Product Safety
P/No.: 3828A20428P 9 001 A8 KS A 9001
For continual product development, LG reserves the right to change specifications without notice Replaces: LM50 2004-F3
LG Electronics INC. Printed in Korea. November/2004
General Description
A high-grade, high-quality, advanced individual air-conditioning system that is able to respond to expanding,
more sophisticated housing environment needs.
Large size indoor units are required for coping with the large space like the condominiums or the big houses
where systems are used at present. Besides, there are needs to provide the room air conditioners
owing to the sophisticated interior and small rooms.
On the background of these needs, the new multi outdoor unit, which can connect both the residential indoor
units and the light commercial indoor units, has been developed.
LG Electronics Inc., has developed "MPS(Multi Power System) Variable Multi" system that can efficiently
control air-conditioning ensuring a better environment.
A lot of information regarding the design and the installation of "MPS Variable Multi" system is included in this
publication.
We hope that with this information you would become an expert of the "MPS Variable Multi" system and be
more comprehensive to the system.
LG Electronics Inc.
Air Conditioning Division
TABLE OF CONTENTS
Table of contents Page
Part 5 Installation.......................................................................................155
1. Refrigerant piping System ...........................................................................................156
2. Electrical Wiring ..........................................................................................................171
3. Drain Pipe Work ..........................................................................................................175
Serial Number
Function
A : Basic, L : Nano Plasma (Wall Mounted)
C: Plasma(Ceiling Cassette) G: Low Static
ART COOL(Mirror) Type Front Panel Color
B: Blue, D: Wood, M: Metal, R: Mirror, W: White
Chassis Name
Electrical Rating
6 : 1, 220-240V, 50Hz
L8U H 100 8 F A 0
Serial Number
Function
A : Basic
Multi Type
F : Free Joint Multi Type
Electrical Ratings
8 : 3, 380-415V, 50Hz
Model Type
H : Heat Pump
C : Cooling Only
Unlike traditional multi-type units, it is a next-generation multi type air-conditioner designed to be installed
under any circumstrance, combining with wall-mounted, ceiling-mounted units.
[12,000 Btu/h]
[24,000 Btu/h]
Circuit 2
Case 2
[Indoor Unit]
Circuit 1
[Outdoor Unit]
[24,000 Btu/h]
Circuit 2
[12,000 Btu/h]
BD(Branch Distributor) Unit
[12,000 Btu/h]
[12,000 Btu/h]
[Outdoor Unit]
[12,000 Btu/h]
Circuit 1
[24,000 Btu/h]
Circuit 2
Case 2
[Indoor Unit]
[Outdoor Unit]
Circuit 1
[24,000 Btu/h]
Circuit 2
[Indoor Unit]
Case 1
[48,000 Btu/h]
Short tube connector
(Accessory) Circuit 1
[Outdoor Unit]
[48,000 Btu/h]
Circuit 2
[12,000 Btu/h]
BD(Branch Distributor) Unit
[12,000 Btu/h]
[12,000 Btu/h]
[12,000 Btu/h]
Circuit 1
[12,000 Btu/h]
[Outdoor Unit]
[12,000 Btu/h]
[12,000 Btu/h]
Circuit 2
[12,000 Btu/h]
Note :
1. See the chapter 3 combination table of "Part 3 Outdoor Units" for possible combinations of indoor units.
2. The total capacity index of indoor units is the sum of capacity index of each units and should be within the
maximum capacity index of the outdoor unit.
LMNH/C126LRL0 LMNH/C126TEC0
LMNH/C186TEC0
LMNH/C186LTL0
LMNH/C246TFC0
LMNH/C246LTL0 LMNH/C306TFC0
LMNH/C366TDC0
LMNH/C486TDC0
Ceiling Concealed Duct High Static Ceiling Concealed Duct - Low Static
LMNH/C186BHA0 LMNH/C126BTG0
LMNH/C246BHA0 LMNH/C186BTG0
LMNH/C306BGA0
LMNH/C366BGA0
LMNH/C486BEA0
100% 100%
100%
Cooling Capacity
Cooling Capacity
35%
Energy Saving
40%
Flare nut
Central Control :
Centralized Controller Deluxe Central Controller
First, We have a simple central controller that can And especially, with an intuitively designed GUI and a
operate up to 16 units simultaneously. user-friendly touch panel, you can simultaneously
control up to 256 indoor units, and the system can be
linked to the building management system.
- Indoor unit max 256
CNU
- 8.0 TFT LCD (800*600)
- Touch screen panel
- Available Ethernet
protocol
- Time schedule function
PC Based Controller - Error display and lock function
- Length max 1km
And especially, with an intuitively designed GUI and a
user-friendly touch panel, you can simultaneously
control up to 256 indoor units, and the system can be
linked to the building management system.
IP I-Gateway
Direct Piping
[Outdoor Unit]
A [Indoor Unit]
B 30m
[Indoor Unit]
[Outdoor Unit]
30m
Distributor Piping
[Outdoor Unit]
L2
B L3
BD Unit 30m
L4
L5
L6
[Indoor Unit]
BD Unit
[Outdoor Unit]
BD Unit 30m
4.2 BD Unit
Branch Distributor Unit - For Distributor piping
- Unit for Variable Refrigerant Volume System
Compact Size
Various models
Quiet Operation
(reduced refrigerant running noise of indoor unit)
Flare Connection - No Brazing
No need of drainage
PMBD5420L(For 2 indoor units)
Installation Pattern
PMBD5430L(For 3 indoor units)
PMBD5440L(For 4 indoor units)
Installation Pattern
Ceiling-suspended type Wall-mounted type
Screws(M5)
ws(M5)
(locally procude)
E F G H
[PMBD5440L]
CHAOS Swing
The most pleasant air flow for the human body can
be found within nature. Countless data and
verification resulted in the application of the new Up Speed :Slow
CHAOS theory to LG Air conditioners. Down Speed :Fast
Wind-up effect is controlled by vane angle and speed
to evenly distribute nature-like air throughout the
room. This function analyzes the characteristic of air
flow distribution and creates the pleasant feeling of Angle of vane
natural wind. movement
JET Cool
Jet Cooling function is for quick cooling. In this mode, Normal Jet Cool
strong and cool air is blown at high speeds for 30
3.8 M 5.8 M
minutes until the room temperature reaches to 18C.
Healthy Dehumidification
The hot and humid air has a tendency to rise by convection.
Healthy Dehumidification optimizes this algorithm to keep an
optimum humidity without feeling cold in indoor place.
Dust
electrode
Dust particles discharge
Pre-filter Ionizer Dusts Collection
+
+6.5KV +
Air Purifying System Polluted
Air
discharge
+ Purified
fresh Air
+
- It not only removes microscopic contaminants & dust, but it +
also removes house mites, pollen, and pet fur to help Odour
Generating dusts aluminum coated
plasma Odor molecule electrode(-)
prevent allergic diseases like asthma.It provides odor free, (3.25KV discharge)
300 + + + +
Group Control
1 2 16
1) Operation Summary
- Where several products are linked, one specific control
device can control a specific number of products.
Remote
2) Specific Operation Controller
Low Noise
The most advanced low-noise design.
The adoption of turbo-fan and round type heat exchanger
provides the quietest operation.
Generating plasma
Odour
Odour molecule
Pipe fixture
Slope 1/50~1/100
Maximum 700mm
Easy Installation
Flexible Duct is easy to install, regardless of room Canvas Indoor Unit
Ceiling
size or heater position. Duct
Air Discharge
Air Intake Ceiling Port
Port Board Ceiling Board
Inspection
Port
Zone Control(Accessory)
It controls the temperature of each zone. Opening or
closing of the damper is controlled by sensing the
temperature of each zone. In the cooling mode, if the
temperature of a particular zone is lower than set
temperature then the damper is closed. On the other
hand if the temperature of a particular zone is higher
than the set temperature, damper is opened to
provide cooling to the zone and vice versa in the
heating mode.
Note: All the central control devices listed above are optional accessory,
so these should be purchased separately when needed.
1. Wall Mounted
1. List of Functions.................................................................29
2. Specifications.....................................................................30
3. Dimensional Drawings .......................................................31
4. Wiring Diagrams ................................................................32
5. Piping Diagrams ................................................................33
6. Air Velocity and Temperature Distribution ..........................34
7. Sound Levels .....................................................................35
8. Installation..........................................................................36
9. Accessories .......................................................................44
Model
Features LMNC-LR/ LT, LMNH-LR/LT
Airflow Direction Control(Left & Right) Manual
Airflow Direction Control(Up & Down) Automatic
Airflow Outlet 1
Airflow Steps(Fan / Cool / Heat) 3/4/3
Auto Changeover(Operation) -
Auto Cleaning -
Auto Restart Operation O
Central Control Accessory
CHAOS Wind(Auto Wind) O
Child Lock Function -
Cooling & Heating Fan Operation -
Deice Control O(Only Heat Pump)
Deodorizing Filter O(Triple)
Drain Pump -
E.S.P Control -
Forced Operation O
Group Control -
High Ceiling Operation -
Hot Start Function O(Only Heat Pump)
Jet Cool O
Plasma Air Purifying Filter O(NANO)
Plasma Heat Exchanger -
Prefilter(Washable / Anti-fungus) O
Self Diagnosis Function O
Sleep Mode Operation O
Soft Dry Operation O
Soft Start Function -
Test Function O
Time Delay Safety Function O
Timer(24 Hour, On/Off) O
Timer(Weekly, On/Off) -
Two Thermistor Control -
Wired LCD Remote Control -
Wireless LCD Remote Control O
Zero Stanby Power -
Zone Control -
Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system
Heat Pump
Indoor Unit Type Wall Mounted
Cooling Only
Indoor Unit Type Wall Mounted
LMNC-LR/LT, LMNH-LR/LT
H
More than
More than 5cm
5cm
D
W
More than 2.3m More than
5cm
CHASSIS Distance(mm)
C (Grade) A B C D
Installation plate SR(12k) 0 40 20 40
D
(unit : mm)
Model W H D
LMNC126LRL0 900 285 156
LMNH126LRL0
LMNC186LTL0
LMNH186LTL0
1090 314 172
LMNC246LTL0
LMNH246LTL0
CN-MOTOR
THERMISTOR(IN-PIPE)
THERMISTOR(ROOM)
ZNR
FUSE
250V 2A
CN-POWER
3854A20135W
:Cooling
Heat Exchanger :Heating
C.F.F
lndoor unit
: Thermistor
2m 2m
1.5 0.5
1.5
1m 1.0 1m
1.0
0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m
2m 2m
21 24
18 33
20 30
1m 1m
27
22
24
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m
Cooling Heating
Air velocity [m/s] Air velocity [m/s]
2.7m 2.7m
2m 2m
2.5 1m 1m
2.0
1.0 1.5
0.5 1.0 1.5 0.5
0m 0m
8m 7m 6m 5m 4m 3m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m
2m 2m
18 33
20 1m 30 1m
21
24 27
24 22
0m 0m
8m 7m 6m 5m 4m 3m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m
Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
1m - Reference accoustic pressure 0dB=20Pa.
