Sei sulla pagina 1di 1

1

PT. BERKAH CIPTA PERSADA\


Electrical Powering Business

?Jetter - Competitive - Passion



Neutral Grounding Resistors

~
;::

~
~

Kawasan lnduslrl Greenland - Ko1a Oel1amas JI. Greenland fl/ Blolc AC No. 07 Clkara119 pusat www.bcp-group.co .id
Bekasl - Indonesia 17530
Pa e 1 of 4
1

PT. BERKAH CIPTA PERSADA Product Brochure


Elet.tric11J.Po1.,t.ri11g B-11.o;/r1tt.;:,.

Zerrer-CompeLitive-Passioll Neutral Grau nd i ng Resistors


Protect Your Power Distribution Equipment With
Neutral Grounding Resistors
Neutral Grounding Resistors are the most effective, common, economical and preferred method of grounding.

Standards
The neutral grounding system's purpose is to protect life and property in the event of 50/60 Hz faults [short-circuitl
and transient phenomena. Neutral Grounding Resistors are designed and tested in strict accordance with IEEE
Standard 32-1972.


. l:J
13.8 kV System.
8 kV Line to Neutral.
400 Ampere,

-

I

10 Second

Designed and tested


in accordance with
IEEE Standard
32-1972
All units tri pie
insulated High Resistance
Grounding System
All stainless steel
13.8 kV System. resistor elements
8 kV Line to Neutral, and terminals
50 Ampere,
10 Second

PT. Berkah Cipta Persada


Kawasan lndustn Greenland -Kola OeltamasJJ. Greenland IV Blok AC No. 07 Cikatang Pusat Bekasl- lndonesla 17530 Phone: +62-2189972630,
31, 33. EXl.137 Fax: +62-21 89972634
Webstte . www.t>cp-group.oo.Jd Page 2 of 4
1
PT. BERKAH CIPTA PERSADA Product Brochure
&!.ttt'Y Compaitive Passion
Neutral Grounding Resistors
Typical Grounding Methods Neutral Grounding Resistors
Ungrounded Systems
Solidly Grounded Neutral Systems The most effective, common, economical and preferred
Resistance Grounded Systems method of grounding.

Ungrounded System
Standards
Transformer or Ungrounded System has no connec- Neutral Grounding Resis-tors
Cenerator tion between the conductors and are designed and tested in
Secondary
...r- earth ground. strict accordance with IEEE

~f
'1...
Under normal operating conditions
this method is fine.
Standard 32-1972-

The standard establishes maxi-


mum allowable temperature rat-
Typical
With fault conditions, damage to ings for neutral grounding
Ungrounded equipment can occur, and the fault devices for various duty
System may be dificult locate. cycles as follows:

Solidly Grounded System


MAX, TEMP. RISE
Transtonner or DUTY CYCLE TYPICAL CURRENT
Gctl<r"tor
A solidly Grounded System is one ABOVE AMBEINT
which the neutral point has been

~n
Stt'~l(t'll')'

connected to earth ground with a


Continuous 385 c 1 to 25 amps

conductor. Extended lime 610 C 10/25/50amps


60 Seconds or less 1soc 100 to 2000 amps
GrouoJ
It lacks the current limiting ability
.. De.fined as 10 minutes or greater. no more than 90 da'(! total per year
of resistance grounding and extra
iypi1;al Solidly protection for your equipment
01\)lutdi:J
Systc:ln

Grounding Through Resistor


Resistance Grounding is the
most effective and preferred
method.

It solves the problem of tran-


sient over voltages, which
reduces equipment damage.

Limiting the fault current prevents equipment damage.

PT. Berkah Cipta Persade


Kawasan loous1rf Greenland - Kola Deltamas JI. Greenland fl/ Blok AC No. 07 Clkarang Pusal Bekasf - Indonesia 17530 Pflone : "62-21 a997 2630,
31, 33. EJ<l 137 Fax +62-218997 2634
._ ..;W,;;e;;;bsll~e,;,: .co.Id
'WYNl~oilbo;o;;;..o1m Pa e 3 of 4
1
PT. BERKAH CIPTA PERSADA Product Brochure
iierrer- Competktv- Passion
Neutral Grounding Resistors
Function
Neutral Grounding Resistors are used to protect power transformers, power generators and other
associated equipment in your power systems against 50/60 Hz faults (shert circuitl and transient
phenomena !lightning).

Specification
There are three parame1ers needed to specify the neutral grounding resistor.
I. Rated voltage line to neutral or system voltage
2. Rated fault current
3. Rated "time on of the line to neutral voltage not exceeding the allowable temperature rise

Range
Rated current: from t amp to 5000 A Groond,ng
Rated voltage: from 0.38 to 34.5kV 7rans!rxrrtBr
CUbicie
Rated time; 1 sec to continuous time rating

Testing & Quality


Neutral Grounding Resistors are designed, rated, manufactured and tested in strict compliance with
IEEE-32-1972. Routine tests performed on each Neutral Grounding Resistor are measurement of
resistance, high voltage power frequency, insulation measurement, aspect verification, dimensional
control. Internal quality system has been developed and certified under ISO 9001 quality system.

Construction
A standard unit includes the stainless steel resistor assembly plus all the required insulators, internal
connections and hardware installed in a standard safety enclosure. Neutral Grounding Resistor units are
completely assembled, prewired, and tested at our facility. For shipping all units are crated for added
protection and ease of handling.

Enclosure Materials
Solid overhung top slightly sloped to prevent standing water and will support heavy ice and snow.
forged eyebolts in all four corners for easy hoisting.
Removable front and rear louvered covers for easy access for connection and inspection.
Corrosion resistant nameplate provides complete ratings and manufacturers information. Hehco# !Mm l"'"nd
Remtor used for Jow
Mill galvanized for maximum protection. -ru~nt applic4fions
Bottom screening prevents the entry of birds and rodents while providing maximum cooling for the
resistors.

Enclosure Options
Mill galvanized, aluminum, stainless steel and hot-dipped galvanized construction. Custom paint finish
is available.
Top or side mounted entrance bushing(s).
Screened covers for indoor applications.
Support stands for elevating the enclosure above ground.

Options
Current or potential transformers mounted and prewired at our facility
ON or OFF Load disconnecting switches

PT. Berkah Cipta Persada


Kawasan lndus!Jl Greenland - Kola Oeltamas JL Greenland IV Blok AC No. 07 Clkatang Pusat Bekasl - lndonesla 17530 <Phooa: 62-21 8997 2630,
31, 33. Ex!. 137' Fax: +62-21 6997 2634
___________________ w,;;,;;:eb;;;:s;;;ite;.;:.;:www:.;;,,;;:;;; Pa e 4 of