gas pipe, water pipe, lighten-
ing rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
4. Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is some-
times removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will
be burnt out.
6. Use 2-core shield cable for transmission line.(O mark in the figure below) If transmission lines of different sys-
tems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erro-
neous operations. (X mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB6 for transmission line, and central
control)

A A

C C
TB6 TB6

B E
D D

TB6 TB6

TB6: Transmission line terminal block


A Outdoor unit
B 2-core cable
C Indoor unit
D Remote control
E Multi-core cable

2004 Product Data 171


2. Electrical Wiring

2.1.2 Transmission and power lines


1) Transmission cable
Types : shielding wire CVVS or CPEVS
Diameter : over 0.75mm2
Insulation material : PVC
Maximum allowable temperature: 60C
Maximum allowable line length: under 300m
2) Remote control cable
Types : 3-core cable
Diameter : 0.5mm2
Maximum length: 100m(over 50m, use over 0.5m2)
3) Simple central control cable
Types : 4-core cable
Diameter : over 0.75mm2
Insulation material : PVC
Maximum allowable line length: under 100m
4) Separation of transmission and power lines
If transmission and power lines are run alongside each other then here is a strong likelihood of operational
faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic cou-
pling.
The tables below indicates our recommendation as to appropriate spacing of transmission and power lines
where these are to be run side by side

Current capacity of power line Spacing


10A 300mm
50A 500mm
100V or more
100A 1000mm
100A or more 1500mm

Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m
the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
- power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
- In the same way, when grouping the lines power and signal lines should not be bunched together.

CAUTION
Have the indoor and outdoor units both been earthed?
If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.

172 MPS(Multi Power System) Variable Multi


2. Electrical Wiring

2.1.3 Example connection of transmission and power lines

MPS Variable Multi - Direct Piping


- No need of power supply on the indoor side

Indoor Unit

Power source
3 Phase, 50Hz, 380~415V

Circuit Breaker Outdoor Unit


60k: 25A
72k/100k: 30A

MPS Variable Multi - Distributor Piping


- Power branching with BD unit
- No need of power supply on the indoor side
Indoor Unit

BD Unit
Power source
3 Phase, 50Hz, 380~415V

Circuit Breaker Outdoor Unit


60k: 25A
72k/100k: 30A

2004 Product Data 173


2. Electrical Wiring

2.2 Electrical Wiring of BD Unit


Connect refrigerant pipes and connection wires to the appropriate ports maked with matching alphabets (A, B
and D) on this unit.
Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor units to termi-
nal board numbers.(1, 2 and 3) Always fix each ground wire separately with a ground screw.(See the figure
below.)
After completing the wiring, fix the outer coating of wires securely with wire clamps. The wire clamp on indoor
unit side is furnished. Follow the procedure below to install.
Refer to the circuit diagram on the control cover inside outdoor unit.

NOTICE :
The terminal board numbers are arranged from top to bottom in order of 1, 2 and 3.

In Case of 3 rooms

WARNING
Do not use tapped wires, stand
wires, extensioncords, or starbust
A connections, as they may cause
C room overtheating, electrical shock, or
B fire.
B room
C
A room CN-PWR

Connection wire for indoor units Connection wire for outdoor units
(H05VV, 4wires, 0.75mm) (H05VV, 4wires, 1.2mm)

(1) Remove the control cover. Loosen the two screws,


and slide the cover in the direction of the arrow.

(3) Put in the cover in the direction of the arrow then


tighten the screws.

(2) Perform wiring with reference the wiring diagram


on a control cover of outdoor unit. Allow 300 mm
for the pulling-out section of harness. Fix the wires
completely with wire clamps(4 locations).

174 MPS(Multi Power System) Variable Multi


3. Drain Pipe Work

Drain pipe gradient and support


1) - The drain pipe must be fitted at a gradient of at least 1/100.
- The drain pipe should be as short as possible and free from airlocks.

Indoor unit

Gradient of at least 1 / 100


(1cm/ 1m)

2) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient
of 1/100 is maintained.(PVC pipe should not be bent)
Spacing of supports for horizontal piping
Class Nominal diameter Spacing

Rigid PVC pipe 25~40mm 1.0m or less

3) The length of pipe laid horizontally should be kept a minimum.

Drain trap
Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.
1) Rig the drain trap as shown in the drawing below

Indoor unit

H H: 50mm or more

2) Provide one trap per unit. A single trap for converging units will prove ineffective.
3) Rig the trap to allow for future changing.

Plug

Indoor unit Indoor unit

Plug

2004 Product Data 175


3. Drain Pipe Work

Grouped drain piping


1) It is standard work practice to make connections to the main pipe from above. The pipe down from the
combination should be as large as possible.

Face piping
downward Face the vent pipe mouth downward to keep
foreign matter from penetrating the system

Vent pipe

2) The pipe work should be kept as short as possible and the number of indoor units per group kept to a min-
imum.

Use of an auxiliary drain hose(flexible)


1) If the drain pan made of polystyrene foam is used then an auxiliary drain hose(flexible) is also essential
A flexible drain hose permits the drain socket and drain pipe to be connected without difficulty and pre-
vents any undue strain being placed on the drain pan.

Indoor unit
Auxiliary drain hose Thermal insulation(drain pipe area)

Drain pan Metal clamp


Thermal insulation(band area)

Important points
- The drain pipe size should be at least equal in size to that of the indoor unit drain pipe.
- The drain pipe is thermally insulated to prevent the formation of condensation outside the pipe.
- The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has
been connected some water should be added to the drain pan and the drain pump check to see that it is
functioning correctly.
- All connections should be secure.(Special care is needed with PVC pipe)
- Insulate auxiliary drain hose with thermal insulation band.

176 MPS(Multi Power System) Variable Multi


MULTI
MPS Variable Multi System(50Hz, R22)
Tropical, Free Joint
20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355
Seoul 150-721, Korea
Phone :3777-7969 Fax:3777-5137/8
http://www.lge.com

ctronics
Ele In Approvals:
BAUART G
c.
L

GEPRFT EN ISO 9001


BS EN ISO 9001
M
REG I

TV
IR

TYPE ST F ANSI/ASQC Q9001


Rheinland
LM50 2004-F4
I

O E R E D 97
APPROVED S
4

Product Safety