- Sound level will vary depending on a range of factors such as
0.8m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
Microphone - The operating conditions are assumed to be standard(KS conditions).
Sound Levels(dBA)
Model
H M L
LMNC126LRL0
38 36 34
LMNH126LRL0
LMNC186LTL0
42 38 35
LMNH186LTL0
LMNC246LTL0
46 40 38
LMNH246LTL0
80 80 80
70 70 70
NC-70 NC-70 NC-70
Sound Pressure Level (dB re 20Pa )
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
A glass of water
Screw driver
CHASSIS Distance(mm)
C (Grade) A B C D
Installation plate 0 40 20 40
SR(12k)
D
Loop
Tubing holder Connecting Gas side
cable piping
To remove the holder, Liquid side
press the bottom of Drain hose piping
chassis near the holder 2 Pull
upward and pull the tab
out of its hole. 1 Press
NOTE: If the drain hose is routed inside the room, insulate
the hose with an insulation material* so that dripping from
CAUTION "sweating"(condensation) will not damage furniture or
When install, make sure that the floors.
remaining parts must be removed
*Foamed polyethylene or equivalent is recommended.
clearly so as not to damage the piping
and drain hose, especially power cord
and connecting cable. 4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
For left rear piping top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are properly
1. Route the indoor tubing and the drain hose in the seated on the installation plate by moving it left and
direction of rear left. right.
Connecting
cable
Drain hose
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
Drain hose
slots(clicking sound).
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole. 5. Connecting the pipings to the indoor unit and drain
Do not connect the cable to the indoor unit. hose to drain pipe.
Make a small loop with the cable for easy connection Align the center of the pipings and sufficiently tighten
later. the flare nut by hand.
Vinyl tape(narrow)
Pipe
Drain pipe
Vinyl tape(wide)
Drain hose
Indoor unit
drain hose
Vinyl tape(narrow)
Adhesive
6. Wrap the insulation material around the connect- 1. Route the indoor tubing and the drain hose to the
ing portion. required piping hole position.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands
Insulation material
Connecting cable
Drain pipe
Drain hose
Installation plate
8cm
Spanner (fixed)
Flare nut
Torque Connection
wrench pipe
Indoor
unit tubing
Wrap with
vinyl tape(wide) Drain hose
Tubing holder
1 Hook
2 Push
Screw
Connecting cable
1(L) 2(N) 3 4
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the
wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.)
7) In a wet or moist area, always install an earth leakage circuit breaker.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the
normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
Standard Accessories
M4 x 12L
for liquid pipe
Name
(Other)
Quantity Owner's manual
Installation manual
Shape
1. List of Functions.................................................................46
2. Specifications.....................................................................47
3. Dimensional Drawings .......................................................48
4. Wiring Diagrams ................................................................51
5. Piping Diagrams ................................................................52
6. Air Velocity and Temperature Distribution ..........................53
7. Sound Levels .....................................................................54
8. Installation..........................................................................55
9. Accessories .......................................................................60
Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system
Heat Pump
Indoor Unit Type Ceilling Cassette - 4way
Notes:-
1. Capacities are based on the following conditions: 2. Capacities are Net Capacities.
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB 3. Due to our policy of innovation some specifications may be changed without notifi-
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB cation.
- Interconnecting Piping Length 7.5m 4. : See the page "Combination Table"
- Level Difference of Zero.
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
Cooling Only
Indoor Unit Type Ceilling Cassette - 4way
Notes:-
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notifi-
cation.
4. : See the page "Combination Table"
LMNC-TE, LMNH-TE
600 (Ceiling opening)
75
Unit:mm
670 570
450
5
570
521
670
6 40
4
1 2
30
110 110
269
90
90
190.5
30
160
120.4
52
(unit : mm)
Number Name Descripition
1 Liquid pipe connection 6.35 flare
2 Gas pipe connection 12.7 flare
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill
6 Air suction grill
66
790 (Ceiling opening)
658 (Hanging bolt)
292 744 Unit size
66
Unit:mm
850
744
658
5
850
572
744
6
70
4
1 2
117
110 110
292
90
90
150
212
192
54
30
(unit : mm)
Number Name Descripition
1 Liquid pipe connection 6.35 flare
2 Gas pipe connection 15.88 flare
3 Drain pipe connection
4 Power supply connection
5 Air discharge grill
6 Air suction grill
LMNC-TD, LMNH-TD
45 785(Hanging bolt) 45
5
Unit:mm
840
678
950
785
840
4
30
40
1
2
30
110 110
290
210.5
52 180
90
90
140
(unit : mm)
A/CL UNIT
HVB
DOOR S/W
OUT-PIPE ROOM IN-PIPE
THERMISTOR THERMISTOR THERMISTOR
STEP STEP STEP STEP
MOTOR MOTOR MOTOR MOTOR
CENTRAL CONTROL
TELE CONTROL
TO OUTDOOR UNIT
RD
3
GN/YL GN/YL
1(L) 2(N)
BL
GRILL CONTROL
BR
FUSE
CN-
CN-REMO CN-PTC CN-FLOATCN-DISP DPUMP
CN- CN-
MOTOR VENTIL
CAPACITOR
:Cooling
Heat Exchanger :Heating
Turbo Fan
lndoor unit
: Thermistor
LMNC126TEC0
LMNH126TEC0
12.7(1/2)
LMNC186TEC0
LMNH186TEC0
LMNC246TFC0
6.35(1/4)
LMNH246TFC0
LMNC306TFC0
15.88(5/8)
LMNH306TFC0
LMNC366TDC0
LMNH366TDC0
LMNC486TDC0
19.05(3/4) 9.52(3/8)
LMNH486TDC0
2m 2.0 2.0 2m
2.0 2.0
1.5 1.5
1.5 1.5
1m 1m
1.0 1.0 1.0 1.0
0.5 0.5
0.5 0.5
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
Overall
Notes:
- Sound measured at 1.5m below
the center of the unit.
- Data is valid at free field condition
Ceiling - Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
1.5m
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard(KS conditions)
80 80 80
Sound Pressure Level (dB re 20uPa)
70 70 70
NC-70 NC-70
Sound Pressure Level (dB re 20uPa) NC-70
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
80 80 80
Sound Pressure Level (dB re 20Pa )
70 70 70
NC-70 NC-70 NC-70
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Anti-bacteria filter
Air
Intake
Air Outlet
50 or 50 or
spot the installation location. more more
400 or less
Above 250
100
Ceiling
Ceiling board
Level gauge
66
66
75
Unit:mm
Unit:mm Unit:mm
CAUTION Select and mark the position for fixing bolts and
piping hole.
This air-conditioner uses a drain pump.
Decide the position for fixing bolts slightly tilted to
Install the unit horizontally using a level gauge.
the drain direction after considering the direction
During the installation, care should be taken not to
of drain hose.
damage electric wires.
Drill the hole for anchor bolt on the wall.
NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Air conditioner
Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
Ceiling
150mm
(W3/8 or M10) from the bracket to 40mm
Nut
Flat washer for M10 Air Conditioner body
(W3/8 or M10)
(accessory) Ceiling board Ceiling board
Spring washer
(M10)
Indoor
power cord
1(L) 2(N) 3 4
WARNING
Make sure that the screws of the terminal are free from looseness.
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by
amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so
that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).
Decoration panel
Display
Key holes
Inlet Grille
CAUTION
Install certainly the decoration Good example Bad example
Air conditioner unit
panel.
Cool air leakage causes sweating. Air conditioner Air
unit Cool air leakage
Water drops fall. (no good)
Ceiling Ceiling
board board
Decoration panel Decoration
Fit the insulator (this part) and panel
be careful for cool air leakage
Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Connect the main drain pipe to the exterior
Feed water Flexible drain hose
(accessory) and leave it provisionally until the test comes
Main to an end.
drain pipe Feed water to the flexible drain hose and
check the piping for leakage.
Drain Be sure to check the drain pump for normal
Drain Pump port Glue the joint
operating and noise when electrical wiring is
Drain hose connection complete.
Use the clip (accessory)
When the test is complete, connect the flexi-
ble drain hose to the drain port on the indoor
unit.
Drain pan
Flexible drain hose
CAUTION 1/50~1/100
The supplied flexible drain hose should not be curved,
MAX 700mm
neither screwed. The curved or screwed hose may
cause a leakage of water.
Flexible drain hose
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows: Flexible drain hose
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the
circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the
unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a
overload protection device.
Proper starting power is not given to the compressor.
Standard Accessories
Washer for Insulation for
Name Drain hose Clamp metal Clamp (Other)
hanging backet fitting
Quantity 1 EA 1 EA 8 EA 8 EA 1 SET
1. List of Functions.................................................................63
2. Specifications.....................................................................64
3. Dimensional Drawings .......................................................65
4. Wiring Diagrams ................................................................66
5. Piping Diagrams ................................................................67
6. External Static Pressure & Air Flow...................................68
7. E.S.P. Setting for Phase Control Motor ..............................69
8. Sound Levels .....................................................................72
9. Installation..........................................................................73
10. Accessories .....................................................................78
LMNC-BH/BG LMNC-BE
Model
Features LMNH-BH/BG LMNH-BE
Airflow Direction Control(Left & Right) - -
Airflow Direction Control(Up & Down) - -
Airflow Outlet 1 1
Airflow Steps(Fan / Cool / Heat) 3/3/3 3/3/3
Auto Changeover(Operation) - -
Auto Cleaning - -
Auto Restart Operation O O
Central Control Accessory Accessory
CHAOS Wind(Auto Wind) - -
Child Lock Function O O
Cooling & Heating Fan Operation O O
Deice Control O(Only Heat Pump) O(Only Heat Pump)
Deodorizing Filter - -
Drain Pump Accessory Accessory
E.S.P Control O -
Forced Operation O O
Group Control O O
High Ceiling Operation - -
Hot Start Function O(Only Heat Pump) O(Only Heat Pump)
Jet Cool - -
Plasma Air Purifying Filter Accessory Accessory
Plasma Heat Exchanger - -
Prefilter(Washable / Anti-fungus) O O
Self Diagnosis Function O O
Sleep Mode Operation - -
Soft Dry Operation O O
Soft Start Function - -
Test Function O O
Time Delay Safety Function O O
Timer(24 Hour, On/Off) O O
Timer(Weekly, On/Off) O O
Two Thermistor Control O O
Wired LCD Remote Control O O
Wireless LCD Remote Control Accessory Accessory
Zero Stanby Power - -
Zone Control Accessory Accessory
Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system
Heat Pump
Indoor Unit Type Ceilling Concealed Duct - High Static
Cooling Only
Indoor Unit Type Ceilling Concealed Duct - High Static
LMNC-BH/BG/BE, LMNH-BH/BG/BE
k
A
B
h
i l
C j
E
f
J
K
e
(G) a b c d
D
F
H
Note:
1. Pipe Specification(mm)
Model Liquid Gas
18k 12.7
6.35
24k, 30k, 36k 15.88
48k 9.52 19.05
(Unit: mm)
Model A B C D E F (G) H J K a b c d e f h i j k l
LMNC18/246BHA0
932 882 355 45.5 450 30 87 750 163 260 61.5 243 212.3 243 110 130 52 66 81 30 158.5
LMNH18/246BHA0
LMNC30/366BGA0 1232 1182
355 45.5 450 30 87 830 186 298 229.5 243 232 243 116 160 53 59 81 19 158.5
LMNH30/366BGA0
LMNC486BEA0 1292 1230
570.5 54 680 30 120 1006 294 370 253.5 253 217 253 152 186 42 143 82 50 172
LMNH486BEA0
H
1000
600 600
Suitable dimension "H" is necessary
to get a slope to drain as figure.
Front
CN-OUT
CN-CC CN-PIPE1 CN-REMO CN-PIPE2 CN-ROOM CN-AIRC CN-PTC VENTILATION
E/HEATER
ZONE CONTROL
CN-ZONE
5
4
TO OUTDOOR UNIT
RD
3
GN/YL
FLOAT S/W
CN-FLOAT
BL
1(L) 2(N)
BR
FUSE
CN-POWER
CN-DISP
CN-MOTOR CN-DPUMP
OPTION
RF-REMOTE
CONTROL
3854A20419B
BR
SENSOR
INDOOR DRAIN
ROOM
GN/YL
MOTOR PUMP
YL
BL
BL
OR
RD
BK
BL
FUSE
1(L) 2(N)
BR 250V10A
BL
TO OUTDOOR UNIT
COMP
PIPE
GN/YL RD SENSOR
3
4
FLOAT S/W
5
REMOTE
TERMINAL CONTROL
BLOCK
:Cooling
Heat Exchanger :Heating
Sirocco Fan
lndoor unit
: Thermistor
LMNC186BHA0
12.7(1/2)
LMNH186BHA0
LMNC246BHA0
6.35 (1/4)
LMNH246BHA0
15.88(5/8)
LMNC30/366BGA0
LMNH30/366BGA0
LMNC486BEA0
19.05(3/4) 9.52(3/8)
LMNH486BEA0
Static Pressure(mmAq) 0 2 4 6 8 10 15
Model Name Step CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CCMM(CFM)
External static pressure given after substracting coil losses motor step factory installed.
External static pressure can be higher than the maximum given in the table, but the unit faces the problem of
freezing the coil.
The assured range of air-conditioner is in the only shady part and in the other part, the specification of
air-conditioner may differ with the above table.
If the static pressure of air-conditioner is out of the shady part, please adjust the static pressure.
* Change the connection of the indoor fan motor connector to increase the motor speed to obtain similar CFM
at 15 mmAq Static Pressure as at 10 mmAq Static pressure.
(1) Open the rear cover of the wired remote-controller to set the mode.
R15H
OP2 OP1
R14H OP3 R19H
SW TH R11H
V-H REMO
MAIN
2TH OP7
R18H
R17H
F-H OP6
V-L LO
C070
STAND
HI R03S
R04S
R01S
R02S
SW HIGH
CAUTION
Select
the position after checking duct work and E.S.P of the unit.
Maunfactured in the position F-H.
Push the "On/Off" button. AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
2 AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
Timer LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
Shift the fan speed mode by pressing the fan speed button.
4 And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "220" and "235" respectively.
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
5 Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
LO Filter Out door
Timer
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
Table-7-1
Static Pressure(mmAq) 0 2 4 6 8 10
Model Name Step CMM(CFM) Setting Value
High 16.5 (583) 235 230 225 215 180
LMNC186BHA0
Med 14.5 (512) 245 238 235 230 215
LMNH186BHA0
Low 13.0 (459) 254 252 248 245 240
High 18.0 (636) 220 205 190 50 1
LMNC246BHA0
Med 16.5 (583) 235 230 220 200 100
LMNH246BHA0
Low 14.0 (494) 250 240 235 230 210
High 26.5(936) 153 150 150 148 130 1
LMNC306BGA0
Med 23(812) 173 173 175 175 170 155
LMNH306BGA0
Low 20(706) 190 190 190 190 190 190
High 32.0(1130) 230 230 230 220 150 1
LMNC366BGA0
Med 29.0(1024) 240 240 240 235 230 220
LMNH366BGA0
Low 26.5(936) 245 245 245 245 240 240
Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from
the table. Value other than that in table will not give the combinations of airflow & ESP
which are mentioned in the table.
2. Table 7-1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Table-7-2
Static Pressure(mmAq) Setting 0 2 4 6 8 10
Model Name Step Value CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM)
High 180 22 (777) 21.0 (742) 19.8 (699) 18.3 (646) 16.5 (583)
LMNC186BHA0
Med 215 18.5 (653) 17.8 (629) 17.1 (604) 16.2 (572) 14.5 (512)
LMNH186BHA0
Low 240 16.1 (569) 15.6 (551) 15.1 (533) 14.2 (501) 13.0 (459)
High 1 24.0 (848) 22.5 (795) 20.8 (735) 19.0 (671) 18.0 (636)
LMNC246BHA0
Med 100 21.3 (752) 19.9 (703) 18.7 (660) 17.2 (607) 16.5 (583)
LMNH246BHA0
Low 210 17.0 (600) 16.1 (569) 15.36 (551) 14.7 (519) 14.0 (494)
High 1 34.2(1208) 33.1(1169) 31.7(1119) 29.9(1056) 27.7(978 26.5(936)
LMNC306BGA0
Med 155 27(954) 26.3(929) 26.1(922) 25.8(911) 24.8(876) 23(812)
LMNH306BGA0
Low 190 21(742) 20.8(735) 20.6(727) 20.4(720) 20.4(720) 20(706)
High 1 42(1483) 40(1413) 38(1342) 35.5(1254) 33.5(1183) 32(1130)
LMNC366BGA0
Med 220 39(1377) 37(1307) 35(1236) 33(1165) 31(1095) 29(1024)
LMNH366BGA0
Low 240 34(1201) 32.5(1148) 31(1095) 29.5(1042) 27(954) 26.5(936)
Note: 1. The above table shows the correlation of External Static Pressure & Air Flow.
2. Duct work must be desined within the shaded range of on installing the table.
3. If duct work is designed under External Static Pressure adjust the External Static
Pressure applying air damper.
Overall
Notes:
DISCHARGE SUCTION - Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
DUCT DUCT - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
2m 1.5m
1m - The operating conditions are assumed to be standard(KS conditions)
1m
80 80 80
70 70 70
NC-70 NC-70 NC-70
Sound Pressure Level (dB re 20Pa )
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
LMNC/H366BGA0 LMNC/H486BEA0
90 90
80 80
70 70
NC-70 NC-70
Sound Pressure Level (dB re 20Pa )
Sound Pressure Level (dB re 20Pa )
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
NC-20 NC-20
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
600 600
The place where the unit shall be leveled.
Front
The place shall allow easy water drainage.(Suitable dimen-
Front view
sion H is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical
noise.
The place where air circulation in the room will be good . H
There should not be any heat source or steam near the unit.
CASE 1
C
E
POSITION OF SUSPENSION BOLT
D
Apply a joint-canvas between the unit and duct to absorb
(G)
F
unnecessary vibration.
Apply a filter Accessory at air return hole.
Refer toDimensinal Drawings.
1-3 mm
I
H
Drainage hole
M10 washer X4
(Local
M10 SP. washer X 4 supply)
CASE 2 M10 Nut X4
A place where the unit will be leveled and that can sup-
port the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
CAUTION 5 Suspension
bolts
Tighten the nut and bolt to prevent unit falling.
1(L) 2(N) 3 4
WARNING
Make sure that the screws of the terminal are free from looseness.
Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control
panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of
live pin on the power plug should be over 1.8m.
9.4 Insulation
THERMAL INSULATION All thermal insulation must comply with local requirement.
INDOOR UNIT
CAUTION
1. Decline Installation of indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe should be 5mm.
Front of view
The unit must be or declined to wards drain hose while installation.
Ceiling
1~3mm
CORRECT INCORRECT
Install the P-Trap (or U-Trap) to prevent
Applied U-Trap Dimension
a water leakage caused by the blocking
of intake air filter. A 70mm
B 2C
C 2 x SP
SP = External Pressure B
(mmAq) C
1/50~1/100
Ex) External Pressure
Drain Pipe = 10mmAq U-Trap
A 70mm A
MAX 700mm B 40mm
C 20mm
Drain Pump
Standard Accessories
Insulation for Screws for
Name Clamp metal Drain hose Clamp (Other)
fitting duct flanges
Owner's manual
Installation manual
Washers(8 pcs.)
Shape for gas pipe
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature
control, etc.).
1. List of Functions.................................................................80
2. Specifications.....................................................................81
3. Dimensional Drawings .......................................................82
4. Wiring Diagrams ................................................................83
5. Piping Diagrams ................................................................84
6. E.S.P. Setting for Phase Control Motor ..............................85
7. Sound Levels .....................................................................87
8. Installation..........................................................................88
9. Accessories .......................................................................92
Model
Features LMNC-BT, LMNH-BT
Airflow Direction Control(Left & Right) -
Airflow Direction Control(Up & Down) -
Airflow Outlet 1
Airflow Steps(Fan / Cool / Heat) 3/3/3
Auto Changeover(Operation) -
Auto Cleaning -
Auto Restart Operation O
Central Control Accessory
CHAOS Wind(Auto Wind) -
Child Lock Function O
Cooling & Heating Fan Operation O
Deice Control O
Deodorizing Filter -
Drain Pump Accessory
E.S.P Control O
Forced Operation O
Group Control O
High Ceiling Operation -
Hot Start Function O
Jet Cool -
Plasma Air Purifying Filter -
Plasma Heat Exchanger -
Prefilter(Washable / Anti-fungus) O
Self Diagnosis Function O
Sleep Mode Operation -
Soft Dry Operation O
Soft Start Function -
Test Function O
Time Delay Safety Function O
Timer(24 Hour, On/Off) O
Timer(Weekly, On/Off) O
Two Thermistor Control O
Wired LCD Remote Control O
Wireless LCD Remote Control Accessory
Zero Stanby Power -
Zone Control -
Notes : O : Basic
Optional : Factory-Installed
Accessory : Field-Installed
- : Not available on this system
Cooling Only
Indoor Unit Type Ceiling Concealed Duct - Low Static
LMNC-BT, LMNH-BT
A
B
C
E
D
F
H
G
Note:
1. Pipe Specification(mm)
Dimension Model Liquid Gas
A B C D E F G H
Capacity
12k, 18k 6.35 12.7
12k 708 678 434 51 537 455 230 172
(unit: mm)
18k 1060 1030 434 51 535 805 230 172
H
600 600
Suitable dimension "H" is necessary to get
a slope to drain as figure
CN-OUT
CN-CC CN-PIPE1 CN-REMO CN-PIPE2 CN-ROOM CN-AIRC CN-PTC VENTILATION
E/HEATER
ZONE CONTROL
CN-ZONE
5
4
TO OUTDOOR UNIT
RD
3
GN/YL
FLOAT S/W
CN-FLOAT
BL
1(L) 2(N)
BR
FUSE
CN-POWER
CN-DISP
CN-MOTOR CN-DPUMP
OPTION
RF-REMOTE
CONTROL
3854A20419A
:Cooling
Heat Exchanger :Heating
Sirocco Fan
lndoor unit
: Thermistor
(1) Open the rear cover of the wired remote-controller to set the mode.
R15H
OP2 OP1
R14H OP3 R19H
SW TH R11H
V-H REMO
MAIN
2TH OP7
R18H
R17H
F-H OP6
V-L LO
C070
STAND
HI R03S
R04S
R01S
R02S
SW HIGH
CAUTION
Select
the position after checking duct work and E.S.P of the unit.
Maunfactured in the position F-H.
Push the "On/Off" button. AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
2 AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
Timer LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
Shift the fan speed mode by pressing the fan speed button.
4 And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "165" and "180" respectively.
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
5 Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED
HI
MED
SUB FUNCTION
AUTO Heater Preheat
JET Defrost Humidify
LO Filter Out door
Timer
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
Table-6-1
Static Pressure(mmAq) 0 1 2
Model Name Step(Hi/Med/Lo) Setting Value
10 CMM 210 85 150
LMNC126BTG0
9 CMM 215 190 170
LMNH126BTG0
8 CMM 220 200 175
14 CMM 170 150 130
LMNC186BTG0
13 CMM 185 165 145
LMNH186BTG0
12 CMM 200 180 160
Overall
Notes:
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
Ceiling
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
1.5m
room in which the equipment is installed.
2.0m
- The operating conditions are assumed to be standard(KS conditions)
Microphone
Sound Levels(dBA)
Model
H M L
LMNC/H126BTG0 37 34 31
LMNC/H186BTG0 38 36 34
80 80
70 70
NC-70 NC-70
Sound Pressure Level (dB re 20Pa )
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
NC-20 NC-20
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
The place shall easily bear a load exceeding four times the
indoor units weight.
The place shall be able to inspect the unit as the figure. 600 600
C
E
CASE 1
D
POSITION OF SUSPENSION BOLT
(Unit:mm)
1-3 mm
G
H
Dimension
Capacity A B C D E F G H
(Btu/h) F
12k 708 678 434 51 537 455 230 172
Drainage hole
18k 1060 1030 434 51 535 805 230 175
M10 Nut X4
(Local
M10 SP. washer X 4 supply)
M10 washer X4
A place where the unit will be leveled and that can sup-
port the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.
NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
Select and mark the position for fixing bolts. Insert the set anchor and washer onto the suspen-
Drill the hole for set anchor on the face of ceiling. sion bolts for locking the suspension bolts on the
ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.
Old building New building
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
CAUTION
5 Suspension
Tighten the nut and bolt to prevent unit falling. bolts
1(L) 2(N) 3 4
Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control
panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of
live pin on the power plug should be over 1.8m.
8.4 Insulation
Union for liquid pipe Thermal insulator for refrigerant pipe
(Local supply) Thermal insulator for
Refrigerant pipe and thermal
piping(Local supply)
insulator(Local supply)
CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view
The unit must be horizontal or declined to the drain hose connected when finished installation.
Ceiling
1~3mm
INCORRECT
Applied U-Trap Dimension
CORRECT
A 70mm
Install the P-Trap (or U-Trap) to prevent B 2C
C 2 x SP
a water leakage caused by the blocking SP = External Pressure B
of intake air filter. (mmAq) C
Ex) External Pressure
= 10mmAq U-Trap
A 70mm A
B 40mm
C 20mm
Standard Accessories
Owner's manual
Installation manual
1. Power Supply.....................................................................94
2. Specifications.....................................................................95
3. Combination Table .............................................................98
4. Dimensional Drawings .....................................................100
5. Wiring Diagrams ..............................................................104
6. Piping Diagrams ..............................................................109
7. Capacity Tables ...............................................................114
8. Capacity Coefficient Factor..............................................121
9. Operation Limit ................................................................126
10. Sound Levels .................................................................127
11. Installation......................................................................128
12. Accessories ...................................................................135
[Outdoor Unit]
Circuit Breaker
60k: 25A
72k, 100k : 30A
Earth Wire
[Indoor Unit]
2) Distributor Piping Type (100k Btu/h model shown)
BD Unit
Power source
BD Unit
[Outdoor Unit]
Circuit Breaker
60k: 25A
72k, 100k : 30A
Earth Wire
2.2 BD Unit
Model PMBD5440L PMBD5430L PMBD5420L
Connectable Indoor Units 1~4 1~3 1~2
Combination(Min~Max.) Btu/h 12000~54000 12000~54000 12000~54000
Casing color Paintingless Paintingless Paintingless
Powre Source 1 , 50/60Hz ,220~240/220V 1 , 50/60Hz ,220~240/220V 1 , 50/60Hz ,220~240/220V
Power Consumption W 10 10 10
Runing Current A 0.05 0.05 0.05
Dimensions W*H*D inch(mm) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252) 11.9*5.6*9.9(302*143*252)
Packing Dimension W*H*D inch(mm) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300) 16.6*8.0*11.8(422*202*300)
Net Weight kg 5.0 4.9 4.8
Connecting Cable Direction Indoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Direction Outdoor Unit No. * mm2 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)
Piping Conntcion Liquid inch(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
(To Outdoor Unit) Gas inch(mm) 3/4(19.05) 3/4(19.05) 3/4(19.05)
Piping Conntcion Liquid inch(mm) 1/4 (6.35)*4 1/4 (6.35)*3 1/4 (6.35)*2
(To Indoor Unit) Gas inch(mm) 1/2 (12.7)*4 1/2 (12.7)*3 1/2 (12.7)*2
Piping Length m - - -
Piping Elevation m - - -
Drain hose Unusable
Heat Insulation Both Liquid and Gas pipes
Accessories Hanger EA 4 4 4
Screw EA 8 8 8
Connector EA - - -
Manual EA 1 1 1
Note :
1. BD unit BD unit, Indoor Unit Indoor Unit : Max. Height - 10m
Set up the BD unit and Indoor Unit in 15m.
2. The piping connection must be suit the piping sizes of the indoor unit which will be connected.
(If need, use the connector which is included in the indoor unit)
3. The BD unit should be installed inside the building.
3.1 L4UC608FA0
Cooling
Combination of Indoor unit Cooling
Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1Unit 36 - - - 36 36000 - - - 36000 4500 7.2
12 18 - - 30 12000 18000 - - 30000 4400 7
1 2Unit 12 24 - - 36 12000 24000 - - 36000 4500 7.2
18 18 - - 36 18000 18000 - - 36000 4500 7.2
3Unit 12 12 12 - 36 12000 12000 12000 - 36000 4500 7.2
2 1Unit 24 - - - 24 24000 - - - 24000 2900 4.6
Notes:
1. Cooling Capacity is based on : indoor temp.27C(80.6F) DB, 19C(66.2F) WB; outdoor temp. 35C(95F) DB
2. The total capacity of indoor unit of "Circuit 1" is up to 36000 Btu/h (10.6kW).
The total capacity of indoor unit of "Circuit 2" is up to 24000 Btu/h (7.1kW).
3. The capacity is based on standard length of interconnecting refrigerant line.
[Standard length : Direct Piping - 7.5m (25ft), Distributor Piping - Main 5m(16.4ft), Branch 5m (16.4ft)]
3.2 L5UC728FA0
Cooling
Combination of Indoor unit Cooling
Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1Unit 48 - - - 48 48000 - - - 48000 5300 8.5
12 36 - - 48 12000 36000 - - 48000 5300 8.5
18 18 - - 36 18000 18000 - - 36000 3800 6
18 24 - - 42 18000 24000 - - 42000 4500 7.2
2Unit 18 30 - - 48 18000 30000 - - 48000 5300 8.5
18 36 - - 54 16000 34000 - - 50000 5400 8.6
24 30 - - 54 22000 28000 - - 50000 5400 8.6
24 24 - - 48 24000 24000 - - 48000 5300 8.5
1 12 12 12 - 36 12000 12000 12000 - 36000 3800 6
12 12 18 - 42 12000 12000 18000 - 42000 4500 7.2
12 12 24 - 48 12000 12000 24000 - 48000 5300 8.5
3Unit 12 12 30 - 54 11110 11110 27780 - 50000 5400 8.6
12 18 18 - 48 12000 18000 18000 - 48000 5300 8.5
12 18 24 - 54 11110 16670 22220 - 50000 5400 8.6
18 18 18 - 54 16670 16670 16670 - 50000 5400 8.6
12 12 12 12 48 12000 12000 12000 12000 48000 5300 8.5
4Unit
12 12 12 18 54 11000 11000 11000 17000 50000 5400 8.6
2 1Unit 24 - - - 24 24000 - - - 24000 2700 4.4
Notes:
1. Cooling Capacity is based on : indoor temp.27C(80.6F) DB, 19C(66.2F) WB; outdoor temp. 35C(95F) DB
2. The total capacity of indoor unit of "Circuit 1" is up to 54000 Btu/h (15.8kW).
The total capacity of indoor unit of "Circuit 2" is up to 24000 Btu/h (7.1kW).
3. The capacity is based on standard length of interconnecting refrigerant line.
[Standard length : Direct Piping - 7.5m (25ft), Distributor Piping - Main 5m(16.4ft), Branch 5m (16.4ft)]
Heating
Combination of Indoor unit Heating
Operation
(k Btu/h) Each Capacity Input Current
Circuit Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
1 Unit 48 - - - 48 48000 - - - 48000 4600 7.3
12 36 - - 48 12000 36000 - - 48000 4600 7.3
18 18 - - 36 18000 18000 - - 36000 3100 4.9
18 24 - - 42 18000 24000 - - 42000 3800 6.0
2 Unit 18 30 - - 48 18000 30000 - - 48000 4600 7.3
18 36 - - 54 16000 34000 - - 50000 4700 7.5
24 30 - - 54 22000 28000 - - 50000 4700 7.5
1 24 24 - - 48 24000 24000 - - 48000 4600 7.3
or 12 12 12 - 36 12000 12000 12000 - 36000 3100 4.9
2 12 12 18 - 42 12000 12000 18000 - 42000 3800 6.0
12 12 24 - 48 12000 12000 24000 - 48000 4600 7.3
3 Unit 12 12 30 - 54 11110 11110 27780 - 50000 4700 7.5
12 18 18 - 48 12000 18000 18000 - 48000 4600 7.3
12 18 24 - 54 11110 16670 22220 - 50000 4700 7.5
18 18 18 - 54 16670 16670 16670 - 50000 4700 7.5
12 12 12 12 48 12000 12000 12000 12000 48000 4600 7.3
4 Unit
12 12 12 18 54 11000 11000 11000 17000 50000 4700 7.5
Notes:
1. Cooling Capacity is based on : indoor temp.27C(80.6F) DB, 19C(66.2F) WB; outdoor temp. 35C(95F) DB
2. Heating Capacity is based on : indoor temp.20C(60F) DB; outdoor temp. 7C(44.6F) DB, 6C(42.8F) WB
3. The total capacity of indoor unit is up to 54000 Btu/h (15.8kW) per circuit.
4. The capacity is based on standard length of interconnecting refrigerant line.
[Standard length : Direct Piping - 7.5m (25ft), Distributor Piping - Main 5m(16.4ft), Branch 5m (16.4ft)]
L4UC608FA0
W D
(unit : mm)
Model
L4UC608FA0
Dimension
W 711
H 828
D 687
L5UC728FA0
806
153 500(bolt hole) 153
15
700(bolt hole)
730
690
Air outlet
40
Air
inlet
Air
inlet
1444
1512
Service Panel
670
Knockout hole
(For the control wiring,
the power supply,
refrigerant connecting
pipe)
100
220
28
Knockout hole
(For the control wiring, the power supply,
refrigerant connecting pipe) (Unit : mm)
L8UC1008FA0/L8UH1008FA0
L4
L3
L2
D
L7
H
L1
L6
D
L8
Model
L8UC1008FA0, L8UH1008FA0
Dimensions
W mm 1,280
H mm 1,520
D mm 730
L1 mm 1,444
L2 mm 700
L3 mm 690
L4 mm 900
L5 mm 10
L6 mm 670
L7 mm 48
L8 mm 28
4.2 BD Unit
(Unit: mm)
6.35 flare
12.7 flare
(298)
(337)
9.52 flare
250
19.05 flare
245
Suspension bolt pitch.
Main Pipe
(36) 50 50 50 40 30 50
(150)
(38) 50
(111)
(56) 50 50 50 45 300 50
Branch Pipe Cover Control
Min 300
Inspection opening
MAGNETIC CONTACTOR
BK
U
WH
V
LEV
W RD
COMP(A)
WH
RD
BK
1
BL
CN-COMP
CN-LEV-SINGLE
(BL)
MAGNETIC CONTACTOR
RD
3
BK
(RD)
U
WH
V
W RD
COMP(B)
MAIN PCB ASSY
BR
WH
RD
BK
(COMP-S)CN-FAN1(4WAY-S)
(WH)
MAGNETIC CONTACTOR
BK
U
WH
V BK
W RD BL
COMP(C) CN-FAN2
BR
YL
FMo
(WH) OR
(WH)
FUSE 250V
(YL)
CN_TH1
CN_POWER CN_COM
3 1 1 2 3 4 5 6 (WH) (RD)
(WH)
OR
RD
BR
BL
BK
WH
OR
RD GN/YL
BL GN/YL
BK BK
BR BR BR BL OR
TB1 HP LP
GN/YL
Main Power
TO INDOOR TO INDOOR
380-415V3N~50Hz UNIT-A UNIT-B
(DISTRIBUTOR)
NOTE
LEV LINEAR EXPANSION VALVE
FMo FAN MOTOR CN/YL GREEN & YELLOW
COMP COMPRESSOR OR ORANGE
BK BLACK RD RED
BR BROWN WH WHITE
BL BLUE YL YELLOW
3854A20392H
L5UC728FA0
BK
WH
RD
CN_COMP CN_3PHASE
MAGNETIC CONTACTOR
BK
U OR OR
WH BL BL
V CN_FAN1 BK BK
W RD BR BR
FAN1
YL YL
COMP (C) BL
YL BK
RD BL BK SV Solenoid Valve2
RD
TB2
CN_4,S
BK
BL BK SV Solenoid Valve1
MAGNETIC CONTACTOR MAIN
BK
U
PCB
WH
V
W RD
COMP (B)
WH
WH
WH
RD
RD
BK
BK
CN_PRESS
MAGNETIC CONTACTOR
BK
U
WH
V
W RD
COMP (A)
CN_COM CN_POWER CN_TH1 CN_TH2 CN_TH3
BL
BK
WH
BK
BL
BR
BK
RD
BL
BL BL
BR BR BR
GN/YL
A ROOM B ROOM
Main Power
TO INDOOR UNIT (DISTRIBUTOR)
NOTE
LEV LINEAR EXPANSION VALVE
FMo FAN MOTOR CN/YL GREEN & YELLOW
COMP COMPRESSOR OR ORANGE
BK BLACK RD RED
BR BROWN WH WHITE
BL BLUE YL YELLOW
L8UH1008FA0
BR
WH
RD
BK
OR OR
CN_COMP CN_3PHASE BL BL
CN_FAN2 BK BK
BR BR FAN2
MAGNETIC CONTACTOR BK YL YL
BK
TB1
U OR OR
WH BL BL
V CN_FAN1 BK BK
W RD BR BR
FAN1
YL YL
COMP (C) BL
YL BK
RD BL BK SV Solenoid Valve2
RD
TB2
CN_4,S WH
BK
BK BL BK SV Solenoid Valve1
MAGNETIC CONTACTOR MAIN
BK
U
PCB
WH BL BK
V BK 4WV 4Way Valve2
W RD
COMP (B)
BL BK
WH BK 4WV 4Way Valve1
WH
WH
RD
RD
BK
BK
CN_PRESS
MAGNETIC CONTACTOR
BK
U
WH
V
W RD
COMP (A)
CN_COM CN_POWER CN_TH1 CN_TH2 CN_TH3
BL
BK
WH
BK
BL
BR
BK
RD
BL
BL BL
BR BR BR
GN/YL
A ROOM B ROOM
Main Power
TO INDOOR UNIT (DISTRIBUTOR)
3854A20354S
L8UC1008FA0
BR
WH
RD
BK
OR OR
CN_COMP CN_3PHASE BL BL
CN_FAN2 BK BK
BR BR FAN2
BK YL YL
MAGNETIC CONTACTOR
BK
TB1
U OR OR
WH BL BL
V CN_FAN1 BK BK
W RD BR BR
FAN1
YL YL
COMP (C) BL
YL BK
RD BL BK SV Solenoid Valve2
RD
TB2
CN_4,S
BK
BL BK SV Solenoid Valve1
MAGNETIC CONTACTOR MAIN
BK
U
PCB
WH
V
W RD
COMP (B)
WH
WH
WH
RD
RD
BK
BK
CN_PRESS
MAGNETIC CONTACTOR
BK
U
WH
V
W RD
COMP (A)
CN_COM CN_POWER CN_TH1 CN_TH2 CN_TH3
BL
BK
WH
BK
BL
BR
BK
RD
BL
BL BL
BR BR BR
GN/YL
A ROOM B ROOM
Main Power
380-415V3N~50Hz TO INDOOR UNIT (DISTRIBUTOR)
3854A20354V
5.2 BD Unit
WIRING DIAGRAM
CN_JIG1
FROM OUTDOOR
TO INDOOR UNIT
UNIT
TROUBLE DIAGNOSIS
LED DIAGNOSIS
NORMAL
3854A22003A
Notes;
1. 'PMBD5420L' unit : "A,B" parts available.
2. 'PMBD5430L' unit : "A,B,C" parts available.
3. 'PMBD5440L' unit : "A, B, C, D" parts available.
OUTDOOR UNIT
Field Piping
Gas (15.88)
Field Piping
Liquid (6.35) Heat
Check Exchanger
Check
Valve Valve
Accumulator
Compressor A Compressor B
Field Piping
Gas (15.88)
Field Piping
Liquid (6.35) LEV Heat
Exchanger
Compressor C
Refrigerant Flow
Cooling
L5UC728FA0
OUTDOOR UNIT
Field Piping
Gas (19.05)
Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve
Accumulator
Compressor A Compressor B
Field Piping
Gas (15.88)
Field Piping
Liquid (6.35) LEV Heat
Exchanger
Compressor C
Refrigerant Flow
Cooling
L8UC1008FA0
OUTDOOR UNIT
Field Piping
Gas (19.05)
Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve
Accumulator
Compressor A Compressor B
Field Piping
Gas (19.05)
Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve
Accumulator
Compressor C Compressor D
Refrigerant Flow
Cooling
L8UH1008FA0
OUTDOOR UNIT
Reversing
Valve
Field Piping
Gas (19.05)
Field Piping
Liquid (9.52) LEV Heat
Check Exchanger
Check
Valve Valve
Accumulator
Compressor A Compressor B
Field Piping
Gas (19.05)
Field Piping
Liquid (9.52) LEV Heat
Check Exchanger
Check
Valve Valve
Accumulator
Compressor C Compressor D
Refrigerant Flow
Cooling
Heating
6.2 BD Unit
Refrigerant Flow
Cooling
Heating
Outdoor
Unit
9.52 Main Liquid
Piping
12.7
D Gas
12.7 LEV-A
C Gas
B Gas 12.7
LEV-B
12.7
A Gas
LEV-C
Indoor
Unit LEV-D
6.35
D Liquid
6.35
C Liquid
6.35
B Liquid
6.35
A Liquid
(Unit : mm)
Notes;
1. Flare connection for the field piping connection
2. Adjust to indoor unit and outdoor unit piping size. Use the connector if the pipe size is
not matched when connecting indoor unit.
3. L.E.V.: Linear Expansion Valve
4. PMBD5420L : A, B
PMBD5430L : A, B, C
PMBD5440L : A, B, C, D
7.1 L4UC608FA0
[Cooling Capacity(English Unit)]
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping - 16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC : Total Cooling Capacity(1,000 Btu/h)
4. PI : Power Input(kW)
7.2 L5UC728FA0
[Cooling Capacity(English Unit)]
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping -16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC : Total Cooling Capacity(1,000 Btu/h)
4. PI : Power Input(kW)
7.3 L8UC1008FA0/L8UH1008FA0
[Cooling Capacity(English Unit)]
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping -16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC : Total Cooling Capacity(1,000 Btu/h)
4. PI : Power Input(kW)
5. This table is the capacity of circuit 1. Circut 2 is same.
Notes : 1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 7CDB/6CWB(44.6FDB/42.8FWB)
Corresponding refrigerant piping length : Direct piping - 25ft
Distributor piping -16.4ft(Main) + 25ft(Branch)
Level difference : 0 ft
3. TC=Total heating capacity(Unit:1,000 Btu/h)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
5. This table is the capacity of circuit 1. Circut 2 is same.
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity" Table above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Correction Factor 0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00
L4UC608FA0
Rate of Cooling Change in Capacity by Main Piping Length & Direct Piping Length
100.0%
Rate of Change in Cooling Capacity(%)
95.0%
Main Piping
90.0% 36k
85.0%
80.0%
75.0%
70.0%
0 5 10 15 20 25 30 35 40 45 50
Piping Length(m)
L5UC728FA0
Rate of Cooling Change in Capacity by Main Piping Length & Direct Piping Length
100.0%
Rate of Change in Cooling Capacity(%)
95.0%
Main Piping
90.0%
48k
85.0%
80.0%
75.0%
70.0%
0 5 10 15 20 25 30 35 40 45 50
Piping Length(m)
L8UC1008FA0/L8UH1008FA0
Rate of Change
in Cooling Capacity 100.0% 98.8% 97.3% 95.8% 94.3% 92.8% 91.3% 89.8% 88.3% 86.8%
Rate of Change
in Cooling Capacity 100.0% 99.6% 99.2% 98.7% 98.3% 97.8% 97.4% 96.9% 96.5% 96.0%
Rate of Change in Capacity by Main Piping Length & Direct Piping Length
100.0%
Rate of Change in Cooling Capacity(%)
95.0%
90.0%
85.0%
80.0%
75.0%
70.0%
0 5 10 15 20 25 30 35 40 45 50
Piping Length(m)
: Heating
99.0%
98.0%
97.0%
96.0%
95.0%
94.0%
0 7.5 11.25 15
Branch Piping Length(m)
99.5% : Heating
99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)
100.0% : Cooling
99.5% : Heating
Rate of Change in Capacity(%)
99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)
100.0% : Cooling
99.5% : Heating
Rate of Change in Capacity(%)
99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)
100.0% : Cooling
99.5% : Heating
Rate of Change in Capacity(%)
99.0%
98.5%
98.0%
97.5%
97.0%
96.5%
96.0%
95.5%
95.0%
0 7.5 11.25 15
Branch Piping Length(m)
Item Range
54(129.2)
Standard operation
21(69.8)
14(57.2) 24(75.2)
Indoor air temperature C W.B.(F)
Outdoor air temperature C W.B.(F)
Standard operation
0(32)
14(57.2) 28(82.4)
Indoor air temperature C D.B.(F)
Overall
Notes:
- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
Center of
Outdoor Unit - Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
1m
- The operating conditions are assumed to be standard
D (KS conditions)
1m
50Hz, 380-415V
Model
Sound Levels(dBA)
L4UC608FA0 63
L5UC728FA0 60
L8UC1008FA0
60
L8UH1008FA0
80 80 80
70 70 70
Sound Pressure Level (dB re 20Pa )
Model : L4UC608FA0
Ensure that the space around the back is more than 90cm and sides is more than 90cm. The front of the unit
should have more than 90cm of space.
Fence or
obstacles More than 120cm
More than
90cm
Fe
ob nce More than
sta or 90cm
cle
s More than 90cm
More than 90cm
Model : L5UC728FA0
(1) Individual installation
Basic Space required
A space of at least 250 mm is nessary at the back for inlet air. Tacking servicing, a space of about 750 mm
should be provided at the front.
Rear B
A : 750 mm or more
B : 250 mm or more
C : Top discharge(open in principle)
D E
D : Front inlet(open in principle)
E : Rear inlet(open in principle)
Front
service space
A
A : 750 mm or more
B : 250 mm or more
C : 150 mm or more A B
Rear B
C C
Front A
B
A : 750 mm or more
B : 250 mm or more B B
A D
B
C F
E
A : Open state
B : 750 mm or more
C : 250 mm or more
D : 250 mm or more
Rear
Front
Rear
Front
Model : L8UC1008FA0/L8UH1008FA0
(1) Individual installation
Basic Space required
A space of at least 250 mm is nessary at the back for inlet air. Tacking servicing, a space of about 750 mm
should be provided at the front.
Rear B
A : 750 mm or more
B : 250 mm or more
C : Top discharge(open in principle)
D E
D : Front inlet(open in principle)
E : Rear inlet(open in principle)
Front
service space
A
When inlet air enters from right and left sides of unit
A : 750 mm or more
B : 250 mm or more
C : 150 mm or more A B
Rear B
C C
Front A
B
A : 750 mm or more
B : 250 mm or more B B
A
D
C F
E
A : Open state
B : 750 mm or more
C : 250 mm or more
Front
D : 250 mm or more
Rear
Rear
Front
7002
Installation foot
50
0
5002
250 250
5002 556 5002 556 5002
Installation foot
90
0
9002
250 250
9002 556 9002 556 9002
A 40 or less A 40 or less
B Rope suspension part B Rope suspension part
Caution:
Be very careful to carry product.
Do not have only one person carry product if it is more than 20 kg.
PP bands are used to pack some products. Do not use them as a mean for transportation because they are
dangerous.
Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support
may make outdoor unit unstable, resulting in a fall of it.
Standard accessories
Installation manual
Optional accessories
No. Name Model No.
PMBD5420L(For 2 Indoor Units)
1 BD Unit PMBD5430L(For 3 Indoor Units)
PMBD5440L(For 4 Indoor Units)
3 Operation Mode
6 Used to select the operation mode.
Selection
16 2 Used to set the timer when the desired time is
7 Timer Set
8 obtained.
Timer Cancel
5
7 8 Timer Cancel Used to cancel the timer.
9 6
Program Week Holiday
10 4 9 Week Used to set a day of the week
11 SET/CLR
12 10 Program Used to set the weekly timer.
Hour Min RESET 14
13 15 11 Holiday Used to set a holiday of the week.
Used to set the time of the day and change the
12 Time Set
time in weekly timer Function.
13 Set and Clear Used to set and clear the weekly timer.
Room Temperature
14 Used to check the room temperature.
Checking
Used to set the current time and clear the setting
15 Reset
time.
Used to take the signal from wireless remote
16 Signal Receptor
control
Outdoor
Outdoor unit
unit
PI485 : PMNFP14A0
MAIN PCB
L PI485
CN_CENTRAL
MAIN PCB
CN_CENTRAL N
L
10
G
PI485 A
B
VCC CENTRAL
GND
CN OUT C
CONTROL
D UNIT
Outdoor
Outdoor unit
unit LED9 LED10
S14
LED11
+ S15
LED12
+ S16
+ +
ON KSDO4H
Master Mode LED17
L1 2 3 4
S19
INDOOR UNIT 2
BUS
B
BUS
A S1
CN-POWER
LED2
S2
L
CN-POWER
GND
CN-COM A
S4
CN-COM B
Master DIP SWITCH
LED3 LED4
GND IC1P
+
S5
+
S6
+ + S3
+10V
+
LED9
S9
+
LED10
S10
+
LED11
S11
LED12
S12
S16
1. Adhere the PI485 Module(For connecting central control) to the Control Box.
S14 + S15 +
+ +
3. In the case of connecting two more than central control, set the Master/Slave mode
+
LED17 ON KSDO4H
L1 2 3 4
BUS
INDOOR UNIT 6 Vcc GND C D 001
B CN-POWER
GND
BUS
A S1
CN-POWER
LED2
S2
LED3
L
LED4
CN-COM A
S4
CN-COM B
+10V +
S9
+
S10
+
S11 S12
Indoor No.
LED9 LED10 LED11 LED12
D C GND VCC
LED14
PWB:6870A10001A
ASM:6711A20005E
S15 S18
+
LED17 ON KSDO4H
Outdoor unit 2 L1 2 3
S19
4
ON KS DO 4H
L1 2 3 4
ON KS DO 4H
1,4 ON + All OFF : Connection of "MPS Variable Multi Connection +
L1 2 3 4
Central Controller applied LGAP" Case.
Function of LG Network
- It is possible to connect the network of LG air conditioners and to connect various contents of the network
system, which is simple, deluxe and PC central control.
- Please refer to "LG Control System Manual" about the detail functions and the products possible to network.
- As the Interface for networking, PMNFP14A0 is applied.
Using Wired Remote Control 1. Press 13(program) and 16(set and clear) key more
than 3 second then "Address Setting Mode" starts.
2. Set the address of indoor unit by using "Temperature
setting" key.
Range of address : 00 ~ FF
AUTO SWING OPERATION SET TEMP FAN SPEED SUB FUNCTION
Room Temp
HI
MED
AUTO Heater Preheat
JET Defrost Humidify 1
LO Filter Out door
Time ZONE 1 2 3 4
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
3
17 2 Ex) 3 A
10 Timer Cancel
5
11
12 6
Program Week Holiday
13 4
Plasma
14 Set/Clr
7
15 Hour Min RESET 8 Group Room(Indoor Unit)
16 9 No. No.
18
3. After setting address, press 13(program) and 16(set
Heat Pump Model
and clear) key more than 3 second then "Address
Setting Mode" is finished.
4
2 10
CANCEL
7 9
ON OFF SET
11 AUTO CLEAN
Group Room(Indoor Unit)
8 16
13 No. No.
12
15
14 3) After address setting, pressing 1(On/Off) key, address
setting is finished. The address that is set is displayed on a
Flip-up door
display window of indoor unit.
(opened) * notice : The mothod of display and time is different
according to indoor unit type.
4) If the remote control is reset, normal mode starts.
2. Address Monitoring
2.
1) Press 6(Chaos Swing) & 13(Reset) key at the same time then "Address Monitoring Mode"
starts.
2) At the address monitoring mode, pressing 1(On/Off) key, The address that is set is displayed
on a display window of indoor unit.
* notice : The mothod of display and time is different according to indoor unit type.
3) If the remote control is reset, normal mode starts.
* Notice : Confirm that wired and wireless remote control are able to select the address or not.
2.1.7 Installation
CAUTIONS
INSTALLATION ORDER
1. Remove upper & lower case. 2. Fixate screw in the holes of the 3. For Dip switch, and Rotary
case bottom. switch setting, refer to the page
How to Install.
4. For wiring connection, refer page 5. Adjust the upper case in accor- 6. Check the operation by supply-
Installation Procedure dance with back case while ing the power.
assembling as shown in the fig-
ure.
Out door unit Terminal Block Wire Color Central Control Terminal
GND BLUE GND
Vcc Red Vcc
C Brown C
D Yellow D
2. After attaching the supplied wire to terminal, link the connecting wire.
If necessary, Cut the indicated part of front case to draw the lead wire.
It is possible to set 0~15 Group(Total 16 Groups). All the numbers on the rotary switch represent the different
Group Numbers. By changing the knob we can set rotary switch to the group number we want to control.
The above fig. Shows the control of group number 0. Similarly we can control all the 16 Groups.
Master Mode
Rotary Switch
Dip Switch
ON
OFF Slave Mode
. ACCEASSORY PARTS
Central control and sub PI485(with wire assembly) should be purchased as optional.
Specially for this system, installation is simple and user's environment is excellent. Central control is available
by a simple manipulation. In addition, this system have the self-battery built-in and can stably operate in spite
of outside disturbance such as temporary power failure. This system has no need of additional peripheral
equipment like UPS (Undisturbed Power System) and AVR to be purchased for stability when composing the
existing PC central control system, and has so attractive advantage in installation costs.
Using the Deluxe Central control enables the management room to setup lock of each air conditioner and
prevent indoor control of the individual air conditioner and restrain the necessary use. In case of releasing the
lock, you may control the system by using the wire/wireless remote control at the place where the individual
air conditioner is installed.
Setup of a weekly schedule is available and detailed schedule of the individual air conditioner can be easily
setup through the GUI. Details of schedule setup can be immediately checked with a graph. This system is a
product to meet energy saving and convenience at the same time at a place like a school by using this sched-
ule function.
Depending on installation environment, location and conditions of use, you can setup groups. With this setup,
more efficient operation at the center is available. Setup without requiring other equipment is available by
using the GUI and change by the consumer is also available after installation.
You can reduce development time to configure special system upon the request by the consumer and conve-
niently this system by using the touch panel.
Where needs from a new customer occur or where purchase of additional air conditioner is done, the Deluxe
Central control can be smoothly installed.
Deluxe
Central control CNU
PI485
PI485
1. Individual/Integrated Operation/Monitoring
You can identify operation status of the air conditioner, operation mode, wind quantity, wind direction, lock-
ing, temperature setting and error, etc by selecting the installed air conditioner through individual selection,
group selection or all selection. Individual setup and operation of the detailed functions are available.
Therefore, managing with Deluxe Central control installed at the control room at a building where a number
of air conditioners are installed, is a convenient way.
2. Group Management
Group management for the installed air conditioners is available. Group can be seperated by their nature,
location and size of each air conditioner which enables convenient use. In addition, allotment of respective
name to the setup group allows further intuitive management.
3. Self-diagnosis Function
The air conditioner installed can self-diagnosed its error status and then transmits the result to the central
control. Therefore, a rapid countermeasure against failure of the air conditioner allows easy management
and increases the usage life of air conditioner.
9. Mobility
A wireless radio system may be installed at the Deluxe Central control, it will control the Airconditioners
directly while going around the building with the wireless radio system and its self-battery function (100 m
where there is no obstacle).
12. Scalability
Scalability of the system is easy in case of additionally purchasing equipment since scalable slot such as
USB, Serial (RS-232c), PCMCIA, CF Type is prepared. This system is designed considering sufficient scal-
ability in provision for special request by the customer.
13. Upgrade
Additional installation of a new program is available via the CF memory card and the existing program can
be upgraded to a new program. Using such upgrade function always enables to construct a modern type of
Central Control System.
Deluxe
PC Central control
Central control
Dedicate PC Required Non-required
Configuration User S/W, Engine S/W Main Body of Web Pad
Deluxe Central control
Position of program Installation Built-in
Max. installation set 256 sets1) 256 sets
numbers
Remote control - -
Control & monitoring Available Available
Schedule management Available Available
System setup Available Available
1) For the PC central control, installation set numbers may respond up to 1024 sets upon users request.
2) JVM (Java Virtual Machine) is basically installed at the Windows but some versions of Window XP may be
manually installed.
[ System Control ]
To check general monitor function of the air con central control
system such as selection of group and air conditioner, air
conditioner control monitor function etc.
PQCSW501A0, PQCSW502A0
[ System Monitor ]
PQCSW501A0, PQCSW502A0
[ System Set-up ]
PQCSW501A0, PQCSW502A0
[ Time Schedule ]
PQCSW502A0
PI485
Cross UTP Cable
(Cross LAN Cable)
RS-485 Cable
PI485
PI485
Main Specifications
1. Control System(PQCSW501A0, PQCSW502A0)
- Centralized control of maximum 256 indoor units
- Simple Touch PAD method
- GUI setting considering convenience of use
- Power failure compensation with independent Battery Built-in (Max. 2 hours)
2. CNU (PQNFG00A0)
- Combination of maximum 8 outdoor units
- 485 to Ethernet Converter Built-in
3. PI485(PMNFP14A0)
- 1 pcs per outdoor units (Control of 8 outdoor units per bridge)
Note: - GUI(Graphic User Interface) may be changed without any notice, for improvement or options.
- Deluxe central control, CNU and sub PI485(with wire assembly) should be purchased as optional.
[ System Control ]
To check general monitor function of the air con central control
system such as selection of group and air conditioner, air
conditioner control monitor function etc.
PQCSS501A0, PQCSS502A0
[ System Monitor ]
PQCSS501A0, PQCSS502A0
[ System Set-up ]
PQCSS501A0, PQCSS502A0
[ Time Schedule ]
PQCSS502A0
PC Central CNU
Control PI485
PI485
Cross UTP Cable
(Cross LAN Cable)
RS-485 Cable
PI485
PI485
Main Specifications
1. Control System(PQCSS501A0, PQCSS502A0)
- Centralized control of maximum 256 indoor units
- Simple Touch PAD method
- GUI setting considering convenience of use
- Power failure compensation with independent Battery Built-in (Max. 2 hours)
2. CNU(PQNFG00A0)
- Combination of maximum 8 outside units
- 485 to Ethernet Converter Built-in
3. PI485(PMNFP14A0)
- 1 pcs per outdoor units (control of 8 outdoor units per bridge)
Note: - GUI(Graphic User Interface) may be changed without any notice, for improvement or options.
- PC Central control, CNU and sub PI485(with wire assembly) should be purchased as optional.
[Outdoor Unit]
A [Indoor Unit]
BD Unit
L1
L2
B
Circuit 1 20m
L3
Circuit 2
[Outdoor Unit]
A [Indoor Unit]
Circuit 1
20m
B
Circuit 2
Refrigerant Charge
Direct Piping Circuit
Indoor Unit Pipe Size Rated Max. Additional
Capacity (Btu/h) Gas Liquid Length Length Refrigerant
24k 5/8" (15.88mm) 1/4" (6.35mm) 7.5m 30m 30g/m
36k 5/8" (15.88mm) 1/4" (6.35mm) 7.5m 50m 40g/m
A
+ 12k Branch pipe length - rated length X 20g/m
Ex 1) Additional charge of distributor piping circuit Ex 2) Additional charge of distributor piping circuit
Total main pipe(A) = 30m Total main pipe(A) = 20m
Each branch pipe(a, b, c) = 10m Each branch pipe(a) = 15m, (b,c) = 7m
L2
B
L3 Circuit 1
30m
L4
Circuit 2
[Outdoor Unit]
A [Indoor Unit]
Circuit 1
30m
B
Circuit 2
The calculation of the additional charge should take account of the length of pipe.
Ex 1) Additional charge of distributor piping circuit Ex 2) Additional charge of distributor piping circuit
Total main pipe(A) = 30m Total main pipe(B) = 30m
Each branch pipe(a, b, c, d) = 7.5m Each branch pipe(a,b) = 10m, (c,d) = 5m
(3) L8UC/H1008FA0
The maximun allowable level and piping length
[Outdoor Unit]
A [Indoor Unit]
B 30m
L2
B L3
BD Unit 30m
L4
L5
L6
BD Unit
Refrigerant Charge
Direct Piping Circuit
Indoor Unit Capacity Pipe Size Rated Max Additional
(Btu/h) Gas Liquid Length Length Refrigerant
The calculation of the additional charge should take account of the length of pipe.
B a b c
+ 12k Branch pipe length - rated length x 20g/m
18k 18k 18k
Circuit 2
+ 18k~36k Branch pipe length - rated length x 30g/m
24 k 24 k
BD Unit
C
A
B
C
Circuit 1
Circuit 2
(2) L5UC728FA0
Pipe Unit A B C
Liquid 3/8(9.52) 1/4(6.35) Adjust to indoor unit
Inch(mm)
Gas 3/4(19.05) 5/8(15.88) piping size
BD Unit
C
A
B C
C Circuit 1
Circuit 2
(3) L8UC/H1008FA0
Pipe Unit A B
Liquid 3/8(9.52) Adjust to indoor unit
inch(mm)
piping size
Gas 3/4(19.05)
BD Unit
A
L8UC1008FA0 A B
L8UH1008FA0
B B B B B
1.4 BD Unit
1.4.1 Installation of BD unit
This unit may be installed suspended from the ceiling or mounted on the wall.
This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up)
However, it may be freely installed in any direction forward or back, and to the sides.
Be sure to leave a 600mm square opening for service and inspection as shown in the diagram below, for both
ceiling - suspended installation and wall-mounted installation.
This unit "does not require drain treatment" as it uses internal foam treatment as low-pressure piping insulation.
Service direction is the side B and C
The piping for the indoor unit may be led around in direction A
The inclination of side B must be within 5C degrees forward or back or to the sides.
6.35 flare
12.7 flare
(298)
(337)
A 9.52 flare
250
19.05 flare
245
Suspension bolt pitch.
Main Pipe
B
(36) 50 50 50 40 30 50
(150)
(38) 50
(111)
(56) 50 50 50 45 300 50
Branch Pipe Cover Control
C
Min 400 Min 400
(Servicing space)
Min 30
Min 300
Inspection opening
NOTICE :
This unit has two different installation types:
(1) Ceiling-suspended type and (2) wall-mounted type.
Choose the proper installation pattern according to the
location of installation.
The installation location for printed wiring board can be
changed.
Follow the procedure specified in the "CONNECTING
THE WIRING" section to change the location.
(1) Ceiling-suspended type (2) Wall-mountde type
BD unit
Six-sided Nut 15.00
(M10 or M8)
Hanger metal
Flat washer
Hanging bolt
(M10 or M8)
(2) Wall-mounted type
Procedure
(1) Fix the fumished hanger metal with two screws.
(3 locations in total).
(2) After checking with a level that the unit is level, fix the unit
Screws(M5)
with the furnished wood screws.
(locally procude) * The tilt of the unit should be within 5 in front/back and
left/right.
CAUTION
Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again or cover it with
alumium tape.(This is to prevent condensation)
Be sure to install the unit with the ceiling-sie up.
Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be audible.
NOTICE :
For flaring work the piping, follow the instructions in the installation manual to each unit.
1. Overlap the connection pipe insulation material and Vinyl tape (wide) Wrap with vinyl tape
the indoor unit pipe insulation material. Bind them Connecting cable
together with vinyl tape so that there is no gap.
Pipe
2. Wrap the area which accommodates the rear piping
Vinyl tape(narrow)
housing section with vinyl tape.
CAUTION
Never use the plastic cap for closing.
E F E A Liquid pipe
B Gas pipe
B A C Electric wire
D Finishing tape
D E Insulating material
C F Transmission cable
Penetrations
Inner wall (concealed) Outer wall Outer wall (exposed) Sleeve
D Heat insulating material
C E
A A B B Lagging
B
Caulking material
Band
I Waterproofing layer
Sleeve with edge
Penetrating portion on fire
Lagging material
Floor (fireproofing) Roof pipe shaft limit and boundary wall
Mortar or other incombustible caulking
D I Incombustible heat insulation material
G J
F
D When filling a gap with mortar, cover the
B
penetration part with steel plate so that
H the insulation material will not be caved in.
G A For this part, use incombustible materials
B for both insulation and covering.(Vinyl
1m 1m
covering should not be used.)
WARNING:
Be sure to have authorized electric engineers to do electrical work using special circuits in accor-
dance with regulations and this installation manual. If power supply circuit has a lack of capacity or
electric work deficiency, it may cause an electric shock or fire.
2. Install the outdoor unit transmission line away from the power source wiring so that it is not affected by elec-
tric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to outdoor unit.
CAUTION:
Be sure to put outdoor unit to earth. Do not connect earth line to any gas pipe, water pipe, lighten-
ing rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
4. Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is some-
times removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will
be burnt out.
6. Use 2-core shield cable for transmission line.(O mark in the figure below) If transmission lines of different sys-
tems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erro-
neous operations. (X mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB6 for transmission line, and central
control)
A A
C C
TB6 TB6
B E
D D
TB6 TB6
Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m
the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
- power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
- In the same way, when grouping the lines power and signal lines should not be bunched together.
CAUTION
Have the indoor and outdoor units both been earthed?
If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
Indoor Unit
Power source
3 Phase, 50Hz, 380~415V
BD Unit
Power source
3 Phase, 50Hz, 380~415V
NOTICE :
The terminal board numbers are arranged from top to bottom in order of 1, 2 and 3.
In Case of 3 rooms
WARNING
Do not use tapped wires, stand
wires, extensioncords, or starbust
A connections, as they may cause
C room overtheating, electrical shock, or
B fire.
B room
C
A room CN-PWR
Connection wire for indoor units Connection wire for outdoor units
(H05VV, 4wires, 0.75mm) (H05VV, 4wires, 1.2mm)
Indoor unit
2) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient
of 1/100 is maintained.(PVC pipe should not be bent)
Spacing of supports for horizontal piping
Class Nominal diameter Spacing
Drain trap
Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.
1) Rig the drain trap as shown in the drawing below
Indoor unit
H H: 50mm or more
2) Provide one trap per unit. A single trap for converging units will prove ineffective.
3) Rig the trap to allow for future changing.
Plug
Plug
Face piping
downward Face the vent pipe mouth downward to keep
foreign matter from penetrating the system
Vent pipe
2) The pipe work should be kept as short as possible and the number of indoor units per group kept to a min-
imum.
Indoor unit
Auxiliary drain hose Thermal insulation(drain pipe area)
Important points
- The drain pipe size should be at least equal in size to that of the indoor unit drain pipe.
- The drain pipe is thermally insulated to prevent the formation of condensation outside the pipe.
- The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has
been connected some water should be added to the drain pan and the drain pump check to see that it is
functioning correctly.
- All connections should be secure.(Special care is needed with PVC pipe)
- Insulate auxiliary drain hose with thermal insulation band.